Moxa Technologies AirWorks AWK-3121 User Manual

Moxa AirWorks AWK-3121
User’s Manual
Third Edition, July 2009
www.moxa.com/product
© 2009 Moxa Inc. All rights reserved.
Moxa AirWorks AWK-3121
User’s Manual
The Moxa software described in this manual is furnished under a license agreement and may be used only in
accordance with the terms of that agreement.
Copyright Notice
Copyright © 2009 Moxa Inc.
All rights reserved.
Trademarks
MOXA is a registered trademark of Moxa Inc.
All other trademarks or registered marks in this manual belong to their respective manufacturers.
Disclaimer
Information in this document is subject to change without notice and does not represent a commitment on the part of Moxa.
Moxa provides this document “as is,” without warranty of any kind, either expressed or implied, including, but not limited to, its particular purpose. Moxa reserves the right to make improvements and/or changes to this manual, or to the products and/or the programs described in this manual, at any time.
Information provided in this manual is intended to be accurate and reliable. However, Moxa assumes no responsibility for its use, or for any infringements on the rights of third parties that may result from its use. This product might include unintentional technical or typographical errors. Changes are periodically made to the information herein to correct such errors, and these changes are incorporated into new editions of the publication.
Technical Support Contact Information
www.moxa.com/support
Moxa Americas: Toll-free: 1-888-669-2872 Tel: +1-714-528-6777 Fax: +1-714-528-6778
Moxa China (Shanghai office)
: Toll-free: 800-820-5036 Tel: +86-21-5258-9955 Fax: +86-10-6872-3958
Moxa Europe
: Tel: +49-89-3 70 03 99-0 Fax: +49-89-3 70 03 99-99
Moxa Asia-Pacific
: Tel: +886-2-8919-1230 Fax: +886-2-8919-1231
Table of Contents
Chapter 1 Introduction..................................................................................................1-1
Overview.................................................................................................................................. 1-2
Package Checklist.................................................................................................................... 1-2
Product Features ...................................................................................................................... 1-2
Product Specifications ............................................................................................................. 1-3
Functional Design.................................................................................................................... 1-5
LED Indicators ............................................................................................................. 1-5
Beeper........................................................................................................................... 1-6
Reset Button ................................................................................................................. 1-6
Relay (Digital Output).................................................................................................. 1-6
Chapter 2 Getting Started.............................................................................................2-1
First-time Installation and Configuration................................................................................. 2-2
Communication Testing ...........................................................................................................2-3
Function Guiding Map............................................................................................................. 2-4
Chapter 3 Web Console Configuration........................................................................3-1
Configuration by W eb Browser...............................................................................................3-2
Overview.................................................................................................................................. 3-4
Basic Settings........................................................................................................................... 3-5
System Info Settings..................................................................................................... 3-5
Network Settings.......................................................................................................... 3-6
Time Settings................................................................................................................ 3-7
Wireless Settings...................................................................................................................... 3-9
Basic Wireless Settings................................................................................................. 3-9
WLAN Security Settings............................................................................................ 3-13
Advanced Wireless Settings....................................................................................... 3-22
WLAN Certification Settings (for EAP-TLS in Client mode only)......................... 3-25
Advanced Settings ................................................................................................................. 3-26
DHCP Server (for AP mode only)............................................................................. 3-26
Packet Filters .............................................................................................................. 3-28
RSTP Settings (for AP mode only)........................................................................... 3-31
SNMP Agent .............................................................................................................. 3-33
Auto W arni ng Settings........................................................................................................... 3-35
System Log................................................................................................................. 3-35
Syslog......................................................................................................................... 3-37
E-mail......................................................................................................................... 3-38
Relay........................................................................................................................... 3-39
Trap ............................................................................................................................ 3-40
Status...................................................................................................................................... 3-41
Associated Client List (for AP mode only).................................................................3-41
DHCP Client List (for AP mode only)....................................................................... 3-41
System Log................................................................................................................. 3-42
Relay Status................................................................................................................ 3-42
DI and Power Status................................................................................................... 3-43
Wireless Status ........................................................................................................... 3-43
Maintenance........................................................................................................................... 3-44
Console Settings......................................................................................................... 3-44
Ping............................................................................................................................. 3-44
Firmware Upgrade ...................................................................................................... 3-45
Config Import Export ................................................................................................. 3-45
Load Factory Default.................................................................................................. 3-46
Password..................................................................................................................... 3-46
Misc. Settings............................................................................................................. 3-46
Save Configuration................................................................................................................ 3-47
Restart.................................................................................................................................... 3-48
Logout.................................................................................................................................... 3-48
Chapter 4 Software Installation/Configuration ...........................................................4-1
Overview.................................................................................................................................. 4-2
AWK Search Utility................................................................................................................. 4-2
Installing AWK Search Utility ..................................................................................... 4-2
Configuring AWK Search Utility................................................................................. 4-5
Chapter 5 Other Console Configurations....................................................................5-1
RS-232 Console Configuration (115200, None, 8, 1, VT100)................................................. 5-2
Configuration by Telnet and SSH Consoles............................................................................. 5-4
Configuration by Web Browser with HTTPS/SSL .................................................................. 5-5
Disabling T elnet and Browser Access...................................................................................... 5-6
Chapter 6 References....................................................................................................6-1
Wireless Distribution System (WDS)...................................................................................... 6-2
Beacon ..................................................................................................................................... 6-3
DTIM....................................................................................................................................... 6-3
Fragment.................................................................................................................................. 6-3
RTS T hreshold......................................................................................................................... 6-3
STP and RSTP......................................................................................................................... 6-4
The STP/RSTP Concept............................................................................................... 6-4
Differences between RSTP and STP............................................................................ 6-4
Chapter 7 Supporting Information ...............................................................................7-1
About This User’s Manual....................................................................................................... 7-2
DoC (Declaration of Conformity)............................................................................................ 7-3
Federal Communication Commission Interference Statement ..................................... 7-3
R&TTE Compliance Statement.................................................................................... 7-3
Firmware Recovery.................................................................................................................. 7-4
Technical Support Contact Information................................................................................... 7-5
1
1
Chapter 1 Introduction
Moxa AirWorks AWK-3121 enables wireless users to access network resources wirelessly. The AWK-3121 is rated to operate at temperatures ranging from 0 to 60°C for standard models and -40 to 75°C for extended temperature models, and is rugged enough for any harsh industrial environment.
In this chapter, we cover the following topics:
Overview Package Checklist Product Features Product Specifications Functional
¾ LED Indicators ¾ Beeper ¾ Reset Button ¾ Relay (Digital Output)
AirWorks AWK-3121 User’s Manual Introduction
1-2
Overview
The AWK-3121 Access Point/Bridge and AP Client is ideal for applications that are hard to wire, too expensive to wire, or use mobile equipment that connects to a TCP/IP network. The AWK-3121 can operate at temp eratures ranging from 0 to 60°C for standard models and -40 to 75°C for extended temperature models, and is rugged enough for any harsh industrial environment. Installation is easy, with either DIN-Rail mounting or wall mounting in distribution boxes. The DIN-rail/wall mounting ability, wide operating temperature range, and IP30 housing with LED indicators make the AWK-3121 a convenient yet reliable solution for any industrial wireless application.
Package Checklist
Moxa’s AWK-3121 is shipped with the following items. If any of these items is missing or damaged, please contact your customer service representative for assistance.
y 1 AWK-3121 y 2 Swivel-type Antennas (2dBi, RP-SMA, 2.4&5GHz) y 1 Quick Installation Guide y 1 Software CD y 1 Moxa Product Warranty Booklet y 1 Cable Holder with a Screw y 2 Protective Caps
NOTE
The above items come with the AWK-3121 standard version. The package contents may vary for different customized versions.
Product Features
y IEEE802.11a/b/g Compliant y Three-in-one design (AP/Bridge/Client) y Advanced Wireless Security:
¾ 64-bit and 128-bit WEP/WPA/WPA2 ¾ SSID Hiding/IEEE 802.1X/RADIUS ¾ Packet access control & filtering
y STP/RSTP support for redundancy of system networking y Long-distance transmission support y Turbo Roaming
TM
enables rapid handover (Client m ode)
y Dedicated antenna selection y Free firmware update for more advanced functions y RS-232 console management y 2DI+1DO for on-site monitor i ng and warming y Operating temperature ranges from -40 to 75°C (-T model) y Power input by redundant 24 VDC power inputs or IEEE802.3af Power over Ethernet
AirWorks AWK-3121 User’s Manual Introduction
1-3
y DIN-Rail or wall mounting ability y IP30 protected high-strength metal housi ng
Product Specifications
WLAN
Standards IEEE 802.11a/g/b for Wireless LAN
IEEE 802.3u 10/100BaseT(X) for Ethernet LAN EEE 802.3af for Power-over-Ethernet IEEE 802.1D/w STP/RSTP
Spread Spectrum and Modulation
DSSS with DBPSK, DQPSK, CCK
OFDM with BPSK, QPSK, 16QAM, 64QAM Operating Channels (Central Frequency)
US: 2.412 to 2.462 GHz (11 channels)
5.18 to 5.24 GHz (4 channels)
EU: 2.412 to 2.472 GHz (13 channels)
5.18 to 5.24 GHz (4 channels)
JP: 2.412 to 2.472 GHz (13 channels, OFDM)
2.412 to 2.484 GHz (14 channels, DSSS)
5.18 to 5.24 GHz (4 channels for W52)
Security 64-bit and 128-bit WEP encryption, WPA /WPA2
(IEEE 802.1X/ RADIUS, TKIP and AES)
Protocol
General Protocols: Proxy ARP, DNS, HTTP, HTTPS, IP, ICMP, SNTP, TCP, UDP,
RADIUS, SNMP, RTP AP-only Protocols: ARP, BOOTP, DHCP, dynamic VLAN-Tags for 802.1X-Clients,
STP/RSTP (IEEE 802.1D/w) Data Rates 802.11b: 1, 2, 5.5, 11 Mbps
802.11a/g: 6, 9, 12, 18, 24, 36, 48, 54 Mbps
Transmit Power 802.11b: 1 to 11 Mbps: Typ. 18±1.5 dBm
802.11g: 6 to 24 Mbps: Typ. 18±1.5 dBm
36 to 48 Mbps: Typ. 16±1.5 dBm
54 Mbps: Typ. 15±1.5 dBm
802.11a: 6 to 24 Mbps: Typ. 16±1.5 dBm
36 to 48 Mbps: Typ. 14±1.5 dBm
54 Mbps: Typ. 13±1.5 dBm Receiver Sensitivity 802.11b: -92 dBm @ 1 Mbps, -90 dBm @ 2 Mbps,
-88 dBm @ 5.5 Mbps, -84dBm @ 11 Mbps
802.11g: -87 dBm @ 6 Mbps, -86 dBm @ 9 Mbps,
-85 dBm @ 12 Mbps, -82dBm @ 18 Mbps,
-80 dBm @ 24 Mbps, -76 dBm @ 36 Mbps,
-72dBm @ 48 Mbps, -70 dBm @ 54 Mbps
802.11a: -87 dBm @ 6 Mbps, -86 dBm @ 9 Mbps,
-85 dBm @ 12 Mbps, -82dBm @ 18 Mbps,
-80 dBm @ 24 Mbps, -76 dBm @ 36 Mbps,
-72dBm @ 48 Mbps, -70 dBm @ 54 Mbps
Interface
Default Antenna 2dBi dual-band, Omni-directional antenna Antenna Connector RP-SMA (female) Connection 10-pin Removable Terminal Block
AirWorks AWK-3121 User’s Manual Introduction
1-4
Alarm Contact 1 relay output (capacity: 1A @24VDC) Digital Input 2 electrically-isolated inputs
+3 to -30V for state “0” (OFF)
13 to 30V for state “1” (ON)
Max. input current: 8 mA
Console RS-232 (RJ45 type) LAN Port 10/100BaseT(X) auto negotiation speed LED Indicators PWR1, PWR2, PoE, FAULT, STATE, Signal Strength,
CLIENT MODE, BRIDGE MODE, WLAN, 10M, 100M
Power
Input Voltage 12 to 48 VDC, redundant dual DC power inp ut s or
48 VDC Power-over-Ethernet (IEEE 802.3af) Input Current 0.494 to 0.121 A (@ 12 to 48 VDC) Input Current (@ 24VDC) 0.3 A Overload Current Protection 1.6 A Reverse Polarity Protection Present
Mechanical
Dimensions 53.6 x 135 x 105 mm (2.11 x 5.31 x 4.13 in) Weight 850 g Installation DIN-rail, or Wall Mounting (with optional wall mounting kit) Casing IP30 protection, aluminum case
Environment
Operating Temperature: Standard models: 0 to 60°C (32 to 140°F)
Wide Temp Models: -40 to 75°C (-40 to 167°F) Storage Temperature: -40 to 85ºC (-40 to 185ºF) Ambient Relative Humidity 5 to 95% (non-condensing)
Regulatory Approvals*
Safety: EN60950-1, UL60950-1 Radio: EN300 328, EN301 893, ARIB STD-33/T66/T71 (Japan) EMC: EN301 489-1/-17, FCC Part 15, EN55022/55024, IEC61000-6-2/-4 Environmental/EMC compliancy
EN50155, EN50121-1/-4
* Please check Moxas website for the most up-to-date certification status.
