• Mini DB9F-to-TB: DB9-female-to-termina l-block connector
- 2 -
LED
Color
Description
Ready
Off
Power is off or a fault condition exists
Green
Steady: Power is on, and the MGate is
functioning normally
up
Blinking slowly: Indicates an IP conflict, or the
Flashing quickly: the microSD card failed
MB/EIP
Off
Modbus: No communication with Modbus device
EtherNet/IP: No I/O data exchange
Green
(Blinking)
Modbus: Communication in progress
EtherNet/IP: I/O data is exchanging
(Blinking)
3. Timeout (slave device is not responding or
3. Received frame error (parity error, checksum
configuration
Off
No connection with PROFINET I/O controller
Green
(Blinking)
controller is
in RUN mode
Red
(Blinking)
PROFINET I/O is connected, but the controller is
in STOP mode
Hardware Introduction
LED Indicators
Red Steady: Power is on, and the MGate is booting
DHCP or BOOTP server is not responding
properly
Red
PN
Communication error
When MGate 5103 acts as Modbus
Client/Master:
1. Slave device returned an error (exception)
2. Received a frame error (parity error,
checksum error)
TCP connection timed out)
When MGate 5103 acts as Modbus
Server/Slave:
1. Received invalid function code
2. Master accessed invalid register address or
coil addresses
error)
When MGate 5103 acts as EtherNet/IP adapter:
1. Refuses connection due to incorrect
PROFINET I/O is connected and the
- 3 -
1 2 3
resistor
resistor
ON
1 kΩ
1 kΩ
120 Ω
OFF
150 kΩ*
150 kΩ*
–*
*Default
Dimensions
Unit: mm (inch)
Reset Button
Restore the MGate to factory default settings by using a pointed object
(such as a straightened paper clip) to hold the reset button down until the
Ready LED stops blinking (approximately five seconds).
Pull-up, Pull-down, and Terminator for RS-485
Beneath the MGate 5103’s top cover, you will find DIP switches to adjust
each serial port’s pull-up resistor, pull-down resistor, and terminator.
SW
Pull-up
Pull-down
Terminator
Hardware Installation Procedure
1. Connect the power adapter. Connect the 12-48 VDC power line or
DIN-rail power supply to the MGate 5103’s terminal block.
2. Use a serial cable to connect the MGate to the Modbus device.
3. Use an Ethernet cable to connect the MGate to the PROFINET IO
controller.
4. The MGate 5103 is designed to be attached to a DIN rail or mounted
on a wall. For DIN-rail mounting, push down the spring and properly
attach it to the DIN rail until it “snaps” into place. For wall mounting,
install the wall-mounting kit (optional) first and then screw the device
onto the wall.
- 4 -
RS-422/
RS-485 (4W)
1
DCD
TxD-(A)
–
2
RXD
TxD+(B)
–
3
TXD
RxD+(B)
Data+(B)
4
DTR
RxD-(A)
Data-(A)
5*
GND
GND
GND
6
DSR – –
7
RTS – –
8
CTS – – 9 – – –
Pin
Signal
1
Tx+ 2 Tx- 3 Rx+ 6 Rx-
The following figure illustrates the two mounting options:
Software Installation Information
Please download the user's manual and Device Search Utility (DSU) from
Moxa’s website: www.moxa.com
Refer to the user’s manual for additional details on using the DSU. The
MGate 5103 also supports login via a web browser.
Default IP address: 192.168.127.254
Default account: admin
Default password: moxa