Moxa MGate 5101-PBM-MN Installation Guide

P/N: 1802051010014
Technical Support Contact Information
www.moxa.com/support
2021 Moxa Inc. All right s reserved.
MGate 5101-PBM-MN Series
Quick Installation Guide
Version 3.2, January 2021
*1802051010014*

Overview

LED
Color
Function
Green
Power is on
Off
Power is off
Green
Power is on
Off
Power is off
MGate Manager’s Location function
Steady on: Power is on and the MGate is booting
BOOTP server is not responding properly
Off
Power is off or fault condition exists
Off
No data exchange
Green
Data exchange with all slaves
flashing
configured slaves can communicate with gateway)
Red
Bus control error
Off
No PROFIBUS configuration
Green
PROFIBUS configuration OK
Off
PROFIBUS master is offline
Red
PROFIBUS master is in STOP mode
Green,
flashing
Green
PROFIBUS master is in OPERATE mode
Green
Gateway holds the PROFIBUS token
Off
Gateway is waiting for the PROFIBUS token
The MGate 5101-PBM-MN is an industrial Ethernet gateway for PROFIBUS-to-Modbus-TCP network communication.

Package Checklist

Before installing the MGate 5101-PBM-MN, verify that the package contains the follo wing items:
• 1 MGate 5101-PBM-MN gateway
• Quick installation guide (printed)
• Warranty Card
Please notify your sales representative if any of the above items are missing or damaged.
Optional Accessories (can be purchased separately):
• CBL-F9M9-150: DB9-female-to-DB9-male serial cable, 150 cm
• CBL-F9M9-20: DB9-female-to-DB9-male ser ial cable, 20 cm
• Mini DB9F-to-TB: DB9-female-to-terminal-block connector
• WK-36-01: Wall-mounting kit

Hardware Introduction

LED Indicators
PWR1
PWR2
Steady on: Power is on and the MGate is
Green
functioning normally Blinking: The MGate has been located by the
Ready
COMM
CFG
PBM
TOK
Green,
up
Red
Blinkin g: Indicates an IP conflict, or the DHCP or
Data exchange with at least one slave (not all
PROFIBUS master is in CLEAR mode
- 2 -
LED
Color
Function
Amber
Steady: 10Mbps, no data is transmitting Blinkin g: 10Mbps, data is transmit ting
Steady: 100Mbps, no data is transmitting Blinkin g: 100Mbps, data is transmitting
Off
Ethernet cable is disconnected
STEP 1:
Connect the power adapter. Connect the 12-48 VDC power line or DIN device’s terminal block. Make sure the adapter is connected to an earthed socket.
STEP 2:
Use a PROFIBUS cable to connect the unit to a PROFIBUS slave device.
STEP 3:
Connect the unit to the Modbus TCP device.
STEP 4:
The
attached to
a DIN
mounting, push
down the spring and properly attach it to the
rail until it “snaps” into place. For wall kit (optiona l) firs
Two metal plates are provided for mounting the unit on a wall or inside a cabinet. Attach the plates to the unit’s rear panel with screws. With the plates attached, use screws to mount the unit on a wall. The heads of the screws should be 5 to 7 mm in diameter, the shafts should be 3 to 4 mm in diameter, and the length of the screws should be more than 10.5 mm.
Ethernet
Green
Reset Button
The reset button is used to load factory defaults. Use a pointed object such as a straightened paper clip to hold the reset button down for five seconds. Release the reset button when the Ready LED stops blinking.
Hardware Installation Procedure
-rail power supply with the MGate 5101-PBM-MN
MGate 5101-PBM-MN series is designed to be
rail or mounted on a wall. For DIN-rail
t and then screw the device onto the wall.
Wall or Cabinet Mounting
For each screw, the head should be 6 mm or less in diameter, and the shaft should be 3.5 mm or less in diameter.
mounting, install the wall-mount
- 3 -
DIN-
The following figure illustrates the two mounting options:
PIN
Signal Name
1 – 2 – 3
PROFIBUS D+
4
RTS 5 Signal common
6
5V 7 – 8 PROFIBUS D-
9
Software Installation Information
To install MGate Manager, please download it from Moxa’s website at
http://www.moxa.com. For more detailed information about MGate
Manager, click the Documents button and select the MGate 5101-PBM-MN User’s Manual.
The MGate 5101 also supports login via a web browser.
Default IP address: 192.168.127.254
Default account: admin
Default password: moxa

Pin Assignments

PROFIBUS Serial Port (Female DB9)
- 4 -
Power Input and Relay Output Pinouts
DC
Input 2
DC
Input 2
DC
Input 1
DC
Input 1
Power Input
12 to 48 VDC
Power Consumption (Input Rating)
12 to 48 VDC, 360 mA (max.)
Operating Temperature
Standard Models: 0 to 60°C (32 to 140°F)
167°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Shielded
Ground
V2+ V2-
Power
Power
N.O. Common N.C.
Power
V1+ V1-

Specifications

Wide Temp. Models: -40 to 75°C (-40 to

ATEX and IECEx Information

1. ATE X Certificate number: DEMKO 14 ATEX 1288
2. IECEx number: IECEx UL 14.0023X
3. Certificate string: Ex nA IIC T4 Gc Ambient range: 0°C Tamb 60°C (for suffix without –T) Ambient range: -40°C Tamb 75°C (for suffix without –T)
4. Standards covered: EN 60079-0: 2012+A11:2013/IEC 60079-0: Ed 6.0 EN 60079-15:2010/IEC 60079-15: Ed 4.0
5. Field-wiring connection: The device uses a terminal block, solder on the power distribut ion board, suitable for 12-24 AWG wire size, torque value 4.5 lb-in (0.51 N-m).
6. Battery information: Battery is not user replaceable.
7. Installation instructions:
• A 4 mm
• Conductors suitable for use at an ambient temperature of 84°C
8. Special conditions for safe use:
• The device is to be installed in an IECEx/ATEX Certified IP54
• The device is for use in an area of not more than pollution degree
2
external grounding screw is utilized.
must be used for the power supply termina l.
enclosure and accessible only through the use of a tool.
2 in accordance with IEC 60664-1.
conductor must be used when the connection to the
Power
- 5 -
ATTENTION
For installat ions in
These devices are to be installed in an enclosure with a tool-removable cover or door, suitable for the environment.
NOTE
The equipment must be suitable for use in Class 1, D ivision 2, Groups A, B, C, D, or nonhazardous locations only.
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless the power has been switched off, or the area is known to be nonhazardous.
WARNING
EXPLOSION HAZARD
Substitution of any components may impair suitability for Class 1, Division 2.
WARNING
EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS USED IN THE FOLLOWING DEVICE: Sealed Relay Device U21.
Moxa Inc. No. 1111, Heping Rd., Bade Dist., Taoyuan City 334004, Taiwan
hazardous locations (Class 1, Division 2):
- 6 -