Warranty
5 years
Details: See http://www.moxa.com/warranty
ATTENTION
The AWK-3121 is NOT a portable mobile device and should be located at least 20 cm away from the human body.
The AWK-3121 is NOT designed for the general public. To deploy AWK-3121 units and establish a wireless network safely, a well-trained technician is required for installation.
AirWorks AWK-3121 User’s Manual Introduction
1-5
Functional Design
LED Indicators
The LEDs on the front panel of the AWK-3121 allow you to identity the status and wireless settings quickly.
The LED for FAULT indicates the system failure and
user-configured events. If the AWK-3121
cannot retrieve the IP address from a DHCP server, the FAULT LED will blink at an interval of one second.
The LEDs for SIGNAL are a signal strength indicator and they merely function in Client mode. The following table is a summary for the wireless settings and LED displays. You can check the
status of the AWK-3121 by reading these LEDs. More information about “Basic Wireless Settings” is presented in Chapter 3.
Basic Wireless Settings LEDs
Operation mode WDS CLIENT BRIDGE SIGNAL
Note
AP Disable off off - AP mode AP Enable off
on
- Bridge mode: WDS is enabled
Client -
on
off 0 Client mode: no association
Client -
on
off 1
Client mode: associated, but poor signal
Client -
on
off 2-5
Client mode: associated; signal is fine
ATTENTION
When the LEDs for FAULT, SIGNAL, CLIENT, BRIDGE and WLAN all light up simultaneously and blink at one-second interval, it means the system failed to boot. This may be due to improper operation or uncontroll a bl e issues, such as an unexpected shutdown during firmware update. To recover the firmware, refer to “Firmware Recovery” in Chapter 6.
AirWorks AWK-3121 User’s Manual Introduction
1-6
Beeper
The beeper signals that the system is ready with two short beeps.
Reset Button
The RESET button is located on the top panel of the AWK-3121. You can reboot the AWK-3121 or reset it to factory default settings by pressing the RESET button with a pointed object such as an unfolded paper clip.
y System reboot: Hold the RESET button down for under 5 seconds and then release. y Reset to factory default: Hold the RESET button down for over 5 seconds until the STATE
LED starts blinking green. Release the button to reset the AWK-3121.
Relay (Digital Output)
The AWK-3121 has one relay output, which consists of the 2 terminal block contacts on the top panel, as shown below. These relay contacts are used to forward system failure and user-configured events.
The two wires attached to the relay contacts form an open circuit when a user-configured event is triggered. If a user-configured event does not occur, the relay circuit will remain closed. For safety reason, the relay circuit is kept open when the AWK-3121 is not powered.
AirWorks AWK-3121 User’s Manual Introduction
1-7
The AWK-3121’s relay status is summarized as follows:
Power Status Event Relay
Off --- Open
Yes Open
On
No Short
2
2
Chapter 2 Getting Started
This chapter explains how to install Moxa’s AirWorks AWK-3121 for the first time, and quick ly set up your wireless network and test whether the connection is running well. With the function guide, you can find out the functions you need easily.
In this chapter, we cover the following topics:
First-time Installation and
Confi
guration
Communication Testing Function Guiding Map
AirWorks AWK-3121 User’s Manual Getting Started
2-2
First-time Installation and Configuration
Before installing the AWK-3121, make sure that all items in the Package Checklist are in the box . In addition, you will need access to a notebook computer or PC equipped with an Ethernet port. The AWK-3121 has a default IP address that you must use when connecting to the device for the first time.
Step 1: Select the power source.
The AWK-3121 can be powered by DC power input or PoE (Power over Ethernet). The AWK-3121 will use whichever power source you choo se.
Step 2: Connect the AWK-3121 to a notebook or PC.
Since the AWK-3121 supports MDI/MDI-X auto-sensing, you can use either a straight-through cable or crossover cable to connect the AWK-3121 to a computer. If the LED indicator on the AWK-3121’s LAN port lights up, it means the connection is established.
Step 3: Set up the computer’s IP address.
Set an IP address on the same subnet as the AWK-3121. Since the AWK-3121’s default IP address is 192.168.127.253, and the subnet mask is 255.255.255.0, you shou ld set the IP address of the computer to 192.168.127.xxx.
NOTE
After you select Maintenance Æ Load Factory Default and click the Submit button, the AW K-3121 will be reset to factory default settings and the IP address will be also reset to
192.168.127.253.
Step 4: Use the web-based manager to configure the AWK-3121
Open your computer’s web browser and type http://192.168.127.253 in the address field to access the homepage of the web-based Network Manager. Before the homepage opens, you will need to enter the user name and password as shown in the following figure. For first-time configuration, enter the default user name and password and then click on the Login button:
AirWorks AWK-3121 User’s Manual Getting Started
2-3
NOTE
Default user name and password: User Name: admin Password: root For security reasons, we strongly recommend changing the default password. To do so, select
Maintenance > Password, and then follow the on-screen instructions to change the password.
NOTE
After you click Submit to apply changes, you can see that the web page is refreshed, and the string “(Update)” and a blinking reminder will be shown on the upper-right corner of web page, as follow.
To make the changes effective, click Restart and then Save and Restart after you change the settings. About 30 seconds are needed for the AWK-3121 to complete its restart process.
Step 5: Select the operation mode for the AWK-3121. By default, the AWK-3121’s operation mode is set to AP. You can change the setting in Wireless
Settings Æ Basic Wireless Settings if you would like to use the Client mode instead. Detailed
information about configuring the AWK-3121’s operation can be found in Chapter 3.
Step 6: Test communications.
We will describe 2 test methods to make sure the network connection has been established. Please refer to the following section for more details.
Communication Testing
After installation, you can run a sample test to make sure the AWK-3121 and wireless connection are functioning normally. Two testing methods are explained in the following sections. Use the first method if you are using only one AWK-3121 device, and use the second method if you are using two or more AWK-3121s.
Testing Method for one AWK-3121
If you are only using one AWK-3121, you will need a second notebook computer equipped with a WLAN card. Configure the WLAN card to connect to the AWK-3121 (NOTE: the default SSID is
MOXA), and change the IP address of the second notebook (B) so that it is on the same subnet as
the first notebook (A), which is connected to the AWK-3121.
AirWorks AWK-3121 User’s Manual Getting Started
2-4
After configuring the WLAN card, establish a wireless connection with the AWK-3121 and open a DOS window on Notebook B. At the prompt, type
ping <IP address of notebook A>
and then press Enter (see the figure below). A “Reply from IP address …” response means the communication was successful. A “Request timed out.” response means the communication failed. In this case, recheck the configuration to make sure the connections are correct.
Testing Method for two or more AWK-3121s
If you have two or more AWK-3121s, you will need a second notebook computer (B) equipped with an Ethernet port. Use the default settings for the first AWK-3121 connected to notebook A and change the second or third AWK-3121 connected to notebook B to Client mode. Then, configure the notebooks and AWK-3121s properly.
After setting up the testing environment, open a DOS window on notebook B. At the prompt, type
ping <IP address of notebook A>
and then press Enter. A “Reply from IP address …” response means the communication was successful. A “Request timed out” response means the communication failed. In this case, recheck the configuration to make sure the connections are correct.
Function Guiding Map
The management functions are categorized in a tree and shown in the left field of the web-based management console. You can efficiently locate the function you need with the following guiding map.
AirWorks AWK-3121 User’s Manual Getting Started
2-5
A quick overview of the AWK-3121’s status
Basic settings for administering the AWK-3121
Essential settings related to establishing a wireless network
Advanced features to support additional network management and secure wired and wireless communication
* These advanced functions are all optional.
Application-oriented device management functions to set up events, traps, and reactions via relay warning, e-mail and SNMP notification
* These functions are all optional.
Real-time status information to monitor wired/wireless network performance, advanced services, and device management functions
Functions to maintain the AWK-3121 and diagnose the network
On-demand functions to support the operations of web-based console management
3
3
Chapter 3 Web Console Configuration
In this chapter, we will explain each web management page of the web-based console configuration. Moxa’s easy-to-use management functions will help you set up your AWK-3121, as well as establish and maintain your wireless network easily.
In this chapter, we cover the following topics:
Configuration by Web Browser Overview Basic Settings Wireless Settings Advanced Settings Auto Warning Setting Status Maintenance Save Configuration Restart Logout
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-2
Configuration by Web Browser
Moxa AWK-3121’s web browser interface provides a convenient way to modify its configuration and access the built-in monitoring and network administration functions. The recommended web browser is Microsoft
®
Internet Explorer 5.5 or 6.0 with JVM (Java Virtual Machine) installed.
NOTE
To use the AWK-3121’s management and monitoring functions from a PC host connected to the same LAN as the AWK-3121, you must make sure that the PC host and the AWK-3121 are on the same logical subnet. Similarly, if the AWK-3121 is configured for other VLAN settings, you must make sure your PC host is on the management VLAN.
The Moxa AWK-3121’s default IP is 192.168.127.253.
