MQ Power WHISPERWATT DCA300SSJU4F2 Operation Manual

OPERATION MANUAL
WHISPERWATT™ SERIES
MODEL DCA300SSJU4F2
60Hz GENERATOR
(JOHN DEERE 6090HFG06 DIESEL ENGINE)
To find the latest revision of this
publication, visit our website at:
www.mqpower.com
THIS MANUAL MUST ACCOMPANY THE EQUIPMENT AT ALL TIMES.
PROPOSITION 65 WARNING
Diesel engine exhaust and some of
PAGE 2 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
DCA300SSJU4F2 60 Hz GENERATOR
Proposition 65 Warning ........................................... 2
Table Of Contents .................................................... 3
Nameplate/Safety Information ................................. 4
Safety Information ................................................ 5-9
Safety Information ................................................. 10
Specifications ........................................................ 11
Dimensions ............................................................ 12
Installation ........................................................ 14-15
General Information ............................................... 16
General Paralleling Information (Option) .......... 17-19
Major Components ................................................ 20
Engine Control Unit (ECU-845) ............................. 21
Gauge Unit Assembly ............................................ 22
Engine/Generator Control Panel............................ 23
Basler Digital Genset Controller (Option) ......... 24-25
Paralleling Panel (Option) ................................. 26-27
Output Terminal Panel Familiarization .............. 28-30
Load Application .................................................... 31
Generator Outputs ............................................ 32-33
Generator Outputs/Gauge Reading ....................... 33
Output Terminal Panel Connections ................. 34-35
Inspection/Setup ............................................... 36-40
Generator Start-Up Procedure (Manual) .......... 41-42
Generator Start-Up Procedure (Auto Mode) .......... 43
Generator Shut-Down Procedures ........................ 44
Maintenance ..................................................... 45-60
Generator Wiring Diagram ..................................... 61
Engine Wiring Diagram (ECU-845)........................ 62
Engine Wiring Diagram (DGC2020HD Option)...... 63
3Ø-480 VAC Parallel Wiring Diagram .................... 64
3Ø-208 VAC Parallel Wiring Diagram .................... 65
Battery Charger Wiring Diagram ........................... 66
Engine Block Heater Wiring Diagram .................... 67
Troubleshooting (Generator) .................................. 68
Troubleshooting (Engine) .................................. 69-70
Troubleshooting (Diagnostics ECU-845) ............... 71
Troubleshooting (Diagnostics DGC2020HD) ......... 72
TABLE OF CONTENTS
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 3
NAMEPLATE/SAFETY INFORMATION
NAMEPLATE AND SAFETY LABELS
Safety labels are attached to the generator as shown in Figure 1. Keep these safety labels clean at all times. When the safety labels become worn or damaged, contact your nearest dealer or the Multiquip Parts Dept.
WARNING
HOT COOLANT can cause
severe burns.
Do not remove cap if radiator is hot.
M90310000
TOP VIEW
50
150
180
25
75
120
140
180
220
60
PSI
RPMX10
°F
0
100
0
210
100
260
OIL PRESS
SPEED
WATER TEMP
50
18
12
24
ECU
%
VOLTS
Integrated Gauge Panel
0
100
0
30
Check
½
½
DEF
Emissions Failure
°F
°F
Emissions
E
E
F
F
Failure
Regen Needed
Low
FUEL
DEF
Regen
Fuel
Inhibit
ECU
Series 800 Controller
Engine Started
Shutdown
Pre-Alarm
Alarm
Screen
Program
Option
Acknowledge
Change
Exit
WARNING
MOVING PARTS can cause severe injury. DO NOT operate with doors open.
Stop engine before servicing.
WARNING
ARC FLASH AND SHOCK HAZARD Appropriate PPE Required
Appropriate Personal Protection Equipment and Tools Required when working on this equipment.
INCREASE DECREASE
V
U
W
OFF
V-W
W-U
U-V
OFF
M9503000004
M92010070
NOTICE
For safety label part numbers, reference parts manual.
CAUTION
Maximum capacity of lifting
bail is 19,000 lbs.
CAUTION
HOT PARTS can burn skin.
DO NOT touch until the
machine has sufficiently cooled.
M911010000
M55100080
300
D
No Diesel
This machine stops and starts automatically and without notice.
CAUTION
EXHAUST FLUID ONLY
Filling this tank with anything other than DIESEL EXHAUST FLUID may result in severe engine damage.
REAR VIEW
CAUTION
M94110000
M92010060
CAUTION
DO NOT disconnect the Battery Cables
after shutting down the engine for
at least 30 seconds
DANGER
Using a generator indoors CAN KILL YOU IN MINUTES.
Generator exhaust contains carbon monoxide. This is a poison gas you cannot see or smell.
NEUTRAL BONDED TO FRAME
120V
120
V
NEUTRAL BONDED TO FRAME
GAC-2.2H
120V
NEUTRE MIS A LA MASSE A
120
15A
V
GAC-2.2H
LA CARCASSE DU MOTEUR
NEUTRE MIS A LA MASSE A
15A
LA CARCASSE DU MOTEUR
POWERED by
POWERED by
Honda Engines
Honda Engines
211052
AC CIRCUIT BREAKER
211052
INTERRUPTEUR DE
AC CIRCUIT BREAKER
OFF
GR PRISE DE
COURANT PRINCIPAL
INTERRUPTEUR DE
TERRE
OFF
GR PRISE DE
COURANT PRINCIPAL
TERRE
ONLY use OUTSIDE and
NEVER use inside a home
far away from windows,
or garage. Even if doors
doors, and vents.
and windows are open.
Avoid other generator hazards. READ MANUAL BEFORE USE.
WARNING
ENVIRONMENTAL
This unit is designed to contain operating uids only. The environmental containment is not designed to control uids from an external source. It is the operator’s responsibility to monitor uid levels at all times.
DO NOT EXCEED THE RECOMMENDED
MAXIMUM CAPACITY
Figure 1. Nameplate
and Safety Decals
CAUTION
Ensure the “Auto-Off/Reset-Manual” switch is in the “Off/Reset” position. If it is not, when the battery cables are connected, the engine will crank and attempt to start.
M90130000
WARNING
ELECTRIC SHOCK HAZARD
Do not touch internal wiring or connections while this machine is operating.
Turn power off before servicing.
M92010000
Operation of this equipment may create sparks that can start fires around dry vegetation.
A spark arrestor may be required. The operator should contact local fire agencies for laws or regulations relating to fire prevention requirements.
NEUTRAL BONDED TO FRAME
120V
120
V
GAC-2.2H
NEUTRE MIS A LA MASSE A
15A
LA CARCASSE DU MOTEUR
POWERED by
Honda Engines
211052
AC CIRCUIT BREAKER INTERRUPTEUR DE
OFF
GR PRISE DE
COURANT PRINCIPAL
TERRE
M90320010
50
150
180 25 75
120
140
180
220
60
PSI
RPMX10
°F
0
0
100
210
100
260
OIL PRESS
SPEED
WATER TEMP
50 18 12
24
ECU
%
VOLTS
Integrated Gauge Panel
0
100
0
30
Check
½
½
DEF
Emissions Failure
°F
°F
Emissions
E
E
F
F
Failure
Regen Needed
Low
FUEL
DEF
Regen
Fuel
Inhibit
ECU
Series 800 Controller
Engine Started
Shutdown
Pre-Alarm
Screen
Program/
Alarm
Option
Change
Exit
Acknowledge
P/N M91110000
M9504200004
DECREASE
INCREASE
V
U
W
OFF
V-W
W-U
U-V
OFF
Denyo
CAUTION
This machine stops and starts automatically and without notice.
MODEL SERIAL NO.
DANGER
HIGH VOLTAGE
FRONT VIEW
SIDE VIEW
S-2731
WARNING
ELECTRIC SHOCK HAZARD
Do not touch output terminals while this machine is operating.
Turn power off before servicing.
M92010060
300
WARNING
ELECTRIC SHOCK HAZARD Always complete the grounding path from the ground terminal on the genset to an external grounding source.
See instruction manual for details.
WARNING
ELECTRIC SHOCK HAZARD
Do not touch internal wiring or connections while this machine is operating.
Turn power off before servicing.
WARNING
Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch.
Serious injury or death may result without this transfer switch.
M92010050
M92010000
SIDE VIEW
WARNING
ENGINE EXHAUST can cause severe injury or death.
Use only in open, well ventilated areas or vent exhaust outside.
M91010040
M9503200004
PAGE 4 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
SAFETY INFORMATION
DO NOT operate or service the generator before reading the entire manual. Safety precautions should be followed at all times when operating this generator. Failure to read and understand the safety messages and operating instructions could result in injury to yourself and others.
SAFETY MESSAGES
The four safety messages shown below will inform you about potential hazards that could injure you or others. The safety messages specifi cally address the level of exposure to the operator and are preceded by one of four words:
DANGER, WARNING, CAUTION
SAFETY SYMBOLS
Potential hazards associated with the operation of this generator will be referenced with hazard symbols which may appear throughout this manual in conjunction with
safety messages.
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in DEATH or SERIOUS INJURY.
WARNING
Indicates a hazardous situation which, if not avoided, COULD result in DEATH or SERIOUS INJURY.
or NOTICE.
CAUTION
Indicates a hazardous situation which, if not avoided, COULD result in MINOR or MODERATE INJURY.
NOTICE
Addresses practices not related to personal injury.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 5
SAFETY INFORMATION
GENERAL SAFETY
NEVER use accessories or attachments that are not
recommended by MQ Power for this generator. Damage
Also, know the
and
This information will be invaluable in
emergency or safety devices.
These devices are intended for operator safety. Disconnection of these devices can cause severe injury, bodily harm or even death. Disconnection of any of these
lubricate components or attempt service on a
keep the generator in proper running condition.
Fix damage to generator and replace any broken parts
store generator properly when it is not being used. Generator should be stored in a clean, dry location out of the reach of children and unauthorized personnel.
CAUTION
NEVER operate this generator without proper protective
clothing, shatterproof glasses, respiratory protection, hearing protection, steel-toed boots and other protective devices required by the job or city and state regulations.
NEVER operate this generator when not
feeling well due to fatigue, illness or when under medication.
NEVER operate this generator under the infl uence of
drugs or alcohol.
ALWAYS check the generator for loosened threads or bolts before starting.
DO NOT use the generator for any purpose other than
its intended purposes or applications.
to the generator and/or injury to user may result.
 ALWAYS know the location of the nearest
fi re extinguisher.
 ALWAYS know the location of the nearest
fi rst aid kit.
 ALWAYS know the location of the nearest
phone or keep a phone on the job site. phone numbers of the nearest ambulance, doctor
fi re department.
the case of an emergency.
GENERATOR SAFETY
 NEVER operate the generator in an explosive
atmosphere or near combustible materials. An explosion or fi re could result causing severe
bodily harm or even death.
DANGER
WARNING
NOTICE
This generator should only be operated by trained and qualifi ed personnel 18 years of age and older.
Whenever necessary, replace nameplate, operation and
safety decals when they become diffi cult read.
Manufacturer does not assume responsibility for any
accident due to generator modifi cations. Unauthorized generator modifi cation will void all warranties.
NEVER disconnect any
devices will void all warranties.
CAUTION
 NEVER
running machine.
NOTICE
 ALWAYS ensure generator is on level ground before use.
 ALWAYS
immediately.
 ALWAYS
PAGE 6 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
ENGINE SAFETY
NOTICE
run engine without an air fi lter or with a dirty air
fi lter. Severe engine damage may occur. Service air fi lter
Wet stacking is a common problem with diesel engines which are operated for extended periods with light or no load applied. When a diesel engine operates without suffi cient load (less than 40% of the rated output), it will not operate at its optimum temperature. This will allow unburned fuel to accumulate in the exhaust system, which can foul the fuel injectors, engine valves and exhaust system, including turbochargers, and reduce
it must be able to provide fuel and air in the proper ratio and at a high enough engine temperature for the engine
Wet stacking does not usually cause any permanent
damage and can be alleviated if additional load is applied to relieve the condition. It can reduce the system performance and increase maintenance. Applying an increasing load over a period of time until the excess fuel is burned off and the system capacity is reached usually can repair the condition. This can take several
State Health Safety Codes and Public Resources Codes specify that in certain locations, spark arresters must be used on internal combustion engines that use hydrocarbon fuels. A spark arrester is a device designed to prevent accidental discharge of sparks or fl ames from the engine exhaust. Spark arresters are qualifi ed and rated by the United States Forest Service for this purpose. In order to comply with local laws regarding spark arresters, consult the engine distributor or the
SAFETY INFORMATION
DANGER
The engine fuel exhaust gases contain poisonous carbon monoxide. This gas is colorless and odorless, and can cause death if inhaled.
The engine in this generator
requires an adequate free fl ow of cooling air. NEVER operate this generator in any enclosed or narrow area where free fl ow of the air is restricted. If the air fl ow is restricted it will cause injury to people and property and serious damage to the generator or engine.
WARNING
DO NOT place hands or fingers inside engine
compartment when engine is running.
NEVER operate the engine with heat shields or
guards removed.
Keep fi ngers, hands hair and clothing away
from all moving parts to prevent injury.
 NEVER
frequently to prevent engine malfunction.
NEVER tamper with the factory settings
of the engine or engine governor. Damage to the engine or generator can result if operating in speed ranges above the maximum allowable.
the operating performance.
In order for a diesel engine to operate at peak effi ciency,
to completely burn all of the fuel.
DO NOT remove the radiator cap while the
engine is hot. High pressure boiling water will gush out of the radiator and severely scald any persons in the general area of the generator.
DO NOT remove the coolant drain plug while the engine
is hot. Hot coolant will gush out of the coolant tank and severely scald any persons in the general area of the generator.
DO NOT remove the engine oil drain plug while the
engine is hot. Hot oil will gush out of the oil tank and severely scald any persons in the general area of the generator.
CAUTION
NEVER touch the hot exhaust manifold,
muffl er or cylinder. Allow these parts to cool before servicing generator.
hours to burn off the accumulated unburned fuel.
local Health and Safety Administrator.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 7
FUEL SAFETY
DANGER
ELECTRICAL SAFETY
 Backfeed to a utility system can cause electrocution
codes. Failure to do so could result in electrical shock or
while AC power from the
cables or cords when
connecting generator to generator. Inspect for cuts in the
connected to the generator’s output receptacles. Incorrect connections may cause electrical shock and
make certain that proper power or extension
cord has been selected for the job. See Cable Selection
DO NOT start the engine near spilled fuel or combustible fl uids. Diesel fuel is extremely fl ammable and its vapors can cause an explosion if ignited.
ALWAYS refuel in a well-ventilated area, away from sparks and open fl ames.
ALWAYS use extreme caution when working with
fl ammable liquids.
SAFETY INFORMATION
and/or property damage. NEVER connect the generator to a building’s electrical system without a transfer switch or other approved device. All installations should be performed by a licensed electrician in accordance with all applicable laws and electrical
burn, causing serious injury or even death.
Power Cord/Cable Safety
DO NOT fi ll the fuel tank while the engine is running
or hot.
DO NOT overfi ll tank, since spilled fuel could ignite if it
comes into contact with hot engine parts or sparks from the ignition system.
Store fuel in appropriate containers, in well-ventilated areas and away from sparks and fl ames.
NEVER use fuel as a cleaning agent.
DO NOT smoke around or near the
generator. Fire or explosion could result from fuel vapors or if fuel is spilled on a hot engine.
DANGER
DO NOT touch output terminals during
operation. Contact with output terminals during operation can cause electrocution,
electrical shock or burn.
The electrical voltage required to operate the generator can cause severe injury or even death through physical contact with live circuits. Turn generator and all circuit breakers OFF before performing maintenance on the generator or making contact with output terminals.
DANGER
 NEVER let power cords or cables lay in water.
 NEVER stand in water
generator is being transferred to a load.
NEVER use damaged or worn
insulation.
NEVER grab or touch a live power
cord or cable with wet hands. The possibility exists of electrical shock,
electrocution or death.
 Make sure power cables are securely
damage to the generator.
NOTICE
 ALWAYS
Chart in this manual.
