MPE SC2000, SC1000 Instruction Manual

Order from: C A Briggs Company; 622 Mary Street; Suite 101 - Warminster, PA 18974
Phone: 267-673-8117 - 800-352-6265 - Fax: 267-673-8118; E-Mail: Sales@cabriggs.com - www.cabriggs.com
SC2000
SC2000
SC2000SC2000
INSTRUCTION MANUAL
INSTRUCTION MANUALINSTRUCTION MANUAL
M
MOTOR
OTOR
MM
OTOROTOR
2464 Vulcan Road Apopka, Florida 32703
Operating Program Revision: 11
P
PROTECTION
PP
ROTECTION
ROTECTIONROTECTION
E
ELECTRONICS, INC.
LECTRONICS, INC.
EE
LECTRONICS, INC.LECTRONICS, INC.
Phone:
Website:
(407) 299-3825 www.mpelectronics.com
Revision Date: 4-17-14
STATION CONTROLLER SC2000
Simplex, Duplex, Triplex, or Quadraplex Liquid Level Control
Pump Down (Empty a Tank) or Pump Up (Fill a Tank)
Fixed or Variable Speed Control
Where Connection to a SCADA System is Required
STANDARD FEATURES
All Setup Parameters Values may be viewed or changed from the
front of the unit
Level Input Source - Menu Selectable:
- Analog Level Input [4-20mA from Pressure Transducer]
- Level Probe [Conductance Probe with 10 Electrodes]
Regulated +20VDC power for Analog Level Input
RS-232 Serial Port with Modbus RTU Protocol
High and Low Level Alarm Relays and Alarm Indication
Adjustable Lag Pump(s) Delay
Alternation Schemes - Menu Selectable:
- Standard Alternation
- Pump 1 Always Lead - Stays On with other Pumps
- Pump 1 Always Lead - Turns Off with other Pumps On
- Split Alternation - Pumps 1&2, and Pumps 3&4
- Fixed Sequence - Pump 1 Always Lead
- Stepped On/Off - Only One Pump Runs at a Time Alternator Logic Skips Disabled Pumps First On - First Off or First On - Last Off Alternation
Level Simulation (Automatically ends after 1 minute)
Security Code Protected Parameter Setup
18 Discrete Inputs programmable for the following functions:
- Pump disable with HOA in OFF, or pump fault
- External Lead Pump Selector Switch
- All pump disable - for connection to Phase Monitor
- Limit number of pumps called while on emergency power
- Alternation by External Time Clock
- Freeze wet well level during a bubbler tube purge
- Call pump last
- Float switch backup
- Low Level Pump Cutoff
- Start Flush Cycle
- A variety of SCADA functions Status of Discrete Inputs may be viewed from front of Controller
Backup Control, and High & Low Alarms using a Level Probe
Output Relays may be programmed for control through SCADA
Automatic Flush Cycle to reduce sludge build up
Flow Calculator that provides the following Flow Data:
- Latest Inflow Rate
- Average Daily Inflow Total (Average of Last 7 Days)
- Pump Outflow Rate (Latest for Each Pump)
OPTIONAL FEATURES
Up to four Isolated 4-20mA Analog Outputs that may be used for
VFD speed control or for sending out a copy of the Level Input
Up to four Isolated 4-20mA Auxiliary Analog Inputs that may be
used to collect analog data for SCADA
4-20mA Analog Level Input may be ordered as an Isolated Input
Ethernet Port with the following protocols:
Modbus TCP or Modbus RTU
SPECIFICATIONS APPLICATIONS
Input Power: 120 VAC ±10%, 13 VA max
External Dimensions: 6.9” x 8.5” x 4.9”
Agency Approvals: UL 508, CAN/CSA
Ambient Operating Temperature:
Without Analog Outputs:
-20°C to +65°C (-4°F to +149°F) With Analog Outputs:
-20°C to +50°C (-4°F to +122°F)
Level Display: 3 Digit, 7 Segment LED
Level Display Range: 0 - 999 feet
(Decimal Point Position is Selectable)
Indicators: LED
Color: White with Blue Lettering
Relays: 6A @ 250VAC
Analog Level Input: 4-20mA, 250 Load,
Transient Protected
Level Probe Inputs: ±8V, 60Hz Square Wave
±0.8mA max, Transient Protected
Discrete Inputs: 24VDC, Transient Protected
Power for Discrete Inputs: Unregulated
+24VDC, Transient Protected
Power for Analog Level Input: Regulated
+20VDC ±1V, Transient Protected
Analog Outputs: Isolated 4-20mA
Maximum Load Resistance: 600
Auxiliary Analog Inputs: Isolated 4-20mA,
250 Load, Transient Protected
ORDERING INFORMATION
Part Number: SC2000 - X X X X
Number of Optional Analog Outputs:
0 = Zero Analog Outputs 1 = One Analog Output 2 = Two Analog Outputs 3 = Three Analog Outputs 4 = Four Analog Outputs
Number of Optional Auxiliary Analog Inputs:
0 = Zero Auxiliary Analog Inputs 1 = One Auxiliary Analog Input 2 = Two Auxiliary Analog Inputs 3 = Three Auxiliary Analog Inputs 4 = Four Auxiliary Analog Inputs
Blank = RS232 Port
E = RS232 Port & Ethernet Port
Blank = Non-Isolated Analog Level Input S = Isolated Analog Level Input
1
OPERATOR INTERFACE FUNCTIONS
Note: There is a 4 second Delay on Changing Parameter Values.
