Overview
The MGate 5118 is an industrial Ethernet gateway for J1939-to-Modbus RTU/ASCII/TCP, PROFINET and EtherNet/IP network communications.
Package Checklist
Before installing the MGate 5118, verify that the package contains the following items:
1 MGate 5118 gateway
Quick installation guide (printed)
Warranty card
Please notify your sales representative if any of the above items is missing or damaged.
Optional Accessories (can be purchased separately)
Mini DB9F-to-TB: DB9-female-to-terminal-block connector
WK-51-01: Wall-mounting kit, 51 mm wide
Hardware Introduction
LED Indicators
LED
Color
Description
PWR 1,
PWR 2
Green
The power cable is connected
Off
The power cable is disconnected
Ready
Off
Power is off or a fault condition exists
Green Steady on: Power is on, and the unit is functioning
normally Blinking: The unit is responding to the software’s
Locate function
Red Steady on: Power is on, and the unit is booting up
Blinking: Indicates an IP conflict, or the DHCP or BOOTP server is not responding properly
Flashing quickly: the microSD card failed
LAN
Green (Flashing
only)
The Ethernet port is receiving or transmitting data
Modbus TCP Client:
Modbus communication in progress Modbus TCP Server: Modbus communication in progress EIP Scanner: I/O is exchanging data with at least one device
EIP Adapter: I/O is exchanging data PROFINET: PROFINET I/O interface is exchanging
data
- 3 -
LED
Color
Description
Red (Flashing
only)
A communication error occurred
Modbus TCP Client:
1. Received an exception code or framing error (parity error, checksum error)
2. Command timeout (slave device is not responding)
3. TCP connection timeout
Modbus TCP Server:
1. Received an invalid function code or framing error (parity error, checksum error)
2. Accessed invalid register address or coil address
Ethernet/IP Scanner:
1. Command timeout (the adapter is not responding)
2. TCP connection timeout
Ethernet/IP Adapter:
The connection was refused due to incorrect
configuration
Off
No communication
MB* Green
(Flashing only)
Modbus is receiving or transmitting data
Red (Flashing
only)
A communication error occurred
Master Mode:
1. Received an exception code or framing error (parity error, checksum error)
2. Command timeout (the slave device is not responding)
Slave Mode:
1. Received an invalid function code or framing error (parity error, checksum error)
2. Accessed invalid register address or coil address
Off
No communication
CAN Green
(Flashing only)
CANbus(J1939) communication is receiving or transmitting data
Red
(Steady)
A communication error occurred
1. The J1939 address claim failed
2. CAN is in bus-off state because the error counter
is exceeding its limitations
Off
No communication
Eth1,
Eth2
Green
Indicates an 100 Mbps Ethernet connection
Amber
Indicates a 10 Mbps Ethernet connection
Off
The Ethernet cable is disconnected
*Only indicates serial communication status; for Modbus TCP status, please refer to LAN LED indicator.