Follow the steps below to access the AWK-3121’s web-based console management.
1. Open your web browser (ex. Internet Explorer) and type the AWK-3121’s IP address in the
address field. Then press Enter to establish the connection.
2. The Web Console Login page will open. Enter the password (User Name is set as admin; the
default password is root if a new password has not been set.) and then click Login to continue.
You may need to wait a few moments for the web page download onto your computer. Please note that the Model name and IP address of your AWK-312 are both shown on the title of the web page. This information can help you identify multiple AWK-3121s.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-3
You can use the menu tree on the left side of the window to open the function pages to access each of the AWK-3121’s functions.
In the following paragraphs, we will go through each of the AWK-3121’s management functions in detail. You can also get a quick overview of these functions in the “Function Guiding Map” section of Chapter 2.
NOTE
The model name of the AWK-3121 is shown as AWK-3121-XX where XX indicates the countr y code. The country code represents the AWK-3121 version and which bandwidth it uses. We use AWK-3121-US as an example in the following figures. The country code of model name on the screen may vary if you are using a different version (band) AWK-3121.
NOTE
For security reasons, you will need to log back into the AWK-3121 after the 5-minute time-out.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-4
Overview
The Overview page summarizes the AWK-3121’s current status. The information is categorized into several groups: System info, Device info and 802.11 info.
NOTE
The values for 802.11 info may not show up due to different operation modes. Therefore, Current BSSID and Signal strength are not available in AP mode.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-5
Basic Settings
The Basic Settings group includes the most commonly used settings required by administrators to maintain and control the AWK-3121.
System Info Settings
The System Info items, especially Device name and Device description, are displayed and included on the Overview page, SNMP information, and alarm emails. Setting System Info items makes it easier to identify the different AWK-3121s connected to you r network.
Device name
Setting Description Factory Default
Max. 31 Characters This option is useful for specifying
the role or application of different AWK-3121 units.
AWK-3121_<Serial No. of this AWK-3121>
Device location
Setting Description Factory Default
Max. 31 Characters To specify the location of different
AWK-3121 units.
None
Device description
Setting Description Factory Default
Max. 31 Characters Use this space to record more detailed
description of AWK-3121
None
Device name
Setting Description Factory Default
Max. 31 Characters To provide information about whom
to contact in order to resolve problems. Use this space to record contact information of the person responsible for maintaining this AWK-3121.
None
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-6
Network Settings
The Network Settings configuration allows you to modify the usual TCP/IP network parameters. An explanation of each configuration item is given below.
IP configuration
Setting Description Factory Default
DHCP The AWK-3121’s IP address will be
assigned automatically by the network’ s DH C P server
Static Set up the AWK-3121’s IP address
manually.
Static
IP address
Setting Description Factory Default
AWK-3121’s IP address Identifies the AWK-3121 on a TCP/IP
network.
192.168.127.253
Subnet mask
Setting Description Factory Default
AWK-3121’s subnet mask
Identifies the type of network to which the AWK-3121 is connected (e.g., 255.255.0.0 for a Class B network, or 255.255.255.0 for a Class C network).
255.255.255.0
Gateway
Setting Description Factory Default
AWK-3121’s default gateway
The IP address of the router th at connects the LAN to an outside network.
None
Primary/ Secondary DNS server
Setting Description Factory Default
IP address of Prim ary/ Secondary DNS server
The IP address of the DNS Server used b y your network. A ft er ent eri n g t he DNS Ser ver’s IP address, you can input the AWK-3121’s URL (e.g., http://ap11.abc.com) in your browser’s address field instead of entering the IP address. The Secondary DNS server will be used if the Primary DNS server fails to connect.
None
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-7
Time Settings
The AWK-3121 has a time calibration function based on information from an NTP server or user specified Date and Time information. Functions such as Auto warning can add real-time information to the message.
Current local time shows the AWK-3121’s system time when you open this web page. You can click on the Set Time button to activate the update after setting up the date and time parameters. An “(Updated)” string will appear to indicate that the change is complete. Local time settings will be immediately activated in the system without running Save and Restart.
NOTE
The AWK-3121 has a real time clock (RTC). Users are strongly recommended to upd ate the Local time for the AWK-3121 after initial setup or long-term shutdown, especially when the network does not have an Internet connection for accessing the NTP server or there is no NTP server on the LAN.
Current local time
Setting Description Factory Default
User adjustable time The date and time parameters allow
configuration of the local time with immediate activation.
None (yyyy/mm/dd hh:mm:ss format; 24-hour format.)
Tim e zone
Setting Description Factory Default
User selectable time zone
The time zone setting allows conversion from GMT (Greenwich Mean Time) to local time.
GMT (Greenwich Mean Time)
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-8
ATTENTION
Changing the time zone will automatically adjust the Current local time. You should configure the Time zone before setting the Current local time.
Daylight saving time
Setting Description Factory Default
Enable/ Disable Daylight saving time (also know as
DST or summer time) involves advancing clocks (usually 1 hour) during the summer time to provide an extra hour of daylight in the afternoon.
Disable
When Daylight saving time is enabled, the following parameters can be shown:
y The Starts at parameter allows users to enter the date that daylight saving time begins. y The Stops at parameter allows users to enter the date that daylight saving time ends. y The Time offset parameter indicates how many hours forwar d t he cloc k sh ould be advanced.
Time server 1/ 2
Setting Description Factory Default
The 1st/ 2nd time server IP/Name
IP or Domain address of NTP time server. The 2nd time will be used if the 1st NTP server fails to connect.
None
Query period
Setting Description Factory Default
Query period time (1- 9999 seconds)
This parameter determines how often the time is updated from the NTP server.
600 (seconds)
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-9
Wireless Settings
The essential settings for wireless networks are presented in this function group. Settings must be properly set before establishing your wireless network.
Basic Wireless Settings
The AWK-3121 mainly supports two operational modes that have distinct roles in the wireless network:
y AP/Bridge:
This mode provides both Access Point and Static LAN-to-LAN Bridging functionality. The static LAN-to-LAN bridging function is supported through the Wireless Distribution System (WDS).
y AP Client:
This mode is for Dynamic LAN-to-LAN Bridging or Device-to-LAN. The AP Client automatically establishes bridge links with other APs.
In either mode, the AW K-3121 forwards packets between its Ethernet interface (LAN) and wireless interface (WLAN) for wired hosts on the Ethernet side and wireless host(s) on the wireless side. There are two types of wireless links as specified by the IEEE802.11 standard:
y STA-AP
This type of wireless link is established between an IEEE802.11 Station (STA) and an IEEE802.11 Access Point (AP). An STA is usually a client computer (PC or PDA) with a WLAN network interface card (NIC). The Client mode is actually an STA.
y WDS
This type of wireless link is established between two IEEE802.11 APs. Wireless packets transmitted along the WDS link comply with the IEEE802.11 WDS (Wireless Distribution System) format at the link layer. You can refer to “Wireless Distribution System (WDS)” in Chapter 5 for more details. Be reminded that WPA/WPA2 CANNOT be supp ort ed in WDS.
To establish a static bridge link based on the WDS, the APs at both end of the WDS link must be configured manually with each other's MAC addresses. To establish a dynamic bridge link between an AP and a Client, both devices must be configured with the same, channel, and security settings (see “WLAN Security Settings”). Moreover, the same SSID is also needed if a client will roam along the APs in Bridge mode. The AP Client automatically scans for any AP that is using the matched SSID and establishes a bridge link with the scanned AP.
When the AWK-3121 is configured to be in Client mode, it can be used as an Ethernet-to-wireless (or LAN-to-WLAN) network adapter. For example, a notebook computer equipped with an Ethernet adapter, but n o wirel e ss card, can be connected to this device with an Ethernet cable for wireless connectivity to another AP.
NOTE
Although it is more convenient to use dynamic bridging, there is a limitation — the AP Client can only transmit IP-based packets between its wireless interface (WLAN) and Ethernet interface (LAN); other types of traffic (such as IPX and AppleTalk) are not forwarded.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-10
The following figure shows the Basic Wireless Settings page. The parameters and options are described as follow:
Wireless enable
Setting Description Factory Default
Enable/Disable The RF (Radio Frequency) module
can be manually turned on or off.
This function can be available in AP operation mode only.
Enable
Operation mode
Setting Description Factory Default
AP AWK-3121 plays a role of wireless
AP/ Bridge.
Client AWK-3121 plays a role of wireless
AP Client.
AP
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-11
NOTE
When you switch to Client mode, you can find an additional Site Survey button on this page. It can support site survey and pop up a dialog box listing the information of available APs, as shown in the following figure. You can click on the SSID of an entity and bring the value of its SSID onto the SSID field of the Basic Wireless Settings page. Clicking on the Refresh button will re-scan and update the table.
NOTE
If the Gateway field in Basic Settings Æ Network Settings is empty, a warning message will appear, reminding you to set the default gateway when Client mode is enabled. You can ignore this message if you are only planning a local network and no packet will be sent outside the network.
RF type
Setting Description Factory Default
A Supports IEEE802.11a standard only B Supports IEEE802.11b standard only G Supports IEEE802.11g standard only B/G Mixed Supports both of IEEE802.11b/g
standards, but 802.11g can be slowed down when 802.11b clients are on the network
B/G Mixed
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-12
Channel (for AP mode only)
Setting Description Factory Default
Available channels vary with RF type
AWK-3121 plays a role of wireless AP.
6 (in B/G Mixed mode)
SSID
Setting Description Factory Default
Max. 31 Characters The SSID of a client and the SSID of
the AP must be identical for them to communicate with each other.
MOXA
SSID broadcast (for AP mode only)
Setting Description Factory Default
Enable/ Disable SSID can be broadcast or not. Enable
NOTE
The AWK-3121-JP (for Japanese frequency bands) only connects SSID-hidden APs in all IEEE802.11a channels and IEEE802.11g channel 1 to 11. The AWK-3121-EU (for European frequency bands) only connects SSID-hidden APs in all IEEE802.11b/g channels.
WDS (for AP mode only)
Setting Description Factory Default
Enable/ Disable AWK-3121 supports WDS or not. Disable
NOTE
When WDS is enabled, you can choose to use a pure point-to-point WDS link by disabling AP functionality.
The AWK-3121 provides 8 entities for WDS settings and can support up to 8 WDS links to other APs or wireless bridges. The list appears when WDS Enable is checked. Enter the MAC address to set up a WDS link. Remember to activate a WDS link by checking the Active check box.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-13
WLAN Security Settings
The AWK-3121 provides four standardized wireless security modes: Open, WEP (Wired Equivalent Privacy), WPA (Wi-Fi Protected Access) and WP A2. Seve ral types of security models are available in AWK-3121 by selecting Security mode and WPA type:
y Open: No authentication, no data encryption. y WEP: Static WEP (Wired Equivalent Privacy) keys must be manually configured. y WPA/WPA2-Personal: also known as WPA/WPA2-PSK. You need to specify the Pre-Shared
Key in the Passphrase field, which will be used by the TKIP or AES engine as a master key to generate keys that actually encrypt outgoing packets and decrypt incoming packets.
y WPA/WPA2-Enterprise: also called WPA/WPA2-EAP (Extensible Authentication Protocol).
