Moxa Technologies MGate MB3270I, MGate MB3270 Quick Installation Manual

— 1 — — 2 — — 3 —
MGate MB3270 and MB3270I
Quick Installation Guide
Third Edition, October 2007
The MGate MB3270 and MB3270I are 2-port advanced Modbus gateways that convert between Modbus TCP and Modbus ASCII/RTU protocols. They can be used to allow Ethernet masters to control serial slaves, or to allow serial masters to control Ethernet slaves. Up to 16 TCP masters and 62 serial slaves can be connected simultaneously.
2. Package Checklist
Before installing the MGate MB3270 or MB3270I Modbus gateway, verify that the package contains the following items:
y MGate MB3270 or MB3270I Modbus gateway y Document & Software CD y MGate MB3270 and MB3270I Quick Installation Guide y Product Warranty Statement
Please notify your sales representative if any of the above items is missing or damaged.
3. Hardware Introduction
LED Indicators
Name Color Function
PWR1 Red Power is being supplied to the power input PWR2 Red Power is being supplied to the power input
(steady) Power is on and the unit is booting up
Red
(blinking) IP conflict, DHCP or BOOTP server did not respond properly, or a relay output occurred (steady) Power is on and the unit is functioning normally
Green
(blinking) Unit is responding to Locate function
RDY
Off Power is off or power error condition exists
Orange 10 Mbps Ethernet connection
Green 100 Mbps Ethernet connection
Ethernet
Off Ethernet cable is disconnected or has a short
Orange Serial port is receiving data
Green Serial port is transmitting data
P1, P2
Off Serial port is not transmitting or receiving data
The MGate MB3270 and MB3270I each provide two DB9 ports to connect to serial devices.
teseR
weiV poT
teseR
1V
+
1V
2V
+2V
1
tupni rewop l
auD
tupt
uo
yaler
dna
1RWP
2RW
P
YDR
1P
1 tenreht
E
2 tenrehtE
MB3270
MGate
2P
r
e
p
poC
t
enreh
tE
DEL
srotac
idnI
w
eiV tnorF
weiV mottoB
584/224/232-SR
P1 P2
Reset Button
The reset button is used to load factory defaults. Use a pointed object such as a straightened paper clip to hold the reset button down for five seconds. Release the reset button when the Ready LED stops blinking.
4. Hardware Installation Procedure
STEP 1: Use a standard straight-through Ethernet cable to connect the
MGate to a network hub or switch.
STEP 2: Connect your device to the MGate serial port.
STEP 3: Mount the MGate on a DIN-rail.
STEP 4: Connect the power source to power input.
5. Software Installation Information
To install MGate Manager, insert the MGate Document & Software CD into your PC’s CD-ROM drive. Once the installation window opens, click the Installation button and follow the onscreen instructions. For more detailed information about MGate Manager, click the Documents button and select the MGate MB3000 User’s Manual.
6. Pin Assignments
Ethernet Port (RJ45)
Pin Signals
1 Tx+ 2 Tx­3 Rx+
8
1
6 Rx-
Serial Port (Male DB9)
54321
987
6
Pin RS-232 RS-422/485 (4W) RS-485 (2W)
1 DCD TxD-(A) --­2 RxD TxD+(B) --­3 TxD RxD+(B) Data+(B) 4 DTR RxD-(A) Data-(A) 5 GND GND GND 6 DSR --- --­7 RTS --- --­8 CTS --- --­9 --- --- ---
P/N: 1802032700011
— 4 — — 5 — — 6 —
Power Input and Relay Output Pinouts
1V
+ 1V
2V
+2V
1
V2+ V2-
V1+ V1-
Shielded
Ground
DC
Power
Input 1
DC
Power
Input 1
Relay
output
Relay
output
DC
Power
Input 2
DC
Power
Input 2
7. Specifications
Power Requirements
Power Input 12 to 48 VDC Power Consumption MB3270: 410 mA@12 VDC, 145 mA@48 VDC
MB3270I: 470 mA@12 VDC, 150 mA@48 VDC
Operating Temperature Standard: 0 to 55°C (32 to 131°F)
Wide Temp. Model: -40 to 75°C (-40 to 167°F) Operating Humidity 5 to 95% RH Dimensions 29 × 124.5 × 89.2 mm