On when Display Shows the Wet Well Level
Press to Display Wet Well Level
On when in Level Simulation Mode
Press to Enter the Level Simulation Mode
On when in Menu Scroll Mode
Press to Change Function of the Up/Down Push-Buttons
On when in Value Change Mode
Press to Scroll Up the Menu, or to Increase Parameter Value
Press to Scroll Down the Menu, or to Decrease Parameter Value
How to View a Setup Parameter Value
1. Press push-button PB-M until the Menu Scroll Mode indicator comes on.
2. Press push-button PB-D and PB-U as needed to arrive at the Parameter you wish to view.
3.
Parameters Shown on Front of Controller: The value of the Parameter is displayed whenever the indicator next to the Parame­ter label is on.
Parameters in the System Setup Sub-Menu: The value of a Parameter in the System Setup Sub-Menu may be viewed by using the push-button PB-M to toggle from the Parameter number (P.13, for example) to the Parameter value.
How to Change a Setup Parameter Value
1. Press push-button PB-M until the Menu Scroll mode indicator comes on.
2. Press push-button PB-D and PB-U as needed to arrive at the Parameter you wish to change.
3.
4. Press and hold for 4 seconds, either push-button PB-D or PB-U, to change the Parameter to the desired new value. (If the Parameter values will not change, they may be locked. See directions below to un-lock Parameters.)
5. Press push-button PB-M or PB-L to exit the Value Change mode.
Parameters Shown on Front of Controller: Press push-button PB-M until the Value Change indicator comes on.
Parameters in the System Setup Sub-Menu: Press push-button PB-M until the Value Change indicator comes on. The current value of the Parameter will then be displayed.
How to Simulate Levels
1. Press push-button PB-S. Note: The Simulation starts from the actual level displayed prior to entering the Level Simulation mode.
2. Press push-button PB-D or PB-U as needed to change the simulated level.
3. To end the level simulation press push-button PB-L. Note: If you do not exit the Level Simulation mode, normal operation will resume automatically 60 seconds after the last time the PB-U, PB-D, or PB-S push-buttons were pressed.
How to Enter the Security Code
1. Press the push-button PB-M until the Menu Scroll mode indicator comes on.
2. Press push-button PB-U until the display reads SEC.
3. Press push-button PB-M to change to the Value Change mode.
4. Press and hold for 4 seconds, either push-button PB-D or PB-U, to change the value displayed, to that of the correct
security code.
2
MENU - SYSTEM SETUP
Parameter
-
-
-
-
-
-
-
-
-
-
-
SEC
Default
Value
2.0 feet
3.0 feet 1st Pump Off Level SCADA Register 40013 Range: 0.2 - 99.9 feet
6.0 feet 1st Pump On Level SCADA Register 40012 Range: 0.2 - 99.9 feet
4.0 feet 2nd Pump Off Level SCADA Register 40015 Range: 0.2 - 99.9 feet
7.0 feet 2nd Pump On Level SCADA Register 40014 Range: 0.2 - 99.9 feet
4.5 feet 3rd Pump Off Level SCADA Register 40017 Range: 0.2 - 99.9 feet
8.0 feet 3rd Pump On Level SCADA Register 40016 Range: 0.2 - 99.9 feet
5.0 feet 4th Pump Off Level SCADA Register 40019 Range: 0.2 - 99.9 feet
9.0 feet 4th Pump On Level SCADA Register 40018 Range: 0.2 - 99.9 feet
10.0 feet High Level Alarm SCADA Register 40020 Range: 0.5 - 99.9 feet 5 sec. Lag Pump(s) Delay Range: 1 - 100 seconds
0
Current
Value Setting Definitions
All Level Settings Have the Decimal Point Artificially Inserted Based on Parameter P.36.
Low Level Alarm SCADA Register 40021 Range: 0.1 - 99.9 feet
Note: To Disable Alarm see Parameter P.50.
Security Code - Enter Your Security Code Here to Allow Parameters to be Changed. Change to other Number to Re-lock All Parameters.
Note: The Security Code may be Customized using Parameter P.26. See Page 2.
P.13
P.14
4
4
Number of Pumps Present See Page 9. 1 = 1 Pump 2 = 2 Pumps 3 = 3 Pumps 4 = 4 Pumps
Number of Pumps Allowed to Run at the Same Time See Page 9. 1 = 1 Pump 2 = 2 Pumps 3 = 3 Pumps 4 = 4 Pumps
Number of Pumps Allowed to Run On Generator See Page 9.
P.15
4
1 = 1 Pump 2 = 2 Pumps 3 = 3 Pumps 4 = 4 Pumps
Note: Must Connect Transfer Switch Contacts to Discrete Input Programmed for Function 7.
Alternator Sequence Mode
1 = Standard Alternation See Page 11. 2 = Pump 1 Always Lead - Stays On With Other Pumps See Page 11.
P.16
P.17
P.18
1
2
1
3 = Pump 1 Always Lead - Turns Off With Other Pumps See Page 12. 4 = Split Alternation - Pumps 1&2, and Pumps 3&4 See Page 12. 5 = Fixed Sequence - Pump 1 Always Lead See Page 13. 6 = Stepped On/Off - Only One Pump Runs at a Time See Page 13.