In addition to device-based authentication, WPA/WPA2-Enterprise enables user-based authentication via IEEE802.1X. The AWK-3121 can support three EAP methods: EAP-TLS, EAP-TTLS, and EAP-PEAP.
Security mode
Setting Description Factory Default
Open No authentication WEP Static WEP is used WPA* WPA is used WPA2* Fully supports IEEE802.11i with
“TKIP/AES + 802.1X”
Open
* WPA and WPA2 cannot be supported in WDS (Bridge) mode.
Open
For security reasons, it is highly recommended that the security mode should be set to the options other than Open System. When the security mode is set to Open System, no authentication or data encryption will be performed.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-14
WEP
According to the IEEE802.11 standard, WEP can be used for authentication and data encryption (confidentiality). Shared (or Shared Key) authentication type is used if WEP authentication and data encryption are both needed. Normally, Open (or Open System) authentication type is often used when WEP data encryption is run with authentication.
When WEP is enabled as a security mode, the length of a key (so-called WEP seed) can be specified as 64/128 bits, which is actually a 40/104-bit secret key with a 24-bit initialization vector. The AWK-3121 provides 4 entities of WEP key settings that can be selected to use with Key index. The selected key setting specifies the key to be used as a send-key for encrypting traffic from the AP side to the wireless client side. All 4 WEP keys are used as receive-keys to decrypt traffic from the wireless client side to the AP side.
The WEP key can be prese nted in two Key type, HEX and ASCII. Each ASCII character has 8 bits, so a 40-bit (or 64-bit) WEP key contains 5 characters, and a 104-bit (or 128-bit) key has 13 characters. In hex, each character uses 4 bits, so a 40-bit key has 10 hex characters, and a 128-bit key has 26 characters.
Authentication type
Setting Description Factory Default
Open Data encryption is enabled, but no
authentication
Shared Data encryption and authentication
are both enabled.
Open
Key type
Setting Description Factory Default
HEX Specifies WEP keys in hex-decimal
number form
ASCII Specifies WEP keys in ASCII form
HEX
Key length
Setting Description Factory Default
64 bits Uses 40-bit secret keys with 24-bit
initialization vector
128 bits Uses 104-bit secret key with 24-bit
initialization vector
64 bits
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-15
Key index
Setting Description Factory Default
1-4 Specifies which WEP key is used Open
WEP key 1-4
Setting Description Factory Default
ASCII type: 64 bits: 5 chars 128 bits: 13chars HEX type: 64 bits: 10 hex chars 128 bits: 26 hex chars
A string that can be used as a WEP seed for RC4 encryption engine.
None
WPA/WPA2-Personal
WPA (Wi-Fi Protected Access) and WPA2 are significantly improved encryption methods of WEP. WPA is a security standard based on 802.11i draft 3, while WPA2 is based on the fully ratified version of 802.11i. The initial vector is transmitted, encrypted, and enhanced with its 48 bits, twice as long as WEP. The key is regularly changed so that true session is secured.
Even though AES encryption is only included in the WPA2 standard, it is widely available in the WPA security mode of some wireless APs and clients as well. Th e AWK-3121 also supports AES algorithms in WPA and WPA2 for better compatibility.
Personal versions of WPA/WPA2, also know as WPA/WPA-PSK (Pre-Shared Key), provides a simple way of encrypting a wireless connection for high confidentiality. A Passphrase is used as a basis for encryption methods (or cipher types) in a WLAN connection. The passphrases should be complex and as long as possible. The number of ASCII characters of the Passphrase must be at least 8 and can go up to 63. For security reason, this passphrase should be disclosed to the relevant users only and changed regularly.
WPA type
Setting Description Factory Default
Personal Provides Pre-Shared Key-enabled
WPA and WPA2
Enterprise Provides enterprise-level security
for WPA and WP A 2
Personal
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-16
Encryption method
Setting Description Factory Default
TKIP Temporal Key Integrity Protocol is
enabled
AES Advance Encryption System is
enabled
Mixed* Provides TKIP broadcast key and
TKIP+AES unicast key for some legacy AP clients. This option is rarely used. *This option is
available in AP mode only, and cannot support AES-enabled clients.
TKIP
Passphrase
Setting Description Factory Default
8 – 63 characters Master key to generate keys for
encryption and decryption
None
Key renewal (for AP mode only)
Setting Description Factory Default
60 – 86400 seconds (1 minute to 1 year)
Specifies the time period of group key renewal
3600 (seconds)
NOTE
The value for key renewal instructs the wireless AP how often it should change the encryption keys. Usually the security level will be higher if you set this value shorter so that the encryption keys are changed more often. Default value is 3600 seconds (6 minutes). Longer time periods can be considered if traffic is not so busy.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-17
WPA/WPA2-Enterprise (for AP mode)
By selecting WPA typ e as Enterprise, you can use EAP (Extensible Authentication Protocol), a framework authentication protocol used by 802.1 X t o pro vi de netw or k a uthentication. In these Enterprise-level security modes, a back-end RADIUS (Remote Authentication Dial-In User Service) server is needed if IEEE 802.1X functionality is enabled in WPA /WPA2. The IEEE
802.1X protocol also offers the possibility of carrying out an efficient connection authentication in a large-scaled network. It is not necessary to exchange keys or passphrases.
WPA type
Setting Description Factory Default
Personal Provides Pre-Shared Key-enabled
WPA and WPA2
Enterprise Provides enterprise-level security
for WPA and WP A 2
Personal
Encryption method
Setting Description Factory Default
TKIP Temporal Key Integrity Protocol is
enabled
AES Advance Encryption System is
enabled
Mixed* Provides TKIP broadcast key and
TKIP+AES unicast key for some legacy AP clients. This option is rarely used. *This option is
available in AP mode only, and cannot support AES-enabled clients.
TKIP
Primary/ Secondary RADIUS server IP
Setting Description Factory Default
The IP address of RADIUS server
Specifies the delegated RADIUS server for EAP
None
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-18
Primary/ Secondary RADIUS port
Setting Description Factory Default
Port number Specifies the port number of the
delegated RADIUS server
1812
Primary/ Secondary RADIUS shared key
Setting Description Factory Default
Max. 31 characters The secret key shared between AP
and RADIUS server
None
Key renewal
Setting Description Factory Default
60 – 86400 seconds (1 minute to 1 year)
Specifies the time period of group key renewal
3600 (seconds)
WPA/WPA2-Enterprise (for Client mode)
In a client role, the AWK-3121 can support th ree EAP methods (or EAP protocols): EAP-TLS, EAP-TTLS, and EAP-PEAP, corresponding to WPA/WPA-Enterprise settings on the AP side.
Encryption method
Setting Description Factory Default
TKIP Temporal Key Integrity Protocol is
enabled
AES Advance Encryption System is
enabled
TKIP
EAP Protocol
Setting Description Factory Default
TLS Specifies Transport Layer Security
protocol
TTLS Specifies Tunneled Transport
Layer Security
PEAP Specifies Protected Extensible
Authentication Protocol, or Protected EAP
TLS
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-19
Before choosing the EAP protocol for your WPA/WPA2-Enterpise settings on the client end, please contact the network administrator to make sure the system supports the protocol on the AP end. Detailed information on these three popular EAP protocols is presented in the following sections:
EAP-TLS
TLS is the standards-based successor to the Secure Socket Layer (SSL). It can establish a trusted communication channel over a distrusted network. TLS provides mutual authentication through certificate exchange. EAP-TLS is also secure to use. You are required to submit a digital certificate to the authentication server for validation, but the authentication server must also supply a certificate.
You can use Basic Wireless Settings Æ WLAN Certificate Settings to import your WLAN certificate and enable EAP-TLS on the client end.
You can check the current certificate status in Current Status if it is available.
Certificate issued to: shows the certificate user Certificate issued by: shows the certificate issuer Certificate expiration date: indicates when the certificate has expired
EAP-TTLS
It is usually much easier to re-use existing authentication systems, such as a Windows domain or Active Directory, LDAP directory, or Kerberos realm, rather than creating a parallel authentication system. As a result, TTLS (Tunneled TLS) and PEAP (Protected EAP) are used to support the use of so-called “legacy authentication methods.”
TTLS and PEAP work in a similar way. First, they establish a TLS tunnel, like EAP-TLS, and validate whether the network is trustworthy with digital certificates on the authentication server. This step is run to establish a tunnel that protects the next step (or “inner” authentication) so it is sometimes referred to as the “outer” authentication. Then the TLS tunnel is used to encrypt an older authentication protocol that authenticates the user for the network.
As you can see, digital certificates are still needed for the outer authentication in a simplified form. Only a small number of certificates are required, which can be generated by a small certificate authority. Certificate reduction makes TTLS and PEAP much more popular than EAP-TLS.
The AWK-3121 provides some non-cryptographic EAP methods including PAP, CHAP, MS-CHAP, and MS-CHAP-V2. These EAP methods are not recommended for direct use on wireless networks. However, they may be useful as inner authentication methods with TTLS or PEAP.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-20
Because the inner and outer authentications can use distinct user names in TTLS and PEAP, you can use an anonymous user name for the outer authentication, while the true user na me is shown only through the encrypted channel. Remember, not all client software supports anonymous altercation. Confirm this with the network administrator before you enable identity hiding in TTLS and PEAP.
TTL Inner Authentication
Setting Description Factory Default
PAP Password Authentication Protocol
is used
CHAP Challenge Handshake
Authentication Protocol is used
MS-CHAP Microsoft CHAP is used MS-CHAP-V2 Microsoft CHAP version 2 is used
MS-CHAP-V2
Anonymous
Setting Description Factory Default
Max. 31 characters A di st i nct nam e used fo r o ut er
authentication
None
User name & Password
Setting Description Factory Default
User name and password used in
inner authentication
None
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-21
PEAP
There are a few differences in the inner authentication procedures for TTLS and PEAP. TTLS uses the encrypted channel to exchange attribute-value pairs (AVPs), while PEAP uses the encrypted channel to start a second EAP exchange inside of the tunnel. The AWK-3121 provides MS-CHAP-V2 merely as an EAP method for inner authentication.
Inner EAP protocol
Setting Description Factory Default
MS-CHAP-V2 Microsoft CHAP version 2 is used MS-CHAP-V2
Anonymous
Setting Description Factory Default
Max. 31 characters A di st i nct nam e used fo r o ut er
authentication
None
User name & Password
Setting Description Factory Default
User name and password used in
inner authentication
None
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-22
Advanced Wireless Settings
Additional wireless-related parameters are presented in this section to help you set up your wireless network in detail.