NEVER insert any objects into the output
receptacles during operation. This is extremely dangerous. The possibility exists of electrical shock, electrocution
or death.
PAGE 8 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
SAFETY INFORMATION
Grounding Safety
BATTERY SAFETY
keep the battery charged. If the battery is not
recharge the battery in a well-ventilated
environment to avoid the risk of a dangerous concentration
If the battery liquid (dilute sulfuric acid) comes into
, rinse skin or clothing
If the battery liquid (dilute sulfuric acid) comes into
, rinse eyes immediately with plenty
of water and contact the nearest doctor or hospital to
NEGATIVE battery terminal
keep battery cables in good working condition.
WARNING
DANGER
This generator is equipped with a grounding terminal attached to the enclosure. Electrical grounding requirements can differ by State, Province, District,
Municipality, and unique application settings.
For portable and vehicle-mounted generators, Multiquip recognizes the guidance provided in NEC Handbook Article 250.34 Parts A and B, and 29 CFR 1926.404 (f) (3) (i). If a more defi nitive earth-to-ground safeguard is required, please consult a qualifi ed electrician and reference appropriate National Electrical Code (NEC) guidelines in establishing an exterior grounding point
generator.
NEVER use gas piping as an electrical ground.
NOTICE
There is a permanent conductor bond between generator (stator winding) and the frame.
DANGER
DO NOT drop the battery. There is a possibility that the
battery will explode.
DO NOT expose the battery to open fl ames,
sparks, cigarettes, etc. The battery contains combustible gases and liquids. If these gases and liquids come into contact with a fl ame or spark, an explosion could occur.
ALWAYS wear safety glasses when
handling the battery to avoid eye irritation. The battery contains acids that can cause injury to the eyes and skin.
 Use well-insulated gloves when picking up the battery.
 ALWAYS
charged, combustible gas will build up.
 ALWAYS
of combustible gasses.
contact with clothing or skin immediately with plenty of water.
contact with eyes
seek medical attention.
CAUTION
 ALWAYS disconnect the
before performing service on the generator.
 ALWAYS
Repair or replace all worn cables.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 9
SAFETY INFORMATION
ENVIRONMENTAL SAFETY/DECOMMISSIONING
Decommissioning is a controlled process used to safely retire a piece of generator that is no longer serviceable. If the generator poses an unacceptable and unrepairable safety risk due to wear or damage or is no longer cost effective to maintain (beyond life-cycle reliability) and is to be decommissioned (demolition and dismantlement),be sure to follow rules below.
EMISSIONS INFORMATION
The diesel engine used in this generator has been designed to reduce harmful levels of carbon monoxide (CO), hydrocarbons (HC) and nitrogen oxides (NOx) contained
This engine has been certifi ed to meet US EPA Evaporative
Attempting to modify or make adjustments to the engine emission system by unauthorized personnel without proper training could damage the generator or create an unsafe
Additionally, modifying the fuel system may adversely affect evaporative emissions, resulting in fi nes or other penalties.
The emission control label is an integral part of the emission
If a replacement emission label is needed, please contact
NOTICE
DO NOT pour waste or oil directly onto the ground, down
a drain or into any water source.
Contact your country's Department of
Public Works or recycling agency in your area and arrange for proper disposal of any electrical components, waste or oil associated with this generator.
When the life cycle of this generator is over, remove
battery(s) and bring to an appropriate facility for lead reclamation. Use safety precautions when handling batteries that contain sulfuric acid.
When the life cycle of this generator is over, it is
recommended that the generator frame and all other metal parts be sent to a recycling center.
Metal recycling involves the collection of metal from discarded products and its transformation into raw materials to use in manufacturing a new product.
Recyclers and manufacturers alike promote the process of recycling metal. Using a metal recycling center promotes energy cost savings.
NOTICE
in diesel exhaust emissions.
emissions requirements in the installed confi guration.
condition.
Emission Control Label
system and is strictly controlled by regulations.
The label must remain with the engine for its entire life.
your authorized engine distributor.
PAGE 10 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
Table 1. Generator Specifications
Model
Type
Armature Connection Star with Neutral
Phase
Standby Output
Prime Output
3Ø Voltage (L-L/L-N)
Voltage Change-Over Bd. at 3Ø 240/139
3Ø Voltage (L-L/L-N)
Voltage Change-Over Bd. at 3Ø 480/277
1Ø Voltage (L-L/L-N)
Voltage Change-Over Bd. at 1Ø 240/120
Power Factor
Frequency
Speed
Aux. AC Power
Aux. Voltage/Output
Dry Weight
Wet Weight
Table 2. Engine Specifications
Model
Type
No. of Cylinders
Bore x Stroke
Displacement
Rated Output
Starting
Cold Weather Starting Aid
Coolant Capacity with Radiator
Lube Oil Capacity
Lubricating Type Oil
DEF Tank Capacity
Fuel Type
Fuel Tank Capacity
16.7 gal. (63.2 L)/hr at full load 12.5 gal. (47.4 L)/hr at 3/4 load
Fuel Consumption
Battery
1
Includes engine and radiator hoses, 2 Includes filters
SPECIFICATIONS
DCA300SSJU4F2
Revolving field, self ventilated,
open protected type synchronous generator
264 kW (330 kVA)
240 kW (300 kVA)
208Y/120, 220Y/127, 240Y/139
416Y/240, 440Y/254, 480Y/277
N/A
0.8
60 Hz
1800 rpm
Single Phase, 60 Hz
4.8 Kw (2.4 kW x 2)
11,220 lbs. (5,090 kg)
15,010 lbs. (6,810 kg)
John Deere 6090HFG09 EPA Tier 4 Final Certified
4 cycle, water-cooled, direct injection, turbo-charged
charged air cooled, EGR, DOC and SCR
6 cylinders
4.64 in. x 5.34 in. (118.4 mm x 136 mm)
549.2 cu. in. (9.0 liter)
437 HP (326 kW) at 1800 rpm
Electric
NVT Dieselmatic Starting Fluid System
17.7 gal. (67 liters)
API service class CJ-4, ACEA E9 or ACEA E6
#2 Diesel Fuel (Ultra low sulfur diesel fuel only)
8.9 gal. (33.8 L)/hr at 1/2 load 5.8 gal. (21.9 L)/hr at 1/4 load
8D (CCA 0°F 1400A) X 1
1
John Deere Cool-Gard II ™
9.3 gal. (35 liters)
2
29.7 gal. (112.4 liters)
430.6 gal. (1,630 liters)
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 11
DIMENSIONS
TOP VIEW
SIDE VIEW
B
MAXIMUM
LIFTING
POINT
19,000 lbs.
(8,618 kg)
A F
C
D
E
300
G
FRONT VIEW
50
150
180
25
75
120
140
180
220
60
PSI
RPMX10
°F
0
100
0
210
100
260
DECREASE
INCREASE
OIL PRESS
SPEED
WATER TEMP
50 18 12 24
ECU
% VOLTS
Integrated Gauge Panel
0
100
0
30
Check
½
½
DEF
Emissions Failure
°F
°F
Emissions
E
E
F
F
Failure
Regen
V
Needed
Low
FUEL
DEF
Regen
Fuel
Inhibit
U
W
OFF
ECU
Series 800 Controller
Engine Started
Shutdown
V-W
Pre-Alarm
W-U
U-V
OFF
Screen
Program/
Alarm
Option
Change
Exit
Acknowledge
Figure 2. Dimensions
Table 3. Dimensions
H
Denyo
I
Reference
Letter
Dimension in. (mm) Reference Letter Dimension in. (mm)
A 38.19 (970) F 46.42 (1,179)
B 38.19 (970) G 149.60 (3,800)
C 45.47 (1,155) H 96.46 in. (2,450)
D 23.03 (585) I 59.05 in. (1,500)
E 25.20 (640)
PAGE 12 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
NOTES
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 13
INSTALLATION
./2.4 M (MINIMUM)
CONNECTING THE GROUND
Consult with local Electrical and Safety Codes for proper connection based on condition of use.
EXAMPLE of how to ground the unit if the condition of use requires such a device:
The ground terminal on the generator should always be used to connect the generator to a suitable ground when required.
The ground cable should be #8 size wire (aluminum) minimum. If copper wire is used, #10 size wire minimum should be used.
Connect one end of the ground cable terminal to the generator ground point (Figure 3). Connect the other end of the ground cable to a suitable earth ground (ground rod)
GENERATOR
GROUND LUG
GROUND CABLE
IF THE GENERATOR IS PROVIDING ELECTRIC POWER TO A BUILDING VIA A TRANSFER SWITCH IT MUST BE CONNECTED TO A GROUND ROD.
REFERENCE
NEC 250
8 FT
Figure 3. Typical Generator Grounding Application
PAGE 14 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
INSTALLATION
OUTDOOR INSTALLATION
Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.
The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.
Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.
CAUTION
Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.
GENERATOR GROUNDING
NOTICE
The Occupational Safety and Health Administration (OSHA) and the National Electrical Code (NEC) recommend that if the generator is providing electrical power to a structure (home, office shop, trailer or similar) it must be connected to a grounding electrode system, such as driven ground rod (Figure 3).
If applicable, to guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground, (Figure 3).
NOTICE
ALWAYS check with State, Province, District and Municipalities for electrical grounding requirements before using generator.
Article 250 (Grounding) of the NEC handbook provides guidelines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.
INDOOR INSTALLATION
Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.
MOUNTING
The generator must be mounted on a solid foundation such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running. The generator must set at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 54.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.
NEC article 250 specifices the following grounding requirements:
1. Use one of the following wire types to connect the generator to earth ground.
a. Copper 10 AWG (5.3 mm
b. Aluminum 8 AWG (8.4 mm
2
) or larger.
2
) or larger.
2. When grounding of the generator (Figure 3) is required, connect one end of the ground cable to the ground lug on the generator. Connect the other end of the ground cable to the ground rod (earth ground).
3. NEC article 250 specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.
NOTICE
When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 15
GENERAL INFORMATION
GENERATOR
This generator (Figure 7) is designed as a high quality portable (requires a trailer for transport) power source for telecom sites, lighting facilities, power tools, submersible pumps and other industrial and construction machinery.
OPERATING PANEL
The “Operating Panel” is provided with the following:
 ECU-845 Controller  Gauge Unit (ECU-670)
• Oil Pressure Gauge
• Water Temperature Gauge
• Charging Voltmeter
• Fuel Gauge/DEF Gauge
• Tachometer/Generator Load
 Panel Light/Panel Light Switch  Hour Check Button  Auto Start/Stop Switch  Emergency Stop Button  Engine Speed Switch  Fuel Leak Detected Alarm Lamp
CONTROL PANEL
The “Control Panel” is provided with the following:
 Frequency Meter (Hz)  AC Ammeter (Amps)  AC Voltmeter (Volts)  Ammeter Change-Over Switch  Voltmeter Change-Over Switch  Voltage Regulator  3-Pole, 800 amp Main Circuit Breaker  “Control Box” (located behind Control Panel)
• Automatic Voltage Regulator
• Current Transformer
• Over-Current Relay
• Starter Relay
• Voltage Change-Over Board
OUTPUT TERMINAL PANEL
The “Output Terminal Panel” is provided with the following:
 Three 120/240V output receptacles (CS-6369), 50A  Three auxiliary circuit breakers, 50A  Two 120V output receptacles (GFCI), 20A  Two GFCI circuit breakers, 20A  Eight output terminal lugs (3Ø power)  Ground lug  Battery Charger (Optional)  Jacket Water Heater (Optional)
OPEN DELTA EXCITATION SYSTEM
Each generator is equipped with the state of the art “Open­Delta” excitation system. The open delta system consist
of an electrically independent winding wound among stationary windings of the AC output section.
There are four connections of the open delta A, B, C and D. During steady state loads, the power from the voltage regulator is supplied from the parallel connections of A to B, A to D, and C to D. These three phases of the voltage input to the voltage regulator are then rectified and are the excitation current for the exciter section.
When a heavy load, such as a motor starting or a short circuit occurs, the automatic voltage regulator (AVR) switches the configuration of the open delta to the series connection of B to C. This has the effect of adding the voltages of each phase to provide higher excitation to the exciter section and thus better voltage response during the application of heavy loads.
The connections of the AVR to the AC output windings are for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation current, offering maximum motor starting capabilities. The excitation does not have a “fixed ceiling” and responds according the demands of the required load.
ENGINE
This generator is powered by a 6 cylinder, 4-cycle water cooled, direct injection, turbocharged, air cooled EGR John
Deere 6090HFG06 diesel engine. This engine is designed to meet every performance requirement for the generator. Reference Table 2 for engine specifications.
In keeping with MQ Power’s policy of constantly improving its products, the specifications quoted herein are subject to change without prior notice.
ELECTRIC GOVERNOR SYSTEM
The electric governor system controls the RPMs of the engine. When the engine demand increases or decreases, the governor system regulates the frequency variation to ±.25%.
EXTENSION CABLES
When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the cable selection chart (Table 8) as a guide for selecting proper extension cable size.
PAGE 16 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
GENERAL PARALLELING INFORMATION (OPTION)
NOTICE
When the paralleling option is employed, the Basler DGC-2020HD controller must be installed. The factory installed ECU-845 controller cannot be used for paralleling.
PARALLELING
Paralleling is the sharing of a load between two generator sets or more.
LOAD SHARING
Load sharing is defined as the proportional division of the kW and kVAR total load between multiple generator sets in a paralleled system.
Load sharing is essential to avoid overloading and stability problems on the systems’ generator sets.
ACTIVE POWER (KW) LOAD SHARING
When generator sets operate in parallel, the engine speed governor of each generator set determines the proportional sharing of the total active power requirements (kW) of the systems’.
The kW load sharing is achieved by increasing or decreasing fuel to the systems’ engines. As the fuel to the engine of one generator set in a group is increased it will not lead to an increase in speed and hence frequency (as it would if it were operating alone) but it will lead to an increase in the proportion of the total kW load that it will deliver.
As the fuel to the engine of one generator set in a group is decreased it will not lead to a decrease in speed and hence frequency (as it would if it were operating alone) but it will lead to a decrease in the proportion of the total kW load that it will deliver.
The control system of the generator sets (via the engine speed control system) monitors and controls the sharing of the total kW load in proportion to the relative rating of the engines on the systems’ generator sets.
REACTIVE POWER (KVAR) LOAD SHARING
When generator sets operate in parallel the alternator field excitation system of each generator set controls the proportional sharing of the total reactive power requirements (kVAR) of the system.
As the field excitation of one generator set in a group is increased i.e. over excited it will not lead to an increase in voltage (as it would if it were operating alone) but It will lead to an increase in the proportion of the total kVAR load it will deliver and a decrease in its power factor.
As the field excitation of one generator set in a group is decreased i.e. over excited it will not lead to an decrease in voltage (as it would if it were operating alone) but It will lead to an decrease in the proportion of the total kVAR load it will deliver and a increase in its power factor.
An undesirable circulating reactive current (cross current) will flow in the system if the excitation of the alternators are not matched.
ETHERNET COMMUNICATION
Ethernet communication is the preferred method for paralleling. This method supports breaker negotiation to avoid simultaneous breaker closures, kW load sharing and kVAR sharing, soft load transfers on and off loading.
The Ethernet ports are located at the output bus splash panel area. There are two ports which are identical so either one can be used. Using a standard Ethernet cable, inter­connect units to be paralleled and or sequenced.
LOAD MANAGEMENT
These generators are set up to automatically manage load, based on demand. Load management is only functional in auto mode. While in auto mode, if the auto start contacts are closed, load management is active by default. Load management will only run the number of units needed to support the load.
If the load demand is small, only one generator will remain running while the other generators will be in standby mode. If the load increases above 80% of its capacity, it will start the next generator. The next generator priority is based on the time remaining on the maintenance timer.
Generators with more time until scheduled maintenance will take priority over units that are almost due for maintenance. Once the second unit starts it will synchronize and parallel in then ramp up to share the load. If the load levels drop below 35% of its combined rating, the generator that is no longer needed will ramp off, shut down and wait in standby mode.
