Safety labels are attached to the generator as shown in
Figure 1. Keep these safety labels clean at all times. When
the safety labels become worn or damaged, contact your
nearest dealer or the Multiquip Parts Dept.
WARNING
HOT COOLANT can cause
severe burns.
Do not remove cap if
radiator is hot.
M90310000
TOP VIEW
50
150
180
25
75
120
140
180
220
60
PSI
RPMX10
°F
0
100
0
210
100
260
OIL PRESS
SPEED
WATER TEMP
50
18
12
24
ECU
%
VOLTS
Integrated Gauge Panel
0
100
0
30
Check
½
½
DEF
Emissions
Failure
°F
°F
Emissions
E
E
F
F
Failure
Regen
Needed
Low
FUEL
DEF
Regen
Fuel
Inhibit
ECU
Series 800 Controller
Engine Started
Shutdown
Pre-Alarm
Alarm
Screen
Program
Option
Acknowledge
Change
Exit
WARNING
MOVING PARTS can cause
severe injury.
DO NOT operate with doorsopen.
Stop engine before servicing.
WARNING
ARC FLASH AND SHOCK HAZARD
Appropriate PPE Required
Appropriate Personal Protection
Equipment and Tools Required
when working on this equipment.
INCREASE DECREASE
V
U
W
OFF
V-W
W-U
U-V
OFF
M9503000004
M92010070
NOTICE
For safety label part numbers, reference parts manual.
CAUTION
Maximum capacity of lifting
bail is 19,000 lbs.
CAUTION
HOT PARTS can burn skin.
DO NOT touch until the
machine has sufficiently
cooled.
M911010000
M55100080
300
D
No Diesel
This machine stops and starts automatically
and without notice.
CAUTION
EXHAUST FLUID ONLY
Filling this tank with
anything other than
DIESEL EXHAUST FLUID
may result in severe
engine damage.
REAR VIEW
CAUTION
M94110000
M92010060
CAUTION
DO NOT disconnect the Battery Cables
after shutting down the engine for
at least 30 seconds
DANGER
Using a generator indoors CAN KILL YOU IN MINUTES.
Generator exhaust contains carbon monoxide. This is
a poison gas you cannot see or smell.
NEUTRAL BONDED TOFRAME
120V
120
V
NEUTRAL BONDED TO FRAME
GAC-2.2H
120V
NEUTRE MIS A LA MASSE A
120
15A
V
GAC-2.2H
LA CARCASSE DU MOTEUR
NEUTRE MIS A LA MASSE A
15A
LA CARCASSE DU MOTEUR
POWERED by
POWERED by
Honda Engines
Honda Engines
211052
AC CIRCUIT BREAKER
211052
INTERRUPTEUR DE
AC CIRCUIT BREAKER
OFF
GR PRISE DE
COURANT PRINCIPAL
INTERRUPTEUR DE
TERRE
OFF
GR PRISE DE
COURANT PRINCIPAL
TERRE
ONLY use OUTSIDE and
NEVER use inside a home
far away from windows,
or garage. Even if doors
doors, and vents.
and windows are open.
Avoid other generator hazards.
READ MANUAL BEFORE USE.
WARNING
ENVIRONMENTAL
This unit is designed to contain operating uids only.
The environmental containment is not designed to
control uids from an external source. It is the operator’s
responsibility to monitor uid levels at all times.
DO NOT EXCEED THE RECOMMENDED
MAXIMUM CAPACITY
Figure 1. Nameplate
and Safety Decals
CAUTION
Ensure the “Auto-Off/Reset-Manual” switch is
in the “Off/Reset” position. If it is not, when
the battery cables are connected, the engine
will crank and attempt to start.
M90130000
WARNING
ELECTRIC SHOCK HAZARD
Do not touch internal wiring
or connections while this
machine is operating.
Turn power off before
servicing.
M92010000
Operation of this equipment may create
sparks that can start fires around dry
vegetation.
A spark arrestor may be required.
The operator should contact local fire
agencies for laws or regulations
relating to fire prevention requirements.
NEUTRAL BONDED TO FRAME
120V
120
V
GAC-2.2H
NEUTRE MIS A LA MASSE A
15A
LA CARCASSE DU MOTEUR
POWERED by
Honda Engines
211052
AC CIRCUIT BREAKER
INTERRUPTEUR DE
OFF
GR PRISE DE
COURANT PRINCIPAL
TERRE
M90320010
50
150
180
25
75
120
140
180
220
60
PSI
RPMX10
°F
0
0
100
210
100
260
OIL PRESS
SPEED
WATER TEMP
50
18
12
24
ECU
%
VOLTS
Integrated GaugePanel
0
100
0
30
Check
½
½
DEF
Emissions
Failure
°F
°F
Emissions
E
E
F
F
Failure
Regen
Needed
Low
FUEL
DEF
Regen
Fuel
Inhibit
ECU
Series 800 Controller
Engine Started
Shutdown
Pre-Alarm
Screen
Program/
Alarm
Option
Change
Exit
Acknowledge
P/N M91110000
M9504200004
DECREASE
INCREASE
V
U
W
OFF
V-W
W-U
U-V
OFF
Denyo
CAUTION
This machine stops and starts automatically
and without notice.
MODEL
SERIAL NO.
.
y
DANGER
HIGH VOLTAGE
FRONT VIEW
SIDE VIEW
S-2731
WARNING
ELECTRIC SHOCK HAZARD
Do not touch output
terminals while this
machine is operating.
Turn power off before
servicing.
M92010060
300
WARNING
ELECTRIC SHOCK HAZARD
Always complete the grounding
path from the ground terminal
on the genset to an external
grounding source.
See instruction manual for
details.
WARNING
ELECTRIC SHOCK HAZARD
Do not touch internal wiring
or connections while this
machine is operating.
Turn power off before
servicing.
WARNING
Before connecting this generator to any building’s
electrical system, a licensed electrician must install
an isolation (transfer) switch.
Serious injury or death may result without this
transfer switch.
M92010050
M92010000
SIDE VIEW
WARNING
ENGINE EXHAUST can cause
severe injury or death.
Use only in open, well
ventilated areas or
vent exhaust outside.
DO NOT operate or service the generator before reading
the entire manual. Safety precautions should be followed at
all times when operating this generator. Failure to read and
understand the safety messages and operating instructions
could result in injury to yourself and others.
SAFETY MESSAGES
The four safety messages shown below will inform you
about potential hazards that could injure you or others. The
safety messages specifi cally address the level of exposure
to the operator and are preceded by one of four words:
DANGER, WARNING, CAUTION
SAFETY SYMBOLS
Potential hazards associated with the operation of this
generator will be referenced with hazard symbols which
may appear throughout this manual in conjunction with
safety messages.
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in DEATH or SERIOUS INJURY.
WARNING
Indicates a hazardous situation which, if not avoided,
COULD result in DEATH or SERIOUS INJURY.
or NOTICE.
CAUTION
Indicates a hazardous situation which, if not avoided,
COULD result in MINOR or MODERATE INJURY.
NOTICE
Addresses practices not related to personal injury.
NEVER use accessories or attachments that are not
recommended by MQ Power for this generator. Damage
Also, know the
and
This information will be invaluable in
emergency or safety devices.
These devices are intended for operator safety.
Disconnection of these devices can cause severe injury,
bodily harm or even death. Disconnection of any of these
lubricate components or attempt service on a
keep the generator in proper running condition.
Fix damage to generator and replace any broken parts
store generator properly when it is not being
used. Generator should be stored in a clean, dry location
out of the reach of children and unauthorized personnel.
CAUTION
NEVER operate this generator without proper protective
clothing, shatterproof glasses, respiratory protection,
hearing protection, steel-toed boots and other protective
devices required by the job or city and state regulations.
NEVER operate this generator when not
feeling well due to fatigue, illness or when
under medication.
NEVER operate this generator under the infl uence of
drugs or alcohol.
ALWAYS check the generator for loosened threads or
bolts before starting.
DO NOT use the generator for any purpose other than
its intended purposes or applications.
to the generator and/or injury to user may result.
ALWAYS know the location of the nearest
fi re extinguisher.
ALWAYS know the location of the nearest
fi rst aid kit.
ALWAYS know the location of the nearest
phone or keep a phone on the job site.
phone numbers of the nearest ambulance, doctor
fi re department.
the case of an emergency.
GENERATOR SAFETY
NEVER operate the generator in an explosive
atmosphere or near combustible materials. An
explosion or fi re could result causing severe
bodily harm or even death.
DANGER
WARNING
NOTICE
This generator should only be operated by trained and
qualifi ed personnel 18 years of age and older.
Whenever necessary, replace nameplate, operation and
safety decals when they become diffi cult read.
Manufacturer does not assume responsibility for any
accident due to generator modifi cations. Unauthorized
generator modifi cation will void all warranties.
NEVER disconnect any
devices will void all warranties.
CAUTION
NEVER
running machine.
NOTICE
ALWAYS ensure generator is on level ground before use.
run engine without an air fi lter or with a dirty air
fi lter. Severe engine damage may occur. Service air fi lter
Wet stacking is a common problem with diesel engines
which are operated for extended periods with light or
no load applied. When a diesel engine operates without
suffi cient load (less than 40% of the rated output), it will
not operate at its optimum temperature. This will allow
unburned fuel to accumulate in the exhaust system,
which can foul the fuel injectors, engine valves and
exhaust system, including turbochargers, and reduce
it must be able to provide fuel and air in the proper ratio
and at a high enough engine temperature for the engine
Wet stacking does not usually cause any permanent
damage and can be alleviated if additional load is
applied to relieve the condition. It can reduce the system
performance and increase maintenance. Applying an
increasing load over a period of time until the excess
fuel is burned off and the system capacity is reached
usually can repair the condition. This can take several
State Health Safety Codes and Public Resources
Codes specify that in certain locations, spark arresters
must be used on internal combustion engines that use
hydrocarbon fuels. A spark arrester is a device designed
to prevent accidental discharge of sparks or fl ames
from the engine exhaust. Spark arresters are qualifi ed
and rated by the United States Forest Service for this
purpose. In order to comply with local laws regarding
spark arresters, consult the engine distributor or the
SAFETY INFORMATION
DANGER
The engine fuel exhaust gases contain poisonous carbon
monoxide. This gas is colorless and odorless, and can
cause death if inhaled.
The engine in this generator
requires an adequate free
fl ow of cooling air. NEVER
operate this generator in
any enclosed or narrow area
where free fl ow of the air is
restricted. If the air fl ow is
restricted it will cause injury to people and property and
serious damage to the generator or engine.
WARNING
DO NOT place hands or fingers inside engine
compartment when engine is running.
NEVER operate the engine with heat shields or
guards removed.
Keep fi ngers, hands hair and clothing away
from all moving parts to prevent injury.
NEVER
frequently to prevent engine malfunction.
NEVER tamper with the factory settings
of the engine or engine governor. Damage
to the engine or generator can result if
operating in speed ranges above the
maximum allowable.
the operating performance.
In order for a diesel engine to operate at peak effi ciency,
to completely burn all of the fuel.
DO NOT remove the radiator cap while the
engine is hot. High pressure boiling water
will gush out of the radiator and severely
scald any persons in the general area of
the generator.
DO NOT remove the coolant drain plug while the engine
is hot. Hot coolant will gush out of the coolant tank and
severely scald any persons in the general area of the
generator.
DO NOT remove the engine oil drain plug while the
engine is hot. Hot oil will gush out of the oil tank and
severely scald any persons in the general area of the
generator.
CAUTION
NEVER touch the hot exhaust manifold,
muffl er or cylinder. Allow these parts to cool
before servicing generator.
Backfeed to a utility system can cause electrocution
codes. Failure to do so could result in electrical shock or
while AC power from the
cables or cords when
connecting generator to generator. Inspect for cuts in the
connected to the generator’s output receptacles.
Incorrect connections may cause electrical shock and
make certain that proper power or extension
cord has been selected for the job. See Cable Selection
DO NOT start the engine near spilled fuel or combustible
fl uids. Diesel fuel is extremely fl ammable and its vapors
can cause an explosion if ignited.
ALWAYS refuel in a well-ventilated area, away from
sparks and open fl ames.
ALWAYS use extreme caution when working with
fl ammable liquids.
SAFETY INFORMATION
and/or property damage. NEVER
connect the generator to a building’s
electrical system without a transfer
switch or other approved device. All
installations should be performed by a
licensed electrician in accordance
with all applicable laws and electrical
burn, causing serious injury or even death.
