MPS R00D Installation And Operating Instructions Manual

Model Number R00D
Dual Air Pressure Booster System • Installation and Operating Instructions
MPS
M I DW EST PRESSURE SY ST E M S
MPS
M I DW E ST PRESSURE SY S T EM S
1-1/2" Square
2" Square
A
A
C
B
1
1
2
334
4
2
Installation
Bolt the assembly to the floor using the four mounting brackets located on each corner of the system (A). The mounting pattern is a 7.5” x 16.3” rectangle. Mounting screws can be up to 7/16 of an inch in diameter.
Connect the drive air supply to the 3/4 inch FNPT 5 micron inlet filter (B). The air supply piping should be 3/4 inch pipe diameter or larger.
Connect the discharge line to the 1 inch FNPT pipe port located on the back of the system (C). The discharge piping should be 3/4 inch pipe diameter or larger.
WARNING: Make sure that the discharge piping components are rated for 230 psi. If the discharge piping has a lower pressure rating it should be protected by a safety relief valve.
Startup
This booster can be operated with one or both boosters. To operate with both boosters, open the inlet valves (1) and discharge valves (2). To operate with one booster, close the inlet valve and discharge valve of the desired booster.
There is a discharge pressure regulator for each of booster. Pull up on the black knob on the top of the booster to unlock it. Turn the knob to increase or decrease the desired discharge pressure. The regulators are self-relieving. If one is set for a higher pressure, the other regulator will try to vent the pressure. When both boosters are operating at the same time, the regulators must be set to the same pressure. The location of the
pressure gauges (3) and the discharge pressure gauges (4) are shown above. When the boosters have pressurized the downstream components to the maximum desired pressure, they will stall. If one of the self-relieving regulators vents at the stall condition, turn the knob clockwise until the venting stops. The maximum recommended discharge pressure is 230 psi. If the supply pressure is higher than 115 psi, it is possible to set the regulators so the system exceeds the maximum discharge pressure of 230 psi. During startup, do not turn the regulators to their highest setting, but slowly increase the regulator settings until the desired pressure is reached.
WARNING: Do not exceed the maximum allowable discharge pressure of 230 psi.
Operation
The system is fully automatic. When the desired discharge pressure has been reached, and no flow is required, the boosters will stop automatically. They will restart when the discharge pressure drops about 5 psi.
Maintenance
The air supply filter should be checked periodically. If a booster needs to be removed for service, close the air supply valve and the discharge valve. The discharge valve will vent the pressure between the two valves and the booster pressure gauges should both read zero. The idle booster can be safely removed and repaired while the other booster continues to operate.
Midwest Pressure Systems, Inc.
850 Transport Drive, Valparaiso, IN 46383 Phone 219-462-0070 Fax 219-318-2277
www.midwestpressuresystems.com
Model Number R00D
Bootstrap Compressor • Operation and Warranty
MPS
M I DW EST PRESSURE SY ST E M S
MPS
M I DW E ST PRESSURE SY S T EM S
1-1/2" Square
2" Square
Compression Chamber A1
Compression Chamber A2
Drive Chamber B2
Drive Chamber B1
Piston 1
Piston 2
4-way Valve Switch
4-way Valve Switch
Pilot Signal to regulator Built-in discharge regulator Regulated drive air
Plant air
Exhaust air
Pilot signal to regulator
High pressure air
Exhaust air
Regulated drive air
Please refer to the operating description on the right, and the schematic above to gain an understanding of the design principles and mechanical function of the model R00D Booster System. The moving parts of each Bootstrap Compressor are permanently lubricated with a multipurpose grease (except for the check valves). Operation with a lubricator upstream voids the warranty. If a lubricator is required, it should be installed on the downstream (discharge) side. A well-maintained 5 micron inlet air filter is required to maintain the warranty by ensuring that no dust particles enter the units and foul the seals, or cause premature wear of the highly-polished seal surfaces. The wear parts in the boosters consist of check valves, springs and dynamic seals. These parts are designed for 1800 miles of piston travel. The four-way valve, which controls movement of the pistons, is a lapped, stainless steel valve with no elastomeric seals subject to wear. Under normal conditions, this valve will provide many years of operation. The discharge regulator built into the center of the unit sees very little wear, and is designed to provide many years of service under normal conditions. The wear parts are typically replaced 2 to 3 times before a valve or regulator kit is required.
#KRW • Wear parts kit #KRV • Valve kit #KRR • Regulator kit
The plant air stream always fills Compression Chambers A1 and A2 directly, through a set of check valves. These two chambers are always pressurized to the maximum initial air pressure available (the R00D Booster System is not designed for inlet air pressures higher than 150 psig). A branch of the plant air stream flows through a pilot-activated regulator, which reduces the pressure to the level required to attain the desired Bootstrap Compressor discharge pressure (the discharge pressure is set manually by adjusting the regulator handle). This regulated air stream flows through a four­way valve which directs it to Drive Chamber B2. At the same time, the four-way valve opens Drive Chamber B1 to exhaust. The pressure force exerted on the interconnected pistons by the pressures in Drive Chamber B2 and Compression Chamber A1, is sufficient to compress the air in Chamber A2 to a higher pressure (the maximum discharge pressure attainable is two times the plant air pressure). At the end of its travel, Piston 2 switches the four way valve, which opens Drive Chamber B2 to exhaust, and pressurizes Drive Chamber B1 with regulated drive air, thus reversing the direction of the interconnected pistons, until Piston 1 switches the valve back to its original position. The interconnected pistons shuttle back and forth continuously, producing a high pressure air stream, determined by the discharge pressure set on the built-in regulator. The R00D Booster System is designed to operate at a maximum discharge pressure of 230 psig. Higher discharge pressures, though possible, can result in catastrophic failure of the booster.
Operating Description
General Concerns
Midwest Pressure Systems, Inc. warrants the R00D Booster System to be free of defects in material and workmanship for a period of one year after purchase, except piston seals, rod seals, and check valves which are warranted for six months after purchase. We will either repair or replace a failed unit returned by the customer. No other warranty is expressed or implied. Proof of the purchase date is required. This warranty does not apply to equipment which has been abused, and is voided by use of a lubricator, or failure to use a well-maintained inlet filter. Customer must obtain a return authorization number before shipping the unit to the factory.
WARRANTY
04/07/15
Midwest Pressure Systems, Inc.
850 Transport Drive, Valparaiso, IN 46383 Phone 219-462-0070 Fax 219-318-2277
www.midwestpressuresystems.com
Loading...