MGate MB3180
Quick Installation Guide
Fourth Edition, May 2014
Overview
The MGate MB3180 is a 1-por t Modbus gateway that converts
between Modbus TCP and Modbus ASCII/RTU protocols. It can be
used to allow Ethernet masters to control serial slaves, or to allow
serial masters to control Ethernet slaves. Up to 16 TCP masters
and 31 serial slaves can be connected simultaneously.
Package Checklist
Before installin g the MGate MB3 180 Modbus gateway, verify that
the package contains the following items:
• 1 MGate MB3180 Modbus gateway
• 4 stick-on pads
• Document & Software CD
• Quick Installat ion Guide
• Product Warranty Statement
• Power adapter
Optional Accessory
• DK-35A: DIN-rail mount ing kit (35 mm)
• Mini DB9F-to-TB Adaptor: DB9 fema le to termina l block
adapter
• DR-4524: 45W/2A DIN-ra il 24 VDC power supply with
universal 85 to 2 64 VAC input
• DR-75-24: 75W/3.2A D IN-rail 24 VDC p ower supply wit h
universal 85 to 2 64 VAC input
• DR-120-24: 120W/5A DIN -rail 24 VDC power supply with 88
to 132 VAC/176 to 264 VAC input by switch
Notify your sales representative if any of the above items is
missing or damaged.
Hardware Introduction
As shown in the following figures, the MGate MB3180 has one DB9
male port for transmitting serial data.
Reset Button—The reset button is used to load factory defaults.
Using a pointed object such as a straightened paper clip to hold the
reset button down for five seconds. Release the reset button when
the Ready LED stops blinking in order to load the factory defaults.
LED Indicators—Three LED indicators are located on the top
panel:
Power is on and the unit is booting
up
Blinking: IP conflict exis ts, or DHCP or
BOOTP server is not responding
Green
Steady on:
Power is on and the unit is
Unit has been found by the
Location command in MGate
Power is off or power error condition exists
10 Mbps Ethernet connection
100 Mbps Ethernet connection
Ethernet cable is disconnected or has a short
Unit is receiv ing data from device.
Unit is transmit ting data to device.
No data is being exchanged with device.
Hardware Installation Procedure
STEP 1: After unpacking the MGate
MB3180, connect the power
-through Ethernet cable to
to a network hub or switch.
Use a cross-over Ethernet cable if you are connecting the
gateway directly to a PC
STEP 3: Connect your device to the MGate MB3180
Place or mount the MGate MB3180. The unit may be
placed on a horizontal serface such as a desktop,
mounted on a DIN-rail, or mounted on the wall.

+1-714-528-6777 (toll-free: 1-888-669-2872)
+86-21-5258-9955 (toll-free: 800-820-5036)
2014 Moxa Inc. All r ights reserved.
Adjustable Pull H igh/Low Resistors for the RS-485 Port
In some critical RS-485 environments, you may need to add
termination resistors to prevent the reflection of serial signals.
When using termination resistors, it is important to set the pull
high/low resistors correctly so that the electrical signal is not
corrupted. Jumpers JP3 and JP4 are used to set the pull high/low
resistor values for the serial port. To
Set the pull high /low resistor s to 150 KΩ, which is the factory
default setting, leave the two jumpers open. To set the pull
high/low resistors to 1 KΩ, use the jumper caps to short the two
jumpers.
MGate MB3180 Jumper s
Software Installation
To install MGate Manager, insert the MGate Documentation
and Software CD into your PC's CD-ROM drive, and then run the
following setup program to begin the installation process from the
“Software” directory:
MGM_Setup_[Version]_Build _[DateTime].exe
The filename of the latest version may have the following format:
MGM_Setup_Verx.x.x_Build_xxxxxxxx.exe.
For detailed information about MGate Manager, refer to the MGate
MB3000 User's Manual, which can be found in the “Document”
directory .
Pin Assignments
Ethernet Port (RJ45)
Environmental Specifications
200 mA@12 VDC, 60 mA@48 VDC
-40 to 85°C (-40 to 185°F)
Dimensions
With ears:
Without ears:
x 75 x 80 mm (0.87 x 2.95 x 3.15 inch
)
22 x 52 x 80 mm (0.87 x 2.05 x 3.15 inch)
15 KV ESD for seria l port
4 KV burst (EFT), EN61000-4-4
2 KV surge, EN61000-4-5
FCC Class A, CE Class A, UL , CUL, TUV