The kVAR load sharing is achieved by increasing or decreasing the field excitation to the systems’ alternators
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 17
GENERAL PARALLELING INFORMATION (OPTION)
SEQUENCING
NOTICE
Ethernet communication is required when the generators are configured for the sequencing mode of operation.
These generators are capable of sequencing for control of balanced maintenance schedules. As described above, these generators can start and stop as demand raises or lowers. In addition, if the units get to the point of maintenance, it will ramp off and start the next generator to relieve it based on the time remaining on the maintenance timer.
After maintenance is performed, the maintenance timers should be reset to the recommended service interval. This is usually 250 hours depending on the engine oil type.
MAINTENANCE INTERVAL
Maintenance intervals are factory set for 250 hours. The maintenance interval timer will count down to zero indicating that it is time for the unit to be serviced.
Once the timer counts down to zero, a pre-alarm will appear indicating that the unit is due for maintenance. To reset the maintenance interval back to the default time of 250 hours, press and hold the “Reset” button for ten seconds.
The complete password sequence is shown in Figure 4. The set-point for the desired hours until maintenance can now be changed. Press edit to save.
Edit Edit
Figure 4. Password Sequence 2.04 and Lower
PASSWORD ENTRY 2.04 AND HIGHER
User Name and Password is A.
Once prompted, the cursor will be in the user name field. Press the down button () twice to highlight the A character.
Once the user name of A is populated in the user name field, press the up arrow () button four times to highlight the check box in the upper right corner of the screen. With the check box highlighted press the edit button to accept the entry.
The cursor will move to the password field. Again, press the down arrow () button twice until the A is highlighted and then press edit. Press the up arrow () button four times to highlight the check box in the upper right corner of the screen. With the check box highlighted press the edit button to accept the entry. This completes the password entry.
The complete password sequence is as follows:
To reset the maintenance interval using the reset button, the Maintenance Due pre-Alarm must be active, and the Basler controller must display the “Overview Screen” (Main Screen).
If the maintenance timer has not yet expired and it is desired to reset the unit back to 250 hours, navigate back to the settings menu. Settings Menu->System Parameters­>Engine Statistics->Hours To Maintenance.
PASSWORD ENTRY 2.04 AND LOWER
When highlighted, press the “Edit” button. Username and Password is required. User Name is A and Password is A. Use the up arrow button () and scroll to the alpha character A, then press edit to select.
Next, the cursor will move to the password field, press the up arrow button () and scroll to the alpha character A, then press edit to select.
PAGE 18 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
Edit Edit
Edit Edit
Figure 5. Password Sequence 2.04 and Higher
Pre-alarm Silence allows the user to suppress the toggling of the alarm screen when a new Pre-alarm becomes active. While a Pre-alarm is active, pressing the Alarm Silence button will suppress the fault display.
This happens to be very handy function when the “Maintenance Interval” Pre-Alarm occurs. Right after the Pre-Alarm occurs it will begin toggling between the pre- alarm and the overview screen.
While in this mode, pressing the reset button does not reset the maintenance interval. In order to reset the maintenance interval the overview screen must be selected.
GENERAL PARALLELING INFORMATION (OPTION)
Pressing the alarm silence button will stop the toggling between the pre-alarm and the overview screen.
Once the overview screen is selected, the maintenance interval can be reset by pressing and holding the reset button for 10 seconds.
THREE PHASE 480V/208V PARALLEL WIRING VIA CAMLOCKS
REQUIRED EQUIPMENT
 4/0 Single Conductor Cable (User Supplied)
 CAT5E Shielded Cable or Better (User Supplied)
 Power Distribution Panel (User Supplied)
The following procedure intended to assist the user with the parallel wiring configuration for the DCA300SSJU4F2 generator using the camlok connector panel.
NOTICE
Only a qualified service technician or licensed electrician with proper training should perform
this installation. Follow all shop safety rules when performing this installation.
NOTICE
When connecting load cables to the power distribution panel be sure to select the correct size of the load cables to handle full load/amperage of both generators (parallel).
3Ø-208 VAC PARALLEL WIRING CONFIGURATION
1. Using 4/0 cables connect the two generators to the power distribution panel as referenced in the 3Ø-208V parallel wiring diagram.
ETHERNET CABLE CONNECTION
1. Connect a CAT5E Ethernet cable (shielded) between port 1 on both generators as shown in Figure 6.
CAT5E PORT 1 GENERATOR 1
PORT 2
CAT5E ETHERNET CABLE (SHIELDED)
PREPARATION
1. Make sure generator is turned off and engine is cool.
2. Disconnect any loads connected to the generator.
3. Place the main circuit breaker in the OFF position.
4. Place the generator in an area free of dirt and debris Make sure it is on secure level ground.
5. Disconnect negative battery cable from the battery.
3Ø-480 VAC PARALLEL WIRING CONFIGURATION
1. Using 4/0 cables connect the two generators to the power distribution panel as referenced in the 3Ø-480V parallel wiring diagram.
DANGER
To prevent arcing make sure cables are securely tighten at power distribution panel, the possibility exist of the unit catching on fire thus causing equipment damage and severe bodily harm.
CAT5E PORT 1 GENERATOR 2
PORT 2
Figure 6. Ethernet Cable Connection
2. Reference Table 4 for additional Ethernet port connections.
Table 4. Ethernet Cable Connections
Generator 1 Generator 2
Port 2 Port 1
Port 1 Port 2
Port 2 Port 2
3. Reconnect battery.
4. Start generator as outlined in start up section of this manual.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 19
MAJOR COMPONENTS
1
300
U
V W
2
300
3
4
W
12
11
6
5
7
9
8
Table 5. Generator Major Components
ITEM NO. DESCRIPTION
50
150
180
25
75
120
140
180
220
60
PSI
RPMX10
°F
0
0
100
210
100
260
DECREASE
INCREASE
OIL PRESS
SPEED
WATER TEMP
50 18 12
24
ECU
% VOLTS
Integrated Gauge Panel
0
100
0
30
Check
½
½
DEF
Emissions Failure
°F
°F
Emissions
E
E
F
F
Failure
Regen
V
Needed
Low
FUEL
DEF
Regen
Fuel
Inhibit
U
W
ECU
Acknowledge
OFF
Series 800 Controller
Engine Started
Shutdown
V-W
Pre-Alarm
W-U
U-V
OFF
Screen
Program/
Alarm
Option
Change
Exit
10
1 Muffler Assembly
2 Air Filter Assembly
3 Generator Assembly
4 Engine Assembly
5 Fuel Tank Assembly
6 Output Terminal Assembly
Denyo
7 ECU-670 Gauge Unit Assembly
8 Generator Control Panel Assembly
9 Voltage Change-Over Board Assembly
9 Auto Start/Stop Controller Assembly
10 Circuit Breaker Assembly
11 Battery Assembly
12 ECU-845 Controller Assembly
Figure 7. Major Components
PAGE 20 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
ECU
Acknowledge
Series 800 Controller
A
Alarm
Screen Change
Option
1
Program
Exit
Engine Started
Shutdown
Pre-Alarm
ENGINE CONTROL UNIT (ECU-845)
50
25
75
PSI
0
ECU
OIL PRESS
Check DEF
Emissions Failure
Emissions Failure
Regen Needed
Regen Inhibit
Alarm
Acknowledge
100
12
0
Series 800 Controller
Screen Change
B C D
150
180
120
140
180
220
60
RPMX10
°F
0
210
100
260
SPEED
WATER TEMP
50
18
24
ECU
%
VOLTS
Integrated Gauge Panel
0
100
30
½
½
°F
°F
E
E
F
Low Fuel
Option
F
FUEL
DEF
Engine Started
Shutdown
Pre-Alarm
Program
Exit
INCREASE DECREASE
V
U
W
OFF
V-W
W-U
U-V
OFF
E F
G
H
Figure 8. Engine Control Unit (ECU-845)
The definitions below describe the controls and functions of the Engine Control Unit (Figure 8).
1. ECU-845 Controller — This auto start/stop
controller displays the parameters and the diagnostic troubleshooting messages of the engine.
In addition, this controller also displays symbols and indications related to the exhaust gas after treatment system (DOC, SCR) including the Diesel Exhaust Fluid (DEF) level in the DEF tank.
A. ECU Display Screen — Engine fault diagnostic
messages are shown on this LCD display. screen
B. Engine Started Lamp — This lamp when lit
indicates engine is operating normally.
C. Engine Shutdown Lamp — When an engine
failure has occured this lamp will blink, indicating the engine has been shutdown. The diagnostic fault message will be displayed on the LCD screen.
The fault message will be displayed on the screen. When multiple engine faults occur, the lamp will continue blinking until all fault messages are confirmed. The blinking lamp will change to a solid lamp display all current confirmed fault messages will scroll across the screen.
F. Screen Change Button — When this button is
pushed during operation, the screen (Figure 9) will cycle through main and secondary parameter screens.
VOLTS AMPS
278
UO
VO
278 278
WO
240 kW
60 Hz
ENGINE GENERATOR SYSTEM OK
UV
VW WU
480 480
480
U
361
V
361
W
361
300 kVA
100 h
D. Pre Alarm Lamp — When an engine failure has
occured this lamp will blink. Indicating a pre-fault engine condition and the possibility of engine shutdown.The diagnostic fault message will be displayed on the LCD screen.
E. Alarm Acknowledge Button — When the engine
experiences a fault, the "Pre Alarm Lamp" or the "Shutdown Lamp" will start blinking. Pushing this button will confirm the fault message and the blinking lamp will change to a solid lamp display.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 21
Figure 9. Generator Parameter Screen
NOTICE
The screen as shown in (Figure 9) represents the phase voltages for each phase to neutral (UO, VO and WO) and the line voltages between each phase (UV, VW and WU).
G. Option Button — This button is not active. Do
not use.
H. Program/Exit Button — Push this button from the
home screen to enter the main menu.
GAUGE UNIT ASSEMBLY
1
50
180
25
75
140
220
PSI
ECU
0
OIL PRESS
Check DEF
Emissions Failure
Emissions Failure
Regen Needed
Regen Inhibit
Series 800 Controller
Alarm
Acknowledge
°F
100
100
260
WATER TEMP
18
12
24
VOLTS
0
30
½
°F
E
F
Low
FUEL
Fuel
Screen
Program
Option
Change
Exit
A
50
25
PSI
0
OIL PRESS
Check DEF
Emissions Failure
Emissions Failure
Regen Needed
Regen Inhibit
H
B
75
100
12
D
0
180
140
°F
100
WATER TEMP
18
24
VOLTS
30
½
°F
E
F
Low
FUEL
Fuel
C
150
120
220
260
50
%
0
F
G
180
60
RPMX10
0
210
SPEED
EC U
Integrated Gauge Panel
E
100
½
°F
E
F
DEF
I
Figure 10. Gauge Unit
The definitions below describe the readouts and functions of the Gauge Unit Assembly (Figure 10).
1. Gauge Unit Assembly — This assembly houses the
various engine monitoring gauges. These gauges indicate: oil pressure, water temperature, charging voltmeter, generator load, fuel level, DEF level and engine speed RPM (tachometer).
A. Oil Pressure Gauge — During normal operation,
this gauge should read approximately 44 psi. (300 kPa). When starting the generator, the oil pressure may read a little higher but after the engine warms up, the oil pressure should return to the correct pressure range.
B. Water Temperature Gauge — During normal
operation this gauge should read between 185° and 207°F (85°~97°C).
C. Tachometer — Indicates engine speed in RPM’s
for 60 Hz operation. This meter should indicate 1800 RPM’s when the rated load is applied.
0
120
60
0
50
%
100
E
Engine Started
Shutdown
Pre-Alarm
150
180
RPMX10
210
SPEED
ECU
Integrated Gauge Panel
½
°F
F
4
DEF
5
INCREASE DECREASE
V
U
W
OFF
V-W
W-U
U-V
OFF
D. Battery Voltmeter Gauge — During normal
operation this gauge indicates a minimum 14 VDC.
E. Generator Load Gauge — Indicates the generator
load rate. It is recommended the load be above the red area (20%) for maintaining sufficient exhaust temperature.
F. Fuel Gauge — Indicates amount of diesel fuel
available. The red area in the gauge indicates a low fuel level (20%).
G. DEF Gauge — Indicates amount of diesel exhaust
fluid available. The red area in the gauge indicates a low DEF level (10%).
H. Exhaust System State Indicator Lamps — Lamps
illuminate when engine is at Exhaust System State or DEF state. Refer to the maintenance section of this manual for more detailed indormation.
I. Low fuel Warning LED — When ON (lit) indicates
that fuel level is low.
PAGE 22 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
ENGINE/GENERATOR CONTROL PANEL
Table 6.
1
2
6
7
V
U
W
OFF
8
V-W
W-U
U-V
OFF
0
ECU
50
25
PSI
OIL PRESS
Check DEF
Emissions Failure
Emissions Failure
Regen Needed
Regen Inhibit
Series 800 Controller
75
100
100
18
12
24
VOLTS
0
30
E
Low Fuel
140
WATER TEMP
120
180
220
60
RPMX10
°F
0
210
260
SPEED
50
ECU
%
Integrated Gauge Panel
0
100
½
½
°F
°F
E
F
F
FUEL
3
DEF
INCREASE DECREASE
150
180
4
Engine Started
Shutdown
Pre-Alarm
5
Alarm
Screen
Program
Option
Acknowledge
Change
Exit
10
11
12
9
Figure 11. Generator/Engine Control Panel
The definitions below describe the controls and functions of the Generator/Engine Control Panel (Figure 11).
1. Panel Light — For operation at night, panel light
illuminates control panel for ease of reading meters and gauges. Make sure oanel light switch is in the OFF position when light is not in use.
2. Panel Light Switch — When activated will turn on
control panel light.
3. Frequency Meter — Indicates the output frequency
in hertz (Hz). Normally 60 Hz
4. AC Ammeter — Indicates the amount of current the
load is drawing from the generator per leg selected by the ammeter phase-selector switch.
5. AC Voltmeter — Indicates the output voltage present at the U,V, and W Output Terminal Lugs.
6. Voltage Regulator Control — Allows ±15% manual adjustment of the generator’s output voltage.
7. Ammeter Change-Over Switch — This switch allows the AC ammeter to indicate the current flowing to the load connected to any phase of the output terminals, or to be switched off. This switch does not effect the generator output in any fashion, it is for current reading only.
13
X
2
U
1
U
1
2
3
4
Y
2
1
V
V
5
Z
2
W
1
W
6
O
14
8. Voltmeter Change-Over Switch — This switch allows
the AC voltmeter to indicate phase to phase voltage between any two phases of the output terminals or to be switched off.
9. Emergency Stop Switch Button — In the event
of an emergency press this button to shut down the generator.
10. Hour Check Button — With the engine stopped, press
and hold ths button. The total running hours, fuel level, and battery voltage will be displayed.
11. Auto/Start Switch — This switch selects either manual or automatic operation. Center position is OFF (reset).
12. Engine Speed Switch Switch — This switch controls the speed of the engine low or high.
13. Voltage Change-Over Board — 6 jumper plates that allows the generator to be configured for either 3Ø, 240 or 480 VAC output.
14. Main Circuit Breaker — This three-pole, 800 amp main breaker is provided to protect the U,V, and W
Output Terminal Lugs from overload.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 23
BASLER DIGITAL GENSET CONTROLLER (OPTION)
Figure 12. Basler DGC-2020HD
NOTICE
The Basler DGC-2020HD is an option. It replaces the ECU 845 controller that comes standard with this generator when the paralleling option is employed.
PAGE 24 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
BASLER DIGITAL GENSET CONTROLLER (OPTION)
The definitions below describe the controls and functions of the Digital Genset Controller (Figure 12).
1. LCD Display — Display consists of a LCD color touch
screen. The backlit, 272X480 pixel color LCD serves as the local information source for metering, alarms, pre-alarms, and protective functions. Touch screen capability provides convenient navigation through metering and settings. Display operation is maintained down to –4°F (−20°C).
2. Not In Auto Indicator — This red LED lights when the DGC-2020HD is not operating in AUTO mode.
3. Alarm Indicator — This red LED lights continuously during alarm conditions and flashes during pre-alarm conditions.
4. Supplying Load Indicator — This green LED lights when the generator current is greater than emergency power supply (EPS) threshold current.
