MPE PMR1 Quick Start Manual

The Pump Monitor Relay provides Motor Over Temperature and Seal Leakage alarms for Submersible Pumps.
Motor Over Temperature Alarm - The unit applies a low voltage
DC signal to the Motor Thermal Sensor to check its status. If the unit detects that the Motor Thermal Sensor contacts are closed (normal condition), the Overtemp indication remains off, and the Overtemp Relay is energized closing the contacts between terminals 2 and 11.
If the Motor Thermal Sensor contacts open (Over Temperature condition), the Overtemp Indication is turned on and the Overtemp Alarm Relay is de-energized opening the contacts between terminals 2 and 11 and closing the contacts between terminals 2 and 1.
When the High Motor Temperature condition has cleared, the unit will reset based on the position of Alarm Reset Mode Select Switch (Auto or Manual). When in the Auto position, the Overtemp Alarm resets automatically. If the switch is in the Manual position, the Overtemp Reset Push-button must be pushed for approximately 1.5 seconds to clear the alarm.
Seal Leakage Alarm - The unit detects moisture inside a pump
motor by using a low voltage AC signal to measure the resistance between a single (or dual) Leakage Probe(s) and the grounded motor housing, or across two Leakage Probes. A Seal Leakage condition is considered present when the amount of moisture in the motor causes the resistance between terminal 6 and 5 to drop below the setting on the potentiometer. When this occurs the unit turns on the Leakage Indication and energizes the Leakage Alarm Relay closing the contacts between terminals 9 and 10.
The alarm trip point may be set by the following procedure: Isolate the Leakage Probe(s) from terminals 5 and 6. Connect a resistor, with the desired trip value, across terminals 5 and 6. Slowly adjust the potentiometer to the point where the alarm turns on. Remove the resistor and reconnect to the Leakage Probe(s).
OPERATION
Pump Monitor Relay PMR1
Input Power: Output Rating: Operating Temp: Storage Temp: Temp Sensor Voltage: Leak Sensor Voltage: Enclosure: Base:
120 VAC ±10%, 7.0 VA max 8A Resistive @ 120VAC
-20°C to +65 °C
-45°C to +85 °C
6.6 VDC ±10%
4.7 VAC ±10% White Lexan Phenolic
ORDERING INFORMATION
Part Number: PMR1
SPECIFICATIONS
UL FILE #E101681
2464 Vulcan Road, Apopka, Florida 32703 (407) 299-3825 www.mpelectronics.com
MADE IN
THE U.S.A.
Pump Monitor Relay
CONNECTION DIAGRAMS
CHECKS RESISTANCE BETWEEN
TWO PROBES AND MOTOR HOUSING
CHECKS RESISTANCE BETWEEN
TWO PROBES
CHECKS RESISTANCE BETWEEN
ONE PROBE AND MOTOR HOUSING
2464 Vulcan Road, Apopka, Florida 32703 (407) 299-3825 www.mpelectronics.com