Power Cord/Cable Safety
DO NOT fi ll the fuel tank while the engine is running
or hot.
DO NOT overfi ll tank, since spilled fuel could ignite if it
comes into contact with hot engine parts or sparks from
the ignition system.
Store fuel in appropriate containers, in well-ventilated
areas and away from sparks and fl ames.
NEVER use fuel as a cleaning agent.
DO NOT smoke around or near the
generator. Fire or explosion could result
from fuel vapors or if fuel is spilled on a
hot engine.
DANGER
DO NOT touch output terminals during
operation. Contact with output terminals
during operation can cause electrocution,
electrical shock or burn.
The electrical voltage required to
operate the generator can cause severe
injury or even death through physical contact with live
circuits. Turn generator and all circuit breakers OFF
before performing maintenance on the generator or
making contact with output terminals.
DANGER
NEVER let power cords or cables lay in water.
NEVER stand in water
generator is being transferred to a load.
NEVER use damaged or worn
insulation.
NEVER grab or touch a live power
cord or cable with wet hands. The
possibility exists of electrical shock,
electrocution or death.
Make sure power cables are securely
damage to the generator.
NOTICE
ALWAYS
Chart in this manual.
NEVER insert any objects into the output
receptacles during operation. This is
extremely dangerous. The possibility
exists of electrical shock, electrocution
environment to avoid the risk of a dangerous concentration
If the battery liquid (dilute sulfuric acid) comes into
, rinse skin or clothing
If the battery liquid (dilute sulfuric acid) comes into
, rinse eyes immediately with plenty
of water and contact the nearest doctor or hospital to
NEGATIVE battery terminal
keep battery cables in good working condition.
WARNING
DANGER
This generator is equipped with a grounding terminal
attached to the enclosure. Electrical grounding
requirements can differ by State, Province, District,
Municipality, and unique application settings.
For portable and vehicle-mounted generators, Multiquip
recognizes the guidance provided in NEC Handbook
Article 250.34 Parts A and B, and 29 CFR 1926.404
(f) (3) (i). If a more defi nitive earth-to-ground safeguard
is required, please consult a qualifi ed electrician and
reference appropriate National Electrical Code (NEC)
guidelines in establishing an exterior grounding point
generator.
NEVER use gas piping as an electrical ground.
NOTICE
There is a permanent conductor bond between
generator (stator winding) and the frame.
DANGER
DO NOT drop the battery. There is a possibility that the
battery will explode.
DO NOT expose the battery to open fl ames,
sparks, cigarettes, etc. The battery contains
combustible gases and liquids. If these
gases and liquids come into contact with a
fl ame or spark, an explosion could occur.
ALWAYS wear safety glasses when
handling the battery to avoid eye irritation.
The battery contains acids that can cause
injury to the eyes and skin.
Use well-insulated gloves when picking up the battery.
ALWAYS
charged, combustible gas will build up.
ALWAYS
of combustible gasses.
contact with clothing or skin
immediately with plenty of water.
Decommissioning is a controlled process used to safely
retire a piece of generator that is no longer serviceable.
If the generator poses an unacceptable and unrepairable
safety risk due to wear or damage or is no longer cost
effective to maintain (beyond life-cycle reliability) and is to
be decommissioned (demolition and dismantlement),be
sure to follow rules below.
EMISSIONS INFORMATION
The diesel engine used in this generator has been designed
to reduce harmful levels of carbon monoxide (CO),
hydrocarbons (HC) and nitrogen oxides (NOx) contained
This engine has been certifi ed to meet US EPA Evaporative
Attempting to modify or make adjustments to the engine
emission system by unauthorized personnel without proper
training could damage the generator or create an unsafe
Additionally, modifying the fuel system may adversely affect
evaporative emissions, resulting in fi nes or other penalties.
The emission control label is an integral part of the emission
If a replacement emission label is needed, please contact
NOTICE
DO NOT pour waste or oil directly onto the ground, down
a drain or into any water source.
Contact your country's Department of
Public Works or recycling agency in your
area and arrange for proper disposal of
any electrical components, waste or oil
associated with this generator.
When the life cycle of this generator is over, remove
battery(s) and bring to an appropriate facility for lead
reclamation. Use safety precautions when handling
batteries that contain sulfuric acid.
When the life cycle of this generator is over, it is
recommended that the generator frame and all other
metal parts be sent to a recycling center.
Metal recycling involves the collection of metal from
discarded products and its transformation into raw
materials to use in manufacturing a new product.
Recyclers and manufacturers alike promote the process
of recycling metal. Using a metal recycling center
promotes energy cost savings.
NOTICE
in diesel exhaust emissions.
emissions requirements in the installed confi guration.
condition.
Emission Control Label
system and is strictly controlled by regulations.
The label must remain with the engine for its entire life.
Consult with local Electrical and Safety Codes for proper
connection based on condition of use.
EXAMPLE of how to ground the unit if the condition
of use requires such a device:
The ground terminal on the generator should always be
used to connect the generator to a suitable ground when
required.
The ground cable should be #8 size wire (aluminum)
minimum. If copper wire is used, #10 size wire minimum
should be used.
Connect one end of the ground cable terminal to the
generator ground point (Figure 3). Connect the other end
of the ground cable to a suitable earth ground (ground rod)
GENERATOR
GROUND LUG
GROUND CABLE
IF THE GENERATOR IS PROVIDING
ELECTRIC POWER TO A BUILDING
VIA A TRANSFER SWITCH IT MUST
BE CONNECTED TO A GROUND ROD.
Install the generator in a area that is free of debris,
bystanders, and overhead obstructions. Make sure the
generator is on secure level ground so that it cannot slide
or shift around. Also install the generator in a manner so
that the exhaust will not be discharged in the direction of
nearby homes.
The installation site must be relatively free from moisture
and dust. All electrical equipment should be protected from
excessive moisture. Failure to do will result in deterioration
of the insulation and will result in short circuits and
grounding.
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to
engine and alternator parts.
CAUTION
Pay close attention to ventilation when operating the
generator inside tunnels and caves. The engine exhaust
contains noxious elements. Engine exhaust must be
routed to a ventilated area.
GENERATOR GROUNDING
NOTICE
The Occupational Safety and Health Administration
(OSHA) and the National Electrical Code (NEC)
recommend that if the generator is providing electrical
power to a structure (home, office shop, trailer or
similar) it must be connected to a grounding electrode
system, such as driven ground rod (Figure 3).
If applicable, to guard against electrical shock and possible
damage to the equipment, it is important to provide a good
EARTH ground, (Figure 3).
NOTICE
ALWAYS check with State, Province, District and
Municipalities for electrical grounding requirements
before using generator.
Article 250 (Grounding) of the NEC handbook provides
guidelines for proper grounding and specifies that the cable
ground shall be connected to the grounding system of the
building as close to the point of cable entry as practical.
INDOOR INSTALLATION
Exhaust gases from diesel engines are extremely
poisonous. Whenever an engine is installed indoors the
exhaust fumes must be vented to the outside. The engine
should be installed at least two feet from any outside wall.
Using an exhaust pipe which is too long or too small can
cause excessive back pressure which will cause the engine
to heat excessively and possibly burn the valves.
MOUNTING
The generator must be mounted on a solid foundation such
as concrete) and set firmly on the foundation to isolate
vibration of the generator when it is running. The generator
must set at least 6 inches above the floor or grade level
(in accordance to NFPA 110, Chapter 54.1). DO NOT
remove the metal skids on the bottom of the generator.
They are to resist damage to the bottom of the generator
and to maintain alignment.
NEC article 250 specifices the following grounding
requirements:
1. Use one of the following wire types to connect the
generator to earth ground.
a. Copper 10 AWG (5.3 mm
b. Aluminum 8 AWG (8.4 mm
2
) or larger.
2
) or larger.
2. When grounding of the generator (Figure 3) is required,
connect one end of the ground cable to the ground lug
on the generator. Connect the other end of the ground
cable to the ground rod (earth ground).
3. NEC article 250 specifies that the earth ground rod
should be buried a minimum of 8 ft. into the ground.
NOTICE
When connecting the generator to any buildings
electrical system ALWAYS consult with a licensed
electrician.
This generator (Figure 7) is designed as a high quality
portable (requires a trailer for transport) power source for
telecom sites, lighting facilities, power tools, submersible
pumps and other industrial and construction machinery.
OPERATING PANEL
The “Operating Panel” is provided with the following:
The “Control Panel” is provided with the following:
Frequency Meter (Hz) AC Ammeter (Amps) AC Voltmeter (Volts) Ammeter Change-Over Switch Voltmeter Change-Over Switch Voltage Regulator 3-Pole, 800 amp Main Circuit Breaker “Control Box” (located behind Control Panel)
• Automatic Voltage Regulator
• Current Transformer
• Over-Current Relay
• Starter Relay
• Voltage Change-Over Board
OUTPUT TERMINAL PANEL
The “Output Terminal Panel” is provided with the following:
Three 120/240V output receptacles (CS-6369), 50A Three auxiliary circuit breakers, 50A Two 120V output receptacles (GFCI), 20A Two GFCI circuit breakers, 20A Eight output terminal lugs (3Ø power) Ground lug Battery Charger (Optional) Jacket Water Heater (Optional)
OPEN DELTA EXCITATION SYSTEM
Each generator is equipped with the state of the art “OpenDelta” excitation system. The open delta system consist
of an electrically independent winding wound among
stationary windings of the AC output section.
There are four connections of the open delta A, B, C and
D. During steady state loads, the power from the voltage
regulator is supplied from the parallel connections of A to
B, A to D, and C to D. These three phases of the voltage
input to the voltage regulator are then rectified and are the
excitation current for the exciter section.
When a heavy load, such as a motor starting or a short
circuit occurs, the automatic voltage regulator (AVR)
switches the configuration of the open delta to the series
connection of B to C. This has the effect of adding the
voltages of each phase to provide higher excitation to the
exciter section and thus better voltage response during the
application of heavy loads.
The connections of the AVR to the AC output windings are
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a “fixed ceiling” and responds
according the demands of the required load.
ENGINE
This generator is powered by a 6 cylinder, 4-cycle water
cooled, direct injection, turbocharged, air cooled EGR John
Deere 6090HFG06 diesel engine. This engine is designed
to meet every performance requirement for the generator.
Reference Table 2 for engine specifications.
In keeping with MQ Power’s policy of constantly improving
its products, the specifications quoted herein are subject
to change without prior notice.
ELECTRIC GOVERNOR SYSTEM
The electric governor system controls the RPMs of the engine.
When the engine demand increases or decreases, the
governor system regulates the frequency variation to ±.25%.
EXTENSION CABLES
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generator and point of use (load) is held to
a minimum. Use the cable selection chart (Table 8) as a
guide for selecting proper extension cable size.
When the paralleling option is employed, the Basler
DGC-2020HD controller must be installed. The
factory installed ECU-845 controller cannot be used
for paralleling.
PARALLELING
Paralleling is the sharing of a load between two generator
sets or more.
LOAD SHARING
Load sharing is defined as the proportional division of the
kW and kVAR total load between multiple generator sets
in a paralleled system.
Load sharing is essential to avoid overloading and stability
problems on the systems’ generator sets.
ACTIVE POWER (KW) LOAD SHARING
When generator sets operate in parallel, the engine speed
governor of each generator set determines the proportional
sharing of the total active power requirements (kW) of the
systems’.
The kW load sharing is achieved by increasing or decreasing
fuel to the systems’ engines. As the fuel to the engine of
one generator set in a group is increased it will not lead to
an increase in speed and hence frequency (as it would if it
were operating alone) but it will lead to an increase in the
proportion of the total kW load that it will deliver.
As the fuel to the engine of one generator set in a group
is decreased it will not lead to a decrease in speed and
hence frequency (as it would if it were operating alone) but
it will lead to a decrease in the proportion of the total kW
load that it will deliver.
The control system of the generator sets (via the engine
speed control system) monitors and controls the sharing
of the total kW load in proportion to the relative rating of
the engines on the systems’ generator sets.
REACTIVE POWER (KVAR) LOAD SHARING
When generator sets operate in parallel the alternator
field excitation system of each generator set controls the proportional sharing of the total reactive power
requirements (kVAR) of the system.