5. Programmable Indicators — These three red LEDs light when the corresponding logic element is set true. Logic element PROGLED 1 controls the upper LED, PROGLED 2 controls the middle LED, and PROGLED 3 controls the lower LED. A card is provided for labeling the programmable indicators. See Programmable Indicator Configuration, below.
6. Alarm Silence Pushbutton — Pressing this button tests the DGC-2020HD indicators by exercising all LCD pixels and lighting all LEDs.
7. Lamp Test Pushbutton — Pressing this button tests the DGC-2020HD indicators by exercising all LCD pixels and lighting all LEDs.
8. Auto Pushbutton and Mode Indicator — Pressing the Auto button places the DGC-2020HD in Auto mode. The green Auto mode LED lights when Auto mode is active.
9. Off Pushbutton and Mode Indicator. — Pressing this
button places the DGC-2020HD in Off mode.The red Off mode LED lights when the DGC-2020HD is in Off mode. This button also resets the Breaker Management Pre-Alarms and all MTU ECU Alarms.
10. Run Pushbutton and Mode Indicator. — Pressing
this button places the DGC-2020HD in Run mode. The green Run mode LED lights when Run mode is active.
11. Reset Pushbutton — This button is pressed to cancel
a settings editing session and discard any settings changes. When pressed momentarily, this button resets the Breaker Management Pre-Alarms and all MTU ECU Alarms. This button is also used to reset the Maintenance Interval when pressed for 10 seconds while viewing Hours Until Maintenance or Maintenance Due Pre-Alarm.
12. Arrow Pushbuttons — These four buttons are used
to navigate through the front panel display menus and modify settings.
• The left and right arrow buttons are used to navigate through the menu levels. The right arrow button is pressed to move downward through the menu levels and the left arrow button is pressed to move upward through the menu levels.
• Within a level, the up and down arrow buttons are used to move among items within the menu level. Pressing the down arrow button moves to items lower in the list. Pressing the up arrow button moves to items higher in the list.
• During a settings editing session, the up and down arrow buttons are used to raise and lower the value of the selected setting. The right and left arrow buttons move to different digits.
While in “AUTO” the controller will be in standby awaiting a signal to start via the remote start terminals. While in auto, closure of the auto start contacts will immediately start the engine. Once the generator is up to speed and voltage it will compare its voltage to the bus.
If the bus is dead it will immediately close the contactor to provide power to the load(s). If the bus is already hot from another generator it will first synchronize then close its contactor then slowly ramp up to share load if load were present.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 25
13. Edit Pushbutton — Pressing this button starts an
editing session and enables changes to DGC-2020HD settings. At the conclusion of an editing session, the Edit pushbutton is pressed again to save the setting changes.
PARALLELING PANEL (OPTION)
PANEL
LIGHTS
VOLTAGE
ADJUST
CONTACTOR
CLOSE
CONTACTOR
OPEN
EMERGENCY STOP
WHISPERWATT
300 kVA AC GENERATOR
Figure 13. Paralleling Panel Components
CONTROL
POWER
PAGE 26 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
PARALLELING PANEL (OPTION)
The definitions below describe the controls and functions of the Paralleling Panel (Figure 13).
1. Panel Lights — For operation at night or in dark areas,
panel light illuminates paralleling panel for ease of reading.
2. Panel Light Switch — When activated will turn on
control panel light.
3. Voltage Adjust potentiometer — The voltage adjust
potentiometer is a way to adjust the voltage up or down for fine tuning. The adjustment sends a signal to the controller to offset the system rated voltage (Trim Voltage). It is important that all machines are set to the same value when paralleling.
When first turning on the control power, the controller will begin its boot sequence much like a computer does. After completing the boot sequence the unit will be ready to run or be placed in auto for auto start applications.
4. Control Power Toggle Switch — The control power
switch is a master power switch for the digital controller. The control power switch has a latch feature that prevents powering down control power while the engine is running.
For units with manual operated breakers, the breaker will need to be reset by toggling the handle down, then can be turned back to the “ON” position. On models with spring charged breakers resetting the breaker is not necessary.
6. Contactor Operation (Manual Mode) — The For
manual run applications, user action is required to get the generator power to the output bus. Depending on the model, some utilize contactors in series with toggle handle circuit breakers and others have spring charged automatic circuit breakers.
On the spring charged types, the buttons on the breaker itself are not intended for circuit breaker operation. For instructional purposes both will be referred to as “contactor”.
There are two pushbuttons on the control panel for controlling the contactor. There is a green “CLOSE CONTACTOR” button to close the contactor and a red “OPEN CONTACTOR” button to open the contactor. These buttons illuminate to show the contactor status. If the contactor is open, the red “OPEN CONTACTOR” button will be illuminated. If the contactor is closed the green “CLOSE CONTACTOR” button will be illuminated.
5. Emergency Stop Button Switch — The Emergency
Stop pushbutton switch is used to stop the engine in case of emergency or to lock out operation during service. The emergency stop button should not be used for routine stopping of the engine.
Actuation of the Emergency stop button while the control power is on will illuminate the light on the button as well as display “Emergency Stop” on the controller display. Actuating the Emergency stop button will de­energize all controller outputs and cause the engine to stop as well as tripping the circuit breaker. This condition is a latched condition that must be reset prior to restarting the engine.
The procedure for resetting the emergency stop requires several actions. Rotate the emergency stop button to release the spring latch. To clear the latch, the controller must be placed into the off mode by pressing the “OFF” button. While in the “OFF” mode, the “RESET” button must be pressed to clear the E-STOP fault.
These buttons can sometimes be multifunctional depending on the situation. For stand-alone operation the buttons simply close and open the contactor as expected. For paralleling the buttons can act a little different.
When the bus is already hot from another generator, pressing the green online button will initiate a synchronizing sequence before closing the contactor. There will be an image of a synchro scope on the controller display and when the voltage and phases are matched, the contactor will close.
If there was already load on the bus the unit will slowly ramp up load until it is sharing equally with the other generator(s). While sharing load with other generators, pressing the red “OPEN CONTACTOR” button once will initiate a ramp down sequence. The unit will begin to ramp down and when at a low level of load it will automatically open it contactor. Pressing the red “OPEN CONTACTOR” button twice will immediately open the contactor.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 27
OUTPUT TERMINAL PANEL FAMILIARIZATION
OUTPUT TERMINAL PANEL
The Output Terminal Panel (Figure 15) shown below is provided for the connection of electrical loads. Lift up on the cover to gain access to receptacles and terminal lugs.
NOTICE
Terminal legs “O” and “Ground” are considered bonded grounds
300
V W
W
U
OUTPUT TERMINAL FAMILIARIZATION
The “Output Terminal Panel” (Figure 15) is provided with the following:
 Three (3) 240/139V output receptacles @ 50 amp
 Three (3) Circuit Breakers @ 50 amps
 Two (2) 120V GFCI receptacles @ 20 amp
 Two (2) GFCI Circuit Breakers @ 20 amps
 Eight (8) Output Terminal Lugs ( U, V, W, O, Ground)
1Ø AND 3Ø,
480 -120 VAC
OUTPUT TERMINALS
V
U
BLACK RED BLUE WHITE GREEN
NEUTRAL
TERMINAL
W
CS-6369 TWIST-LOCK
Figure 14. Output Terminal Panel
GROUND
TERMINAL
O
RECEPTACLES (3)
240Y/139, 50 AMPS
HOOKUP PANEL
W
CS-6369
TWIST-LOCK
HARD WIRE
Y
X
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
CIRCUIT BREAKERS FOR CS-6369 TWIST
LOCK RECEPTACLES
PAGE 28 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
OUTPUT TERMINAL PANEL FAMILIARIZATION
120 VAC GFCI Receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) receptacles provided on the output terminal panel. These receptacles can be accessed in any voltage change-over board position. Each receptacle is protected by a 20 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the U, V, and W output terminal lugs.
Pressing the reset button resets the GFCI receptacle after being tripped. Pressing the test button (See Figure 15) in the center of the receptacle will check the GFCI function. Both receptacles should be tested at least once a month.
Each auxiliary receptacle is protected by a 50 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) on all three receptacles is dependent on the load requirements of the output terminal lugs.
Turn the voltage regulator control knob (Figure 17) on the control panel to obtain the desired voltage. Turning the knob clockwise will increase the voltage, turning the knob counter-clockwise will decrease the voltage.
Figure 17. Voltage Regulator Control Knob
Figure 15. G.F.C.I. Receptacle
Twist Lock Dual Voltage 120/240 VAC Receptacles
There are three 240/139V, 50 amp auxiliary twist-lock (CS-6369) receptacles (Figure 16) provided on the output terminal panel. These receptacles can only be accessed when the voltage change-over board is configured for single-phase 240/120 application
Figure 16. 240/139V Twist-Lock Auxiliary
Receptacles
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 29
OUTPUT TERMINAL PANEL FAMILIARIZATION
CS-6369
Connecting Loads
Loads can be connected to the generator by the Output Terminal Lugs or the convenience receptacles (Figure 18).
Make sure to read the operation manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole, 800A main circuit breaker is provided. Make sure to switch ALL circuit breakers to the OFF position prior to starting the engine.
TWIST-LOCK
RECEPTACLES
GFCI
RECEPTACLES
BLACK
U
HARD WIRE
HOOKUP PANEL
BLUE
RED
V
W
LOAD
WHITE
O
NEUTRAL
GREEN
GROUND
CAMLOCKS
LOAD
LOAD
Over Current Relay
An over current relay (Figure 19) is connected to the main circuit breaker. In the event of an overload, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the reset button on the over current relay must be pressed. The over current relay is located in the control box.
Figure 19. Over Current Relay
NOTICE
Figure 18. Connecting Loads
Remember the overcurrent relay monitors the current flowing from the U,V, and W Output Terminal Lugs to the load.
In the event of a short circuit or over current condition, it will automatically trip the 800 amp main breaker.
To restore power to the Output Terminal Panel, press the reset button on the overcurrent relay and place the
main circuit breaker in the closed position (ON).
PAGE 30 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
LOAD APPLICATION
SINGLE PHASE LOAD
Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.
Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.
NOTICE
If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generator is 0.8. See Table 7 below when connecting loads.
Table 7. Power Factor By Load
Type of Load Power Factor
Single-phase induction motors 0.4-0.75
Electric heaters, incandescent lamps 1.0
Fluorescent lamps, mercury lamps 0.4-0.9
Electronic devices, communication equipment
Common power tools 0.8
Table 8. Cable Selection (60 Hz, Single Phase Operation)
Current
in
Amperes
2.5 300 600 1000 ft. 600 ft. 375 ft. 250 ft.
5 600 1200 500 ft. 300 ft. 200 ft. 125 ft.
7.5 900 1800 350 ft. 200 ft. 125 ft. 100 ft.
10 1200 2400 250 ft. 150 ft. 100 ft.
15 1800 3600 150 ft. 100 ft. 65 ft.
20 2400 4800 125 ft. 75 ft. 50 ft.
Load in Watts Maximum Allowable Cable Length
At 100
Volts
CAUTION: Equipment damage can result from low voltage
At 200
Volts
#10 Wire #12 Wire #14 Wire #16 Wire
1.0
THREE PHASE LOAD
When calculating the power requirements for 3-phase power use the following equation:
NOTICE
If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732
NOTICE
Motors and motor-driven equipment draw much greater current for starting than during operation.
An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.
 When connecting a resistance load such as an
incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.
 When connecting a fluorescent or mercury lamp, a
capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.
 When connecting an electric drill or other power tools,
pay close attention to the required starting current capacity.
When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.
DANGER
Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 31
GENERATOR OUTPUTS
X
Y
Z
O
U
U
1
2
V
V
2
1
W
W
2
1
JUMPER
6 PLACES
1
2
3
4
5
6
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by using the voltage change-over board (Figure 20). To obtain some of the voltages as listed in Table 9 (see below) will require a fine adjustment using the voltage regulator (VR)
control knob located on the control panel.
Voltage Change-Over Board
The voltage change-over board (Figure 20) is located on the control box, behind the generator control panel. This board has been provided for ease of voltage selection.
Maximum Amps
Table 10 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed.
Table 10. Generator Maximum Amps
Rated Voltage Maximum Amps
1Ø 120 Volt 666.7 X 2 amps (4 wire)
1Ø 240 Volt 333.3 amps (4 wire)
3Ø 240 Volt 722 amps
3Ø 480 Volt 360 amps
Main Line Circuit
Breaker Rating
800 amps
Figure 20. Voltage Change-Over Board
CAUTION
NEVER attempt to place jumper plates on the voltage change-over board while the generator is in operation. There exist the possibility of electrocution, electrical shock or burn, which can cause severe bodily harm or even death!
Table 9. Voltages Available
UVWO Output Terminal Lugs
Line-Line
Line-Neutral 120V 127V 139V 240V 254V 277V
Line-Neutral/
Line-Line
Voltage Change-Over Board
3-Phase 240/139V Position
208V 220V 240V 416V 440V 480V
Voltage Change-Over Board Single-Phase 240/120V Position
120V
Line-Neutral
PAGE 32 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
N/A N/A
Voltage Change-Over Board
3-Phase 480/270V Position
240V
Line-Line
N/A N/A
GENERATOR OUTPUTS/GAUGE READING
X
Y
Z
O
U
U
1
2
V
V
2
1
W
W
2
1
JUMPER
6 PLACES
1
2
3
4
5
6
HOW TO READ THE AC AMMETER AND AC VOLTAGE GAUGES
The AC ammeter and AC voltmeter gauges are controlled by the AC ammeter and AC voltmeter change-over switches.
Both of these switches are located on the control panel and DO NOT effect the generator output. They are provided to help observe how much power is being supplied, produced at the UVWO terminals lugs.
Before taking a reading from either gauge, configure the Voltage Change-Over Board (Figure 21) for the desired output voltage.
AC Ammeter Gauge Reading
Place the AC Ammeter Change-Over Switch (Figure 24) in the U position and observe the current reading (load drain) on the U terminal as indicated on the AC Ammeter Gauge (Figure 25). This process can be repeated for terminals V and W.
Figure 24. AC Ammeter Change-Over Switch
NOTICE
The ammeter gauge will only show a reading when the Output Terminal Lugs are connected to a load and in use.
Figure 25. AC Ammeter
(Amp reading on U Lug)
Figure 21. Voltage Change-Over Board-
Ø Position
240/3
AC Voltmeter Gauge Reading
Place the AC Voltmeter Change-Over Switch (Figure 22) in the W-U position and observe the phase to phase voltage reading between the W and U terminals as indicated on the AC Voltmeter Gauge (Figure 23).
Figure 22. AC Voltmeter Change-Over Switch
Figure 23. AC Voltmeter Gauge (Volt reading on W-U Lug)
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 33
OUTPUT TERMINAL PANEL CONNECTIONS
X
Y
Z
O
U
U
1
2
V
V
2
1
W
W
2
1
JUMPER
6 PLACES
1
2
3
4
5
6
BE USED
BE USED
UVWO TERMINAL OUTPUT VOLTAGES
Various output voltages can be obtained using the UVWO output terminal lugs. The voltages at the terminals are dependent on the placement of the jumpers plates (6) on the Voltage Change-Over Board and the adjustment of the Voltage Regulator Control Knob.
Remember the voltage change-over board determines the range of the output voltage and can be configured in two different positions that provide 6 different output voltages at the UVWO output terminals. The generator is shipped from the factory in the 240V configuration. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.
3Ø-240V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 240V operation as shown in Figure 26
3. Turn the voltage regulator knob (Figure 28) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fine tuning of the output voltage is required
Figure 28. Voltage Regulator Knob
1Ø-240V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered for 240V operation as shown in Figure 26.