Transmission Rate
Setting Description Factory Default
Auto AWK-3121 will sense and adjust the
data rate automatically
Available rates User can manually select a target
transmission data rate
Auto
Transmission Power
Setting Description Factory Default
Auto
Specifies wireless signal coverage by automatically selecting the strength of Tx power
Full Equivalent to 100% of maximum Tx power High Equivalent to 75% of maximum Tx power
Medium Equivalent to 50% of maximum Tx power Low Equivalent to 25% of maximum Tx power
Full
Beacon Interval (for AP mode only)
Setting Description Factory Default
Beacon Interval (40-1000 ms)
This value indicates the frequency interval of the beacon
100 (ms)
DTIM Interval (for AP mode only)
Setting Description Factory Default
Data Beacon Rate (1-15) This value indicates how often the
AWK-3121 sends out a Delivery Traffic Indication Message
1
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-23
Fragment threshold
Setting Description Factory Default
Fragment Length (256-2346)
This parameter specifies the maximum size a data packet before splitting and creating another new packet
2346
RTS threshold
Setting Description Factory Default
RTS/CTS T hreshold (256-2346)
This setting determines how large a packet can be before the Access Point coordinates transmission and reception to ensure efficient communication
2346
NOTE
You can refer to the related glossaries in Chapter 5 for more detailed information about the above-mentioned settings. By setting these parameters properly, you can better tune the performance of your wireless network.
Transmission distance
Setting Description Factory Default
Distance or max. range for transmission (500-10000m)
The distance specifies the transmission distance or max. range between two AWK devices. This parameter should be set properly, especially for long-distance communication.
500
Transmission enhancement
Setting Description Factory Default
Enable/Disable This setting can enhance communication by
strengthening the AWK-3121’s transmission power. It is quite useful for long-distance transmission or countering environmental interference. The user must
carefully evaluate and measure the transmission power of the entire system to make sure that it is still below the regulative limit. Note, too, that RF type
802.11a mode cannot be used if this function is enabled.
Disable
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-24
NOTE
Make sure the same Transmission distance parameters are set in both AP and Client sides, and both Bridges. When this parameter is more than 500, an optimal algorithm will be enabled to support long-distance transmission.
Transmission enhancement is also recommended to enable communication at both ends when long-distance transmission is required. A high-gain antenna installed at a fixed antenna connector can also improve performance. (Select Antenna at MAIN or AUX.)
Antenna
Setting Description Factory Default
Auto
The AWK-3121 uses two antennas (MAIN and AUX) and enables the diversity function for reducing multipath effect.
MAIN
Diversity function is disabled. Only MAIN antenna is in use.
AUX
Diversity function is disabled. Only AUX antenna is in use.
Auto
EAPOL Version
Setting Description Factory Default
1 EAPOL version 1 was standardized in the 2001
version of 802.1X, which is much more commonly implemented.
2 EAPOL version 2 was specified in
802.1X-2004.
1
Turbo Roaming (for Client mode only)
Setting Description Factory Default
Enable/ Disable Moxa’s Turbo Roaming can enable rapid
handover when the AWK-3121, as a client, roams among a group of APs.
Disable
When Turbo Roaming is enabled, RF type and Scan channels will be shown as follows. RF type shows the current RF type, which this client is using now. You can set up Scan channels for the APs among which this client is going to roam. There are three Scan channels available. Please note that the Scan channels may need to be modified when the RF type is changed. (For example, channel 36 is not available in B, G or B/G Mix mode.)
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-25
WLAN Certification Settings (for EAP-TLS in Client mode only)
When EAP-TLS is used, a WLAN Certificate will be required at the client end to support WPA/WPA2-Enterprise. The AWK-3121 can support the PKCS #12, also known as Personal Information Exchange Syntax Standard, certificate formats that define file formats commonly used to store private keys with accompanying public key certificates, protected with a password-based symmetric key.
Current St atus displays information for the current WLAN certificate, which has been imported into the AWK-3121. Nothing will be shown if no certificate is available.
Certificate issued to: shows the certificate user Certificate issued by: shows the certificate issuer Certificate expiration date: indicates when the certificate has expired
You can import a new WLAN certificate in Import WLAN Certificate by following these steps in order:
1. Input the corresponding password (or key) in the Certificate private password field. Then
click Submit to set the password.
2. You can see the password displayed in the Certificate private password field. Then click on
the Browse button in Select certificate/key file and select the certificate file.
3. Click Upload Certificate File to import the certificate file. If it succeeds, you can see the
information uploaded in Current Certificate. If it fails, you may need to return to step 1 to set the password correctly and then import the certificate file again.
NOTE
The WLAN certificate will remain after the AWK-3121 reboots. Even though it is expired, it can still be seen on Current Certificate.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-26
Advanced Settings
Several advanced functions are available to increase the functionality of your AWK-3121 and wireless network system. The DHCP server helps you deploy wireless clients efficiently. Packet filters provide security mechanisms, such as firewalls, in different network layers. Moreover, the AWK-3121 can support STP/RSTP protocol to increase the reliability across the entire network. In additional, SNMP support can ease the network management via SNMP protocols.
DHCP Server (for AP mode only)
DHCP (Dynamic Host Configuration Protocol) is a networking protocol that allows administrators to assign temporary IP addresses to network computers by “leasing” an IP address to a user for a limited amount of time, instead of assigning permanent IP addresses.
The AWK-3121 can act as a simplified DHCP server and easily assign IP addresses to your wireless clients by responding to the DHCP requests from the client ends. The IP-related parameters you set on this page will also be sent to the client.
You can also assign a static IP address to a specific client by entering its MAC address. The AWK-3121 provides a Static DHCP mapping list with up to 16 entities. Be reminded to check the Active check box for each entity to activate the setting.
You can check the IP assignment status under Status Æ DHCP Client List.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-27
DHCP server (AP only)
Setting Description Factory Default
Enable Enables AWK-3121 as a DH CP server Disable Disable DHCP server function
Disable
Default gateway
Setting Description Factory Default
IP address of a default gateway
The IP address of the router that connects to an outside network
None
Subnet mask
Setting Description Factory Default
subnet mask Identifies the type of sub-network (e.g.,
255.255.0.0 for a Class B network, or
255.255.255.0 for a Class C network)
None
Primary/ Secondary DNS server
Setting Description Factory Default
IP address of Prim ary/ Secondary DNS server
The IP address of the DNS Server used by your network. After entering the DNS Server’s IP address, you can use URL as well. The Secondary DNS server will be used if the Primary DNS server fails to connect.
None
Start IP address
Setting Description Factory Default
IP address Indicates the IP address which AWK-3121
can start assigning
None
Maximum number of users
Setting Description Factory Default
1 – 999 Specifies how many IP address can be
assigned continuously
None
Client lease time
Setting Description Factory Default
1 – 10 days The lease time for which an IP address is
assigned. The IP address may go expired after the lease time is reached.
10 (days)
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-28
Packet Filters
The AWK-3121 includes various filters for IP-based packets going thr ough LAN and WLAN interfaces. You can set these filters as a firewall to help enhance network security.
MAC Filter
The AWK-3121’s MAC filter is a policy-based filter that can allow or filter out IP-based packets with specified MAC addresses. The AWK-3121 provides 8 entities for setting MAC addresses in your filtering policy. Remember to check the Active check box for each entity to activate the setting.
Enable
Setting Description Factory Default
Enable Enables MAC filter Disable Disables MAC filter
Disable
Policy
Setting Description Factory Default
Accept Only the packets fitting the entities on list
can be allowed.
Drop Any packet fitting the entities on list will be
denied.
Drop
ATTENTION
Be careful when you enable the filter function:
Drop + “no entity on list is activated” = all packets are allowed Accept + “no entity on list is activated” = all packets are denied
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-29
IP Protocol Filter
The AWK-3121’s IP protocol filter is a policy-based filter that can allow or filter out IP-based packets with specified IP protocol and source/destination IP addresses.
The AWK-3121 provides 8 entities for setting IP protocol and source/destination IP addresses in your filtering policy. Four IP protocols are available: All, ICMP, TCP, and UDP. You must specify either the Source IP or the Destination IP. By combining IP addresses and netmasks, you can specify a single IP address or a range of IP addresses to accept or drop. For example, “IP address 192.168.1.1 and netmask 255.255.255.255” refers to the sole IP address 192.168.1.1. “IP address 192.168.1.1 and netmask 255.255.255.0” refers to the range of IP addresses from
192.168.1.1 to 192.168.255. Remember to check the Active check box for each entity to activate the setting.
Enable
Setting Description Factory Default
Enable Enables IP protocol filter Disable Disables IP protocol filter
Disable
Policy
Setting Description Factory Default
Accept Only the packets fitting the entities on the list
can be allowed
Drop Any packet fitting the entities on the list will
be denied
Drop
ATTENTION
Be careful when you enable the filter function:
Drop + “no entity on list is activated” = all packets are allowed. Accept + “no entity on list is activated” = all packets are denied.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-30
TCP/UDP Port Filter
The AWK-3121’s TCP/UDP port filter is a policy-based filter that can allow or filter out TCP/UDP-based packets with a specified source or destination port.
The AWK-3121 provides 8 entities for setting the range of source/destination ports of a specific protocol. In addition to selecting TCP or UDP protocol, you can set either the sou rce port, destination port, or both. The end port can be left empty if only a single port is specified. Of course, the end port cannot be larger then the start port.
The Application name is a text string that describes the corresponding entity with up to 31 characters. Remember to check the Active check box for each entity to activate the setting.
Enable
Setting Description Factory Default
Enable
Enables TCP/UDP port filter
Disable
Disables TCP/UDP port filter
Disable
Policy
Setting Description Factory Default
Accept
Only the packets fitting the entities on list can be allowed.
Drop
Any packet fitting the entities on list will be denied.
Drop
ATTENTION
Be careful when you enable the filter function:
Drop + “no entity on list is activated” = all packets are allowed Accept + “no entity on list is activated” = all packets are denied
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-31
RSTP Settings (for AP mode only)
AWK-3121 supports IEEE802.1D Spanning Tree Protocol and IEEE802.1w Rap id STP standards. In addition to eliminating unexpected path looping, STP/RSTP can provide a backup path recovery if a wired/ wireless path fails accidentally. The reliability and availability can increase because this fail-over function.
AWK-3121’s STP/RSTP feature is disabled by default. To be completely effective, you must enable RSTP/STP on every AWK-3121 connected to your network. If AWK-3121 plays a Client role, which is connected to a device (PLC, RTU, etc.) as opposed to network switch equipment, it is not necessary to enable STP/RSTP. The reason is that it will cause unnecessary negotiation. AWK-3121s support STP/RSTP in AP mode (including WDS) only.
The following figures indicate which Spanning Tree Prot o col pa rameters can be configured. A more detailed explanation of each parameter is given below the figure.
RSTP status
This field will appear only when selected to operate STP/RSTP. It indicates whether this AWK-3121 is the Root of the Spanning Tr ee (the root is determined automatically) or not.
Bridge priority
Setting Description Factory Default
Numerical value selected by user
You can increase the bridge priority by selecting a lower number. A higher brid ge priority brings a greater chance of being established as the root of the Spanning Tree topology.
32768
Hello time
Setting Description Factory Default
Numerical value input by user (1 – 10 seconds)
The root of the Spanning Tree topology periodically sends out a “hello” message to other devices on the network to check if the topology is healthy. Hello time indicates how often the root sends hello messages.
2 (seconds)
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-32
Forwarding delay
Setting Description Factory Default
Numerical value input by user (4 – 30 seconds)
The amount of time this device waits before checking to see if it should change to a different topology.