As the field excitation of one generator set in a group is
increased i.e. over excited it will not lead to an increase
in voltage (as it would if it were operating alone) but It will
lead to an increase in the proportion of the total kVAR load
it will deliver and a decrease in its power factor.
As the field excitation of one generator set in a group is
decreased i.e. over excited it will not lead to an decrease
in voltage (as it would if it were operating alone) but It will
lead to an decrease in the proportion of the total kVAR load
it will deliver and a increase in its power factor.
An undesirable circulating reactive current (cross current)
will flow in the system if the excitation of the alternators
are not matched.
ETHERNET COMMUNICATION
Ethernet communication is the preferred method for
paralleling. This method supports breaker negotiation to
avoid simultaneous breaker closures, kW load sharing
and kVAR sharing, soft load transfers on and off loading.
The Ethernet ports are located at the output bus splash
panel area. There are two ports which are identical so either
one can be used. Using a standard Ethernet cable, interconnect units to be paralleled and or sequenced.
LOAD MANAGEMENT
These generators are set up to automatically manage load,
based on demand. Load management is only functional in
auto mode. While in auto mode, if the auto start contacts
are closed, load management is active by default. Load
management will only run the number of units needed to
support the load.
If the load demand is small, only one generator will remain
running while the other generators will be in standby mode.
If the load increases above 80% of its capacity, it will start
the next generator. The next generator priority is based on
the time remaining on the maintenance timer.
Generators with more time until scheduled maintenance will
take priority over units that are almost due for maintenance.
Once the second unit starts it will synchronize and parallel
in then ramp up to share the load. If the load levels drop
below 35% of its combined rating, the generator that is no
longer needed will ramp off, shut down and wait in standby
mode.
The kVAR load sharing is achieved by increasing or
decreasing the field excitation to the systems’ alternators
Ethernet communication is required when the
generators are configured for the sequencing mode
of operation.
These generators are capable of sequencing for control
of balanced maintenance schedules. As described
above, these generators can start and stop as demand
raises or lowers. In addition, if the units get to the point of
maintenance, it will ramp off and start the next generator to
relieve it based on the time remaining on the maintenance
timer.
After maintenance is performed, the maintenance timers
should be reset to the recommended service interval. This
is usually 250 hours depending on the engine oil type.
MAINTENANCE INTERVAL
Maintenance intervals are factory set for 250 hours.
The maintenance interval timer will count down to zero
indicating that it is time for the unit to be serviced.
Once the timer counts down to zero, a pre-alarm will appear
indicating that the unit is due for maintenance. To reset the
maintenance interval back to the default time of 250 hours,
press and hold the “Reset” button for ten seconds.
The complete password sequence is shown in Figure 4.
The set-point for the desired hours until maintenance can
now be changed. Press edit to save.
EditEdit
Figure 4. Password Sequence 2.04 and Lower
PASSWORD ENTRY 2.04 AND HIGHER
User Name and Password is A.
Once prompted, the cursor will be in the user name field.
Press the down button () twice to highlight the A character.
Once the user name of A is populated in the user name
field, press the up arrow () button four times to highlight
the check box in the upper right corner of the screen. With
the check box highlighted press the edit button to accept
the entry.
The cursor will move to the password field. Again, press the
down arrow () button twice until the A is highlighted and
then press edit. Press the up arrow () button four times
to highlight the check box in the upper right corner of the
screen. With the check box highlighted press the edit button
to accept the entry. This completes the password entry.
The complete password sequence is as follows:
To reset the maintenance interval using the reset button,
the Maintenance Due pre-Alarm must be active, and the
Basler controller must display the “Overview Screen” (Main
Screen).
If the maintenance timer has not yet expired and it is
desired to reset the unit back to 250 hours, navigate back
to the settings menu. Settings Menu->System Parameters>Engine Statistics->Hours To Maintenance.
PASSWORD ENTRY 2.04 AND LOWER
When highlighted, press the “Edit” button. Username and
Password is required. User Name is A and Password is
A. Use the up arrow button () and scroll to the alpha
character A, then press edit to select.
Next, the cursor will move to the password field, press the
up arrow button () and scroll to the alpha character A,
then press edit to select.
Pre-alarm Silence allows the user to suppress the toggling
of the alarm screen when a new Pre-alarm becomes active.
While a Pre-alarm is active, pressing the Alarm Silence
button will suppress the fault display.
This happens to be very handy function when the
“Maintenance Interval” Pre-Alarm occurs. Right after the
Pre-Alarm occurs it will begin toggling between the pre-alarm and the overview screen.
While in this mode, pressing the reset button does not reset
the maintenance interval. In order to reset the maintenance
interval the overview screen must be selected.
GENERAL PARALLELING INFORMATION (OPTION)
Pressing the alarm silence button will stop the toggling
between the pre-alarm and the overview screen.
Once the overview screen is selected, the maintenance
interval can be reset by pressing and holding the reset
button for 10 seconds.
THREE PHASE 480V/208V PARALLEL WIRING VIA
CAMLOCKS
REQUIRED EQUIPMENT
4/0 Single Conductor Cable (User Supplied)
CAT5E Shielded Cable or Better (User Supplied)
Power Distribution Panel (User Supplied)
The following procedure intended to assist the user with
the parallel wiring configuration for the DCA300SSJU4F2
generator using the camlok connector panel.
NOTICE
Only a qualified service technician or licensed
electrician with proper training should perform
this installation. Follow all shop safety rules when
performing this installation.
NOTICE
When connecting load cables to the power distribution
panel be sure to select the correct size of the load
cables to handle full load/amperage of both generators
(parallel).
3Ø-208 VAC PARALLEL WIRING CONFIGURATION
1. Using 4/0 cables connect the two generators to the
power distribution panel as referenced in the 3Ø-208V
parallel wiring diagram.
ETHERNET CABLE CONNECTION
1. Connect a CAT5E Ethernet cable (shielded) between
port 1 on both generators as shown in Figure 6.
CAT5E PORT 1
GENERATOR 1
PORT 2
CAT5E ETHERNET
CABLE (SHIELDED)
PREPARATION
1. Make sure generator is turned off and engine is cool.
2. Disconnect any loads connected to the generator.
3. Place the main circuit breaker in the OFF position.
4. Place the generator in an area free of dirt and debris
Make sure it is on secure level ground.
5. Disconnect negative battery cable from the battery.
3Ø-480 VAC PARALLEL WIRING CONFIGURATION
1. Using 4/0 cables connect the two generators to the
power distribution panel as referenced in the 3Ø-480V
parallel wiring diagram.
DANGER
To prevent arcing make sure cables are securely tighten
at power distribution panel, the possibility exist of the
unit catching on fire thus causing equipment damage
and severe bodily harm.
CAT5E PORT 1
GENERATOR 2
PORT 2
Figure 6. Ethernet Cable Connection
2. Reference Table 4 for additional Ethernet port
connections.
Table 4. Ethernet Cable Connections
Generator 1Generator 2
Port 2Port 1
Port 1Port 2
Port 2Port 2
3. Reconnect battery.
4. Start generator as outlined in start up section of this
manual.
The definitions below describe the controls and functions
of the Engine Control Unit (Figure 8).
1. ECU-845 Controller — This auto start/stop
controller displays the parameters and the diagnostic
troubleshooting messages of the engine.
In addition, this controller also displays symbols and
indications related to the exhaust gas after treatment
system (DOC, SCR) including the Diesel Exhaust Fluid
(DEF) level in the DEF tank.
A. ECU Display Screen — Engine fault diagnostic
messages are shown on this LCD display. screen
B. Engine Started Lamp — This lamp when lit
indicates engine is operating normally.
C. Engine Shutdown Lamp — When an engine
failure has occured this lamp will blink, indicating
the engine has been shutdown. The diagnostic
fault message will be displayed on the LCD screen.
The fault message will be displayed on the screen.
When multiple engine faults occur, the lamp will
continue blinking until all fault messages are
confirmed. The blinking lamp will change to a solid
lamp display all current confirmed fault messages
will scroll across the screen.
F. Screen Change Button — When this button is
pushed during operation, the screen (Figure 9)
will cycle through main and secondary parameter
screens.
VOLTSAMPS
278
UO
VO
278
278
WO
240 kW
60 Hz
ENGINE GENERATOR SYSTEM OK
UV
VW
WU
480
480
480
U
361
V
361
W
361
300 kVA
100 h
D. Pre Alarm Lamp — When an engine failure has
occured this lamp will blink. Indicating a pre-fault
engine condition and the possibility of engine
shutdown.The diagnostic fault message will be
displayed on the LCD screen.
E. Alarm Acknowledge Button — When the engine
experiences a fault, the "Pre Alarm Lamp" or the
"Shutdown Lamp" will start blinking. Pushing this
button will confirm the fault message and the
blinking lamp will change to a solid lamp display.
The screen as shown in (Figure 9) represents the
phase voltages for each phase to neutral (UO, VO and
WO) and the line voltages between each phase (UV,
VW and WU).
G. Option Button — This button is not active. Do
not use.
H. Program/Exit Button — Push this button from the
home screen to enter the main menu.
GAUGE UNIT ASSEMBLY
1
50
180
25
75
140
220
PSI
ECU
0
OIL PRESS
Check
DEF
Emissions
Failure
Emissions
Failure
Regen
Needed
Regen
Inhibit
Series 800 Controller
Alarm
Acknowledge
°F
100
100
260
WATER TEMP
18
12
24
VOLTS
0
30
½
°F
E
F
Low
FUEL
Fuel
Screen
Program
Option
Change
Exit
A
50
25
PSI
0
OIL PRESS
Check
DEF
Emissions
Failure
Emissions
Failure
Regen
Needed
Regen
Inhibit
H
B
75
100
12
D
0
180
140
°F
100
WATER TEMP
18
24
VOLTS
30
½
°F
E
F
Low
FUEL
Fuel
C
150
120
220
260
50
%
0
F
G
180
60
RPMX10
0
210
SPEED
EC U
Integrated Gauge Panel
E
100
½
°F
E
F
DEF
I
Figure 10. Gauge Unit
The definitions below describe the readouts and functions
of the Gauge Unit Assembly (Figure 10).
1. Gauge Unit Assembly — This assembly houses the
various engine monitoring gauges. These gauges
indicate: oil pressure, water temperature, charging
voltmeter, generator load, fuel level, DEF level and
engine speed RPM (tachometer).
A. Oil Pressure Gauge — During normal operation,
this gauge should read approximately 44 psi.
(300 kPa). When starting the generator, the oil
pressure may read a little higher but after the
engine warms up, the oil pressure should return
to the correct pressure range.
B. Water Temperature Gauge — During normal
operation this gauge should read between 185°
and 207°F (85°~97°C).
C. Tachometer — Indicates engine speed in RPM’s
for 60 Hz operation. This meter should indicate
1800 RPM’s when the rated load is applied.
0
120
60
0
50
%
100
E
Engine Started
Shutdown
Pre-Alarm
150
180
RPMX10
210
SPEED
ECU
Integrated Gauge Panel
½
°F
F
4
DEF
5
INCREASEDECREASE
V
U
W
OFF
V-W
W-U
U-V
OFF
D. Battery Voltmeter Gauge — During normal
operation this gauge indicates a minimum 14 VDC.
E. Generator Load Gauge — Indicates the generator
load rate. It is recommended the load be above the
red area (20%) for maintaining sufficient exhaust
temperature.
F. Fuel Gauge — Indicates amount of diesel fuel
available. The red area in the gauge indicates a
low fuel level (20%).
G. DEF Gauge — Indicates amount of diesel exhaust
fluid available. The red area in the gauge indicates
a low DEF level (10%).
H. Exhaust System State Indicator Lamps — Lamps
illuminate when engine is at Exhaust System State or
DEF state. Refer to the maintenance section of this
manual for more detailed indormation.
The definitions below describe the controls and functions
of the Generator/Engine Control Panel (Figure 11).
1. Panel Light — For operation at night, panel light
illuminates control panel for ease of reading meters
and gauges. Make sure oanel light switch is in the OFF
position when light is not in use.
2. Panel Light Switch — When activated will turn on
control panel light.
3. Frequency Meter — Indicates the output frequency
in hertz (Hz). Normally 60 Hz
4. AC Ammeter — Indicates the amount of current the
load is drawing from the generator per leg selected by
the ammeter phase-selector switch.
5. AC Voltmeter — Indicates the output voltage present
at the U,V, and W Output Terminal Lugs.