2. Connect the load wires to the UVWO terminals as shown in Figure 29.
BLACK
U
240V
RED
V
BLUE
W
240V
WHITE
O
GREEN
Figure 26. Voltage Change-Over Board 240V
Configuration
2. Connect the load wires to the UVWO terminals as shown in Figure 27
BLACK
U
Figure 27. UVWO Terminal Lugs
3Ø-240/1Ø-139 Connections
PAGE 34 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
RED
V
THREE-PHASE
240 VAC (LOAD CONNECTIONS)
BLUE
W
WHITE
O
GREEN
GROUND
CONNECTION
MUST
AT ALL TIMES
240V
SINGLE-PHASE
240 VAC (LOAD CONNECTIONS)
GROUND
CONNECTION
BE USED
MUST
AT ALL TIMES
Figure 29. UVWO Terminal Lugs
1Ø-240V Connections
1Ø-120V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered for 240V operation as shown in Figure 26.
2. Adjust voltage regulator knob (Figure 28) for an output of 208V to obtain 120V at the UVWO terminals.
3. Connect the load wires to the UVWO terminals as shown in Figure 30
BLACK
U
RED
V
SINGLE-PHASE
BLUE
W
120V
120V
120V
Figure 30. UVWO Terminal Lugs 1Ø-120V
Connections
WHITE
O
GREEN
GROUND
CONNECTION
MUST
AT ALL TIMES
OUTPUT TERMINAL PANEL CONNECTIONS
BE USED
480 VAC (LOAD CONNECTIONS)
BE USED
277 VAC (LOAD CONNECTIONS)
NOTICE
ALWAYS make sure that the connections to the UVWO terminals are secure and tight. The possibility of arcing exist that could cause a fire.
3Ø-480V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 480V operation as shown in Figure 31. This configuration uses 6 jumper plates in 3 different positions. Remember there are 2 jumper plates at every position. Every jumper plate must be used.
1Ø-480V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered for 480V operation as shown in Figure 31.
2. Connect the load wires to the UVWO terminals as shown in Figure 33.
BLACK
U
RED
V
480V
480V
THREE-PHASE
BLUE
W
480V
Figure 33. UVWO Terminal Lugs 1Ø-480V
Connections
WHITE
O
GREEN
GROUND
CONNECTION
MUST
AT ALL TIMES
1Ø-277V UVWO Terminal Output Voltages
Figure 31. UVWO Terminal Lugs 1Ø-120V
Connections
2. Connect the load wires to the UVWO terminals as shown in Figure 32.
BLACK
U
RED
V
THREE-PHASE
480 VAC (LOAD CONNECTIONS)
BLUE
W
Figure 32. UVWO Terminal Lugs
3Ø-480V Connection
WHITE
O
GREEN
GROUND
CONNECTION
BE USED
MUST
AT ALL TIMES
1. Make sure the voltage change-over board is jumpered for 480V operation as shown inFigure 31.
2. Connect the load wires to the UVWO terminals as shown in Figure 34.
BLACK
U
RED
V
SINGLE-PHASE
BLUE
W
277V
277V
277V
Figure 34. UVWO Terminal Lugs 1Ø-277V
Connections
WHITE
O
GREEN
GROUND
CONNECTION
MUST
AT ALL TIMES
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 35
INSPECTION/SETUP
CIRCUIT BREAKERS
To protect the generator from an overload, a 3-pole, 800 amp, main circuit breaker is provided to protect the U , V, and W Output Terminals from overload. In addition two single-pole, 20 amp GFCI circuit breakers are provided to protect the GFCI receptacles from overload. Three 50 amp load circuit breakers have also been provided to protect the auxiliary receptacles from overload. Make sure to switch ALL circuit breakers to the OFF position prior to starting the engine.
LUBRICATION OIL
Fill the engine crankcase with lubricating oil through the filler hole, but DO NOT overfill. Make sure the generator is level and verify that the oil level is maintained between the two notches (Figure 35) on the dipstick. See Table 11 for proper selection of engine oil.
FUEL CHECK
DANGER
Fuel spillage on a hot engine can cause a fire or explosion. If fuel spillage occurs, wipe up the spilled fuel completely to prevent fire hazards. NEVER smoke around or near the generator.
Refilling the Fuel System
CAUTION
ONLY properly trained personnel who have read
and understand this section should refill the fuel tank system.
This generator has an internal fuel tank located inside the enclosure (). ALWAYS fill the fuel tank with clean fresh #2 diesel fuel. DO NOT fill the fuel tank beyond its capacity. Some units may be equipped with a fuel cell mounted inside the trailer frame.
Figure 35. Engine Oil Dipstick
When checking the engine oil, be sure to check if the oil is clean. If the oil is not clean, drain the oil by removing the oil drain plug, and refill with the specified amount of oil as outlined in the John Deere Owner’s Manual. Oil should be warm before draining.
API service class engine oil is the recommended engine oil for this generator. When replacing engine oil please refill using API CJ-4, ACEA E9 or ACEA E6 engine oil.
Table 11. Recommended Motor Oil
Pay attention to the fuel tank capacity when replenishing fuel. The fuel tank cap must be closed tightly after filling. Handle fuel in a safety container. If the container does not have a spout, use a funnel. Wipe up any spilled fuel immediately.
300
FUEL CAP
Figure 36. Internal Fuel Tank System
INTERNAL
FUEL TANK
PAGE 36 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
INSPECTION/SETUP
Unlevel Ground
Unlevel Ground
Refueling Procedure:
WARNING
Diesel fuel and its vapors are dangerous
to your health and the surrounding environment. Avoid skin contact and/or inhaling fumes.
1. Level Tanks — Make sure fuel cells are level with the
ground. Failure to do so will cause fuel to spill from the tank before reaching full capacity (Figure 37).
CAUTION
ALWAYS place trailer on firm level ground before
refueling to prevent spilling and maximize the amount of fuel that can be pumped into the tank.
300
DO NOT fill on unlevel ground
!
!
3. NEVER overfill fuel tank — It is important to read the fuel gauge when filling trailer fuel tank. DO NOT wait for fuel to rise in filler neck (Figure 39).
FUEL GAUGE LOCATED
ON GAUGE UNIT ASSEMBLY
½
°F
E
F
FUEL
Figure 39. Full Fuel Tank
CAUTION
DO NOT OVERFILL fuel system. Leave room for fuel
expansion. Fuel expands when heated (Figure 40).
=
Level Ground
Level Ground
Figure 37. Only Fill on Level Ground
NOTICE
ONLY use #2 diesel fuel (ultra low sulfur diesel fuel) when refueling.
2. Open the enclosure door and remove fuel cap and fill tank as shown in Figure 38.
FUEL TANK
FILLER PORT
DIESEL
FUEL
Figure 40. Fuel Expansion
Figure 38. Fueling the Generator
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 37
INSPECTION/SETUP
DEF Refilling
NOTICE
ONLY fill the DEF tank with diesel exhaust fluid. Any other type of fluid may cause severe engine damage.
Diesel exhaust fluid is an aqueous solution made with 32.5% high puirty urea carbamide) and 67.5 deionized water. DEF is used as a consumable in selective catalytic reduction (SCR) in order to lower NOx concentration from diesel exhaust emissions.
1. Make sure engine is OFF.
2. Open the enclosure door and remove the filler cap from the DEF tank (Figure 41).
3. Upon initial start up, completely fill the DEF tank with DEF fluid. DO NOT overfill.
DEF Refilling (Continuous Operation)
It is recommended to shut down the engine prior to refilling the DEF tank. However, in special applications where shutdown is not possible, it is recommended to ONLY refill the DEF tank when the fluid level has been consumed down to 50%.
COOLANT (ANTIFREEZE/SUMMER COOLANT/ WATER)
John Deere recommends Cool-Gard II coolant for use in their engines, which can be purchased in concentrate (and mixed with 50% demineralized water) or pre-diluted. See the John Deere Engine Owner’s Manual for further details.
WARNING
If adding coolant/antifreeze mix to the radiator, DO NOT remove the radiator cap until the unit has completely cooled. The possibility of hot! coolant exists which can cause severe burns.
Day-to-day addition of coolant is done from the recovery tank. When adding coolant to the radiator, DO NOT remove the radiator cap until the unit has completely cooled. See Table 12 for engine, radiator, and recovery tank coolant capacities. Make sure the coolant level in the recovery tank is always between the “H” and the “L” markings.
Table 12. Coolant Capacity
TM
antifreeze/summer
The DEF level sending unit requires a gradual DEF level decrease during continuous operation to validate proper operation. Failure of this sensor to report the decrease could result in an engine shutdown. A engine service technician would be required to remedy the shutdown.
DEF TANK
CAUTION
EXHAUST FLUID ONLY
Filling this tank with
D
anything other than DIESEL EXHAUST FLUID
No Diesel
may result in severe engine damage.
M94110000
Figure 41. DEF Tank Filling
CAP
REAR VIEW
Engine and Radiator 17.7gal (67 liters)
Reserve Tank N/A
Operation in Freezing Weather
When operating in freezing weather, be certain the proper amount of antifreeze (Table 13) has been added.
Table 13. Coolant Capacity
Climate
Warm
Cold
Outside
Temperature
10°F (-12°C) or
Above
-22°F (30°C) or Above
NOTICE
When the antifreeze is mixed with water, the antifreeze mixing ratio must be less than 50%.
Longlife Coolant
Concentration
30%
50%
PAGE 38 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
INSPECTION/SETUP
Cleaning the Radiator
The engine may overheat if the radiator fins become overloaded with dust or debris. Periodically clean the radiator fins with compressed air. Cleaning inside the machine is dangerous, so clean only with the engine turned off and the negative battery terminal disconnected.
AIR CLEANER
Periodic cleaning/replacement is necessary. Inspect air cleaner in accordance with the John Deere Engine
Owner’s Manual.
FAN BELT TENSION
A slack fan belt may contribute to overheating, or to insufficient charging of the battery. Inspect the fan belt for damage and wear and adjust it in accordance with the John
Engine Owner’s Manual.
The fan belt tension is proper if the fan belt bends 10 to 15 mm (Figure 42) when depressed with the thumb as shown below.
BATTERY
This unit is of negative ground DO NOT connect in reverse. Always maintain battery fluid level between the specified marks. Battery life will be shortened, if the fluid level are not properly maintained. Add only distilled water when replenishment is necessary.
DO NOT over fill. Check to see whether the battery cables are loose. Poor contact may result in poor starting or malfunctions. Always keep the terminals firmly tightened. Coating the terminals with an approved battery terminal treatment compound. Replace battery with only recommended type battery. The battery type used in this generator is BCI Group 27.
The battery is sufficiently charged if the specific gravity of the battery fluid is 1.28 (at 68° F). If the specific gravity should fall to 1.245 or lower, it indicates that the battery is dead and needs to be recharged or replaced.
Before charging the battery with an external electric source, be sure to disconnect the battery cables.
Battery Cable Installation
Figure 42. Fan Belt Tension
CAUTION
NEVER place hands near the belts or fan
while the generator set is running.
0.17 ~ 0.20 IN. (4.2 ~ 5.0 MM) DEFLECTION
ALWAYS be sure the battery cables (Figure 43) are properly connected to the battery terminals as shown below. The red cable is connected to the positive terminal of the battery, and the black cable is connected to the negative terminal of the battery.
CAUTION
ALWAYS disconnect the negative terminal FIRST and reconnect negative terminal LAST.
NEGATIVE
POSITIVE
Figure 43. Battery Connections
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 39
INSPECTION/SETUP
When connecting battery do the following:
1. NEVER connect the battery cables to the battery
terminals when the Auto-Off/Reset-Manual Switch is in either the AUTO or MANUAL position. ALWAYS make sure that this itch is in the OFF/RESET position when connecting the battery.
2. Place a small amount of battery terminal treatment compound around both battery terminals. This will ensure a good connection and will help prevent corrosion around the battery terminals.
NOTICE
If the battery cable is connected incorrectly, electrical damage to the generator will occur. Pay close attention to the polarity of the battery when connecting the battery.
CAUTION
Inadequate battery connections may cause poor starting of the generator, and create other malfunctions.
ALTERNATOR
This unit is equipped with an automatic controlled Engine Starting Fluid System (KBi’s DIESELMATIC NVT) that assists the engine starting during low ambient temperature operation.
The system is designed to spray a controlled amount of starting fluid into the air intake system of the engine during and immediately after the engine cranks. The fluid cylinder is located on the unit’s right side center frame.
WARNING
The engine starting fluid used in the system is extremely flammable and toxic. It can be harmful and fatal if swallowed. Avoid contact with skin or breathing fumes.
DO NOT smoke when installing, removing, maintaining, testing or troubleshooting the system. Make sure you are in a well-ventilated area away from heat, open flames or sparks.
In low ambient temperature condition, if the engine does not start within a normal period of cranking, the starting fluid cylinder may be empty and need to be replaced. For more information about the system, refer to the provided KBi DIESELMATIC NVT Instruction Manual.
The polarity of the alternator is negative grounding type. When an inverted circuit connection takes place, the circuit will be in short circuit instantaneously resulting the alternator failure.
DO NOT put water directly on the alternator. Entry of water into the alternator can cause corrosion and damage the alternator.
WIRING
Inspect the entire generator for bad or worn electrical wiring or connections. If any wiring or connections are exposed (insulation missing) replace wiring immediately.
PIPING AND HOSE CONNECTION
Inspect all piping, oil hose, and fuel hose connections for wear and tightness. Tighten all hose clamps and check hoses for leaks.
If any hose (fuel or oil) lines are defective replace them immediately. cold weather engine starting fluid (ether system)
PAGE 40 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
GENERATOR START-UP PROCEDURE (MANUAL)
BEFORE STARTING
CAUTION
The engine’s exhaust contains harmful emissions. ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.
WARNING
NEVER manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.
1. Place the main, G.F.C.I., and aux. circuit breakers
(Figure 44) in the OFF position prior to starting the engine.
STARTING (MANUAL)
1. Place the Auto-Off/Reset Manual Switch in the
MANUAL position to start the engine (Figure 46).
Figure 46. Auto-Off/Reset Manual Switch
(Manual Position)
NOTICE
If engine fails to start in a specified number attempts, the shutdown lamp will illuminate and the Auto-Off/ Reset Switch must be placed in the Off/Reset position before the engine can be restarted.
NOTICE
Engine will pre-heat automatically in cold weather conditions." Glow Plug Hold " message will be displayed and the engine will start automatically after pre-heating..
Figure 44. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Make sure the voltage change-over board has been
configured for the desired output voltage.
3. Connect the load to the receptacles or the output
terminal lugs as shown in Figure 18. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.
4. Tighten terminal nuts securely to prevent load wires
from slipping out.
5. Close all engine enclosure doors (Figure 45).
2. Once the engine starts, let the engine run for 1-2 minutes Let engine idle longer in cold weather conditions. Listen for any abnormal noises. If any abnormalities exist, shut down the engine and correct the problem.
3. The generator’s frequency meter (Figure 47) should be displaying the 60 cycle output frequency in HERTZ.
Figure 47. Frequency Meter
4. The generator’s AC-voltmeter (Figure 48) will display the generator’s output in VOLTS.
INCORRECTCORRECT
Figure 45. Engine Enclosure Doors
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 41
Figure 48. Voltmeter
GENERATOR START-UP PROCEDURE (MANUAL)
5. If the voltage is not within the specified tolerance, use the voltage adjustment control knob (Figure 49) to increase or decrease the desired voltage.
Figure 49. Voltage Adjust Control Knob
6. The ammeter (Figure 50) will indicate zero amps with no load applied. When a load is applied, the ammeter will indicate the amount of current that the load is drawing from the generator.
Figure 50. Ammeter (No Load)
7. The engine oil pressure gauge (Figure 51A) will indicate the oil pressure of the engine. Under normal operating conditions the oil pressure is approximately 35 to 65 psi. (193~586 kPa).
10. The generator load gauge (Figure 52) Indicates the
generator load rate. It is recommended the load be above the red area (20%) for maintaining sufficient exhaust temperature.
50
0
%
100
Figure 52. Generator Load Gauge
11. Place the main, GFCI, and aux. circuit breakers in the ON position (Figure 53).
25
0
50
PSI
OIL PRESS
75
100
140
100
WATERTEMP
180
°F
220
260
AB
150
120
60
0
RPMX10
SPEED
180
210
C
Figure 51. Engine Gauges
8. The coolant temperature gauge (Figure 51B) will
indicate the coolant temperature. Under normal operating conditions the coolant temperature should be between 185°~207°F (85°~97°C).
