MP Pumps HTO 120 User Manual

MP PUMPS HTO SERIES
HTO 120 INSTALLATION AND SERVICE INSTRUCTIONS
This bulletin must be read completely before installing, operating, or servicing the pump.
WARNING:
If any of the items listed below are violated, serious injury or death from burns caused by hot oil may occur.
DO NOT operate the pump in a manner that it was not intended to be use.
DO NOT install for use in an open environment where people are present.
DO NOT install in a rigid piping system that does not allow the pipe to expand and cause the pump to be strained.
DO NOT continue to operate the pumping
• system when a known leak exists or the system continues to smoke.
DO NOT continue to operate the pump when unusual noise or vibration occurs.
DO NOT operate beyond the pressure or temperature limits stated in the product literature, see form 9050.
DO NOT allow severe temperature changes to occur in a short time period within the pumping system.
DO NOT mix dif within the oil system.
DO NOT use an oil that is not a recommended heat transfer oil by the manufacturer.
DO NOT exceed the maximum oil temperature rated by the oil manufacturer at the hottest point in the pumping system.
DO NOT mount the pump such that high piping loads exist on the pump flanges.
ferent types or grades of oil
DO NOT install or use near water where the pumping system may come into contact with water or is splashed by water.
FORM 3061-B
PRINTED IN U.S.A. (1-07)
MP PUMPS HTO SERIES
APPLICATION AND INSTALLATION INSTRUCTIONS
Application assistance and technical information can be obtained by calling MP PUMPS at 800-563-8006.
The HTO pump is designed for pumping high temperature fluids that are non-corrosive, non-volatile and have good lubricating qualities.
INSTALLATION AND START-UP
INSTALLATION
1. The pump must be installed in a horizontal shaft position.
2. The housing may be rotated to a horizontal or vertical discharge to fit the particular piping installation.
3. Rigid and supported piping must be used that will not strain the pump housing when temperature changes are made during the use of the pump.
4. The piping system must be free of foreign material and moisture before start-up.
5. Pipe thread sealing compound must be used on the NPT flanges that is compatible with the fluid being pumped and is rated for the temperature requirements.
The installation should permit adequate
6.
circulation of air to provide proper cooling of the motor and pump seal housing.
7. Do not install in a sealed enclosure or insulate the pump adapter and motor. The motor and/or pump seal may fail from excessive heat.
The primary application for use is with heat transfer oils.
It is the users' responsibility to determine the pump and product compatibility with the materials of construction.
START-UP
1. Follow all requirements and recommendations from the heat transfer fluid manufacturer for fill, start-up and use.
2. Check for leaks before insulating the piping system.
3. Check for proper shaft rotation by jogging the power and observing the fan clamp. Rotation arrows are provided on pump housing.
4. The seal cavity inside the pump will internally vent during fill and start-up.
5. A small amount of oil may leak from the seal cavity at the shaft; this is normal for a new installation and will stop after approximately one hour.
6. Do not allow the pump to run dry, or continue to operate the pump when it is noisy leaks are observed. These noticeable signs give a warning that something is wrong with the equipment and must be investigated to avoid possible damage or injury from burns caused by hot oil.
, vibrating, or
8. A good installation will have an enclosure that provides adequate air flow of ambient air to the motor of the pump.
- 2 -