15 (seconds)
Max. age
Setting Description Factory Default
Numerical value input by user (6 – 40 seconds)
As a non-root role, if the device has not received a hello message from the root longer than Max. age, it will reconfigure itself as a root. Once two or more devices on the network are recognized as a root, the devices will renegotiate to set up a new Spanning Tree topology.
20 (seconds)
The AWK-3121 comes with 10 “ports” for RSTP settings. Numbers 3-10 (WDS1-WDS8) are available only when WDS is enabled in AP mode.
Enable RSTP
Setting Description Factory Default
Enable/ disable Enables or disables the port as a node on th e
Spanning Tree topology.
Disable (unchecked)
Port priority
Setting Description Factory Default
Numerical value selected by user
Increase this port’s priority as a node on the Spanning Tree topology by inputting a lower number.
128
Port cost
Setting Description Factory Default
Enable/ Disable Input a higher cost to indicate that this port is
less suitable as a node for the Spanning Tree topology
2000000
Edge port
Setting Description Factory Default
Checked/ unchecked Sets a port, which no BPDU expectedly goes
through, as an edge port
unchecked, except AP port
NOTE
We recommend you set an edge port for the port, which is connected to a non-STP/RSTP sub-network or an end device (PLC, RTU, etc.) as opposed to network equipment. This can prevent unnecessary waiting and negotiation of STP/RSTP protocol, and accelerate system initialization. When an edge port receives BPDUs, it can still function as an STP/RSTP port and start negotiation.
Setting an edge port is different from disabling STP/RSTP on a port. If you disable STP/RSTP, a port will not deal with STP/RSTP BPDUs at all.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-33
Port Status
Port Status indicates the current Spanning Tree status of this port. Use Forwarding for normal transmission, or Blocking to block transmission.
SNMP Agent
The AWK-3121 supports SNMP V1/V2c/V3. SNMP V1 and SNMP V2c use a co mmunity string match for authentication, which means that SNMP servers access all objects with read-only or read/write permissions using the community string public/private (default value). SNMP V3, which requires you to select an authentication level of MD5 or SHA, is the most secure protocol. You can also enable data encryption to enhance data security.
The AWK-3121’s MIB can be found in the software CD and supports read ing the attributes via SNMP. (Only get method is supported.)
SNMP security modes and security levels supported by the AWK-3121 are shown in the following table. Select the security mode and level that will be used to communicate between the SNMP agent and manager.
Protocol
Version
Setting on
UI web page
Authentication
Type
Data
Encryption
Method
V1, V2c Read Community
Community
string
No Use a community string match for
authentication
SNMP
V1, V2c
V1, V2c Write/Read Community
Community
string
No Use a community string match for
authentication
No-Auth No
No
Use account with admin or user to access objects
MD5 or SHA Authentication
based on MD5
or SHA
No Provides authentication based on
HMAC-MD5, or HMAC-SHA algorithms. 8-character passwords are the minimum requirement for authentication.
SNMP V3
MD5 or SHA Authentication
based on MD5
or SHA
Data encryption
key
Provides authentication based on HMAC-MD5 or HMAC-SHA algorithms, and data encryption key. 8-character passwords and a data encryption key are the minimum requirements for authentication and encryption.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-34
The following parameters can be configured on the SNMP Agent page. A more detailed explanation of each parameter is given below the following figure.
Enable
Setting Description Factory Default
Enable Enables SNMP Agent Disable Disables SNMP Agent
Disable
Read community (for V1, V2c)
Setting Description Factory Default
V1, V2c Read Community
Use a community string match with a maximum of 31 characters for authentication. This means that the SNMP agent can access all objects with read-only permissions using this community string.
public
Write community (for V1, V2c)
Setting Description Factory Default
V1, V2c Read /Write Community
Use a community string match with a maximum of 31 characters for authentication. This means that the SNMP agent can accesses all objects with read/write permissions using this community string.
private
SNMP agent version
Setting Description Factory Default
V1, V2c, V3, or V1, V2c, or V3 only
Select the SNMP protocol version used to manage the switch.
V1, V2c
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-35
Admin auth type (for V1, V2c, V3, and V3 only)
Setting Description Factory Default
No Auth Use admin account to access objects. No
authentication
MD5 Provide authentication based on the HMAC-MD5
algorithms. 8-character passwords are the minimum requirement for authentication.
SHA Provides authentication based on
HMAC-SHA algorithms. 8-character passwords are the minimum requirement for authentication.
No Auth
Admin private key (for V1, V2c, V3, and V3 only)
Setting Description Factory Default
Disable No data encryption DES DES-based data encryption AES AES-based data encryption
Disable
Private key
A data encryption key is the minimum requirement for data encryption (maximum of 63 characters)
Private MIB Information Device Object ID Also know as OID. This is the AWK-3121’s enterprise value. It is fixed.
Auto Warning Settings
Since industrial-grade devices are often located at the endpoints of a system, these devices will not always know what is happening elsewhere on the network. This means that these devices, including wireless APs or clients, mu st provide system maintainers with real-time alarm messages. Even when system administrators are out of the control room for an extended period, they can still be informed of the status of devices almost instantaneously when exceptions occur.
In addition to logging these events, the AWK-3121 supports different approaches to warn engineers automatically, such as SNMP trap, e-mail, and relay output. It also supports two digital inputs to integrate sensors into your system to automate alarms by email and relay output.
System Log
System Log Event Types
Detail information for grouped events is shown in the following table. You can check the box for Enable log to enable the grouped events. All default values are enabled (checked). The log for system events can be seen in Status Æ System Log.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-36
System-related events Event is triggered when…
System restart (warm start)
The AWK-3121 is rebooted, such as when its settings are changed (IP address, subnet mask, etc.).
Network-related events Event is triggered when…
LAN link on The LAN port is connected to a device or network. LAN link off
The port is disconnected (e.g., the cable is pulled out, or the opposing device shuts down).
Client joined/ left
(for AP mode)
A wireless client is associated or disassociated.
WLAN connected to AP
(for Client mode)
The AWK-3121 is associated with an AP.
WLAN disconnected
(for Client mode)
The AWK-3121 is disassociated from an AP.
Config-related events Event is triggered when…
Configuration Changed A configuration item has been changed. Configuration file import via Web
Console
The configuration file is imported to the AWK-3121.
Console authentication failure An incorrect password is entered. Firmware upgraded The AWK-3121’s firmware is updated.
Power events Event is triggered when…
Power 1/2 transition (On -> Off) The AWK-3121 is powered down in PWR1/2. PoE transition (On -> Off) The AWK-3121 is powered down in PoE. Power 1/2 transition (Off -> On) The AWK-3121 is powered via PWR1/2. PoE transition (Off -> On) The AWK-3121 is powered via PoE.
DI events Event is triggered when…
DI1/2 transition (On -> Off) Digital Input 1/2 is triggered by on to off transition DI1/2 transition (Off -> On) Digital Input 1/2 is triggered by off to on transition
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-37
Syslog
This function provides the event logs for the Syslog server. The function supports up to three configurable Syslog servers and Syslog server UDP port numbers. When an event occurs, the event will be sent as a Syslog UDP packet to the specified Syslog servers.
Syslog Event Types
Detail information for the grouped events is shown in the following table. You can check th e box for Enable log to enable the grouped events. All default values are enabled (checked). Details for each event group can be found on the “System log Event Types” table on page 3-31.
Syslog Server Settings
You can configure the parameters for your Syslog servers in this page.
Syslog server 1/ 2/ 3
Setting Description Factory Default
IP address Enter the IP address of the 1st/ 2nd/ 3rd
Syslog Server
None
Syslog port
Setting Description Factory Default
Port destination (1 to 65535)
Enter the UDP port of the corr e sp on di n g Syslog server
514
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-38
E-mail
E-mail Event Types
Check the box for Active to enable the event items. All default values are deactivated (unchecked). Details for each event item can be found on the “System log Event Types” table on page 3-31.
E-mail Server Settings
You can set up to 4 e-mail addresses to receive alarm emails from the AWK-3121. The following parameters can be configured on the E-mail Server Settings page. In addition, a Send Test Mail button can be used to test whether th e Mail server and e-mail addresses work well. More detailed explanations about these parameters are given after the following figure.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-39
Mail server (SMTP)
Setting Description Factory Default
IP address The IP Address of your email server. None
User name & Password
Setting Description Factory Default
User name and password used in the SMTP
server
None
From e-mail address
Setting Description Factory Default
Max. 63 characters Enter the administrator’s e-mail address
which will be shown in the “From” field of a warning e-mail.
None
To E-mail address 1/ 2/ 3/ 4
Setting Description Factory Default
Max. 63 characters Enter the receivers’ e-mail addresses. None
Relay
The AWK-3121 has one relay output, which consists of 2 terminal block contacts on the AW K-3121’s top panel. These relay contacts are used to indicate user-configured events and system failure.
The two wires attached to the relay contacts form an open circuit when a user-configured event is triggered. If a user-configured event does not occur, the relay circuit will remain closed. For safety reasons, the relay circuit is kept open when the AWK-3121 is not powered.
Relay Event Types
You can check the box for Active to enable the event items. All default values are deactivated (unchecked). Details for each event item can be found in the “System log Event Types” table on page 3-31.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-40
Trap
Traps can be used to signal abnormal conditions (notifications) to a management station. This trap-driven notification can make your network more efficient.
Because a management station usually takes care of a large number of devices that have a large number of objects, it will be overloading for the management station to poll or send requests to query every object on every device. It would be better if the managed device agent could notify the management station by sending a message known as a trap for the event.
Trap Event Types
SNMP Trap Receiver Settings
SNMP traps are defined in SMIv1 MIBs (SNMPv1) and SMIv2 MIBs (SNMPv2c). The two styles are basically equivalent, and it is possible to convert between the two. You can set the parameters for SNMP trap receivers through the web page.
1st / 2nd Trap versi on
Setting Description Factory Default
V1 SNMP trap defined in SNMPv1 V2 SNMP trap defined in SNMPv2
V1
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-41
1st / 2nd Trap server IP/name
Setting Description Factory Default
IP address or host name Enter the IP address or name of the
trap server used by your network.
None
1st / 2nd Trap community
Setting Description Factory Default
Max. 31 characters
Use a community string match with a maximum of 31 characters for authentication.
alert
Status
Associated Client List (for AP mode only)
Associated Client List shows all the clients that are currently associated to a particular AWK-3121. You can click Select all to select all the content in the list for further editing. You can click Refresh to refresh the list.
DHCP Client List (for AP mode only)
The DHCP Client List shows all the clients that require and have successfully received IP assignments. You can click the Refresh button to refresh the list.
You can press Select all button to select all content in the list for further editing.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-42
System Log
Triggered events are recorded in System Log. You can export the log contents to an available viewer by clicking Export Log. You can use the Clear Log button to clear the log contents and the Refresh button to refresh the log.
Relay Status
The status of user-configurable events can be found under Relay Status. The status will refresh every 5 seconds if the Auto refresh box is checked.
If an event is triggered, it will be noted on this list. System administrators can click Acknowledge Event when he has acknowledged the event and addressed it.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-43
DI and Power Status
The status of power inputs and digital inputs is shown on this web page. The status will refresh every 5 seconds if the Auto refresh box is checked.