Pump Stop Mode See Page 10. 1 = First On Last Off 2 = First On First Off
Automatic Alternation See Page 10. 1 = Enabled 2 = Disabled
Pump Up or Down Mode
P.19
1
1 = Pump Down - Empty a Tank 2 = Pump Up - Fill a Tank
Note: When Parameter P.19 is Changed New Default Level Parameter Values will be loaded.
P.20 - P.23 - VFD Speed Control Setup See Page 21.
3
See Page 25.
See Page 25.
See Page 10.
See Page 10.
MENU - SYSTEM SETUP
Parameter
P.24
P.25
Default
Value
11.5 feet
0.0 feet
Current
Value
All Level Settings Have the Decimal Point Artificially Inserted Based on Parameter P.36.
Setting Definitions
Level Input Calibration - Span Range: 0.9 - 99.9 feet See Page 20.
Notes:
1. 20mA is Typically Applied to the Analog Input while Setting the Span.
2. Parameter P.24 Shows the Wet Well Level, while allowing the Up & Down Push-buttons to Change the Internal Number used to Calculate the Displayed Level.
3. When Controller is set to Operate using a Level Probe, Parameter P.24 shows “77.7”.
Level Input Calibration - Zero
Notes:
1. 4.0mA is Typically Applied to the Analog Input while Setting the Zero.
2. Parameter P.25 Shows the Wet Well Level, while allowing the Up & Down Push-buttons to Change the Internal Number used to Zero the Displayed Level.
3. When Controller is set to Operate using a Level Probe, Parameter P.25 shows “77.7”.
See Page 20.
Security Code Setup Parameter - Establishes What Value Will Be Accepted as the Security Code at Parameter SEC. Range: 0 - 255
P.26
P.28
0
1 Slave Address
Notes:
1. To Change Parameter P.26, the Current Security Code Must First be Entered into SEC.
2. When You Change Parameter P.26 and Exit the Value Change Mode Parameter, P.26 Will No Longer Be Viewable, Until You Enter the New Security Code into Parameter SEC.
3. If You Forget Your Security Code, Consult the Factory for the Master Security Code.
P.29 - P.32 - RS232 Serial Port Setup See Page 26.
P.33
P.35
P.36
P.37
P.38
P.39
1 Register Access Mode
Stop Pump Delay Range: 1 - 100 seconds
1 sec.
1
1 min.
1 min.
0
Note: This is the Time Period that the Wet Well Level Must Remain At or Below (At or Above for Pump Up P.19 = 2) the Respective OFF Level Setting in order to Turn Off a Pump.
Display Decimal Point Position 0 = No Decimal Point 1 = XX.X 2 = X.XX
Pump Re-enable Delay after Float Backup Low Level (High Level)
Notes: Range: 1 - 255 minutes
1. Pump Down (Parameter P.19 = 1) - Delay Starts when the Low Level Float Input Opens.
2. Pump Up (Parameter P.19 = 2) - Delay Starts when the High Level Float Input Opens.
Delay Canceling Remote Control Commands
Notes: Range: 0 - 254 minutes
1. Delay Starts when Serial Communication is Lost.
2. To Allow all Remote Commands to Remain in Effect (Until Power Loss) Set P.38 = 255.
Forced Lead Pump Position SCADA Register 40022 0 = Normal Alternation 1(2,3,4) = Pump 1(2,3,4) as Lead
P.40 - P.43 - Flush Cycle Setup See Page 22. P.44 - P.47 - Flow Calculator Setup See Pages 23 - 24.
P.49
240
P.50
P.51
FLC -
LFC -
oPr -
1
0
Analog Level Input - Signal Conditioning Control Range: 1 - 254 10 = Very Slow 100 = Slow 240 = Normal 250 = Fast
Low Level Alarm Mode 0 = Disabled 1 = Enabled
Note: Setting “0” Disables Low Level Alarms from the Analog Level Input or Level Probe Inputs.
Time Based Alternation Range: 1 - 255 1/6 hour 0 = Disabled 1 = 1/6 hour 6 = 1 hour 48 = 8 hours 144 = 24 hours
Fault Code SCADA Register 40047 See Fault Code Table on Pages 18 - 19.
Note: This Automatically Returns to Zero when the Fault Clears (Except for Faults 20-29).
Last Fault Code SCADA Register 40048 See Fault Code Table on Pages 18 - 19.
Note: This is a Copy of the Last Non-Zero Fault Code that was shown on Parameter FLC.
Operating Program Revision Number - Controller SCADA Register 40063
EPr -
Operating Program Revision Number - Ethernet Board
4
MENU - SYSTEM SETUP
Parameter
F.01
F.02
F.03
F.04
F.05
F.06
F.07
F.08
F.09
F.10
F.11
F.12
F.13
F.14
F.15
F.16
F.17
F.18
Default
Value
10
11
12
13
14
15
16
17
18
Current
Value Setting Definitions
1
2
3
4
5
6
7
8
9
All Level Settings Have the Decimal Point Artificially Inserted Based on Parameter P.36.