6. Voltage Regulator Control — Allows ±15% manual
adjustment of the generator’s output voltage.
7. Ammeter Change-Over Switch — This switch allows
the AC ammeter to indicate the current flowing to the load
connected to any phase of the output terminals, or to be
switched off. This switch does not effect the generator
output in any fashion, it is for current reading only.
13
X
2
U
1
U
1
2
3
4
Y
2
1
V
V
5
Z
2
W
1
W
6
O
14
8. Voltmeter Change-Over Switch — This switch allows
the AC voltmeter to indicate phase to phase voltage
between any two phases of the output terminals or to
be switched off.
9. Emergency Stop Switch Button — In the event
of an emergency press this button to shut down the
generator.
10. Hour Check Button — With the engine stopped, press
and hold ths button. The total running hours, fuel level,
and battery voltage will be displayed.
11. Auto/Start Switch — This switch selects either manual
or automatic operation. Center position is OFF (reset).
12. Engine Speed Switch Switch — This switch controls
the speed of the engine low or high.
13. Voltage Change-Over Board — 6 jumper plates that
allows the generator to be configured for either 3Ø,
240 or 480 VAC output.
14. Main Circuit Breaker — This three-pole, 800 amp
main breaker is provided to protect the U,V, and W
The Basler DGC-2020HD is an option. It replaces
the ECU 845 controller that comes standard with this
generator when the paralleling option is employed.
The definitions below describe the controls and functions
of the Digital Genset Controller (Figure 12).
1. LCD Display — Display consists of a LCD color touch
screen. The backlit, 272X480 pixel color LCD serves
as the local information source for metering, alarms,
pre-alarms, and protective functions. Touch screen
capability provides convenient navigation through
metering and settings. Display operation is maintained
down to –4°F (−20°C).
2. Not In Auto Indicator — This red LED lights when the
DGC-2020HD is not operating in AUTO mode.
3. Alarm Indicator — This red LED lights continuously
during alarm conditions and flashes during pre-alarm
conditions.
4. Supplying Load Indicator — This green LED lights
when the generator current is greater than emergency
power supply (EPS) threshold current.
5. Programmable Indicators — These three red
LEDs light when the corresponding logic element
is set true. Logic element PROGLED 1 controls the
upper LED, PROGLED 2 controls the middle LED,
and PROGLED 3 controls the lower LED. A card is
provided for labeling the programmable indicators. See
Programmable Indicator Configuration, below.
6. Alarm Silence Pushbutton — Pressing this button
tests the DGC-2020HD indicators by exercising all
LCD pixels and lighting all LEDs.
7. Lamp Test Pushbutton — Pressing this button tests
the DGC-2020HD indicators by exercising all LCD
pixels and lighting all LEDs.
8. Auto Pushbutton and Mode Indicator — Pressing
the Auto button places the DGC-2020HD in Auto
mode. The green Auto mode LED lights when Auto
mode is active.
9. Off Pushbutton and Mode Indicator. — Pressing this
button places the DGC-2020HD in Off mode.The red Off mode LED lights when the DGC-2020HD is in Off
mode. This button also resets the Breaker Management
Pre-Alarms and all MTU ECU Alarms.
10. Run Pushbutton and Mode Indicator. — Pressing
this button places the DGC-2020HD in Run mode. The
green Run mode LED lights when Run mode is active.
11. Reset Pushbutton — This button is pressed to cancel
a settings editing session and discard any settings
changes. When pressed momentarily, this button
resets the Breaker Management Pre-Alarms and all
MTU ECU Alarms. This button is also used to reset
the Maintenance Interval when pressed for 10 seconds
while viewing Hours Until Maintenance or Maintenance
Due Pre-Alarm.
12. Arrow Pushbuttons — These four buttons are used
to navigate through the front panel display menus and
modify settings.
• The left and right arrow buttons are used to navigate
through the menu levels. The right arrow button is
pressed to move downward through the menu levels
and the left arrow button is pressed to move upward
through the menu levels.
• Within a level, the up and down arrow buttons are used
to move among items within the menu level. Pressing
the down arrow button moves to items lower in the list.
Pressing the up arrow button moves to items higher
in the list.
• During a settings editing session, the up and down
arrow buttons are used to raise and lower the value of
the selected setting. The right and left arrow buttons
move to different digits.
While in “AUTO” the controller will be in standby
awaiting a signal to start via the remote start terminals.
While in auto, closure of the auto start contacts will
immediately start the engine. Once the generator is
up to speed and voltage it will compare its voltage to
the bus.
If the bus is dead it will immediately close the contactor
to provide power to the load(s). If the bus is already
hot from another generator it will first synchronize then
close its contactor then slowly ramp up to share load
if load were present.
13. Edit Pushbutton — Pressing this button starts an
editing session and enables changes to DGC-2020HD
settings. At the conclusion of an editing session, the
Edit pushbutton is pressed again to save the setting
changes.
The definitions below describe the controls and functions
of the Paralleling Panel (Figure 13).
1. Panel Lights — For operation at night or in dark areas,
panel light illuminates paralleling panel for ease of
reading.
2. Panel Light Switch — When activated will turn on
control panel light.
3. Voltage Adjust potentiometer — The voltage adjust
potentiometer is a way to adjust the voltage up or
down for fine tuning. The adjustment sends a signal to
the controller to offset the system rated voltage (Trim
Voltage). It is important that all machines are set to the
same value when paralleling.
When first turning on the control power, the controller
will begin its boot sequence much like a computer
does. After completing the boot sequence the unit
will be ready to run or be placed in auto for auto start
applications.
4. Control Power Toggle Switch — The control power
switch is a master power switch for the digital controller.
The control power switch has a latch feature that
prevents powering down control power while the engine
is running.
For units with manual operated breakers, the breaker
will need to be reset by toggling the handle down, then
can be turned back to the “ON” position. On models
with spring charged breakers resetting the breaker is
not necessary.
6. Contactor Operation (Manual Mode) — The For
manual run applications, user action is required to get
the generator power to the output bus. Depending on
the model, some utilize contactors in series with toggle
handle circuit breakers and others have spring charged
automatic circuit breakers.
On the spring charged types, the buttons on the breaker
itself are not intended for circuit breaker operation.
For instructional purposes both will be referred to as
“contactor”.
There are two pushbuttons on the control panel for
controlling the contactor. There is a green “CLOSE
CONTACTOR” button to close the contactor and a red
“OPEN CONTACTOR” button to open the contactor.
These buttons illuminate to show the contactor status.
If the contactor is open, the red “OPEN CONTACTOR”
button will be illuminated. If the contactor is closed
the green “CLOSE CONTACTOR” button will be
illuminated.
5. Emergency Stop Button Switch — The Emergency
Stop pushbutton switch is used to stop the engine in
case of emergency or to lock out operation during
service. The emergency stop button should not be used for routine stopping of the engine.
Actuation of the Emergency stop button while the
control power is on will illuminate the light on the button
as well as display “Emergency Stop” on the controller
display. Actuating the Emergency stop button will deenergize all controller outputs and cause the engine
to stop as well as tripping the circuit breaker. This
condition is a latched condition that must be reset prior
to restarting the engine.
The procedure for resetting the emergency stop
requires several actions. Rotate the emergency stop
button to release the spring latch. To clear the latch,
the controller must be placed into the off mode by
pressing the “OFF” button. While in the “OFF” mode,
the “RESET” button must be pressed to clear the
E-STOP fault.
These buttons can sometimes be multifunctional
depending on the situation. For stand-alone operation
the buttons simply close and open the contactor as
expected. For paralleling the buttons can act a little
different.
When the bus is already hot from another generator,
pressing the green online button will initiate a
synchronizing sequence before closing the contactor.
There will be an image of a synchro scope on the
controller display and when the voltage and phases
are matched, the contactor will close.
If there was already load on the bus the unit will slowly
ramp up load until it is sharing equally with the other
generator(s). While sharing load with other generators,
pressing the red “OPEN CONTACTOR” button once
will initiate a ramp down sequence. The unit will begin
to ramp down and when at a low level of load it will
automatically open it contactor. Pressing the red
“OPEN CONTACTOR” button twice will immediately
open the contactor.
The Output Terminal Panel (Figure 15) shown below is
provided for the connection of electrical loads. Lift up on
the cover to gain access to receptacles and terminal lugs.
NOTICE
Terminal legs “O” and “Ground” are considered bonded
grounds
300
V W
W
U
OUTPUT TERMINAL FAMILIARIZATION
The “Output Terminal Panel” (Figure 15) is provided with
the following:
Three (3) 240/139V output receptacles @ 50 amp
Three (3) Circuit Breakers @ 50 amps
Two (2) 120V GFCI receptacles @ 20 amp
Two (2) GFCI Circuit Breakers @ 20 amps
Eight (8) Output Terminal Lugs ( U, V, W, O, Ground)
There are two 120 VAC, 20 amp GFCI (Duplex Nema
5-20R) receptacles provided on the output terminal panel.
These receptacles can be accessed in any voltage change-over board position. Each receptacle is protected
by a 20 amp circuit breaker. These breakers are located
directly above the GFCI receptacles. Remember the load
output (current) of both GFCI receptacles is dependent on
the load requirements of the U, V, and W output terminal
lugs.
Pressing the reset button resets the GFCI receptacle after
being tripped. Pressing the test button (See Figure 15) in
the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.
Each auxiliary receptacle is protected by a 50 amp circuit
breaker. These breakers are located directly above the
GFCI receptacles. Remember the load output (current) on
all three receptacles is dependent on the load requirements
of the output terminal lugs.
Turn the voltage regulator control knob (Figure 17) on
the control panel to obtain the desired voltage. Turning the
knob clockwise will increase the voltage, turning the knob
counter-clockwise will decrease the voltage.
Figure 17. Voltage Regulator Control Knob
Figure 15. G.F.C.I. Receptacle
Twist Lock Dual Voltage 120/240 VAC Receptacles
There are three 240/139V, 50 amp auxiliary twist-lock
(CS-6369) receptacles (Figure 16) provided on the output
terminal panel. These receptacles can only be accessed
when the voltage change-over board is configured for
single-phase 240/120 application
Loads can be connected to the generator by the Output
Terminal Lugs or the convenience receptacles (Figure 18).
Make sure to read the operation manual before attempting
to connect a load to the generator.
To protect the output terminals from overload, a 3-pole,
800A main circuit breaker is provided. Make sure to switch ALL circuit breakers to the OFF position prior to starting
the engine.
TWIST-LOCK
RECEPTACLES
GFCI
RECEPTACLES
BLACK
U
HARD WIRE
HOOKUP PANEL
BLUE
RED
V
W
LOAD
WHITE
O
NEUTRAL
GREEN
GROUND
CAMLOCKS
LOAD
LOAD
Over Current Relay
An over current relay (Figure 19) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the reset button on the over
current relay must be pressed. The over current relay is
located in the control box.
Figure 19. Over Current Relay
NOTICE
Figure 18. Connecting Loads
Remember the overcurrent relay monitors the current
flowing from the U,V, and W Output Terminal Lugs
to the load.
In the event of a short circuit or over current condition,
it will automatically trip the 800 amp main breaker.
To restore power to the Output Terminal Panel, press
the reset button on the overcurrent relay and place the
Always be sure to check the nameplate on the generator
and equipment to insure the wattage, amperage, frequency,
and voltage requirements are satisfactorily supplied by the
generator for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require
130—150% more wattage than the rating on the nameplate,
as the wattage is influenced by the efficiency, power factor
and starting system of the equipment.
NOTICE
If wattage is not given on the equipment’s name plate,
approximate wattage may be determined by multiplying
nameplate voltage by the nameplate amperage.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generator is 0.8. See Table 7 below
when connecting loads.
Table 7. Power Factor By Load
Type of LoadPower Factor
Single-phase induction motors0.4-0.75
Electric heaters, incandescent lamps1.0
Fluorescent lamps, mercury lamps0.4-0.9
Electronic devices, communication
equipment
Common power tools0.8
Table 8. Cable Selection (60 Hz, Single Phase Operation)
Current
in
Amperes
2.53006001000 ft.600 ft.375 ft.250 ft.
56001200500 ft.300 ft.200 ft.125 ft.
7.59001800350 ft.200 ft.125 ft.100 ft.
1012002400250 ft.150 ft.100 ft.
1518003600150 ft.100 ft.65 ft.