Wireless Status
The status for 802.11 info parameters, such as Operation mode and Channel, are shown on the Wireless Status page. The status will refresh every 5 seconds if the Auto refresh box is checked.
Certain values for 802.11 info may not show up due to different operation modes. As a result, Current BSSID and Signal strength are not available in AP mode.
It is helpful to use the continuously updated information on this page, such as Signal strength, to monitor the signal strength of the AWK-3121 in Client mode.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-44
Maintenance
Maintenance functions provide the administrator with tools to manage the AWK-3121 and wired/wireless networks.
Console Settings
You can enable or disable access permission for the following consoles: HTTP, HTTPS, Telnet and SSH connections. For more security, we recommend you only allow access to the two secured consoles, HTTPS and SSH.
Ping
Ping helps to diagnose the integrity of wired or wireless networks. By inputting a node’s IP address in the Destination field, you can use the ping command to make sure it exists and whether or not the access path is available.
If the node and access path are available, you will see that all packets were successfully transmitted with no loss. Otherwise, some, or even all, packets may get lost, as shown in the following figure.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-45
Firmware Upgrade
The AWK-3121 can be enhanced with more value-added functions by installing firmware upgrades. The latest firmware is available at Moxa’s download center.
Before running a firmware upgrade, make sure the AWK-3121 is off-line. Click the Browse button to specify the firmware image file and click Firmware Upgrade and Restart to start the firmware upgrade. After the progress bar reaches 100%, the AWK-3121 will reboot itself.
When upgrading your firmware, the AWK-3121’s other functions are forbidden.
ATTENTION
Please make sure the power source is stable when you upgrade your firmware. An unexpected power breakup may damage your AWK-3121.
Config Import Export
You can back up or restore the AWK-3121’s configuration with Config Import Export. In the Config Import section, click Browse to specify the configuration file and click Config
Import button to begin importing the configuration.
In the Config Export section, click the Config Export button and save the configuration file onto your local storage media. The configuration file is a text file and you can view and edit it with a general text-editing tool.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-46
Load Factory Default
Use this function to reset the AWK-3121 and roll all settings back to the factory default values. You can also reset the hardware by pressing the reset button on the top panel of the AWK-3121.
Password
You can change the administration password for each of the AWK-3121’s console managers by using the Password function. Before you set up a new password, you must input the current password and reenter the new password for confirmation. For your security, do not use the default password root, and remember to change the administration password regularly.
Misc. Settings
Additional settings to help you manage your AWK-3121, are available on this page .
Reset button
Setting Description Factory Default
Always enable The AWK-3121’s Reset button works
normally.
Disable after 60 sec The AWK-3121’s reset to default function
will be inactive 60 seconds after the AWK-3121 finishes booting up.
Always enable
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-47
Save Configuration
The following figure shows how the AWK-3121 stores the setting changes into volatile and non-volatile memory. All data stored in volatile memory will disappear when the AWK-3121 is shutdown or rebooted unless they are y. Because the AWK-3121 starts up and initializes with the settings stored in flash memory, all new changes must be saved to flash memory before restarting the AWK-3121.
This also means the new changes will not work unless you run either the Save Configuration function or the Restart function.
After you click on Save Configuration in the left menu box, the following screen will appear. Click Save if you wish to update the configuration settings in the flash memory at this time. Alternatively, you may choose to run other functions and put off saving the configuration until later. However, the new setting changes will remain in the non-volatile memory until you save the configurations.
AirWorks AWK-3121 User’s Manual Web Console Configuration
3-48
Restart
If you submitted configuration changes, you will find a blinking string in the upper right corner of the screen. After making all your changes, click the Restart function in the left menu box. One of two different screens will appear.
If you made changes recently but did not save, you will be given two options. Clicking the Restart button here will reboot the AWK-3121 directly, and all setting changes will be ignored. Clicking the Save and Restart button will apply all setting changes and then reboot the AWK-3121.
If you run the Restart function without changing any configurations or saving all your changes, you will see just one Restart button on your screen.
You will not be able to run any of the AWK-3121’s functions while the system is rebooting.
Logout
Logout helps users disconnect the current HTTP or HTT PS sessi o n and go to the Login page. For security reasons, we recommend you logout before quitting the console manager.
4
4
Chapter 4 Software Installation/Configuration
In this chapter, we cover the following topics:
Overview AWK Search Utility
¾ Installing AWK Search Utility ¾ Configuring AWK Search Utility
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-2
Overview
The Documentation & Software CD included with your AWK-3121 is designed to make the installation and configuration procedure easy and straightforward. This auto-run CD includes AWK Search Utility (to broadcast search for all AWK’s accessible over the network), the AWK-3121 User’s Manual, and Quick Installation Guide.
AWK Search Utility
Installing AWK Search Utility
1. Click the INSTALL UTILITY button in the AWK Installation CD au to-run window to install
AWK Search Utility. Once the program starts running, click Yes to proceed.
2. Click Next when the Welcome screen opens to proceed with the installation.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-3
3. Click Next to install program files to the default directory, or click Browse to select an
alternate location.
4. Click Next to create the program’s shortcut files to the default directory, or click Browse to
select an alternate location.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-4
5. Click Next to select additional tasks.
6. Click Next to proceed with the installation. The installer then displays a summary of the
installation options.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-5
7. Click Install to begin the installation. The setup window will report the pro gress of the
installation. To change the installation settings, click Back and navigate to the previous screen.
8. Click Finish to complete the installation of AWK Search Utility.
Configuring AWK Search Utility
The Broadcast Search function is used to locate all AWK-3121 APs that are connected to the same LAN as your computer. After locating an AWK-3121, you will be able to change its IP address. Since the Broadcast Search function searches by TCP packet and not IP address, it doesn’t matter if the AWK-3121 is configured as an AP or Client. In either case, APs and Clients connected to the LAN will be located, regardless of whether or not they are part of the same subnet as the host.
1. Start the AWK Search Utility program. When the Login page appears, select the “Search
AW K only” option to search for AWKs and to view each AWK’s configuration. Select the “AWK management” option to assign IPs, upgrade firmware, and locate devices.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-6
2. Open the AWK Search Utility and then click the Search icon.
The “Searching” window indicates the progress of the search.
3. When the search is complete, all AWKs that were located will be displayed in the AWK
Search Utility window.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-7
Click Locate to cause the selected device to beep.
Make sure your AWK is unlocked before using the search utility’s icons setting. The AWK will unlock automatically if the password is set to the default. Otherwise you must enter the new password manually.
Go to Tools Æ AWK login Options to manage and unlock additional AWKs.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-8
Use the scroll down list to select the MAC addresses of those AWKs you would like to manage, and then click Add. Key in the password for the AWK device and then click OK to save. If you return to the search page and search for the AWK again, you will find that the AWK will unlock automatically.
ATTENTION
For security purposes, we suggest you can change the AWK search utility login password instead of using default.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-9
To modify the configuration of the highlighted AWK, click on the Web icon to open the web console. This will take you to the web console, where you can make all configuration changes. Refer to Chapter 3, “Using the Web Console,” for information on how to use the web console.
Click on Telnet if you would like to use telnet to configure your AWKs.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-10
Click Assign IP to change the IP setting.
The three advanced options—Search, Connection, and Miscellaneous—are explained below:
Search
Retry count (default=5): Indicates how many times the search will be retried automatically. Retry interval (ms): The time lapsed between retries.
AirWorks AWK-3121 User’s Manual Web Console Configuration
4-11
Connection
Connection timeout (secs): Use this option to set the waiting time for the Default Login, Locate, Assign IP, Upload Firmware, and Unlock to complete.
Upgrade timeout (secs): Use this option to set the waiting time for the connection to disconnect
while the firmware is upgrading.
Use this option to set the waiting time for the Firmware to write
to flash.
Misc.
Search on start: Checkmark this box if you would like the search function to start searching for devices after you log in to the AWK search Utility.
5
5
Chapter 5 Other Console Configurations
This chapter explains how to access the AWK-3121 for the first time. In addition to HTTP access, there are four ways to access AWK-3121: serial console, Telnet console, SSH console, and HTTPS console. The serial console connection method, which requires using a short serial cable to connect the AWK-3121 to a PC’s COM port, can be used if you do not know the AWK-3121’s IP address. The other consoles can be used to access the AWK-3121 over an Ethernet LAN, or over the Internet.
In this chapter, we cover the following topics:
RS-232 Console Configuration (115200, None, 8, 1, VT100) Configuration by Telnet and SSH Consoles Configuration by Web Browser with HTTPS/SSL Disabling Telnet and Browser Access
AirWorks AWK-3121 User’s Manual Other Console Configurations
5-2
RS-232 Console Configuration (115200, None, 8, 1, VT100)
The serial console connection method, which requires using a short serial cable to connect the AWK-3121 to a PC’s COM port, can be used if you do not know the AWK-3121’s IP address. It is also convenient to use serial console configurations when you cannot access the AWK-3121 over Ethernet LAN, such as in the case of LAN cable disconnections or broadcast storming over the LAN.
ATTENTION
Do not use the RS-232 console manager when the AWK-3121 is powered at reversed voltage (ex. -48VDC), even though reverse voltage protection is supported.
If you need to connect the RS-232 console at reversed voltage, Moxa’s TCC-82 isolator is your best solution.
NOTE
We recommend using Moxa PComm (Lite) Terminal Emulator, which ca n be do w nl oa d ed free of charge from Moxa’s website.
Before running PComm Terminal Emulator, use an RJ45 to DB9-F (or RJ45 to DB25-F) cable to connect the AWK-3121’s RS-232 console port to your PC’s COM port (generally COM1 or COM2, depending on how your system is set up). After installing PComm Terminal Emulator, take the following steps to access the RS-232 console utility.
1. From the Windows desktop, open the Start menu and start PComm Terminal Emulator in the
PComm (Lite) group.
ATTENTION
1. You CANNOT connect to the AWK-3121 by two ore more of these console configurations
simultaneously.
2. You can connect to the AWK-3121 simultaneously by web browser and serial/ Telnet /SSH
console. However, we strongly suggest that you do NOT use more than one connection method at the same time. Following this advice will allow you to maintain better control over the configuration of your AWK-3121.
AirWorks AWK-3121 User’s Manual Other Console Configurations
5-3
2. Select Open under Port Manager to open a new connection.
3. The Communication Parameter page of the Property window opens. Select the appropriate
COM port for Console Connection, 115200 for Baud Rate, 8 for Data Bits, None for Parity, and 1 for Stop Bits.
4. Click on the Terminal tab, and select VT100 (or ANSI) for Terminal T ype. Click on OK to
continue.
5. The Console login screen will appear. Log into the RS-232 console with the login name
(default: admin) and password (default: root, if no new password is set).
AirWorks AWK-3121 User’s Manual Other Console Configurations
5-4
6. The AWK-3121’s device information and Main Menu will be displayed. Please follow the
description on screen and select the administration option you wish to perform.
NOTE
To modify the appearance of the PComm Terminal Emulator window, select Edit Æ Font and then choose the desired formatting options.