9. The tachometer gauge (Figure 51C) will indicate the
speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.
Figure 53. Main, Aux. and GFCI
Circuit Breakers (ON)
12. Observe the generator’s ammeter (Figure 54) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if a load is in use.
Figure 54. Ammeter (Load)
13. The generator will run until manually stopped or an abnormal condition occurs.
PAGE 42 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
GENERATOR START-UP PROCEDURE (AUTO MODE)
STARTING (AUTO MODE)
DANGER
Before connecting this generator to any building’s electrical system, a licensed
electrician must install an isolation (transfer) switch. Serious damage to
the building’s electrical system may occur without this transfer switch.
CAUTION
When connecting the generator to a isolation (transfer) switch, ALWAYS have power applied to the generator’s internal battery charger. This will ensure that the engine will not fail due to a dead battery.
NOTICE
When the generator is set in the AUTO mode, the generator will automatically start in the event of commercial power falling below a prescribed level by means of a contact closure that is generated automatically by a transfer switch.
WARNING
When running the generator in the AUTO mode, remember the generator can start up at any time without warning. NEVER attempt to perform any maintenance when the generator is in the auto mode.
NOTICE
When the Auto Off/Reset Manual Switch is placed in the AUTO position, the engine glow plugs will be warmed and the engine will start automatically.
When starting generator in AUTO mode use the “Manual Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the Auto Off/Reset Manual Switch (Figure 55)
in the AUTO position.
Figure 55. Auto Off/Reset Manual Switch (AUTO)
3. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 2).
NOTICE
If the unit has Power Balance™ installed and once the main breaker is closed, the Power Balance™ should activate after 1 minute if the load is below 30% of rated load.
If at any time the load spikes to 90% or more, the Power Balance will immediately drop out and wait 5 minutes to re-evaluate the load.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 43
GENERATOR SHUT-DOWN PROCEDURES
MANUAL
(CENTER)
WARNING
NEVER stop the engine suddenly except in an
emergency.
NORMAL SHUTDOWN PROCEDURE
To shutdown the generator, use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers as shown in Figure 56 to the OFF position.
EMERGENCY SHUTDOWN PROCEDURE
1. In the event of an emergency, push the Emergency Stop Pushbutton Switch (Figure 58) to shutdown
the generator.
Figure 58. Auto Off/Reset Manual Switch (OFF)
Figure 56. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Let the engine cool by running it at low speed for 3-5 minutes with no load applied.
3. Place the Auto Off/Reset Manual Switch (Figure 57) in the OFF/RESET position.
AUTO
OFF/RESET
Figure 57. Auto Off/Reset Manual itch
(Off/Reset)
4. Verify that all status LEDs on the ECU control panel are OFF (not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of components that may have occurred during operation.
PAGE 44 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
MAINTENANCE
Table 14. Inspection/Maintenance
Check Engine Oil and Coolant Levels X
Check Fuel Filter/Water Separator Bowl X
Check Air Cleaner/Element X
Clean or Replace Air Cleaner/Element X
Check for Leaks/Hoses/Clamps X
Check for Loosening of Parts X
Change Engine Oil and Oil Filter *
Clean Unit, Inside and Outside X
Replace Fuel Filter Elements X
Check Engine Mounts X
Service Battery X
Check Air Intake Hoses X
Check Fan Belt Condition X
Check Automatic Belt Tensioner X
Engine
Generator
*1 During initial operation of a new engine, change oil and filter between a minimum of 100 hrs. and a maximum of 500 hrs. Service interval depends
on type of oil.
2
Perform inspection and maintenance of Urea SCR system every 4500 hours. The system does not need to replace/exchange if no problem is
*
found. Do not make any modification, changes or remove the emission control system and related parts. Please contact your nearest dealer or Multiquip Service Dept. for SCR maintenance.
3
If John Deere COOL-GARD™ II is used, the flushing intervals may be extended. See "Testing Diesel Coolant" in engine manual.
*
*4 Replace primary air filter element when restriction indicator shows a vacuum of 625 mm (25 in. H20).
*5 Service should be done as indicated by Diagnostic Gauge. Contact Multiquip Service Dept. for DOC replacement.
Check Electrical Ground Connection X
Clean Radiator, Check Cooling System X
Coolant Solution Analysis, Add SCA's As Required X
Pressure Test Cooling System X
Check Engine Speed X
Test Thermostats X
Check and Adjust Engine Valve Clearance 1000 hrs.
Test Glow Plugs X
Replace DEF Filter In (Supply Module) 4500 hrs.
Replace DOC Catalyst*
Check SCR System*
Inspect Dosing Module (SRC System) 4500 hrs
Flush and Refill Cooling System*
Clean Inside of Fuel Tank 1000 hrs.
Clean DEF Tank As Required
Replace Air Cleaner Elements *
Measure Insulation Resistance Over 3M ohms X
Check Rotor Rear Support Bearing X
5
2
1
3
4
10 Hrs
DAILY
250 Hrs
X
500 Hrs
or Every
12 Months
3000 Hrs or Every
36 Months
OTHER
As Required
4500 hrs.
1 yr. or 2000 hrs.
As Required
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 45
MAINTENANCE
PUSH BUTTON TO RESET
AN)
GENERAL INSPECTION
Prior to each use, the generator should be cleaned and inspected for deficiencies. Check for loose, missing or damaged nuts, bolts or other fasteners. Also check for fuel, oil, and coolant leaks. Use Table 14 as a general maintenance guideline Engine Side (Refer to the Engine Instruction Manual)
Air Filter Dust Indicator
NOTICE
The air filter should not be changed until the indicator reads “RED”. Dispose of old air filter. It may not be cleaned or reused.
The air filter indicator (Figure 59) is attached to the air filter. When the air filter element is clogged, air intake restriction becomes greater and the air filter indicator signal shows RED. When indicator is red, replace filter immediately. After changing the air filter, press the air filter indicator button to reset.
CAUTION
Wear protective equipment such as approved safety glasses or face shields and dust masks or respirators when cleaning air filters with compressed air.
Primary and Secondary Air Cleaner Elements
1. Release the latches (Figure 60) that secures the cover to the air cleaner body.
2. Remove the air cleaner cover and set aside.
3. Remove both the primary and secondary air cleaner elements.
4. Check the air cleaner daily or before starting the engine.
5. Check for and correct heavy buildup of dirt and debris along with loose or damaged components.
NOTICE
Operating the engine with loose or damaged air cleaner components could allow unfiltered air into the engine causing premature wear and failure.
Figure 59. Air Filter Dust Indicator
AIR CLEANER
NOTICE
If the engine is operating in very dusty or dry grass conditions, a clogged air cleaner will result. This can lead to a loss of power, excessive carbon buildup in the combustion chamber and high fuel consumption. Change air cleaner more frequently if these conditions exist.
Every 250 hours: Remove air cleaner element (Figure 60) and clean the heavy duty paper element with light spray of compressed air. Replace the air cleaner as needed.
This John Deere diesel engine is equipped with a replaceable, high-density paper air cleaner element. This air cleaner is also equipped with an inner element (secondary) that is used as a backup filter should the primary element becomes damaged.
25 INCHES HO
6.23 kPa
6. To clean the primary element (paper air filter) as referenced in (Figure 60), tap the filter element several times on a hard surface to remove dirt, or blow
2
compressed air not to exceed 30 psi (207 kPa, 2.1
2
kgf/cm
BODY
) through the filter element from the inside out.
PRIMARY
AIR FILTER
ELEMENT
SECONDARY
AIR FILTER
ELEMENT
BLOW COMPRESSED
AIR FROM THE
INSIDE OUT
Figure 60. Air Cleaner
AIR FILTER INDICATOR
LATCH
EVACUATOR
ARROW
(DUST P
VALV E
MARK
7. Clean the secondary element (paper air filter) as referenced in step 6.
8. Replace both elements if they are damaged or excessively dirty.
PAGE 46 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
MAINTENANCE
TER BODY
FUEL
9. Clean the inside of the air cleaner body.
10. Reinstall the primary and secondary air filter elements back into air cleaner body.
11. Reinstall the air cleaner cover, and secure with latches.
DRAINING FUEL FILTER CARTRIDGE
NOTICE
Inspect the fuel filter daily. If the fuel filter (Figure 61) has collected a significant amount of water and sediment at the bottom of the cartridge, it should be drained off immediately.
1. Loosen the air bleeder plug (Figure 61) on the fuel filter body.
2. To discharge the fuel inside the fuel filter cartridge OPEN the drain valve on the fuel filter by turning the knob counterclockwise (A) approximately 3-1/2 turns until the valve drops down 1-inch (25.4 mm) and draining occurs (B).
FUEL FILTER ELEMENT REPLACEMENT
1. Use a filter wrench to remove the fuel filter cup (Figure 62) from the fuel filter body.
FIL
(HEAD)
RETAINING
RING
GASKET
GASKET
FILTER
CARTRIDGE
AIR BLEEDER
PLUG
FUEL FILTER
CARTRIDGE
DRAIN VALV E
FILTER BODY
(HEAD)
RETAINING
RING
A
B
OPEN
DRAIN
Figure 61. Fuel Filter Draining
C
CLOSE
Figure 62. Fuel Filter Cartridge Replacement
2. Wipe the inside of the filter body (head) with a clean cloth to remove any foreign matter or debris that may have accumulated.
3. Replace both gaskets. Coat each gasket with a small amount of clean 15W-40 engine oil.
4. Install new fuel filter cartridge first by hand until it makes contact with the fuel filter body surface.
5. Tighten fuel filter cartridge securely. DO NOT over- tighten.
6. Remove the air from the fuel system. Reference John Deere Owner's Manual, "Bleeding the Fuel System.
3. Let the residue or foreign substances inside the cartridge flow into a suitable container.
4. At completion of draining CLOSE drain valve (C).
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 47
MAINTENANCE
FUEL FILTER
WATER SEPARATOR
CARTRIDGE
SEDIMENT
BOWL
FUEL WATER SEPARATOR SEDIMENT BOWL
1. Remove the sediment bowl from the fuel water separator cartridge as shown in Figure 63.
Figure 63. Sediment Bowl
2. Let the residue or foreign substances inside the sediment bowl flow into a suitable container.
FUEL WATER SEPARATOR REPLACEMENT
1. Use a filter wrench to remove the fuel water separator
cartridge (Figure 59) from the cartridge body head.
CARTRIDGE BODY
(HEAD)
RETAINING
RING
FUEL WATER
SEPARATOR
CARTRIDGE
Figure 64. Fuel Water Separator
2. Wipe the inside of the fuel water separator cartridge body (head) with a clean cloth to remove any foreign matter or debris that may have accumulated.
3. Wipe the inside of the sediment bowl with a clean cloth to remove any foreign matter or debris that may have accumulated.
4. Reinstall sediment bowl back onto fuel water separator cartridge
5. Tighten securely. DO NOT over-tighten.
3. Install new fuel water separator cartridge first by hand until it makes contact with the cartridge body (head) surface.
4. Tighten fuel water cartridge securely. DO NOT over- tighten.
Removing Water from the Fuel Tank
After prolonged use, water and other impurities accumulate in the bottom of the tank. Occasionally inspect the fuel tank for water contamination and drain the contents if required.
During cold weather, the more empty volume inside the tank, the easier it is for water to condense. This can be reduced by keeping the tank full with diesel fuel.
PAGE 48 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
MAINTENANCE
H (UPPER LIMIT)
(LOWER LIMIT)
Cleaning Inside the Fuel Tank
If necessary, drain the fuel inside the fuel tank completely. Using a spray washer (Figure 65) wash out any deposits or debris that have accumulated inside the fuel tank.
FUEL TANK
Drive Belt Inspection
Inspect the drive belt for damage and wear. Horizontal cracks (across the belt) are acceptable. Vertical (direction of belt ribs) cracks that intersect with horizontal cracks are not acceptable.
Also, examine the belt and determine if it is oil soaked or "glazed " (hard shiny appearance on the sides of the belt). Either of these two conditions can cause the belt to run hot, which can weaken it and increase the danger of it breaking.
If the drive belt exhibits any of the above wear conditions, replace the drive belt immediately.
NO
Figure 65. Fuel Tank Cleaning
FUEL TANK INSPECTION
In addition to cleaning the fuel tank, the following components should be inspected for wear:
Rubber Suspension — Look for signs of wear or
deformity due to contact with oil. Replace the rubber suspension if necessary.
Fuel Hoses — Inspect nylon and rubber hoses for signs
of wear, deterioration and hardening.
Fuel Tank Lining — Inspect the fuel tank lining for signs
of excessive amounts of oil or other foreign matter.
DRIVE BELT DAILY)
Drive Belt Tension
A slack drive belt (Figure 12) may contribute to overheating, or to insufficient charging of the battery, adjust drive belt in accordance with the John Deere Operator's manual.
NO
Figure 66. Drive Belt Inspection
ENGINE OIL CHECK (DAILY)
1. When checking or adding oil, place the machine so
the engine is level.
2. Pull the engine oil dipstick from its holder.
3. Determine if engine oil is low. Oil level should be
between the upper land lower limit (Figure 67) on the dipstick.
DO NOT
OVERFILL
L
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 49
Figure 67. Dipstick Engine Oil Level
MAINTENANCE
104
122
4. If oil level is low, add correct amount of engine oil to bring oil level to a normal safe level. See Recommended Viscosity Grades.
5. Allow enough time for any added oil to make its way to the oil pan before rechecking.
Table 15. Oil Selection Chart
5W/40
OIL: SAE
10W/30
10W
10W/40
15W/40
40
30
20W/20
F
86
68
50
-14
-4
-22
-40
50
40
30
20
10
-10
-20
-30
-40
C
032
5W/30
DRAINING ENGINE OIL
1. Run the engine until the engine coolant reaches a temperature of 140°F (60°C) Turn the engine off.
ENGINE OIL FILTER REPLACEMENT
1. Using an oil filter wrench (Figure 69), remove engine oil filter.
OIL FILTER
HEAD
FILTER
WRENCH
REMOVE AND
DISCARD OIL FILTER
INSTALL
NEW OIL
FILTER
COAT RUBBER
SEAL WITH THIN
LAYER OF OIL
2. Remove the oil dipstick from its holder.
3. Next, remove oil drain cap (Figure 68)
4. Place the oil drain valve in the OPEN position and
allow the oil to drain into a suitable container.
OIL DRAIN
CAP
(REMOVE)
OPEN
OIL DRAIN VALV E
Figure 68. Draining Engine Oil
5. After engine oil has been completely drained, reinstall oil drain cap and tighten securely.
6. Place the oil drain valve in the CLOSED position.
Figure 69. Engine Oil Filter Removal
2. Clean the area around the lubricating oil filter head.
3. Coat the rubber seal (gasket) surface of oil filter (Figure 69) with clean 15W-40 engine oil.
4. Install new oil filter first by hand until it makes contact with the filter head surface. Tighten it another 3/4 turn using the filter wrench.
5. Fill engine crankcase with high quality detergent oil classified "For Service CI-4". Fill to the upper limit of dipstick. DO NOT overfill. Reference Table 2 for engine crankcase oil capacity.
6. Run the engine for several minutes. Watch for oil leakage. Shut the engine down and allow it to sit for several minutes. Top off the oil to the upper limit on the dipstick.
PAGE 50 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
MAINTENANCE
COOLANT
DRAIN VALVE
(OPEN)
FLUSHING OUT RADIATOR AND REPLACING COOLANT
WARNING
DO NOT remove the pressure cap from the
radiator when the engine is hot! Wait until the coolant temperature is below 120°F (50°C) before removing pressure cap.
Heated coolant spray or steam can cause severe scalding and personal injury.
1. Place the coolant drain valve in the OPEN position
(Figure 70) and allow the coolant to drain into a suitable container.
RADIATOR CLEANING
The radiator (Figure 71) should be sprayed cleaned) with a high pressure washer when excessive amounts of dirt and debris have accumulated on the cooling fins or tube. When using a high pressure washer, stand at least 5 feet (1.5 meters) away from the radiator to prevent damage to the fins and tube.