2024004800125 ft.75 ft.50 ft.
Load in WattsMaximum Allowable Cable Length
At 100
Volts
CAUTION: Equipment damage can result from low voltage
At 200
Volts
#10 Wire #12 Wire #14 Wire #16 Wire
1.0
THREE PHASE LOAD
When calculating the power requirements for 3-phase
power use the following equation:
NOTICE
If 3Ø load (kVA) is not given on the equipment
nameplate, approximate 3Ø load may be determined
by multiplying voltage by amperage by 1.732
NOTICE
Motors and motor-driven equipment draw much greater
current for starting than during operation.
An inadequate size connecting cable which cannot carry the
required load can cause a voltage drop which can burn out
the appliance or tool and overheat the cable. See Table 6.
When connecting a resistance load such as an
incandescent lamp or electric heater, a capacity of up
to the generating set’s rated output (kW) can be used.
When connecting a fluorescent or mercury lamp, a
capacity of up to the generating set’s rated output (kW)
multiplied by 0.6 can be used.
When connecting an electric drill or other power tools,
pay close attention to the required starting current
capacity.
When connecting ordinary power tools, a capacity of up to
the generating set’s rated output (kW) multiplied by 0.8 can
be used.
DANGER
Before connecting this generator to any building’s
electrical system, a licensed electrician must install
an isolation (transfer) switch. Serious damage to
the building’s electrical system may occur without this
transfer switch.
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage change-over board (Figure 20). To obtain
some of the voltages as listed in Table 9 (see below) will
require a fine adjustment using the voltage regulator (VR)
control knob located on the control panel.
Voltage Change-Over Board
The voltage change-over board (Figure 20) is located on
the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.
Maximum Amps
Table 10 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
Table 10. Generator Maximum Amps
Rated VoltageMaximum Amps
1Ø 120 Volt666.7 X 2 amps (4 wire)
1Ø 240 Volt333.3 amps (4 wire)
3Ø 240 Volt722 amps
3Ø 480 Volt360 amps
Main Line Circuit
Breaker Rating
800 amps
Figure 20. Voltage Change-Over Board
CAUTION
NEVER attempt to place jumper plates on the voltage
change-over board while the generator is in operation. There exist the possibility of electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death!
Table 9. Voltages Available
UVWO Output
Terminal Lugs
Line-Line
3Ø
1Ø Line-Neutral120V127V139V240V254V277V
1Ø Line-Neutral/
Line-Line
Voltage Change-Over Board
3-Phase 240/139V Position
208V220V240V416V440V480V
Voltage Change-Over Board Single-Phase 240/120V Position
The AC ammeter and AC voltmeter gauges are controlled
by the AC ammeter and AC voltmeter change-over switches.
Both of these switches are located on the control panel and
DO NOT effect the generator output. They are provided to
help observe how much power is being supplied, produced
at the UVWO terminals lugs.
Before taking a reading from either gauge, configure the
Voltage Change-Over Board (Figure 21) for the desired
output voltage.
AC Ammeter Gauge Reading
Place the AC Ammeter Change-Over Switch (Figure 24)
in the U position and observe the current reading (load
drain) on the U terminal as indicated on the AC Ammeter Gauge (Figure 25). This process can be repeated for
terminals V and W.
Figure 24. AC Ammeter
Change-Over Switch
NOTICE
The ammeter gauge will only show a reading when
the Output Terminal Lugs are connected to a load
and in use.
Figure 25. AC Ammeter
(Amp reading on U Lug)
Figure 21. Voltage Change-Over Board-
Ø Position
240/3
AC Voltmeter Gauge Reading
Place the AC Voltmeter Change-Over Switch (Figure 22)
in the W-U position and observe the phase to phase voltage
reading between the W and U terminals as indicated on
the AC Voltmeter Gauge (Figure 23).
Figure 22. AC Voltmeter
Change-Over Switch
Figure 23. AC Voltmeter Gauge
(Volt reading on W-U Lug)
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are
dependent on the placement of the jumpers plates (6) on
the Voltage Change-Over Board and the adjustment of
the Voltage Regulator Control Knob.
Remember the voltage change-over board determines the
range of the output voltage and can be configured in two
different positions that provide 6 different output voltages
at the UVWO output terminals. The generator is shipped
from the factory in the 240V configuration. The voltage
regulator (VR) allows the user to increase or decrease the
selected voltage.
3Ø-240V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 240V
operation as shown in Figure 26
3. Turn the voltage regulator knob (Figure 28) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required
Figure 28. Voltage Regulator Knob
1Ø-240V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 26.
2. Connect the load wires to the UVWO terminals as
shown in Figure 29.
BLACK
U
240V
RED
V
BLUE
W
240V
WHITE
O
GREEN
Figure 26. Voltage Change-Over Board 240V
Configuration
2. Connect the load wires to the UVWO terminals as
shown in Figure 27
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 26.
2. Adjust voltage regulator knob (Figure 28) for an output
of 208V to obtain 120V at the UVWO terminals.
3. Connect the load wires to the UVWO terminals as
shown in Figure 30
BLACK
U
RED
V
SINGLE-PHASE
BLUE
W
120V
120V
120V
Figure 30. UVWO Terminal Lugs 1Ø-120V
Connections
WHITE
O
GREEN
GROUND
CONNECTION
MUST
AT ALL TIMES
OUTPUT TERMINAL PANEL CONNECTIONS
BE USED
480 VAC (LOAD CONNECTIONS)
BE USED
277 VAC (LOAD CONNECTIONS)
NOTICE
ALWAYS make sure that the connections to the UVWO
terminals are secure and tight. The possibility of arcing
exist that could cause a fire.
3Ø-480V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 480V
operation as shown in Figure 31. This configuration
uses 6 jumper plates in 3 different positions. Remember
there are 2 jumper plates at every position. Every
jumper plate must be used.
1Ø-480V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 480V operation as shown in Figure 31.
2. Connect the load wires to the UVWO terminals as
shown in Figure 33.
BLACK
U
RED
V
480V
480V
THREE-PHASE
BLUE
W
480V
Figure 33. UVWO Terminal Lugs 1Ø-480V
Connections
WHITE
O
GREEN
GROUND
CONNECTION
MUST
AT ALL TIMES
1Ø-277V UVWO Terminal Output Voltages
Figure 31. UVWO Terminal Lugs 1Ø-120V
Connections
2. Connect the load wires to the UVWO terminals as
shown in Figure 32.
BLACK
U
RED
V
THREE-PHASE
480 VAC (LOAD CONNECTIONS)
BLUE
W
Figure 32. UVWO Terminal Lugs
3Ø-480V Connection
WHITE
O
GREEN
GROUND
CONNECTION
BE USED
MUST
AT ALL TIMES
1. Make sure the voltage change-over board is jumpered
for 480V operation as shown inFigure 31.
2. Connect the load wires to the UVWO terminals as
shown in Figure 34.
To protect the generator from an overload, a 3-pole, 800
amp, main circuit breaker is provided to protect the U , V, and W Output Terminals from overload. In addition two
single-pole, 20 amp GFCI circuit breakers are provided to
protect the GFCI receptacles from overload. Three 50 amp
load circuit breakers have also been provided to protect the
auxiliary receptacles from overload. Make sure to switch
ALL circuit breakers to the OFF position prior to starting
the engine.
LUBRICATION OIL
Fill the engine crankcase with lubricating oil through the
filler hole, but DO NOT overfill. Make sure the generator is
level and verify that the oil level is maintained between the
two notches (Figure 35) on the dipstick. See Table 11 for
proper selection of engine oil.
FUEL CHECK
DANGER
Fuel spillage on a hot engine can cause
a fire or explosion. If fuel spillage occurs,
wipe up the spilled fuel completely to
prevent fire hazards. NEVER smoke
around or near the generator.
Refilling the Fuel System
CAUTION
ONLY properly trained personnel who have read
and understand this section should refill the fuel tank
system.
This generator has an internal fuel tank located inside the
enclosure (). ALWAYS fill the fuel tank with clean fresh #2 diesel fuel. DO NOT fill the fuel tank beyond its capacity.
Some units may be equipped with a fuel cell mounted inside
the trailer frame.
Figure 35. Engine Oil Dipstick
When checking the engine oil, be sure to check if the oil is
clean. If the oil is not clean, drain the oil by removing the
oil drain plug, and refill with the specified amount of oil as
outlined in the John Deere Owner’s Manual. Oil should
be warm before draining.
API service class engine oil is the recommended engine
oil for this generator. When replacing engine oil please refill
using API CJ-4, ACEA E9 or ACEA E6 engine oil.
Table 11. Recommended Motor Oil
Pay attention to the fuel tank capacity when replenishing
fuel. The fuel tank cap must be closed tightly after filling.
Handle fuel in a safety container. If the container does
not have a spout, use a funnel. Wipe up any spilled fuel
immediately.
to your health and the surrounding
environment. Avoid skin contact and/or
inhaling fumes.
1. Level Tanks — Make sure fuel cells are level with the
ground. Failure to do so will cause fuel to spill from the
tank before reaching full capacity (Figure 37).
CAUTION
ALWAYS place trailer on firm level ground before
refueling to prevent spilling and maximize the amount
of fuel that can be pumped into the tank.
300
DO NOT fill on
unlevel ground
!
!
3. NEVER overfill fuel tank — It is important to read the
fuel gauge when filling trailer fuel tank. DO NOT wait
for fuel to rise in filler neck (Figure 39).
FUEL GAUGE LOCATED
ON GAUGE UNIT ASSEMBLY
½
°F
E
F
FUEL
Figure 39. Full Fuel Tank
CAUTION
DO NOT OVERFILL fuel system. Leave room for fuel
expansion. Fuel expands when heated (Figure 40).
=
Level Ground
Level Ground
Figure 37. Only Fill on Level Ground
NOTICE
ONLY use #2 diesel fuel (ultra low sulfur diesel fuel)
when refueling.
2. Open the enclosure door and remove fuel cap and fill
tank as shown in Figure 38.
ONLY fill the DEF tank with diesel exhaust fluid. Any
other type of fluid may cause severe engine damage.
Diesel exhaust fluid is an aqueous solution made with 32.5%
high puirty urea carbamide) and 67.5 deionized water. DEF
is used as a consumable in selective catalytic reduction
(SCR) in order to lower NOx concentration from diesel exhaust
emissions.
1. Make sure engine is OFF.
2. Open the enclosure door and remove the filler cap from
the DEF tank (Figure 41).
3. Upon initial start up, completely fill the DEF tank with
DEF fluid. DO NOT overfill.
DEF Refilling (Continuous Operation)
It is recommended to shut down the engine prior to refilling
the DEF tank. However, in special applications where shutdown
is not possible, it is recommended to ONLY refill the DEF tank
when the fluid level has been consumed down to 50%.
COOLANT (ANTIFREEZE/SUMMER COOLANT/
WATER)
John Deere recommends Cool-Gard II
coolant for use in their engines, which can be purchased in
concentrate (and mixed with 50% demineralized water) or
pre-diluted. See the John Deere Engine Owner’s Manual
for further details.
WARNING
If adding coolant/antifreeze mix to the
radiator, DO NOT remove the radiator cap
until the unit has completely cooled. The
possibility of hot! coolant exists which can
cause severe burns.
Day-to-day addition of coolant is done from the recovery
tank. When adding coolant to the radiator, DO NOT remove
the radiator cap until the unit has completely cooled. See
Table 12 for engine, radiator, and recovery tank coolant
capacities. Make sure the coolant level in the recovery tank
is always between the “H” and the “L” markings.
Table 12. Coolant Capacity
TM
antifreeze/summer
The DEF level sending unit requires a gradual DEF level
decrease during continuous operation to validate proper
operation. Failure of this sensor to report the decrease could
result in an engine shutdown. A engine service technician
would be required to remedy the shutdown.
DEF TANK
CAUTION
EXHAUST FLUID ONLY
Filling this tank with
D
anything other than
DIESEL EXHAUST FLUID
No Diesel
may result in severe
engine damage.
M94110000
Figure 41. DEF Tank Filling
CAP
REAR VIEW
Engine and Radiator17.7gal (67 liters)
Reserve TankN/A
Operation in Freezing Weather
When operating in freezing weather, be certain the proper
amount of antifreeze (Table 13) has been added.