Discrete Input 1 Function
Discrete Input 2 Function
Discrete Input 3 Function
Discrete Input 4 Function
Discrete Input 5 Function
Discrete Input 6 Function
Discrete Input 7 Function
Discrete Input 8 Function
Discrete Input 9 Function
Discrete Input 10 Function
Discrete Input 11 Function
Discrete Input 12 Function
Discrete Input 13 Function
Discrete Input 14 Function
Discrete Input 15 Function
Discrete Input 16 Function
Discrete Input 17 Function
Discrete Input 18 Function
Function of Input: Connect To:
0 = No Function 1 = Pump 1 Disable …….………...…………...…. HOA and Fault Logic
2 = Pump 2 Disable …….….....…..……….….….. HOA and Fault Logic
3 = Pump 3 Disable ………..……..…….…..…..... HOA and Fault Logic
4 = Pump 4 Disable …….….…..………….….….. HOA and Fault Logic
5 = Level Freeze ……………...………....…. Bubbler Tube Purge Logic
6 = External Alternation ………...……......………. External Time Clock
7 = On Generator ………………….……….. Automatic Transfer Switch 8 = All Pump Disable …………...…………...…………... Phase Monitor
9 = Sequence Input 1 ……....…..…… Lead Select Switch - 1 as Lead
10 = Sequence Input 2 ….…….........… Lead Select Switch - 2 as Lead
11 = Sequence Input 3 …...…...…….… Lead Select Switch - 3 as Lead
12 = Sequence Input 4 ….……......…… Lead Select Switch - 4 as Lead
13 = Call Pump 1 Last ……...…….………...…………..…. Logic Contact
14 = Call Pump 2 Last ……...……………....…………..…. Logic Contact
15 = Call Pump 3 Last …….…….……..…...…………..…. Logic Contact
16 = Call Pump 4 Last …….………….….....…………..…. Logic Contact
17 = Low Level Alarm ……..………..…..…….… Low Level Float Switch 18 = High Level Alarm …………………...…..… High Level Float Switch
19 = Telemetry E ………...…………………....……… Telemetry Contact
20 = Telemetry F …….………………….....…….…… Telemetry Contact
21 = Telemetry G ……..……………………........…… Telemetry Contact
22 = Telemetry H …………………………...………… Telemetry Contact 23 = Telemetry J ………………………….…..….…… Telemetry Contact 24 = Telemetry K ……………………………...……… Telemetry Contact 25 = Telemetry L ……………………….…..….……… Telemetry Contact 26 = Telemetry M ………………………..……….…… Telemetry Contact 27 = Telemetry A ………………………..….…….…… Telemetry Contact 28 = Telemetry B ……………………...….….…..…… Telemetry Contact 29 = Telemetry C ……….…………………...…...…… Telemetry Contact 30 = Telemetry D ………………………...…..……..… Telemetry Contact
31 = Normal Pump Operation Disable ......................…..
32 = Float Backup – Low Level .….………........ Low Level Float Switch
33 = Float Backup – Off Level ….……….….….... Off Level Float Switch
34 = Float Backup – 1ST
35 = Float Backup – 2ND On Level ……..... 2ND On Level Float Switch
36 = Float Backup – 3RD On Level ……..... 3RD On Level Float Switch
37 = Float Backup – 4TH On Level ……...... 4TH On Level Float Switch
38 = Float Backup – High Level .………...…..... High Level Float Switch
39 = Start Flush Cycle …………………...……...…. External Time Clock Notes:
1. Function of Discrete Inputs may be set to “0” when Input is used only to collect data for SCADA and no other Function is desired.
2. All Discrete Inputs may be read from SCADA Registers 40035 ­40037, regardless of the Function assigned to the Input.
3. See Pages 14 - 16 for description of each of the above Functions.
On Level ……...... 1ST On Level Float Switch
.. Fault Contact
F.19
F.20 F.21
F.22
1
12 in. Level Probe Electrode Spacing Range: 3 - 24 inches
0.0 feet
100
Level Input Source 1 = Analog Level Input (4-20mA) on J21 2 = Level Probe Input on J25 3 = Level Probe Input on J25 (Flashes Level Probe Electrode No. of Level Settings.)
4 = Remote Level Input (Follows the Level written to SCADA Register 40025.) Note: Level Probe not suitable for applications measuring Storm Water or Well Water.
Level Offset Range: 0.0 - 5.0 feet
Note: This adds to the Level from the Analog Level Input or Level Probe Input.
Level Probe Sensitivity Range: 90 - 210 100 = Typical Sewage 150 = Light Sewage
Check value of Parameter L.10 with Electrode 10 covered, add 40 to it, and enter value for F.22. Note: Level Probe not suitable for applications measuring Storm Water or Well Water.
5
MENU - SYSTEM SETUP
Parameter
Default
Value
Current
Value Setting Definitions
F.23 1 Analog Output 1 Function F.24 2 Analog Output 2 Function F.25 3 Analog Output 3 Function F.26 4 Analog Output 4 Function
HI Relay Output Function
F.31 1
0 = Disabled 1 = High Level Alarm 2 = Remote Control
Note: High Level indicator on front of unit will operate regardless of setting.
LO Relay Output Function
F.32 1
0 = Disabled 1 = Low Level Alarm 2 = Remote Control (SCADA Coil 26)
Note: Low Level indicator on front of unit will operate regardless of setting.
P1 Relay Output Function
F.33
1
0 = Disabled 1 = Pump 1 Call 2 = Remote Control (SCADA Coil 27)
Note: When set on “0” or “2” Pump 1 will be skipped over in all Alternation Sequence Modes.
