Overview
Introduction
TCF-142 series converters are equipped w ith a multiple inte r f a c e c ircuit
that can handle RS-232, RS-422, and RS-485 serial interfaces, as well as
multi-mode or single-mode fiber. TCF-142 converters are used to extend
serial transmission distance up to 5 km (TCF-142-M, with multi-mode
fiber) or up to 40 km (TCF-142-S, with single-mode fiber). The TCF-142
must be configured to transmit a particular serial interface. You cannot
transmit both RS-232 and RS-485 signals at the same time.
Why Convert Serial to Fiber?
Fiber communication not only extends the communication distance, but
also provides many advantageous features.
IMMUNITY FROM ELECTRICAL INTERFERENC E: Fiber is not affected
by electromagnetic interference or radio frequency interference. It
provides a clean communication path and is immune to cross-talk.
INSULATION: Optical fiber is an insulator; the glass fiber eliminates the
need for using electric currents as the communication medium.
SECURITY: Fiber cannot be tapped by conventional electric means and is
very difficult to tap into optically.
RELIABILITY & MAINTENANCE: Fiber is immune to adverse
temperature and moisture conditions, d oes not corrode o r lose its signal,
and is not affected by short circuits, power surges, or static electricity.
Reverse Power Protection
The Reverse Power Protection feature provides extra protection against
accidentally connecting the power cables to th e wrong terminal. The
converter automatically detects which power w ire is positive and which is
negative.
Ring Mode
To allow one half-duplex serial device to communicate with multiple
half-duplex devices connected to a fiber ring, you should configure the
TCF-142 for “ring mode” by setting DIP switch “SW4” to the “On” position.
The Tx port of a particular TCF-142 unit connects to the neighboring
converter’s Rx port on the ring. Note that when one node transmits a
signal, the signal travels around the ring until it returns back to the
transmitting unit, which then
blocks the signal.
ensure that the total fiber ring
length is less than 100 km when
using

To avoid problems when setting up a fiber ring, each TCF
unit making up the ring must be powered down and set to “Ring
mode.” Next, make
sure all cables are connected properly, and
then power up all devices connected to the ring .
“Ring Mode” can only be used with half-duplex applications (i.e.,
RS-485 multi-drop communication).
DIP Switch Selectable Terminator
The TCF-142’s termination resistor is set with a DIP switch located on the
outside of the converter’s casing.
No Configuration Required for Baudrate Settings
The TCF-142 is c ompat ible w ith any baudrate from 50 bps to 921.6 kbps.
The TCF-142 automatically converts the signal back and f ort h between
serial (RS-232, RS-422, or RS-485) and fiber, and does not need to
interpret the signal or the baudrate of the transmitting device. For this
reason, the TCF-142 does not have any DIP switch es or jumpers for
setting the baudrate.
Features
• “Ring” or “Point to Point” transmission
• Extend RS-232/422/485 transmission distance:
up to 40 km with single-mode—TCF-142-S Series
up to 5 km with multi-mode—TCF-142-M Series
• Compact size
• Decrease signal interference
• Protect against electronic degradation and chemical corrosion
• Supports baudrates up to 921.6 kbps
• Extended operating temperature from -40 to 75°C (for “T” models)
Package Checklist
Before installing the TCF-142, verify that the package contains the
following items:
• 1 TCF-142 media converter
• Power jack to 3-pin terminal block adaptor
• Stick-on pads
• Quick installation guide (printed)
• Warranty card
NOTE: Please notify your sales representative if any of the above items
are missing or damaged.

- 4 -
Dimensions and Appearance
TCF-142 fiber converters are easy to set up and use. The serial terminal
block of one of the converters connects to your computer, the serial
terminal block of the other converter conn ects to your serial device, and
the two converters are connected by fiber cable(s).
Electrostatic Discharge Warning!
To protect the product from damage due to e l ectrostatic
discharge, we recommend wearing a grounding device when
handling your TCF-142.
Wiring Examples
Connecting the Power Supply
Before using the TCF-142, first connect the DC power supp ly to the power
supply terminal block located on the TCF-142’s bottom panel.
Connecting RS-422 and 4-wire RS-485 Serial Devices
Connecting 2-wire RS-485 Serial Devices

- 5 -
Connecting an RS-232 Serial Device to a PC
Switch Settings
Built-in 120 Ω
Terminator
This switch setting is used for product revision 3.2 or later; for
previous revisions, refer to the label on the product's rear panel
for the correct information.
The S1 DIP Switch is located inside the TCF-142. When the TCF-142 is in
RS-485 mode, use this DIP switch to configure RS-485 data direction
control, data format, and baudrate. When the TCF-142 is in RS-232/422
mode, the S1 DIP switch cannot affect RS-232/422 communication.
RS-485 Data Direction Control Settings
RS-485 Data Direction Control

The S2 DIP switch is located inside the TCF-142. This switch is used to
configure the pull high/low resistors. Note that S2 Pin 1 and Pin 2 must
both be configured to ON or both must be configured to OFF.
* These DIP switches are located inside the TCF-142.
We recommend setting S2 Pin 1 and Pin 2 to the 1K option
(ON/ON) when termination is enabled.
LED Description
There are 3 LEDs on the front panel of the TCF-142.
Blinking when fiber is transmitting data
Blinking when fiber is receiving data
TCF-142-M-SC
TCF-142-S-ST
TCF-142-M-SC-T
TCF-142-S-ST-T
TxD+, TxD-, RxD+, RxD-, SGND
Signals for 4-wire RS-485
TxD+, TxD-, RxD+, RxD-, SGND
Signals for 2-wire RS-485

Distance TCF-142-S series:
Single mode fiber for 40 km
TCF-142-M series:
Multi mode fiber for 5 km
8.3/125, 8.7/125, 9/125 or 10/125 μm
TCF-142-M series:
50/125, 62.5/125, or 100/140 μm
TCF-142-S series: 1310 nm
TCF-142-M series: 850 nm
TCF-142-S series: > -5 dBm
TCF-142-M series: > -5 dBm
TCF-142-S series: -25 dBm
TCF-142-M series: -20 dBm
Point-to-Point
Transmission
Half or Full duplex
Ring Transmission
0 to 60°C (32 to 140°F), 5 to 95 % RH
Extended Operating
Temperature (T models)
-40 to 75°C (-40 to 167°F)
Storage Temperature
-40 to 75°C (-40 to 167°F), 5 to 95 % RH
1 kV Burst (EFT), EN61000-4-4
1 kV Surge, EN61000-4-5
Reverse Power Prot e ction
Protects against V+/V- reversal
Protects against 2 signals shorted together:
1.1A
67 x 100 x 22 mm
90 x 100 x 22 mm (including ears)
FCC Part 15 Subpart B Class B, EN 55022
Class B
EN61000-4-2 (ESD), Criteria B, Level 2
EN61000-4-3 (RS), Criteria B, Level 2
EN61000-4-4 (EFT), Criteria B, Level 2
EN61000-4-5 (Surge), Criteria B, Level 2
EN61000-4-6 (CS), Criteria B, Level 2