Table 13. Coolant Capacity
Climate
Warm
Cold
Outside
Temperature
10°F (-12°C) or
Above
-22°F (30°C) or
Above
NOTICE
When the antifreeze is mixed with water, the antifreeze
mixing ratio must be less than 50%.
The engine may overheat if the radiator fins become
overloaded with dust or debris. Periodically clean the
radiator fins with compressed air. Cleaning inside the
machine is dangerous, so clean only with the engine turned
off and the negative battery terminal disconnected.
AIR CLEANER
Periodic cleaning/replacement is necessary. Inspect
air cleaner in accordance with the John Deere Engine
Owner’s Manual.
FAN BELT TENSION
A slack fan belt may contribute to overheating, or to
insufficient charging of the battery. Inspect the fan belt for
damage and wear and adjust it in accordance with the John
Engine Owner’s Manual.
The fan belt tension is proper if the fan belt bends 10 to
15 mm (Figure 42) when depressed with the thumb as
shown below.
BATTERY
This unit is of negative ground DO NOT connect in reverse.
Always maintain battery fluid level between the specified
marks. Battery life will be shortened, if the fluid level are
not properly maintained. Add only distilled water when
replenishment is necessary.
DO NOT over fill. Check to see whether the battery
cables are loose. Poor contact may result in poor starting
or malfunctions. Always keep the terminals firmly
tightened. Coating the terminals with an approved battery
terminal treatment compound. Replace battery with only
recommended type battery. The battery type used in this
generator is BCI Group 27.
The battery is sufficiently charged if the specific gravity
of the battery fluid is 1.28 (at 68° F). If the specific gravity
should fall to 1.245 or lower, it indicates that the battery is
dead and needs to be recharged or replaced.
Before charging the battery with an external electric source,
be sure to disconnect the battery cables.
Battery Cable Installation
Figure 42. Fan Belt Tension
CAUTION
NEVER place hands near the belts or fan
while the generator set is running.
0.17 ~ 0.20 IN.
(4.2 ~ 5.0 MM)
DEFLECTION
ALWAYS be sure the battery cables (Figure 43) are
properly connected to the battery terminals as shown below.
The red cable is connected to the positive terminal of the
battery, and the black cable is connected to the negative
terminal of the battery.
CAUTION
ALWAYS disconnect the negative terminal FIRST and reconnect negative terminal LAST.
1. NEVER connect the battery cables to the battery
terminals when the Auto-Off/Reset-Manual Switch
is in either the AUTO or MANUAL position. ALWAYS
make sure that this itch is in the OFF/RESET position
when connecting the battery.
2. Place a small amount of battery terminal treatment
compound around both battery terminals. This will
ensure a good connection and will help prevent
corrosion around the battery terminals.
NOTICE
If the battery cable is connected incorrectly, electrical
damage to the generator will occur. Pay close attention
to the polarity of the battery when connecting the battery.
CAUTION
Inadequate battery connections may cause poor
starting of the generator, and create other malfunctions.
ALTERNATOR
This unit is equipped with an automatic controlled Engine
Starting Fluid System (KBi’s DIESELMATIC NVT) that
assists the engine starting during low ambient temperature
operation.
The system is designed to spray a controlled amount of
starting fluid into the air intake system of the engine during
and immediately after the engine cranks. The fluid cylinder
is located on the unit’s right side center frame.
WARNING
The engine starting fluid used in the system is extremely
flammable and toxic. It can be harmful and fatal if
swallowed. Avoid contact with skin or breathing fumes.
DO NOT smoke when installing, removing, maintaining,
testing or troubleshooting the system. Make sure you are
in a well-ventilated area away from heat, open flames
or sparks.
In low ambient temperature condition, if the engine does
not start within a normal period of cranking, the starting
fluid cylinder may be empty and need to be replaced. For
more information about the system, refer to the provided
KBi DIESELMATIC NVT Instruction Manual.
The polarity of the alternator is negative grounding type.
When an inverted circuit connection takes place, the
circuit will be in short circuit instantaneously resulting the
alternator failure.
DO NOT put water directly on the alternator. Entry of water
into the alternator can cause corrosion and damage the
alternator.
WIRING
Inspect the entire generator for bad or worn electrical wiring
or connections. If any wiring or connections are exposed
(insulation missing) replace wiring immediately.
PIPING AND HOSE CONNECTION
Inspect all piping, oil hose, and fuel hose connections for
wear and tightness. Tighten all hose clamps and check
hoses for leaks.
If any hose (fuel or oil) lines are defective replace them
immediately. cold weather engine starting fluid (ether
system)
The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilationwhen operating.
Direct exhaust away from nearby personnel.
WARNING
NEVER manually start the engine with the main, GFCI
or auxiliary circuit breakers in the ON (closed) position.
1. Place the main, G.F.C.I., and aux. circuit breakers
(Figure 44) in the OFF position prior to starting the
engine.
STARTING (MANUAL)
1. Place the Auto-Off/Reset Manual Switch in the
MANUAL position to start the engine (Figure 46).
Figure 46. Auto-Off/Reset Manual Switch
(Manual Position)
NOTICE
If engine fails to start in a specified number attempts,
the shutdown lamp will illuminate and the Auto-Off/
Reset Switch must be placed in the Off/Reset position
before the engine can be restarted.
NOTICE
Engine will pre-heat automatically in cold weather
conditions." Glow Plug Hold " message will be displayed
and the engine will start automatically after pre-heating..
Figure 44. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Make sure the voltage change-over board has been
configured for the desired output voltage.
3. Connect the load to the receptacles or the output
terminal lugs as shown in Figure 18. These load
connection points can be found on the output terminal
panel and the output terminal panel’s hard wire hookup
panel.
4. Tighten terminal nuts securely to prevent load wires
from slipping out.
5. Close all engine enclosure doors (Figure 45).
2. Once the engine starts, let the engine run for 1-2
minutes Let engine idle longer in cold weather
conditions. Listen for any abnormal noises. If any
abnormalities exist, shut down the engine and correct
the problem.
3. The generator’s frequency meter (Figure 47) should be
displaying the 60 cycle output frequency in HERTZ.
Figure 47. Frequency Meter
4. The generator’s AC-voltmeter (Figure 48) will display
the generator’s output in VOLTS.
5. If the voltage is not within the specified tolerance, use
the voltage adjustment control knob (Figure 49) to
increase or decrease the desired voltage.
Figure 49. Voltage Adjust Control Knob
6. The ammeter (Figure 50) will indicate zero amps with
no load applied. When a load is applied, the ammeter
will indicate the amount of current that the load is
drawing from the generator.
Figure 50. Ammeter (No Load)
7. The engine oil pressure gauge (Figure 51A) will
indicate the oil pressure of the engine. Under normal
operating conditions the oil pressure is approximately
35 to 65 psi. (193~586 kPa).
10. The generator load gauge (Figure 52) Indicates the
generator load rate. It is recommended the load be
above the red area (20%) for maintaining sufficient
exhaust temperature.
50
0
%
100
Figure 52. Generator Load Gauge
11. Place the main, GFCI, and aux. circuit breakers in the
ON position (Figure 53).
25
0
50
PSI
OIL PRESS
75
100
140
100
WATERTEMP
180
°F
220
260
AB
150
120
60
0
RPMX10
SPEED
180
210
C
Figure 51. Engine Gauges
8. The coolant temperature gauge (Figure 51B) will
indicate the coolant temperature. Under normal
operating conditions the coolant temperature should
be between 185°~207°F (85°~97°C).
9. The tachometer gauge (Figure 51C) will indicate the
speed of the engine when the generator is operating.
Under normal operating conditions this speed is
approximately 1800 RPM’s.
Figure 53. Main, Aux. and GFCI
Circuit Breakers (ON)
12. Observe the generator’s ammeter (Figure 54) and
verify it reads the anticipated amount of current with
respect to the load. The ammeter will only display a
current reading if a load is in use.
Figure 54. Ammeter (Load)
13. The generator will run until manually stopped or an
abnormal condition occurs.
Before connecting this generator to any
building’s electrical system, a licensed
electrician must install an isolation
(transfer) switch. Serious damage to
the building’s electrical system may occur
without this transfer switch.
CAUTION
When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
NOTICE
When the generator is set in the AUTO mode, the
generator will automatically start in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
WARNING
When running the generator in the AUTO mode,
remember the generator can start up at any time without
warning. NEVER attempt to perform any maintenance
when the generator is in the auto mode.
NOTICE
When the Auto Off/Reset ManualSwitch is placed
in the AUTO position, the engine glow plugs will be
warmed and the engine will start automatically.
When starting generator in AUTO mode use the “Manual
Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the Auto Off/Reset Manual Switch (Figure 55)
in the AUTO position.
Figure 55. Auto Off/Reset Manual Switch (AUTO)
3. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 2).
NOTICE
If the unit has Power Balance™ installed and once
the main breaker is closed, the Power Balance™
should activate after 1 minute if the load is below 30%
of rated load.
If at any time the load spikes to 90% or more, the Power
Balance will immediately drop out and wait 5 minutes
to re-evaluate the load.
*1 During initial operation of a new engine, change oil and filter between a minimum of 100 hrs. and a maximum of 500 hrs. Service interval depends
on type of oil.
2
Perform inspection and maintenance of Urea SCR system every 4500 hours. The system does not need to replace/exchange if no problem is
*
found. Do not make any modification, changes or remove the emission control system and related parts. Please contact your nearest dealer or
Multiquip Service Dept. for SCR maintenance.
3
If John Deere COOL-GARD™ II is used, the flushing intervals may be extended. See "Testing Diesel Coolant" in engine manual.
*
*4 Replace primary air filter element when restriction indicator shows a vacuum of 625 mm (25 in. H20).
*5 Service should be done as indicated by Diagnostic Gauge. Contact Multiquip Service Dept. for DOC replacement.
Prior to each use, the generator should be cleaned and
inspected for deficiencies. Check for loose, missing or
damaged nuts, bolts or other fasteners. Also check for
fuel, oil, and coolant leaks. Use Table 14 as a general
maintenance guideline Engine Side (Refer to the Engine
Instruction Manual)
Air Filter Dust Indicator
NOTICE
The air filter should not be changed until the indicator
reads “RED”. Dispose of old air filter. It may not be
cleaned or reused.
The air filter indicator (Figure 59) is attached to the air filter.
When the air filter element is clogged, air intake restriction
becomes greater and the air filter indicator signal shows
RED. When indicator is red, replace filter immediately.
After changing the air filter, press the air filter indicator
button to reset.
CAUTION
Wear protective equipment such as
approved safety glasses or face shields
and dust masks or respirators when
cleaning air filters with compressed air.
Primary and Secondary Air Cleaner Elements
1. Release the latches (Figure 60) that secures the cover
to the air cleaner body.
2. Remove the air cleaner cover and set aside.
3. Remove both the primary and secondary air cleaner
elements.
4. Check the air cleaner daily or before starting the engine.
5. Check for and correct heavy buildup of dirt and debris
along with loose or damaged components.
NOTICE
Operating the engine with loose or damaged air cleaner
components could allow unfiltered air into the engine
causing premature wear and failure.
Figure 59. Air Filter Dust Indicator
AIR CLEANER
NOTICE
If the engine is operating in very dusty or dry grass
conditions, a clogged air cleaner will result. This can
lead to a loss of power, excessive carbon buildup in
the combustion chamber and high fuel consumption.
Change air cleaner more frequently if these conditions
exist.
Every 250 hours: Remove air cleaner element (Figure 60)
and clean the heavy duty paper element with light spray of
compressed air. Replace the air cleaner as needed.
This John Deere diesel engine is equipped with a
replaceable, high-density paper air cleaner element.
This air cleaner is also equipped with an inner element
(secondary) that is used as a backup filter should the
primary element becomes damaged.
25 INCHES HO
6.23 kPa
6. To clean the primary element (paper air filter) as
referenced in (Figure 60), tap the filter element
several times on a hard surface to remove dirt, or blow
2
compressed air not to exceed 30 psi (207 kPa, 2.1
2
kgf/cm
BODY
) through the filter element from the inside out.
PRIMARY
AIR FILTER
ELEMENT
SECONDARY
AIR FILTER
ELEMENT
BLOW COMPRESSED
AIR FROM THE
INSIDE OUT
Figure 60. Air Cleaner
AIR FILTER
INDICATOR
LATCH
EVACUATOR
ARROW
(DUST P
VALV E
MARK
7. Clean the secondary element (paper air filter) as
referenced in step 6.