P2 Relay Output Function
F.34 1
0 = Disabled 1 = Pump 2 Call 2 = Remote Control (SCADA Coil 28)
Note: When set on “0” or “2” Pump 2 will be skipped over in all Alternation Sequence Modes.
P3 Relay Output Function
F.35 1
0 = Disabled 1 = Pump 3 Call 2 = Remote Control (SCADA Coil 29)
Note: When set on “0” or “2” Pump 3 will be skipped over in all Alternation Sequence Modes.
1 = Pump 1 Speed (Active When Pump 1 is Called) 2 = Pump 2 Speed (Active When Pump 2 is Called) 3 = Pump 3 Speed (Active When Pump 3 is Called) 4 = Pump 4 Speed (Active When Pump 4 is Called) 5 = Speed Reference any Pump (Always Active) 6 = Copy of Wet Well Level
(SCADA Coil 25)
P4 Relay Output Function
F.36
E.01 - E.62
b.01 0 b.02 0 b.03 0 b.04 0 b.05 0 b.06 0 b.07 0
Notes For Level Probe Backup Functions: For status of Level Probe inputs see Coils 583 - 592 in SCADA Register 40037.
1. When the controller is set up to follow a 10 Electrode Conductance Level Probe as the primary level input source (Parameter F.19 = 2 or 3), the backup functions described here are not needed and will not operate.
2. If a Function (such as Pump Control – 4TH On Level) is not desired set the respective parameter equal to zero.
3. An effective Backup Pump Control would involve having a 3 point Level Probe placed high in the wet well. The Level Probe would be connected to Connector J25 terminals 1, 2, and 3. The Off Level should be made to operate from the bottom Electrode by setting Parameter b.02 = 3. The 1ST On Level should be set to operate from Electrode 2 by setting Parameter b.03 = 2. The 2ND On Level should be set to operate from Electrode 1 by setting Parameter b.04 = 1. If additional pumps are present set the 3RD On and 4TH On Levels, to operated from Electrode 1 by setting Parameter b.05 = 1, and b.06 = 1.
4. If a Backup High Level Alarm is desired, set Parameter b.07 to the number of the Electrode Input that the High Level Probe is con­nected to. This feature is for alarm and telemetry only and will not function as a redundant pump call. See SCADA notes page 32.
5. If a Backup Low Level Alarm is desired, set Parameter b.01 to the number of the Electrode Input that the Low Level Probe is con­nected to. This feature is for alarm and telemetry only and will not function as a redundant pump off. See SCADA notes page 33.
6. Whenever the Backup Pump Control is active the Fault indicator will be on and fault code of 30 will be present in Parameter FLC, and set Coil 15 in SCADA Register 40001.
1
0 = Disabled 1 = Pump 4 Call 2 = Remote Control (SCADA Coil 30)
Note: When set on “0” or “2” Pump 4 will be skipped over in all Alternation Sequence Modes.
- Ethernet Port Setup See Page 27.
Level Probe Backup Functions
Low Level Alarm Pump Control – Off Level Pump Control – 1ST On Level Pump Control – 2ND On Level Pump Control – 3RD On Level Pump Control – 4TH On Level High Level Alarm
0 = Function Not Used 1 = Electrode Input 1 on Connector J25-1 2 = Electrode Input 2 on Connector J25-2 3 = Electrode Input 3 on Connector J25-3 4 = Electrode Input 4 on Connector J25-4 5 = Electrode Input 5 on Connector J25-5 6 = Electrode Input 6 on Connector J25-6 7 = Electrode Input 7 on Connector J25-7 8 = Electrode Input 8 on Connector J25-8 9 = Electrode Input 9 on Connector J25-9 10 = Electrode Input 10 on Connector J25-10
6
MENU - DATA DISPLAY
Parameter Data Description
L.01 L.02 L.03 L.04 L.05 L.06 L.07 L.08 L.09
Electrode 1 Status Value Electrode 2 Status Value Electrode 3 Status Value Electrode 4 Status Value Electrode 5 Status Value Electrode 6 Status Value Electrode 7 Status Value Electrode 8 Status Value Electrode 9 Status Value
Level Probe Electrode Status Values Normal Range when Un-Covered: 240 - 255 Normal Range when Covered by Typical Sewage: 55 - 70
Notes:
1. The Controller compares each of the Electrode Status Values with what is set on Parameter F.22. When the value drops below the setting on Parameter F.22, the Controller logic considers the Electrode to be covered by liquid.
2. Parameters L.01 - L.10 are also used to diagnose Out of Sequence Faults (Fault Codes 21 - 29).
3. For the status of the Level Probe inputs see Coils 583 - 592 in SCADA Register
40037.
L.10
L.11
FLH
FLL
FdH
FdL
F1H
F1L
F2H
F2L
F3H
F3L
F4H
F4L
Electrode 10 Status Value Level Probe Test Signal Status Normal Range: 230 - 254
Note: This is a Measure of the ±8V, 60Hz Square Wave Sent Out to Each Electrode to read the level. If the value is below 210, a malfunction has occurred in the circuit that provides the Square Wave used to read the level. In this case the wet well level display will show zero, the Fault indicator will be turned on, and Fault Code 20 will be generated.
Flow Calculator - Latest Inflow Rate FLH , FLL Gallons Per Minute
See pages 18 - 19. SCADA Register 40080
Flow Calculator - Average Daily Inflow Total FdH , FdL Units set by Parameter P.45.