Figure 70. Draining Engine Coolant
2. Check hoses for softening and kinks. Check clamps for signs of leakage.
3. Remove and inspect radiator cap.
4. Flush the radiator by running clean tap water through radiator until signs of rust and dirt are removed. DO NOT clean radiator core with any objects, such as a screwdriver.
5. Tighten water cock and replace the overflow tank.
6. Place the coolant drain valve in the CLOSED position.
Figure 71. Radiator Cleaning
GENERATOR STORAGE
For long term storage of the generator the following is recommended:
 Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
 Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
 Clean the entire generator, internal and external.
 Cover the generating set and store in a clean, dry place.
 Disconnect the battery.
 Make sure engine coolant is at proper level.
 If generator is mounted on a trailer, jack trailer up and
place on blocks so tires do not touch the ground or block and completely remove the tires.
7. Replace with coolant as recommended by the engine manufacturer.
8. Reinstall radiator cap. Tighten securely.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 51
MAINTENANCE
ENGINE BLOCK
WG.
ENGINE BLOCK HEATING ELEMENT AND INTERNAL BATTERY CHARGER 120 VAC INPUT RECEPTACLES (OPTIONAL)
This generator can be equipped as an option with a engine block heating element and an internal battery charger. They are provided with electric cords to connect
to a commercial power source.
The engine block heating element and internal battery charger both require 120 VAC in order to operate. A receptacle (Figure 72) has been provided on the output terminal panel to allow commercial power to be applied.
These units will ONLY function when commercial power has been supplied to them. When using extension cords, refer to Table 6 for the correct size and length.
HEATING ELEMENT
When using the generator in hot climates, there is no need to apply power to jacket water heater (heating element). However, if the generator will be used in cold climates, it is best to apply power to the jacket water heater at all times.
If the generator will be used daily, the battery should normally not require charging. If the generator will be idle (not used) for long periods of time, apply power to the battery charger receptacle via commercial power using a power cord of adequate size.
NOTICE
If the generator will be idle (not used) for long periods of time and to ensure adequate starting capability, always have power applied to the generator's internal battery charger.
BATTERY CHARGER
HEATING ELEMENT
120 VAC INPUT
RECEPTACLE
OUTPUT TERMINAL
PANELASSEMBLY
BATTERY CHARGER
120 VAC INPUT
RECEPTACLE
TO CHASSIS
GROUND
GREEN 16 A
!
TO STARTER “B”
TERMINAL
RED 16 AWG.
Figure 72. Heater Element and Battery Charger (Option)
PAGE 52 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
MAINTENANCE
EMISSION CONTROL
The emission control system employed with the John Deere 6090HF diesel engine consist of a Diesel Oxidation
Catalyst (DOC) and a Selective Catalytic Reduction (SCR) catalyst as an exhaust gas after-treatment system that helps reducing harmful gases and destroying the organic fraction of the particulate matter produced from the exhaust gas to meet the requirement for EPA Tier 4 Final regulations.
The DOC device (Figure 73) helps in filtering out large amounts of harmful Nitrogen Oxides (NOx) and Particulate Matter (PM) which are emitted by diesel engines. These exhaust emissions pose serious environmental and health risks. It is important to maintain and service the DOC emission safety device on a periodic basis.
Diesel Oxidation Catalyst (DOC)
The DOC does not filter particles it oxidizes them. This catalyst (honeycomb like structure) uses a chemical process to break down pollutants in the exhaust stream into less harmful components. In general, this catalyst collects/burns accumulated particulates. The DOC contains palladium and platinum which serve as a catalysts to oxidize hydrocarbons and carbon monoxide.
EMISSION CARBON CHECK
Deposition of carbon (soot, unburned fuel) in the exhaust pipe line and muffler could cause not only system derates but also could lead to fires.
To reduce soot and unburned fuel, run the unit at rated power until the exhaust gas becomes mostly colorless every 250 hours operation time. More carbon will be generated when the unit operates at less then 30% of rated power. In this case, perform the above procedures more frequently.
NOTICE
Applying a large load suddenly to the unit when the carbon deposition is generated in the exhaust system could produce sparks and will lead to abnormal combustion. Therefore, apply load gradually and observe the exhaust gas color during the process.
Figure 73. Diesel Oxidation Catalyst DOC)
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 53
MAINTENANCE
SCR PURGE
SELECTIVE CATALYTIC REDUCTION (SCR)
Diesel engines can be run with a lean burn air-to-fuel ratio, to ensure the full combustion of soot and to prevent the exhaust of unburnt fuel. The excess of air necessarily leads to generation of nitrogen oxides (NOx), which are harmful pollutants, from the nitrogen in the air. Selective Catalytic Reduction is used to reduce the amount of NOx released into the atmosphere.
Diesel Exhaust Fluid (DEF) from a separate tank is injected into the exhaust pipeline, where the aqueous urea vaporizes and decomposes to form ammonia and carbon dioxide. Within the SCR catalyst, the NO reduced by the ammonia (NH3) into water (H2O) and nitrogen (N2), which are both harmless; and these are then released through the exhaust.
The SCR system creates a certain amount of ammonia
) that is stored in SCR catalyst. During purging
(NH
3
operations the increase in temperature at regular intervals eleminates the stored ammonia.
The process of keeping accurate amonia storage amounts is by counting urea injection quantities from the Dosing Control Unit (DCU)
The SCR Purge symbol (Figure 74) will be displayed on the ECU controller during operation when either an automatic or forced system purge operation is in process.
The pre-alarm lamp is only ON during SCR forced system purging and OFF during automatic system purging
ECU
Series 800 Controller
are catalytically
x
Engine Started
Shutdown
Pre-Alarm
NOTICE
During urea SCR system purging, white smoke may be emitted from the exhaust tailpipe temporarily this shoud not be considered a failure. In addition the smell of ammonia during the purging process should not be considered a failure.
If the purging process is underway while running a light load (0-35%) the unit may produce unusual sounds. This should not be considered a failure or malfunction.
SYSTEM PURGING GUIDELINES
NOTICE
DO NOT perform purging in conditions where it may be unsafe due to high exhaust temperatures.
For safe operation of equipment, the surrounding area and the prevention of bodily harm, use the guidelines below when system purging is required:
NOTICE
The area above and around the generator during the purging process should be free of any type of debris, flammable or combustible materials, as temperatures during the purging process can reach as high 1,022 °F (550 °C).
DO NOT operate the unit in area with poor ventilation.
 If operating the engine indoors, install exhaust/ventilation
equipment and ensure that there is sufficient ventilation.
 If you begin to feel sick, stop the unit immediately and
ventilate the area.
 Exhaust emissions from the tailpipe have a smell different
from those emitted from engines without urea SCR systems due to the exhaust emission reduction functions of the exhaust system.
Alarm
Acknowledge
Screen
Change
Option
Program
Exit
Figure 74. SCR Purge Symbol
PAGE 54 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
MAINTENANCE
EF
If the diesel exhaust fluid (DEF) symbol (Figure 75) is displayed during ECU controller operation, it indicates the following:
 DEF tank level is below 10%. Reference Table 16, DEF
Level System Action System.
 DEF quality is poor. Check DEF tank level and check
active diagnostics trouble codes (DTC).
ECU
Series 800 Controller
Alarm
Acknowledge
Screen Change
DEF STAT
Program
Option
Engine Started
Shutdown
Pre-Alarm
Exit
DIESEL EXHAUST FLUID (DEF)
The amount of fluid in the DEF tank will be shown on the ECU Controller main screen during operation. The symbol shown in Figure 76 will be shown on the ECU monitor indicating the level of fluid in the DEF tank.
DEF
Figure 76. DEF Tank Level Guage
Figure 75. ECU DEF State Pre-Alarm
NOTICE
Models equipped with the 845 Series ECU Controller will enter emergency shutdown when the DEF level has reached 0% and emergency protective measures are necessary. When this condition exist, the unit can only be restarted after the ESCAPE MODE is activated and the unit will run for 30 minutes. Reference "Escape Mode" section in this manual.
Table 16. DEF Level System Action System
DEF Level Over 10% Below 10% 0% Empty or After 4 hrs. From 0%
Controller Message DEF<10% Tank Level DEF<10% Tank Level DEF Tank Empty Level
DEF Symbol
ON
Pre-Alarm Lamp
Shutdown Lamp
Blinking Blinking
ON ON
ON
Engine Shutdown
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 55
INDUCEMENT
When the system senses improper usage such as no supply of DEF, use of poor quality DEF, problems with DEF jets, or disconnection of sensors, a warning will be issued before the situation becomes critical. If the warnings are ignored and the unit enters intermittent operation, the emergency shutdown will activate. The three warning levels are referenced in Table 17:
Table 17. DEF Inducement
MAINTENANCE
Stage Controller Message
Stage 1
Warning Level 1
Stage 2
Warning Level 2
SCR System
Malfunction
SCR System
Malfunction
SCR System
Pop-Up
SCR SYS ERR
SCR SYS ERR
DEF Symbol
Pre-Alarm
Lamp
ON
ON
Shutdown
Lamp
Slow Blinking
Stage 3
Shutdown
1
SCR System
Malfunction
SCR SYS ERR
ON ON
Fast Blinking
1
When emergency shutdown occurs, inspection and repair should generally be performed promptly. However, if
emergency protective measures are necessary, unit will enter ESCAPE MODE and may require as much as 30 minutes to restart.
PAGE 56 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
HOW TO ACTIVATE ESCAPE MODE
BUTT
[PROGRAM EXIT]
BUTTON
If the ECU displays any messages referenced in Table 18 or Figure 77, it may be necessary to restart via ESCAPE MODE.
VOLTS AMPS
UO VO
WO
------
UV
VW WU
KW KVA HZ 00000.9 h
ADD DEF OR USE ESCAPE MENU
Figure 77. Add DEF/Escape Menu Screen
U V
W
MAINTENANCE
SPEED
0000
EF
EF
DEF
CANBUS IS WORKING OK
HOURS
00009.7
Starting
1. Start the Diagnostic Mode as referenced in the "Troubleshooting Diagnostics" section in this manual.
2. Exit the Status Check Screen by pressing the [EXIT] button (Figure 78).
EF
EF
DEF
HOURS
25.1v
CANBUS IS WORKING OK EXIT
[EXIT]
00009.7
DIAGNOSTIC MODE
ON
STATUS
CHECK
Alarm Screen
Change
Option
Program
Exit
Figure 79. Main Screen
4. Press the [DOWN] button (Figure 80) to scroll to the
Escape Mode item.
FORCE REGEN FAULT DIAGNOSTICS ABOUT UNIT USER LOGIN CUSTOMER OPTIONS ADVANCED OPTIONS ESCAPE MODE
UP DOWN SELECT
Figure 78. Status Check Screen
Diagnostic Mode)
3. Next, press the [Program/Exit] button (Figure 79) to enter the Main Menu.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 57
[DOWN]
BUTTON
Figure 80. Main Menu Down Button)
MAINTENANCE
[SELECT]
MANUAL
(CENTER)
5. Press the [SELECT] button (Figure 81) to enter the
“Escape Mode” menu.
FORCE REGEN FAULT DIAGNOSTICS ABOUT UNIT USER LOGIN CUSTOMER OPTIONS ADVANCED OPTIONS ESCAPE MODE
UP DOWN SELECT
BUTTON
Figure 81. Escape Mode (Select Button)
6. Press the [REQUEST] button (Figure 82) to send
"Escape Mode Request" signal to ECM.
ESCAPE MODE REQUEST EMERGENCY RESERVE ENGINE
RUN MAY BE POSSIBLE.
>> ESCAPE MODE ACTIVATED <<
POWER OFF. ON. TO RESTART
TO ATTEMPT ESCAPE MODE:
PRESS THE REQUEST SOFT KEY.
EXIT
REQUEST
Figure 83. Escape Mode Activated Screen
8. Place the Auto Start/Stop Switch (Figure 84), to the “Off /Reset” position.
AUTO
OFF/RESET
ESCAPE MODE REQUEST
EMERGENCY RESERVE ENGINE RUN MAY BE POSSIBLE.
TO ATTEMPT ESCAPE MODE:
PRESS THE REQUEST SOFT KEY.
EXIT
REQUEST
[REQUEST]
BUTTON
Figure 82. Escape Mode (Request Button)
7. Once the [REQUEST] button has been pressed,
the display will indicate that escape mode has been activated (Figure 83).
Figure 84. Auto Off/Reset Manual Switch
(Off/Reset Position)
9. Next, place the Auto Start/Stop Switch (Figure 85) to the “Manual” position to start the engine.
Figure 85. Auto-Off/Reset Manual Switch
(Manual Position)
PAGE 58 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
10. The Escape Mode Timer (Figure 86) will appear on
ESCAPE MODE
the main screen. This timer displays remaining time the unit can be operated.
TIMER (SEC)
DEF LOW! SHUTDOWN IN 0048
UO
100
VO
UV VW
173
U
0000
V
MAINTENANCE
100
WO
------
DERATE CONDITION EXISTS
Figure 86. Escape Mode Timer
 If ESCAPE MODE is temporarily suspended, it is not
necessary to return to the ESCAPE MODE screen and press the [REQUEST] button. ESCAPE MODE operation will be available until around 30 minutes after operation has been ended.
 Once the ESCAPE MODE timer reaches zero minutes,
the engine will stop since the ESCAPE MODE time has expired. Please perform maintenance to return unit to proper operating condition.
 If the unit returns to Warning Level 1 while ESCAPE
MODE is running, ESCAPE MODE will be cancelled, the ESCAPE MODE timer display will close, and normal operation will resume.
WU
173
KW
T
40.0 HZ 00000.9 h
W
0000
------
KVA
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 59
MAINTENANCE
PROTECTION DEVICES
Automatic Shutdown System
This unit is equipped with engine protection devices that automatically shut down the engine if any of the faults shown in Table 18 occur. The “Shutdown” LED on the ECU Controller will turn on just before the shutdown and will stay on after the shutdown. Messages will appear on the ECU display.
After the automatic shutdown, check all Diagnostic Test Codes (DTC) displayed on the ECU Controller. Reference the Troubleshooting Diagnostic section in this manual.
Table 18. Automatic Engine Shutdown System
Operating Parameter
ECU
Shutdown LED
Place the Auto Start/Stop Switch in the “Off/Reset” position. In addition, place all circuit breakers in the OFF position. Before troubleshooting, allow sufficient time for adequate cooling. Before attempting to restart the generator, perform overall inspection of the generator and correct the problem that caused the shutdown. If necessary, contact your nearest Multiquip dealer for additional technical support.
Restart the generator as reference in the Generator Startup Procedure (Manual Start).
NOTICE
Although the unit is equipped with engine protection devices, regularly scheduled preventative maintenance is strongly advised.
Operating Condition/Set Point
Low Oil Pressure
High water Temperature
Low Coolant Level
High Water Level In Fuel Water Separator
High Engine Fuel Temperature
High Charged Air-Cooler Outlet Temperature
Exhaust System Severe Malfunction
Over-Voltage
Under-Voltage
High Power (kW)
Over-Frequency (Hz)
Under-Frequency (Hz)
Over-Current Main CB Trip Load Capacity Exceeded
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Set Point: 17 PSI ((117 kPa)
Set Point: 240°F (116°C)
Falls Below Specified Level
Water Level has Exceeded Filter Capacity
Fuel Temperature Too High
Fuel Temperature Too High
Reference Exhaust System,
DEF, Regeneration Sections
Set Point: 110%
Set Point: 75%
Set Point: 115%
Set Point: 110%
Set Point: 90%
PAGE 60 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
GENERATOR WIRING DIAGRAM
COT. B
X
2
U
1
U
Y
2
1
V
V
Z
2
W
1
W
O
Voltage Change-Over
Board-240V Set
2
1
3
A J C
CN1
CN3
VIEW FROM INSERTING
DKB
1
2
1
3
1
R
CN5
WIRE SIDE
C1
CIRCUIT
BREAKER
C2
SIDE
CB1 CONNECTOR
(VIEW FROM INSERTING
WIRE SIDE)
1
2
CN4
2 3
S
2
C2
1
C1
CN2
T
1
2 3
V W
U
3
2 1
S
T
COT. B
X
Y
Z
O
Voltage Change-Over
Board-480V Set
CONTROL
BOX SIDE
R
CONTROL
PANEL
SIDE
(VIEW FROM INSERTING
U
2
1
U
V
2
1
V
W
2
1W
3 2
W1
S O
1 2
U1 U2 V2
REF. DES.