8. Replace both elements if they are damaged or
excessively dirty.
10. Reinstall the primary and secondary air filter elements
back into air cleaner body.
11. Reinstall the air cleaner cover, and secure with latches.
DRAINING FUEL FILTER CARTRIDGE
NOTICE
Inspect the fuel filter daily. If the fuel filter (Figure 61) has
collected a significant amount of water and sediment
at the bottom of the cartridge, it should be drained off
immediately.
1. Loosen the air bleeder plug (Figure 61) on the fuel
filter body.
2. To discharge the fuel inside the fuel filter cartridge
OPEN the drain valve on the fuel filter by turning the
knob counterclockwise (A) approximately 3-1/2
turns until the valve drops down 1-inch (25.4 mm) and
draining occurs (B).
FUEL FILTER ELEMENT REPLACEMENT
1. Use a filter wrench to remove the fuel filter cup
(Figure 62) from the fuel filter body.
FIL
(HEAD)
RETAINING
RING
GASKET
GASKET
FILTER
CARTRIDGE
AIR BLEEDER
PLUG
FUEL FILTER
CARTRIDGE
DRAIN VALV E
FILTER BODY
(HEAD)
RETAINING
RING
A
B
OPEN
DRAIN
Figure 61. Fuel Filter Draining
C
CLOSE
Figure 62. Fuel Filter Cartridge Replacement
2. Wipe the inside of the filter body (head) with a clean
cloth to remove any foreign matter or debris that may
have accumulated.
3. Replace both gaskets. Coat each gasket with a small
amount of clean 15W-40 engine oil.
4. Install new fuel filter cartridge first by hand until it makes
contact with the fuel filter body surface.
5. Tighten fuel filter cartridge securely. DO NOT over-
tighten.
6. Remove the air from the fuel system. Reference John
Deere Owner's Manual, "Bleeding the Fuel System.
3. Let the residue or foreign substances inside the
cartridge flow into a suitable container.
4. At completion of draining CLOSE drain valve (C).
1. Remove the sediment bowl from the fuel water
separator cartridge as shown in Figure 63.
Figure 63. Sediment Bowl
2. Let the residue or foreign substances inside the
sediment bowl flow into a suitable container.
FUEL WATER SEPARATOR REPLACEMENT
1. Use a filter wrench to remove the fuel water separator
cartridge (Figure 59) from the cartridge body head.
CARTRIDGE BODY
(HEAD)
RETAINING
RING
FUEL WATER
SEPARATOR
CARTRIDGE
Figure 64. Fuel Water Separator
2. Wipe the inside of the fuel water separator cartridge
body (head) with a clean cloth to remove any foreign
matter or debris that may have accumulated.
3. Wipe the inside of the sediment bowl with a clean cloth
to remove any foreign matter or debris that may have
accumulated.
4. Reinstall sediment bowl back onto fuel water separator
cartridge
5. Tighten securely. DO NOT over-tighten.
3. Install new fuel water separator cartridge first by hand
until it makes contact with the cartridge body (head)
surface.
4. Tighten fuel water cartridge securely. DO NOT over-
tighten.
Removing Water from the Fuel Tank
After prolonged use, water and other impurities accumulate
in the bottom of the tank. Occasionally inspect the fuel tank
for water contamination and drain the contents if required.
During cold weather, the more empty volume inside the
tank, the easier it is for water to condense. This can be
reduced by keeping the tank full with diesel fuel.
If necessary, drain the fuel inside the fuel tank completely.
Using a spray washer (Figure 65) wash out any deposits
or debris that have accumulated inside the fuel tank.
FUEL TANK
Drive Belt Inspection
Inspect the drive belt for damage and wear. Horizontal
cracks (across the belt) are acceptable. Vertical (direction
of belt ribs) cracks that intersect with horizontal cracks are
not acceptable.
Also, examine the belt and determine if it is oil soaked or
"glazed " (hard shiny appearance on the sides of the belt).
Either of these two conditions can cause the belt to run hot,
which can weaken it and increase the danger of it breaking.
If the drive belt exhibits any of the above wear conditions,
replace the drive belt immediately.
NO
Figure 65. Fuel Tank Cleaning
FUEL TANK INSPECTION
In addition to cleaning the fuel tank, the following
components should be inspected for wear:
Rubber Suspension — Look for signs of wear or
deformity due to contact with oil. Replace the rubber
suspension if necessary.
Fuel Hoses — Inspect nylon and rubber hoses for signs
of wear, deterioration and hardening.
Fuel Tank Lining — Inspect the fuel tank lining for signs
of excessive amounts of oil or other foreign matter.
DRIVE BELT DAILY)
Drive Belt Tension
A slack drive belt (Figure 12) may contribute to overheating,
or to insufficient charging of the battery, adjust drive belt in
accordance with the John Deere Operator's manual.
NO
Figure 66. Drive Belt Inspection
ENGINE OIL CHECK (DAILY)
1. When checking or adding oil, place the machine so
the engine is level.
2. Pull the engine oil dipstick from its holder.
3. Determine if engine oil is low. Oil level should be
between the upper land lower limit (Figure 67) on the
dipstick.
4. If oil level is low, add correct amount of engine oil to
bring oil level to a normal safe level. See Recommended
Viscosity Grades.
5. Allow enough time for any added oil to make its way
to the oil pan before rechecking.
Table 15. Oil Selection Chart
5W/40
OIL: SAE
10W/30
10W
10W/40
15W/40
40
30
20W/20
F
86
68
50
-14
-4
-22
-40
50
40
30
20
10
-10
-20
-30
-40
C
032
5W/30
DRAINING ENGINE OIL
1. Run the engine until the engine coolant reaches a
temperature of 140°F (60°C) Turn the engine off.
ENGINE OIL FILTER REPLACEMENT
1. Using an oil filter wrench (Figure 69), remove engine
oil filter.
OIL FILTER
HEAD
FILTER
WRENCH
REMOVE AND
DISCARD OIL FILTER
INSTALL
NEW OIL
FILTER
COAT RUBBER
SEAL WITH THIN
LAYER OF OIL
2. Remove the oil dipstick from its holder.
3. Next, remove oil drain cap (Figure 68)
4. Place the oil drain valve in the OPEN position and
allow the oil to drain into a suitable container.
OIL DRAIN
CAP
(REMOVE)
OPEN
OIL
DRAIN
VALV E
Figure 68. Draining Engine Oil
5. After engine oil has been completely drained, reinstall
oil drain cap and tighten securely.
6. Place the oil drain valve in the CLOSED position.
Figure 69. Engine Oil Filter Removal
2. Clean the area around the lubricating oil filter head.
3. Coat the rubber seal (gasket) surface of oil
filter (Figure 69) with clean 15W-40 engine oil.
4. Install new oil filter first by hand until it makes contact
with the filter head surface. Tighten it another 3/4 turn
using the filter wrench.
5. Fill engine crankcase with high quality detergent oil
classified "For Service CI-4". Fill to the upper limit of
dipstick. DO NOT overfill. Reference Table 2 for engine
crankcase oil capacity.
6. Run the engine for several minutes. Watch for oil
leakage. Shut the engine down and allow it to sit for
several minutes. Top off the oil to the upper limit on
the dipstick.
radiator when the engine is hot! Wait until
the coolant temperature is below 120°F
(50°C) before removing pressure cap.
Heated coolant spray or steam can cause severe
scalding and personal injury.
1. Place the coolant drain valve in the OPEN position
(Figure 70) and allow the coolant to drain into a suitable
container.
RADIATOR CLEANING
The radiator (Figure 71) should be sprayed cleaned) with
a high pressure washer when excessive amounts of dirt
and debris have accumulated on the cooling fins or tube.
When using a high pressure washer, stand at least 5 feet
(1.5 meters) away from the radiator to prevent damage to
the fins and tube.
Figure 70. Draining Engine Coolant
2. Check hoses for softening and kinks. Check clamps
for signs of leakage.
3. Remove and inspect radiator cap.
4. Flush the radiator by running clean tap water through
radiator until signs of rust and dirt are removed. DO NOT clean radiator core with any objects, such as a
screwdriver.
5. Tighten water cock and replace the overflow tank.
6. Place the coolant drain valve in the CLOSED position.
Figure 71. Radiator Cleaning
GENERATOR STORAGE
For long term storage of the generator the following is
recommended:
Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
Clean the entire generator, internal and external.
Cover the generating set and store in a clean, dry place.
Disconnect the battery.
Make sure engine coolant is at proper level.
If generator is mounted on a trailer, jack trailer up and
place on blocks so tires do not touch the ground or block
and completely remove the tires.
7. Replace with coolant as recommended by the engine
manufacturer.
ENGINE BLOCK HEATING ELEMENT AND
INTERNAL BATTERY CHARGER 120 VAC INPUT
RECEPTACLES (OPTIONAL)
This generator can be equipped as an option with a
engine block heating element and an internal battery
charger. They are provided with electric cords to connect
to a commercial power source.
The engine block heating element and internal battery
charger both require 120 VAC in order to operate. A
receptacle (Figure 72) has been provided on the output
terminal panel to allow commercial power to be applied.
These units will ONLY function when commercial power
has been supplied to them. When using extension cords,
refer to Table 6 for the correct size and length.
HEATING ELEMENT
When using the generator in hot climates, there is no need
to apply power to jacket water heater (heating element).
However, if the generator will be used in cold climates, it is
best to apply power to the jacket water heater at all times.
If the generator will be used daily, the battery should
normally not require charging. If the generator will be idle
(not used) for long periods of time, apply power to the
battery charger receptacle via commercial power using a
power cord of adequate size.
NOTICE
If the generator will be idle (not used) for long periods
of time and to ensure adequate starting capability,
always have power applied to the generator's internal
battery charger.
BATTERY CHARGER
HEATING ELEMENT
120 VAC INPUT
RECEPTACLE
OUTPUT TERMINAL
PANELASSEMBLY
BATTERY CHARGER
120 VAC INPUT
RECEPTACLE
TO CHASSIS
GROUND
GREEN 16 A
!
TO STARTER “B”
TERMINAL
RED 16 AWG.
Figure 72. Heater Element and Battery Charger (Option)
The emission control system employed with the John
Deere 6090HF diesel engine consist of a Diesel Oxidation
Catalyst (DOC) and a Selective Catalytic Reduction
(SCR) catalyst as an exhaust gas after-treatment system
that helps reducing harmful gases and destroying the
organic fraction of the particulate matter produced from
the exhaust gas to meet the requirement for EPA Tier 4
Final regulations.
The DOC device (Figure 73) helps in filtering out large
amounts of harmful Nitrogen Oxides (NOx) and Particulate Matter (PM) which are emitted by diesel engines. These
exhaust emissions pose serious environmental and health
risks. It is important to maintain and service the DOC
emission safety device on a periodic basis.
Diesel Oxidation Catalyst (DOC)
The DOC does not filter particles it oxidizes them. This
catalyst (honeycomb like structure) uses a chemical
process to break down pollutants in the exhaust stream
into less harmful components. In general, this catalyst
collects/burns accumulated particulates. The DOC contains
palladium and platinum which serve as a catalysts to oxidize
hydrocarbons and carbon monoxide.
EMISSION CARBON CHECK
Deposition of carbon (soot, unburned fuel) in the exhaust
pipe line and muffler could cause not only system derates
but also could lead to fires.
To reduce soot and unburned fuel, run the unit at rated
power until the exhaust gas becomes mostly colorless every
250 hours operation time. More carbon will be generated
when the unit operates at less then 30% of rated power. In
this case, perform the above procedures more frequently.
NOTICE
Applying a large load suddenly to the unit when the
carbon deposition is generated in the exhaust system
could produce sparks and will lead to abnormal
combustion. Therefore, apply load gradually and
observe the exhaust gas color during the process.
Diesel engines can be run with a lean burn air-to-fuel ratio,
to ensure the full combustion of soot and to prevent the
exhaust of unburnt fuel. The excess of air necessarily leads
to generation of nitrogen oxides (NOx), which are harmful
pollutants, from the nitrogen in the air. Selective Catalytic Reduction is used to reduce the amount of NOx released
into the atmosphere.
Diesel Exhaust Fluid (DEF) from a separate tank is
injected into the exhaust pipeline, where the aqueous urea
vaporizes and decomposes to form ammonia and carbon
dioxide. Within the SCR catalyst, the NO
reduced by the ammonia (NH3) into water (H2O) and
nitrogen (N2), which are both harmless; and these are then
released through the exhaust.