See pages 18 - 19. SCADA Register 40081
Flow Calculator - Pump 1 Outflow Rate F1H , F1L Gallons Per Minute
See pages 18 - 19. SCADA Register 40082
Flow Calculator - Pump 2 Outflow Rate F2H , F2L Gallons Per Minute
See pages 18 - 19. SCADA Register 40083
Flow Calculator - Pump 3 Outflow Rate F3H , F3L Gallons Per Minute
See pages 18 - 19. SCADA Register 40084
Flow Calculator - Pump 4 Outflow Rate F4H , F4L Gallons Per Minute
See pages 18 - 19. SCADA Register 40085
7
MENU - DATA DISPLAY
Parameter Data Description
n.01 n.02 n.03 n.04 n.05 n.06 n.07 n.08 n.09 n.10 n.11 n.12
Discrete Input 1 Status Discrete Input 2 Status Discrete Input 3 Status Discrete Input 4 Status Discrete Input 5 Status Discrete Input 6 Status Discrete Input 7 Status Discrete Input 8 Status Discrete Input 9 Status Discrete Input 10 Status Discrete Input 11 Status Discrete Input 12 Status
Discrete Input Status 0 = Input Open 1 = Input Closed
Notes:
1. Discrete Input Status is used when troubleshooting the
2. Discrete Input Status data may be read by SCADA at
wiring and logic connected to the Discrete Inputs.
Registers 40035 - 40037. See Page 29 .
n.13 n.14 n.15 n.16 n.17 n.18
n.19 n.20 n.21 n.22
d.01 d.02
d.03 d.04
Discrete Input 13 Status Discrete Input 14 Status Discrete Input 15 Status Discrete Input 16 Status Discrete Input 17 Status Discrete Input 18 Status
Auxiliary Analog Input 1 Status Auxiliary Analog Input 2 Status Auxiliary Analog Input 3 Status Auxiliary Analog Input 4 Status
Voltage of +5 Volt Power Supply SCADA Register 40049 Normal Range: 8.5V - 11.3V
Note: Voltage is measured ahead of Voltage Regulator.
Auxiliary Analog Input Status Range: 0 - 255 Where: 0 = 0.0 mA 51 = 4.0 mA 255 = 20 mA
Note: Auxiliary Analog Input data may be read by SCADA in either an 8-Bit or 10-Bit format. See Page 30.
Voltage of +24 Volt Power Supply SCADA Register 40050 Normal Range: 21.1V - 25.5V Pump 1 VFD Speed Reference (Percent of Full Speed, 0 - 100%) SCADA Register 40038 Pump 2 VFD Speed Reference (Percent of Full Speed, 0 - 100%) SCADA Register 40039
d.05 d.06 d.07 d.08 d.09
d.10-d.86
Pump 3 VFD Speed Reference (Percent of Full Speed, 0 - 100%) SCADA Register 40040 Pump 4 VFD Speed Reference (Percent of Full Speed, 0 - 100%) SCADA Register 40041 Serial Communication Activity Indicator See Page 34. Serial Communication – Shows the Address of the Last Slave Polled by the Master See Page 34. Serial Communication – Shows the Last Modbus Function Code Received See Page 34. Serial Communication – Shows the Entire Rest of the Last Modbus Message Received
8
PUMP CALL SEQUENCE - Setup Parameters
The following is a description of each of the Setup Parameters used to establish the Pump Call Sequence: Note: Discrete Inputs programmed with Functions 1-4, 6-7, 9-12, and 13-16 are also available to establish or modify the
Pump Call Sequence. See the description of these Discrete Input Functions on pages 14-16.
Number of Pumps Present - Parameter P.13
This Parameter establishes how many pumps are available at the Lift Station to perform level control. Simplex (1 pump) Duplex (2 pumps) Triplex (3 pumps) Quadraplex (4 pumps)
Default
Parameter
Value Setting Definitions
P.13
4
Number of Pumps Present 1 = 1 Pump 2 = 2 Pumps 3 = 3 Pumps 4 = 4 Pumps
Number of Pumps Allowed to Run at the Same Time - Parameter P.14
In cases where there is an inadequately sized discharge pipe, or inadequate electrical power, running all available pumps at the same time may be a problem. This Parameter is used to set an upper limit on the number of pumps called to run at the same time. If there is no need for this feature P.14 may be left on it’s default value of 4.
Default
Parameter
P.14
Value Setting Definitions
4
Number of Pumps Allowed to Run at the Same Time 1 = 1 Pump 2 = 2 Pumps 3 = 3 Pumps 4 = 4 Pumps
Number of Pumps Allowed to Run On Generator - Parameter P.15
In cases where the Emergency Generator is not sized large enough to run all the available pumps, this Parameter is used to set an upper limit on the number of pumps called to run on the Generator. There must be a contact from the Transfer Switch connected to one of the Controller’s Discrete Inputs and it must be programmed for Function 7. If there is no need for this feature Parameter P.15 may be left on it’s default value of 4.
Default
Parameter
Value Setting Definitions
P.15
4
Alternator Sequence Mode - Parameter P.16
This Parameter is provided to allow the Controller to accommodate a variety of special sequence requirements.