K
NOTE: EACH CABLE IS PASSED TWICE THROUGH CURRENT TRANSFORMERS CT4~5
1
3 2
V1
V1
R T
R T
U1 U2 V2
3
W1
S O
21
17 18
6
3 2
19
4
19
4
CONNECTOR
WIRE SIDE)
WIRE SIZE
125: 125 mm 100: 100 mm 80: 80 mm
22: 22 mm 14: 14 mm 8: 8 mm
5.5: 5.5 mm
NO MARK WIRE SIZE: 1.25
CURRENT TRANSFORMERS (CT4 ~ 5)
k
l
L
1
17
2
1
17
2
2
2
2
2
2
2
2
2
3
1
1
B L BR G GR V P
MARK AT CT
X1
NO MARK
H1
NO MARK
1
1
2
3
CODE/WIRE COLOR
BLACK BLUE BROWN GREEN GRAY VIOLET PINK
mm
R W Y LB LG O
2
SYMBOL
Ar
Fg ExAr ExFg
Re
AVR
VR
CT 1~3 CT 4~5
AS
A
~
V
~ F
CB1
CB2~3 CB4~6
CON1~2 CON3~ 5
OC
COT. B
AS
RED WHITE YELLOW LIGHT BLUE LIGHT GREEN ORANGE
DESIGNATION
MAIN GENERATOR ARMATURE WINDING MAIN GENERATOR FIELD WINDING EXCITER ARMATURE WINDING EXCITER FIELD WINDING RECTIFIER AUTOMATIC VOLTAGE REGULATOR VOLTAGE REGULATOR (RHEOSTAT) CURRENT TRANSFORMER 500:5A
CURRENT TRANSFORMER 500:5A CHANGE-OVER SWITCH,AMMETER
AC AMMETER 0~500, 1000A
AC VOLTMETER 0~600V FREQUENCY METER 45~65 Hz @220V CIRCUIT BREAKER, 3P 800A CIRCUIT BREAKER, 1P 20A
CIRCUIT BREAKER, 2P 50A
RECEPTACLE, GFCI, 125 VAC @ 20 AMPS X 2
RECEPTACLE, CS6369, 250 VAC@ 50 AMPS
OVER CURRENT RELAY VOLTAGE CHANGE-OVER BOARD
AC AMMETER CHANGE-OVER SWITCH
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 61
ENGINE WIRING DIAGRAM (ECU-845)
PAGE 62 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
ENGINE WIRING DIAGRAM (BASLER DGC2020HD OPTION)
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 63
(GND.)
THIS EXAMPLE SELECT
O HANDLE FULL
OF GENERA
PHASE
GREEN
(NEU.)
WHITE
(L3)
BLUE
GENERATOR #2
(L2)
RED
3Ø-480 VAC PARALLEL WIRING DIAGRAM
PARALLEL WIRING CONNECTIONS
VIA CAMLOKS DCA300SSJU4F2
3-PHASE 480 VAC
(L1)
BLK
(GND.)
GREEN
(NEU.)
WHITE
(L3)
BLUE
GENERATOR #1
(L2)
RED
(L1)
BLK
PHASE C (W)
(GND.)
GREEN
NOTE:
MINIMUM CABLE SIZE IS 4/0.
ALL FIVE CAMLOK PAIRS ARE CONNECTED.2POINT OF CONNECTION/COMMON OUTPUT BUS
1
POWER DISTRIBUTION PANEL WITH INDIVIDUAL
DISCONNECT SWITCHES.
3
WHITE
(NEUTRAL)
PHASE B (V)
(L3)
BLUE
1
2
PHASE A (U)
3
PHASE C (W)
CORRECT SIZE OF CABLES
LOAD
LOAD/AMPERAGE (722 AMPS @ 480 VAC)
(L2)
RED
TOR.
PHASE B (V)
PAGE 64 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
BLK
(L1)
A (U)
T
IN
(GND.)
THIS EXAMPLE SELECT
FULL LOAD/AMPERAGE (1600
PHASE
GREEN
(NEU.)
WHITE
BLUE
GENERATOR #2
(L2)
RED
(L1)
BLK
3Ø-208 VAC PARALLEL WIRING DIAGRAM
PARALLEL WIRING CONNECTIONS
VIA CAMLOKS DCA300SSJU4F2
3-PHASE 208 VAC
(L3)
(GND.)
GREEN
(NEU.)
WHITE
BLUE
GENERATOR #1
(L2)
RED
(L1)
BLK
(L3)
NOTE:
MINIMUM CABLE SIZE IS 4/0.
1
PHASE C (W)
PHASE B (V)
1
2
PHASE A (U)
3
(GND.)
GREEN
WHITE
(NEUTRAL)
(L3)
BLUE
PHASE C (W)
LOAD
POWER DISTRIBUTION PANEL WITH INDIVIDUAL
ALL FIVE CAMLOK PAIRS ARE CONNECTED.2POINT OF CONNECTION/COMMON OUTPUT BUS
DISCONNECT SWITCHES.
3
AMPS @ 208 VAC) OF GENERATOR.
CORRECT SIZE OF CABLES TO HANDLE
(L2)
RED
PHASE B (V)
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 65
BLK
A (U)
(L1)
IN
BATTERY CHARGER WIRING DIAGRAM
CORD, CAROL 3/C 14 AWG., P/N EE56557.
BLACK 14 AWG. LINE (L)120VAC INPUT
AB
WHITE 14 AWG. NEUTRAL (N)
3
1
2
GREEN 14 AWG. GROUND (G)
4
TO CHASSIS
GROUND
GREEN 16 AWG.
!
3
TO STARTER “B”
TERMINAL
RED 16 AWG.
B
A
4
NOTES:
1
NEMA 5-15, 15A, 120 VAC, P/N HBL5278C/HUBBLE RECEPTACLE.
2
RECEPTACLE IS MOUNTED ON OUTPUT TERMINAL PANEL ASSY.
3
20 AMP, 5-20R RECEPTACLE, P/N HBL5369C/HUBBLE RECEPTACLE.
4
PAGE 66 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
2
1
120 VAC INPUT, INSERT EXTERNAL
POWER CORD HERE.
ENGINE BLOCK HEATER WIRING DIAGRAM
AB
BLACK 14 AWG. LINE (L)120VAC INPUT
WHITE 14 AWG. NEUTRAL (N)
3
4
1
2
GREEN 14 AWG. GROUND (G)
ENGINE
BLOCK HEATER
BLACK 14 AWG.
LINE (L)120VAC INPUT
3
B
4
WHITE 14 AWG.
NEUTRAL (N)
GREEN 14 AWG.
GROUND (G)
120 VAC INPUT, INSERT EXTERNAL
POWER CORD HERE.
TEMP.
SWITCH
120 VAC
HEATING
ELEMENT
GROUND
A
NOTES:
1
NEMA 5-15, 15A, 120 VAC, P/N HBL5278C/HUBBLE RECEPTACLE.
2
RECEPTACLE IS MOUNTED ON OUTPUT TERMINAL PANEL ASSY.
3
20 AMP, 5-20R RECEPTACLE, P/N HBL5369C/HUBBLE RECEPTACLE.
4
CORD, CAROL 3/C 14 AWG., P/N EE56557.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 67
2
1
TROUBLESHOOTING (GENERATOR)
Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a breakdown, use Table 19 shown below for diagnosis of the Generator. If the problem cannot be remedied, consult our company’s business office or service plant.
Table 19. Generator Troubleshooting
Symptom Possible Problem Solution
AC Voltmeter defective? Check output voltage using a voltmeter.
Is wiring connection loose? Check wiring and repair.
No Voltage Output
Low Voltage Output
High Voltage Output
Circuit Breaker Tripped
Is AVR defective? Replace if necessary.
Defective Rotating Rectifier? Check and replace.
Defective Exciter Field? Check for approximately 19 ohms across J & K on CN1
Is engine speed correct? Place engine speed switch in “High” position.
Is wiring connections loose? Check wiring and repair.
Defective AVR? Replace if necessary.
Is wiring connections loose? Check wiring and repair.
Defective AVR? Replace if necessary.
Short Circuit in load? Check load and repair.
Over current? Confirm load requirements and reduce.
Defective circuit breaker? Check and replace.
Over current Relay actuated? Confirm load requirement and replace.
PAGE 68 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
Symptom Possible Problem Solution
Engine will not start or start is delayed, although engine can be turned over.
At low temperatures engine will not start.
Engine fires but stops soon as starter is switched off.
Engine stops by itself during normal operation.
Low engine power, output and speed.
TROUBLESHOOTING (ENGINE)
Troubleshooting (Engine)
No Fuel reaching injection pump? Add fuel. Check entire fuel system.
Defective fuel pump? Replace fuel pump.
Fuel filter clogged? Replace fuel filter and clean tank.
Faulty fuel supply line? Replace or repair fuel line.
Compression too low?
Fuel pump not working correctly? Repair or replace fuel pump.
Oil pressure too low? Check engine oil pressure.
Low starting temperature limit exceeded?
Defective battery? Charge or replace battery.
Air or water mixed in fuel system?
Engine oil too thick?
Defective battery? Replace battery.
Fuel filter blocked? Replace fuel filter.
Fuel supply blocked? Check the entire fuel system.
Defective fuel pump? Replace fuel pump.
Fuel tank empty? Add fuel.
Fuel filter blocked? Replace fuel filter.
Defective fuel pump? Replace fuel pump.
Mechanical oil pressure shutdown sensor stops the engine due to low oil?
Fuel tank empty? Replace fuel filter.
Fuel filter clogged? Replace fuel filter.
Fuel tank venting is inadequate? Ensure that tank is adequately vented.
Leaks at pipe unions?
Speed control lever does not remain in
selected position?
Engine oil level too full? Correct engine oil level.
Injection pump wear?
Check piston, cylinder and valves. Adjust or repair per engine repair manual.
Comply with cold starting instructions and proper oil viscosity.
Check carefully for loosened fuel line
coupling, loose cap nut, etc.
Refill engine crankcase with correct type of oil for winter environment.
Add oil. Replace low oil shutdown sensor if necessary.
Check threaded pipe unions tape and tighten unions a required.
See engine manual for corrective action.
Use No. 2-D diesel fuel only. Check the fuel injection pump element and delivery valve assembly and replace as necessary.
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 69
Symptom Possible Problem Solution
Low engine power output and low speed, black exhaust smoke.
Engine overheats.
TROUBLESHOOTING (ENGINE)
Troubleshooting (Engine) - continued
Air filter blocked? Clean or replace air filter.
Incorrect valve clearances? Adjust valves per engine specification.
Malfunction at injector? See engine manual.
Too much oil in engine crankcase?
Entire cooling air system contaminated/ blocked?
Fan belt broken or elongated? Change belt or adjust belt tension.
Coolant insufficient? Replenish coolant.
Radiator net or radiator fin clogged with dust? Clean net or fin carefully.
Fan, radiator, or radiator cap defective? Replace defective part.
Thermostat defective? Check thermostat and replace if necessary.
Head gasket defective or water leakage? Replace parts.
Drain off engine oil down to uppermark on
dipstick.
Clean cooling air system and cooling fin areas.
PAGE 70 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
TROUBLESHOOTING (DIAGNOSTICS)
PROGRAM EXIT
845 ECU SERIES CONTROLLER
The engine controller of this generator diagnoses problems that arise from the engine control system and the engine itself.
1. With the engine stopped (OFF). Push and hold the
Hour Check Button (Figure 87) located on the control panel.
HOUR CHECK
BUTTON
Figure 87. Hour Check Button
4. Releasing the Hour Check Button and pushing the Program/Exit Button on the ECU controller will return
the controller to the main screen.
BUTTON
Figure 89. Program Exit Button
5. Push the Program/Exit Button on the ECU controller and select the Fault Diagnostics mode. This mode enables the ability to carry out the fault diagnostics as listed below:
2. While keeping the Hour Check Button pressed, place the Auto Off/Reset Manual Switch (Figure 88) in the
MANUAL position.
Figure 88. Auto-Off/Reset
3. The Hour Check Menu Screen will be displayed on the ECU controller.
(Manual Position)
Switch
DM1 Active Faults — Displays active fault messages
and codes.
DM2 Messages and Codes — Displays messages and
codes which previously occurred that are recorded in the Engine Control Module (ECM).
Last Shutdown — Displays the messages and codes
that caused the most recent shutdown.
6. After perfoming diagnostic tests, place the Auto Off/
Reset Manual Switch in the OFF position
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 71
TROUBLESHOOTING (DIAGNOSTICS)
DGC2020HD SERIES CONTROLLER
At times, it may be desired to power up the Engine Control Module (ECM), key switch ON while the engine is not running. This can be useful for diagnostic purposes and fault clearing.
To enter the diagnostic mode with the controller in the OFF mode and the engine not running do the following:
1. Press and hold the Alarm Slience and Lamp Test buttons (Figure 90) at the same time for 10 seconds.
PRESS
LAMP
TEST
BUTTON
ALARM
SILENCE
BUTTON
SIMULTANEOUS
7. The dianostic mode will remain active until the Reset button (Figure 91) is pressed or if the engine rpm becomes greater than zero.
Reset
Figure 91. Reset Button
Figure 90. Alarm Silence/Lamp Test Buttons
2. Listen for an audiable click inside the control panel which is the run relay that controls the key switch.
3. While in diagnostic mode the controller can see real time engine CAN Bus data including Diagnostic Trouble Codes (DTC).
4. To view active DTC codes navigate to Metering >J1939 ECU>DTC Active Data.
5. For previously active codes navigate to Metering>J1939 ECU>DTC Prev Data.
6. Real time ECM parameters are not supported due to lack of sensors etc. and will display NS for No Signal.
PAGE 72 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
NOTES
DCA300SSJU4F2 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (06/26/18) — PAGE 73
OPERATION MANUAL
HERE’S HOW TO GET HELP
© COPYRIGHT 2018, MULTIQUIP INC.
Multiquip Inc
are registered trademarks of Multiquip Inc. and may not be used, reproduced, or altered without written permission. All other
trademarks are the property of their respective owners and used with permission.
This manual
The information and specifi cations included in this publication were in effect at the time of approval for printing. Illustrations, descriptions, references and technical data contained in this manual are for guidance only and may not be considered as binding. Multiquip Inc. reserves the right to discontinue or change specifi cations, design or the information published in this publication at any time without notice and without incurring any obligations.
DENYO CO., LTD, JAPAN
PLEASE HAVE THE MODEL AND SERIAL
NUMBER ON-HAND WHEN CALLING
UNITED STATES
Multiquip Corporate Office MQ Parts Department
18910 Wilmington Ave. Carson, CA 90746 Contact: mq@multiquip.com
Service Department Warranty Department
800-421-1244 310-537-3700
Technical Assistance
800-478-1244 Fax: 310-943-2238
CANADA
Multiquip Multiquip (UK) Limited Head Office
4110 Industriel Boul. Laval, Quebec, Canada H7L 6V3 Contact: infocanda@multiquip.com
Tel. (800) 421-1244 Fax (310) 537-3927
Tel: (450) 625-2244 Tel: (877) 963-4411 Fax: (450) 625-8664
800-427-1244 310-537-3700
800-421-1244 310-537-3700
UNITED KINGDOM
Unit 2, Northpoint Industrial Estate, Globe Lane, Dukinfield, Cheshire SK16 4UJ Contact: sales@multiquip.co.uk
Fax: 800-672-7877
Fax: 310-943-2249
Tel: 0161 339 2223 Fax: 0161 339 3226
, the MQ logo and the MQ Power logo
MUST accompany the equipment at all times. This manual is considered a permanent part of the equipment and should remain with the unit if resold.
Manufactured for
MQ Power Inc.
Your Local Dealer is:
by
Loading...