The SCR system creates a certain amount of ammonia
) that is stored in SCR catalyst. During purging
(NH
3
operations the increase in temperature at regular intervals
eleminates the stored ammonia.
The process of keeping accurate amonia storage amounts
is by counting urea injection quantities from the Dosing
Control Unit (DCU)
The SCR Purge symbol (Figure 74) will be displayed on the
ECU controller during operation when either an automatic
or forced system purge operation is in process.
The pre-alarm lamp is only ON during SCR forced system
purging and OFF during automatic system purging
ECU
Series 800 Controller
are catalytically
x
Engine Started
Shutdown
Pre-Alarm
NOTICE
During urea SCR system purging, white smoke may
be emitted from the exhaust tailpipe temporarily this
shoud not be considered a failure. In addition the smell
of ammonia during the purging process should not be
considered a failure.
If the purging process is underway while running a light
load (0-35%) the unit may produce unusual sounds.
This should not be considered a failure or malfunction.
SYSTEM PURGING GUIDELINES
NOTICE
DO NOT perform purging in conditions where it may be
unsafe due to high exhaust temperatures.
For safe operation of equipment, the surrounding area and
the prevention of bodily harm, use the guidelines below
when system purging is required:
NOTICE
The area above and around the generator during the
purging process should be free of any type of debris,
flammable or combustible materials, as temperatures
during the purging process can reach as high
1,022 °F (550 °C).
DO NOT operate the unit in area with poor ventilation.
If operating the engine indoors, install exhaust/ventilation
equipment and ensure that there is sufficient ventilation.
If you begin to feel sick, stop the unit immediately and
ventilate the area.
Exhaust emissions from the tailpipe have a smell different
from those emitted from engines without urea SCR
systems due to the exhaust emission reduction functions
of the exhaust system.
If the diesel exhaust fluid (DEF) symbol (Figure 75) is
displayed during ECU controller operation, it indicates the
following:
DEF tank level is below 10%. Reference Table 16, DEF
Level System Action System.
DEF quality is poor. Check DEF tank level and check
active diagnostics trouble codes (DTC).
ECU
Series 800 Controller
Alarm
Acknowledge
Screen
Change
DEF STAT
Program
Option
Engine Started
Shutdown
Pre-Alarm
Exit
DIESEL EXHAUST FLUID (DEF)
The amount of fluid in the DEF tank will be shown on the
ECU Controller main screen during operation. The symbol
shown in Figure 76 will be shown on the ECU monitor
indicating the level of fluid in the DEF tank.
DEF
Figure 76. DEF Tank Level Guage
Figure 75. ECU DEF State Pre-Alarm
NOTICE
Models equipped with the 845 Series ECU Controller
will enter emergency shutdown when the DEF level
has reached 0% and emergency protective measures
are necessary. When this condition exist, the unit can
only be restarted after the ESCAPE MODE is activated
and the unit will run for 30 minutes. Reference "Escape
Mode" section in this manual.
Table 16. DEF Level System Action System
DEF LevelOver 10%Below 10%0%Empty or After 4 hrs. From 0%
Controller Message—DEF<10% Tank LevelDEF<10% Tank LevelDEF Tank Empty Level
When the system senses improper usage such as no
supply of DEF, use of poor quality DEF, problems with
DEF jets, or disconnection of sensors, a warning will be
issued before the situation becomes critical. If the warnings
are ignored and the unit enters intermittent operation, the
emergency shutdown will activate. The three warning levels
are referenced in Table 17:
Table 17. DEF Inducement
MAINTENANCE
StageController Message
Stage 1
Warning Level 1
Stage 2
Warning Level 2
SCR System
Malfunction
SCR System
Malfunction
SCR System
Pop-Up
SCR SYS ERR
SCR SYS ERR
DEF Symbol
Pre-Alarm
Lamp
ON
ON
Shutdown
Lamp
—
—
Slow Blinking
Stage 3
Shutdown
1
SCR System
Malfunction
SCR SYS ERR
ON ON
Fast Blinking
1
When emergency shutdown occurs, inspection and repair should generally be performed promptly. However, if
emergency protective measures are necessary, unit will enter ESCAPE MODE and may require as much as 30
minutes to restart.
10. The Escape Mode Timer (Figure 86) will appear on
ESCAPE MODE
the main screen. This timer displays remaining time
the unit can be operated.
TIMER (SEC)
DEF LOW! SHUTDOWN IN 0048
UO
100
VO
UV
VW
173
U
0000
V
MAINTENANCE
100
WO
------
DERATE CONDITION EXISTS
Figure 86. Escape Mode Timer
If ESCAPE MODE is temporarily suspended, it is not
necessary to return to the ESCAPE MODE screen and
press the [REQUEST] button. ESCAPE MODE operation
will be available until around 30 minutes after operation
has been ended.
Once the ESCAPE MODE timer reaches zero minutes,
the engine will stop since the ESCAPE MODE time has
expired. Please perform maintenance to return unit to
proper operating condition.
If the unit returns to Warning Level 1 while ESCAPE
MODE is running, ESCAPE MODE will be cancelled,
the ESCAPE MODE timer display will close, and normal
operation will resume.
This unit is equipped with engine protection devices that
automatically shut down the engine if any of the faults
shown in Table 18 occur. The “Shutdown” LED on the
ECU Controller will turn on just before the shutdown and
will stay on after the shutdown. Messages will appear on
the ECU display.
After the automatic shutdown, check all Diagnostic Test
Codes (DTC) displayed on the ECU Controller. Reference
the Troubleshooting Diagnostic section in this manual.
Table 18. Automatic Engine Shutdown System
Operating Parameter
ECU
Shutdown LED
Place the Auto Start/Stop Switch in the “Off/Reset” position.
In addition, place all circuit breakers in the OFF position.
Before troubleshooting, allow sufficient time for adequate
cooling. Before attempting to restart the generator, perform
overall inspection of the generator and correct the problem
that caused the shutdown. If necessary, contact your
nearest Multiquip dealer for additional technical support.
Restart the generator as reference in the Generator Startup
Procedure (Manual Start).
NOTICE
Although the unit is equipped with engine protection
devices, regularly scheduled preventative maintenance is strongly advised.
NOTE: EACH CABLE IS PASSED TWICE THROUGH
CURRENT TRANSFORMERS CT4~5
1
3 2
V1
V1
R
T
R
T
U1
U2
V2
3
W1
S
O
21
17
18
6
3 2
19
4
19
4
CONNECTOR
WIRE SIDE)
WIRE SIZE
125: 125 mm
100: 100 mm
80: 80 mm
22: 22 mm
14: 14 mm
8: 8 mm
5.5: 5.5 mm
NO MARK WIRE SIZE: 1.25
CURRENT TRANSFORMERS (CT4 ~ 5)
k
l
L
1
17
2
1
17
2
2
2
2
2
2
2
2
2
3
1
1
B
L
BR
G
GR
V
P
MARK AT CT
X1
NO MARK
H1
NO MARK
1
1
2
3
CODE/WIRE COLOR
BLACK
BLUE
BROWN
GREEN
GRAY
VIOLET
PINK
mm
R
W
Y
LB
LG
O
2
SYMBOL
Ar
Fg
ExAr
ExFg
Re
AVR
VR
CT 1~3
CT 4~5
AS
A
~
V
~
F
CB1
CB2~3
CB4~6
CON1~2
CON3~ 5
OC
COT. B
AS
RED
WHITE
YELLOW
LIGHT BLUE
LIGHT GREEN
ORANGE
DESIGNATION
MAIN GENERATOR ARMATURE WINDING
MAIN GENERATOR FIELD WINDING
EXCITER ARMATURE WINDING
EXCITER FIELD WINDING
RECTIFIER
AUTOMATIC VOLTAGE REGULATOR
VOLTAGE REGULATOR (RHEOSTAT)
CURRENT TRANSFORMER 500:5A
CURRENT TRANSFORMER 500:5A
CHANGE-OVER SWITCH,AMMETER
AC AMMETER 0~500, 1000A
AC VOLTMETER 0~600V
FREQUENCY METER 45~65 Hz @220V
CIRCUIT BREAKER, 3P 800A
CIRCUIT BREAKER, 1P 20A
Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a
breakdown, use Table 19 shown below for diagnosis of the Generator. If the problem cannot be remedied, consult our
company’s business office or service plant.
Table 19. Generator Troubleshooting
SymptomPossible ProblemSolution
AC Voltmeter defective?Check output voltage using a voltmeter.
Is wiring connection loose?Check wiring and repair.
No Voltage Output
Low Voltage Output
High Voltage Output
Circuit Breaker Tripped
Is AVR defective?Replace if necessary.
Defective Rotating Rectifier?Check and replace.
Defective Exciter Field?Check for approximately 19 ohms across J & K on CN1
Is engine speed correct?Place engine speed switch in “High” position.
Is wiring connections loose?Check wiring and repair.
Defective AVR?Replace if necessary.
Is wiring connections loose?Check wiring and repair.
Defective AVR?Replace if necessary.
Short Circuit in load?Check load and repair.
Over current?Confirm load requirements and reduce.
Defective circuit breaker?Check and replace.
Over current Relay actuated?Confirm load requirement and replace.
The engine controller of this generator diagnoses problems
that arise from the engine control system and the engine
itself.
1. With the engine stopped (OFF). Push and hold the
Hour Check Button (Figure 87) located on the control
panel.
HOUR CHECK
BUTTON
Figure 87. Hour Check Button
4. Releasing the Hour Check Button and pushing the
Program/Exit Button on the ECU controller will return
the controller to the main screen.
BUTTON
Figure 89. Program Exit Button
5. Push the Program/Exit Button on the ECU controller
and select the Fault Diagnostics mode. This mode
enables the ability to carry out the fault diagnostics
as listed below:
2. While keeping the Hour Check Button pressed, place
the Auto Off/Reset Manual Switch (Figure 88) in the
MANUALposition.
Figure 88. Auto-Off/Reset
3. The Hour Check Menu Screen will be displayed on
the ECU controller.
(Manual Position)
Switch
DM1 Active Faults — Displays active fault messages
and codes.
DM2 Messages and Codes — Displays messages and
codes which previously occurred that are recorded in the
Engine Control Module (ECM).
Last Shutdown — Displays the messages and codes
that caused the most recent shutdown.
6. After perfoming diagnostic tests, place the Auto Off/
At times, it may be desired to power up the Engine Control
Module (ECM), key switch ON while the engine is not
running. This can be useful for diagnostic purposes and
fault clearing.
To enter the diagnostic mode with the controller in the
OFF mode and the engine not running do the following:
1. Press and hold the Alarm Slience and Lamp Test
buttons (Figure 90) at the same time for 10 seconds.
PRESS
LAMP
TEST
BUTTON
ALARM
SILENCE
BUTTON
SIMULTANEOUS
7. The dianostic mode will remain active until the Reset
button (Figure 91) is pressed or if the engine rpm
becomes greater than zero.
Reset
Figure 91. Reset Button
Figure 90. Alarm Silence/Lamp Test Buttons
2. Listen for an audiable click inside the control panel
which is the run relay that controls the key switch.
3. While in diagnostic mode the controller can see real
time engine CAN Bus data including Diagnostic Trouble Codes (DTC).
4. To view active DTC codes navigate to Metering >J1939
ECU>DTC Active Data.
5. For previously active codes navigate to Metering>J1939
ECU>DTC Prev Data.
6. Real time ECM parameters are not supported due to
lack of sensors etc. and will display NS for No Signal.
are registered trademarks of Multiquip Inc. and may not be used, reproduced, or altered without written permission. All other
trademarks are the property of their respective owners and used with permission.
This manual
The information and specifi cations included in this publication were in effect at the time of approval for printing. Illustrations, descriptions, references and technical data contained in
this manual are for guidance only and may not be considered as binding. Multiquip Inc. reserves the right to discontinue or change specifi cations, design or the information published
in this publication at any time without notice and without incurring any obligations.
DENYO CO., LTD, JAPAN
PLEASE HAVE THE MODEL AND SERIAL
NUMBER ON-HAND WHEN CALLING
UNITED STATES
Multiquip Corporate OfficeMQ Parts Department
18910 Wilmington Ave.
Carson, CA 90746
Contact: mq@multiquip.com