Default
Parameter
P.16
Value Setting Definitions
1
Number of Pumps Allowed to Run On Generator 1 = 1 Pump 2 = 2 Pumps 3 = 3 Pumps 4 = 4 Pumps
Alternator Sequence Mode
1 = Standard Alternation See Page 11. 2 = Pump 1 Always Lead - Stays On With Other Pumps See Page 11. 3 = Pump 1 Always Lead - Turns Off With Other Pumps See Page 12. 4 = Split Alternation - Pumps 1&2, and Pumps 3&4 See Page 12. 5 = Fixed Sequence - Pump 1 Always Lead See Page 13. 6 = Stepped On/Off - Only One Pump Runs at a Time See Page 13.
9
PUMP CALL SEQUENCE - Setup Parameters
Pump Stop Mode - Parameter P.17
This Parameter establishes which pump is the next one to be stopped, when there are two or more pumps on. The Controller has a corresponding “Pump Off Level” setting for each of the “Pump On Level” settings. For the
“Pump Stop Mode” feature to operate, the “Pump Off Level” settings must be set on different levels. If all the “Pump Off Level” settings are set on the same level it does not matter what Parameter P.17 is set on.
First On Last Off - In this mode, as the level reaches one of the “Pump Off Level” settings, the pump that was most recently turned on is turned off, leaving the one that was call to run first still running.
First On First Off - In this mode, as the level reaches one of the “Pump Off Level” settings, the pump that was most recently turned on is left on and the pump that has been on the longest is turned off. This results in a longer cool down period for each pump between starts. This mode works the best in stations where one pump is required to run for a long period of time, with an occasional need for an additional pump.
Default
Parameter
Value Setting Definitions
P.17
2 Pump Stop Mode 1 = First On Last Off 2 = First On First Off
Automatic Alternation - Parameter P.18
This Parameter is provided so that normal automatic alternation may be disabled (turned off). Typically, normal alternation is disabled only in applications that have an external Time Clock used to alternated the pumps. (The Time Clock would be connected to a Discrete Input programmed for “External Alternation” , Function 6.)
Default
Parameter
P.18
Value Setting Definitions
1 Automatic Alternation 1 = Enabled 2 = Disabled
Forced Lead Pump Position - Parameter P.39
This Parameter is provided so that a fixed sequence may be established with the selected pump always as lead. For example setting Parameter P.39 on 1 will cause a fixed pump call sequence of 1-2-3-4. Parameter P.39 may also be changed by writing a 0,1,2,3 or 4 to SCADA Register 40022.
Default
Parameter
P.39
Value Setting Definitions
0
Forced Lead Pump Position SCADA Register 40022
0 = Normal Alternation 1(2,3,4) = Pump 1(2,3,4) as Lead
Time Based Alternation - Parameter P.51
This feature may be used to ensure that alternation periodically occurs even in applications that tend to run one pump for a long period of time. The internal Time Clock starts and runs whenever at least one pump is called to run. When it times out, it forces the alternation of the pumps and then resets the Time Clock. The Time Clock is also reset each time a Normal Alternation Occurs.
Default
Parameter
P.51
Value Setting Definitions
0
Time Based Alternation Time Clock Range: 1 - 255 1/6 hour 0 = Disabled 1 = 1/6 hour 6 = 1 hour 48 = 8 hours 144 = 24 hours
10
ALTERNATION SEQUENCE MODE
STANDARD ALTERNATION Parameter P.16 = 1
Notes:
1. Unless there is some special circumstance that requires a more complicated pump call sequence, this is the sequence that should be used.
2. Parameter P.17 must be used to select either First On Last Off or First On First Off.
3. Discrete Inputs programmed as Pump 1-4 Disable inputs may be used to disable pumps.
4. Discrete Inputs programmed as Call Pump 1-4 Last inputs may be used to assign pumps to standby status.
5. Discrete Inputs programmed as Sequence Inputs 1-4 may be used to set the lead pump.
6. Parameter P.39 may be used to set the lead pump.
7. A Discrete Input programmed for External Alternation (Function 6) may be used to force alternation. When this feature is used, Automatic Alternation would normally be disabled by setting Parameter P.18 to Disabled.
8. If connected to a SCADA system, alternation may be initiated by momentar­ily setting Coil 136, or by forcing the lead pump by writing to Register 40022 (Same as Parameter P.39).
9. Parameter P.51 may be used to select and setup Time Based Alternation.
Movement of Lead Pump Upon Alternation
PUMP 1 ALWAYS LEAD Stays On With Other Pumps Parameter P.16 = 2
Notes:
1. This sequence is used when it is required that pump 1 always be lead pump. This sequence keeps pump 1 on, when the other pumps are called to run.
2. Parameter P.17 must be used to select either First On Last Off or First On First Off.
3. Discrete Inputs programmed as Pump 1-4 Disable inputs may be used to disable pumps.
4. Discrete Inputs programmed as Call Pump 1-4 Last inputs may be used to assign pumps to standby status.
5. Discrete Inputs programmed as Sequence Inputs 1-4 may be used to set the lead pump.
6. Parameter P.39 may be used to set the lead pump among pumps 2 - 4.
7. If pump 1 is disabled another pump will be called in its place.
8. A Discrete Input programmed for External Alternation (Function 6) may be used to force alternation. When this feature is used, Automatic Alternation would normally be disabled by setting Parameter P.18 to Disabled.