ATTENTION
If you unplug the RS-232 cable or trigger DTR, a disconnection event will be evoked to enforce logout for network security. You will need to log in again to resume operation.
Configuration by Telnet and SSH Consoles
You may use Telnet or SSH client to access the AWK-3121 and manage the console over a network. To access the AWK-3121’s functions over the network from a PC host that is connected to the same LAN as the AWK-3121, you need to make sure that the PC host and the AWK-3121 are on the same logical subnet. To do this, check your PC host’s IP address and subnet mask.
NOTE
The AWK-3121’s default IP address is 192.168.127.253 and the default subnet mask is
255.255.255.0 (for a Class C network). If you do not set these values properly, please check the
network settings of your PC host and then change the IP address to 192.168.127.xxx and sub net mask to 255.255.255.0.
AirWorks AWK-3121 User’s Manual Other Console Configurations
5-5
Follow the steps below to access the console utility via Telnet or SSH client.
1. From Windows Desktop, run Start > Run, and then use Telnet to access the AWK-3121’s IP
address from the Windows Run window. (You may also issue the telnet command from the MS-DOS prompt.)
When using SSH client (ex. PuTTY), please run the client program (ex. putty.exe) and then input the AWK-3121’s IP address, specifying 22 for the SSH connection port.
2. The Console login screen will appear. Please refer to the previous paragraph “RS-232 Console
Configuration” and for login and administration.
Configuration by Web Browser with HTTPS/SSL
To secure your HTTP access, the AWK-3121 supports HTTPS/SSL encryption for all HTTP traffic. Perform the following steps to access the AWK-3121’s web browser interface via HTTPS/SSL.
1. Open your web browser and type https://<AWK-3121’s IP address> in the address field. Press
Enter to establish the connection.
AirWorks AWK-3121 User’s Manual Other Console Configurations
5-6
2. Warning messages will pop out to warn users that the security certificate was issued by a
company they have not chosen to trust.
3. Select Yes to accept the certificate issued by Moxa IW and then enter the AWK-3121’s web
browser interface secured via HTTPS/SSL. (You can see the protocol in URL is https.) Then you can use the menu tree on the left side of the window to open the function pages to access each of AWK-3121’s functions.
Disabling Telnet and Browser Access
If you are connecting the AWK-3121 to a public network but do not intend to use its management functions over the network, then we suggest disabling both Telnet Console and Web Configuration. Please run Maintenance Æ Console Settings to disable them, as shown in the following figure.
6
6
Chapter 6 References
This chapter provides more detailed information about wireless-related technologies. The information in this chapter can help you administer your AWK-3121s and plan your industrial wireless network better.
The following topics are covered:
Wireless Distribution System (WDS) Beacon DTIM Fragment RTS Threshold STP and RSTP
¾ The STP/RSTP Concept ¾ Differences between RSTP and STP
AirWorks AWK-3121 User’s Manual References
6-2
Wireless Distribution System (WDS)
Traditionally, APs are connected via Ethernet LAN ports. By using a Wireless Distribution System (WDS), APs can communicate with one another wirelessly. For example, AP 2 acts as an access point for the notebook computers or other IEEE802.11-enabled clients, and forwards packets sent from the notebook computers to AP 1 through WDS. Then , AP 1 forwards the packets to the Ethernet LAN. Packets destined for the notebook computers follow a reverse path from the Ethernet LAN through the APs to the notebook computers. In this way, AP 2 acts as an “AP repeater.”
By using WDS, two or more LAN segments can be connected wirelessly. As illustrated in the above figure, a pair of wireless LAN-to-LAN bridges is used to connect two LAN segments. Since the AP is WDS-enabled, it can be used as a wireless bridge.
It is a good idea to plan your wireless network by drawing a diagram so that you know how each AWK-3121 is connected to other peer APs or wireless bridges by WDS, and how bridges are connected to other peer bridges by WDS. See the following figure for an example of a network-planning diagram.
AirWorks AWK-3121 User’s Manual References
6-3
ATTENTION
Be sure to eliminate loops from networks that consist of wireless bridges, Ethernet switches, Ethernet links, and WDS links. If any loops exist, packets will circle around the loops and network performance will be seriously degraded. The following figure shows a network topology containing a loop.
Beacon
A beacon is a packet broadcast by the AP to keep the network synchronized. A beacon includes the wireless LAN service area, the AP address, the Broadcast destination address, a time stamp, Delivery Traffic Indicator Maps (DTIM), and the Tra ffic Indicator Message (TIM). Beacon Interval indicates the frequency interval of AP.
DTIM
Delivery Traffic Indication Map (DTIM) is contained in beacon frames. It is used to indicate that broadcast and multicast frames buffered by the AP will be delivered shortly. Lower settings result in more efficient networking, while preventing your PC from dropping into power-saving sleep mode. Higher settings allow your PC to enter sleep mode, thus saving power.
Fragment
A lower setting means smaller packets, which will create more packets for each transmission. If you have decreased this value and experience high packet error rates, you can increase it again, but it will likely decrease overall network performance. Only minor modifications of this value are recommended.
RTS Threshold
RTS Threshold (256-2346) – This setting determines how large a packet can be before the Access Point coordinates transmission and reception to ensure efficient communication. This value should remain at its default setting of 2,346. When you encounter inconsistent data flow, only minor modifications are recommended.
AirWorks AWK-3121 User’s Manual References
6-4
STP and RSTP
The STP/RSTP Concept
Spanning Tree Protocol (STP) was designed to help reduce li nk fai l ure s i n a netwo rk , and provide protection from loops. Networks that have a complicated architecture are prone to broadcast storms caused by unintended loops in the network. The STP protocol is part of the IEEE802.1D standard, 1998 Edition bridge specification.
Rapid Spanning Tree Protocol (RSTP) implements the Spanning Tree Algorithm and Protocol defined by IEEE802.1w-2001 standard. RSTP provides the following benefits:
y The topology of a bridged network will be determined much more quickly compared to STP. y RSTP is backward compatible with STP, making it relatively easy to deploy. For example:
Defaults to sending 802.1D-style BPDUs if packets with this format are received. STP (802.1D) and RSTP (802.1w) can operate on the LAN ports and WLAN ports (AP
and WDS1-WDS8) of the same AWK-3121.
This feature is particularly helpful when the AWK-31 21 connects to older equipment, such as legacy switches.
Differences between RSTP and STP
RSTP is similar to STP, but includes additional information in the BPDUs that allow each bridge to confirm that it has taken action to prevent loops from forming when it decides to enab le a link to a neighboring bridge. Adjacent bridges connected via point-to-point links will be able to enable a link without waiting to ensure that all other bridges in the network have had time to react to the change. The main benefit of RSTP is that the configuration decision is made locally rather than network-wide, allowing RSTP to carry out automatic configuration and restore a link faster than STP.
7
7
Chapter 7 Supporting Information
This chapter presents additional information about this manual and product. You can also learn how to contact Moxa for technical support.
The following topics are covered:
About This User’s Manual DoC (Declaration of Conformity)
¾ Federal Communication Commission Interference Statement
¾ R&TTE Compliance StatementFirmware Recovery Technical Support Contact Information
AirWorks AWK-3121 User’s Manual Supporting Information
7-2
About This User’s Manual
This manual is mainly designed for, but no limited to, the following hardware and firmware for the AWK-3121:
y Hardware Rev: 1.1 y Firmware Ver: 1.1
You are strongly recommended to visit Moxa’s website (http://www.moxa.com) and find the latest pr
o
duct datasheet, firmware, QIG (Quick Installation Guide), UM (User’s Manual) and related
information.
NOTE
You can find out the hardware revision number of AWK-3121 on th e side label.
The firmware version number can be seen on the Overview page, as follow:
AirWorks AWK-3121 User’s Manual Supporting Information
7-3
DoC (Declaration of Conformity)
Federal Communication Commission Interference Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television recept i on , whi ch can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
y Reorient or relocate the receiving antenna. y Increase the separation between the equipment and receiver. y Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected. y Consult the dealer or an experienced radio/TV technician for help. FCC Caution: To assure continued compliance, (example – use only shielded interface cables
when connecting to computer or peripheral devices). Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment. This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.
FCC Radiation Exposure Statement
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 20 cm between the radiator & your body.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
FCC 15.407(e): Within the 5.15-5.25 GHz band, U-NII devices will be restricted to indoor operations to reduce any potential for harmful interference to co-channel MSS operations.
R&TTE Compliance Statement
This equipment complies with all the requirements of DIRECTIVE 1999/5/CE OF THE EUROPEAN PARLIAMENT AND THE COUNCIL OF 9 March 1999 o n radio e quipment and telecommunication terminal equipment and the mutual recognition of their conformity (R&TTE).
The R&TTE Directive repeals and replaces in the directive 98/13/EEC (Telecommunications Terminal Equipment and Satellite Earth Station Equipment) as of April 8, 2000.
Safety
This equipment is designed with the utmost care for the safety of those who install and use it. However, special attention must be paid to the dangers of electric shock and static electricity when working with electrical equipment. All guidelines of this and of the computer manufacturer must therefore be allowed at all times to ensure the safe use of the equipment.
AirWorks AWK-3121 User’s Manual Supporting Information
7-4
EU Countries Intended for Use
The ETSI version of this device is intended for home and office use in Austria, Belgium, Denmark, Finland, France (with Frequency channel restrictions), Germany, Greece, Ireland, Italy, Luxembourg, Portugal, Spain, Sweden, The Nethe rla n ds, and Uni te d Kingdom.
The ETSI version of this device is also authorized for use in EFTA member states Norway and Switzerland.
EU Countries Not Intended for Use
None.
Potential Restrictive Use
France: only channels 10, 11, 12, and 13.
Firmware Recovery
When the LEDs of FAULT, Signal Stre ng th, CLIENT, BRIDGE and WLAN all light up simultaneously and blink at one-second interval, it means the system booting has failed. It may result from some wrong operation or uncontrollable issues, such as an unexpected shutdown during firmware update. The AWK-3121 is designed to help administrators recover such damage and resume system operation rapidly. You can refer to the following instructions to recover the firmware:
Connect to the AWK-3121’s ES-232 console with 115200bps and N-8-1 . You will see the following message shown on the terminal emulator every one second.
Press Ctrl - C and the following message will appear.
AirWorks AWK-3121 User’s Manual Supporting Information
7-5
Enter 2 to change the network setting. Specify where the AWK-3121’s firmware file on the TFTP server and press y to write the settings into flash memory.
AWK-3121 restarts, and the “Press Ctrl-C to enter Firmware Recovery Process…” message will reappear. Press Ctrl-C to enter the menu and select 1 to start the firmware upgrade process.
Select 0 in the sub-menu to load the firmware image via LAN, and then enter the file name of the firmware to start the firmware recovery.
Technical Support Contact Information
Customer satisfaction is our number one concern, and to ensure that customers receive the full benefit of our products, Moxa Internet Services has been set up to provide technical support, driver updates, product information, certification status, installation guide and user’s manual updates.
The following services are provided: y E-mail for technical support: support@moxa.com (Worldwide) support@usa.moxa.com (The Americas) y World W ide Web (WWW) Site for product information: http://www.moxa.com
Loading...