9. If connected to a SCADA system, alternation may be initiated by momentar­ily setting Coil 136, or by forcing the lag pump by writing to Register 40022 (Same as Parameter P.39).
10. Parameter P.51 may be used to select and setup Time Based Alternation.
11
ALTERNATION SEQUENCE MODE
PUMP 1 ALWAYS LEAD Turns Off With Other Pumps On
Notes:
1. This sequence is used when it is required that pump 1 always be lead, and when it must be turned off when another pump(s) comes on. When a pump from the second group is required, pump 1 is first turned off, then after the Lag Pump Delay, the other pump is turned on.
2. For Triplex and Quadraplex applications Parameter P.17 must be used to select either First On Last Off or First On First Off.
3. Discrete Inputs programmed as Pump 1-4 Disable inputs may be used to disable pumps.
4. For Triplex and Quadraplex applications Discrete Inputs programmed as Call Pump 2-4 Last inputs may be used to assign pumps to standby status.
5. For Triplex and Quadraplex applications Discrete Inputs programmed as Sequence Inputs 2-4 may be used to set the lead pump.
6. For Triplex and Quadraplex applications Parameter P.39 may be used to set the lead pump.
7. If pump 1 is disabled, another pump will Not be called in its place. The 1ST Pump On/Off Level parameters are dedicated to pump 1 and will not call another pump.
8. A Discrete Input programmed for External Alternation (Function 6) may be used to force alternation. When this feature is used, Automatic Alternation would normally be disabled by setting Parameter P.18 to Disabled.
9. If connected to a SCADA system, alternation may be initiated by momentar­ily setting Coil 136, or by forcing the lag pump by writing to Register 40022 (Same as Parameter P.39).
10. Parameter P.51 may be used to select and setup Time Based Alternation.
Parameter P.16 = 3
Movement of Lead Pump Upon Alternation
SPLIT ALTERNATION
Parameter P.16 = 4
Notes:
1. This sequence is used when it is required that pumps be alternated in two separate groups.
2. Parameter P.17 must be used to select either First On Last Off or First On First Off.
3. Discrete Inputs programmed as Pump 1-4 Disable inputs may be used to disable pumps.
4. Discrete Inputs programmed as Call Pump 1-4 Last inputs may be used to assign pumps to standby status.
5. Discrete Inputs programmed as Sequence Inputs 1-4 may be used to set the lead pump.
6. Parameter P.39 may be used to set the lead pump of group #1.
7. If pumps from group 1 are disabled, then pumps in group #2 may be called to take their place.
8. A Discrete Input programmed for External Alternation (Function 6) may be used to force alternation of Group #1. When this feature is used, Automatic Alternation would normally be disabled by setting Parameter P.18 to Dis­abled.
9. If connected to a SCADA system, alternation of Group #1 may be initiated by momentarily setting Coil 136, or by forcing the lead pump position by writing to Register 40022 (Same as Parameter P.39).
10. Parameter P.51 may be used to select and setup Time Based Alternation of Group #1.
12
ALTERNATION SEQUENCE MODE
FIXED ALTERNATION Parameter P.16 = 5
Notes:
1. This sequence is used when no alternation is required and when pump 1 should normally be lead pump. Other pumps may be made lead by setting Parameter P.39.
2. Discrete Inputs programmed as Pump 1-4 Disable inputs may be used to disable pumps.
3. Discrete Inputs programmed as Call Pump 1-4 Last inputs may be used to assign pumps to standby status.
4. Discrete Inputs programmed as Sequence Inputs 1-4 may be used to set the lead pump.
5. Parameter P.39 may be used to set the lead pump.
6. The Pump Stop Mode (Parameter P.17) has no effect on this sequence.
7. Automatic Alternation Enable/Disable (Parameter P.18) has no effect on this sequence.
8. The External Alternation feature will not function when using this sequence.
9. If connected to a SCADA system, the lead pump position may be set by writing to Register 40022 (Same as Parameter P.39).
10. Time Based Alternation using Parameter P.51 will not function when using
this sequence.
STEPPED ON/OFF SEQUENCE Only One Pump Runs at a Time Parameter P.16 = 6
Notes:
1. This sequence is used in stations where there is a significant difference in the size of the pumps, and when only one pump is to be allowed to run at a time. When there is a need for more pumping, the smaller pump is turned off and the next larger pump is called to run. As the need for pumping de­creases, the larger pump is turned off and a smaller pump is called to run in its place (provided the Off Levels are staggered).
2. The Lag Pump Delay operates to give the check valve of the pump being turned off time to close before another pump is called to run.
3. Discrete Inputs programmed as Pump 1-4 Disable inputs should be used to disable pumps that are not able to run. It is critical that the largest pump in the group, have some type of pump fault logic connected to the respective Pump Disable discrete input.
4. Discrete Inputs programmed as Call Pump 1-4 Last will not function when using this sequence.
5. Discrete Inputs programmed as Sequence Inputs 1-4 will not function when using this sequence.
6. Parameter P.39 has no effect on this sequence.
7. The Pump Stop Mode (Parameter P.17) has no effect on this sequence.
8. Automatic Alternation Enable/Disable (Parameter P.18) has no effect on this sequence.
9. The External Alternation feature will not function when using this sequence.
10. The On Generator (Parameter P.15) has no effect on this sequence.
11. Time Based Alternation using Parameter P.51 will not function when using
this sequence.
13
Loading...
+ 32 hidden pages