• This manual has been published to service the MovinCool Office Pro 60. Please use this service
manual only when servicing the Office Pro 60.
1.2 Definition of Terms
WARNING
CAUTION
NOTEProvides additional information that facilitates installation or unit operation.
Describes precautions that should be observed in order to prevent injury to
the user during installation or unit operation.
Describes precautions that should be observed in order to prevent da mage to
the unit or its components, which may occur during installation or unit
operation if sufficient care is not taken.
1.3 General Precautions
WARNING
• All electrical work if necessary, should only be performed by qualified electrical
personnel. Repair to electrical components by non-certified technicians may result in
personal injury and/or damage to the unit. All electrical components replaced must be
genuine MovinCool parts, purchased from an authorized reseller.
• When handling refrigerant, always wear proper eye protection and do not allow the
refrigerant to come in contact with your skin.
• Do not expose refrigerant to an open flame.
• The proper electrical outlet for MovinCool units must be equipped with a “UL” approved
ground-fault breaker to prevent electrical shock from the unit.
• When brazing any tubing, always wear eye protection, and work only in a well ventilated
area.
• Disconnect power before servicing unit.
• Be careful of any sharp edges when working on unit.
2. GENERAL DESCRIPTION
2.1 Spot Cooler
• In general, conventional air conditioners cool
the entire enclosed environment. They act as
“heat exchangers”, requiring an interior unit
(evaporator) to blow cool air into the interior
and an exterior unit (condenser) to exhaust
exchanged heat to the outdoors.
• Unlike conventional air conditioners, the
Condenser
(Outdoor Unit)
Operation Section
7
Evaporator
(Indoor Unit)
MovinCool Office Pro 60 is a spot cooler which
directs cool air to particular areas or objects.
MovinCool Office Pro 60 has the following features:
2.2 Compact Design
• The innovative design of MovinCool Office Pro
60 has resulted in one compact unit, replacing
the need for two separate units.
2.3 Easy Transportation and
Installation
• With the whole cooling system built into one
compact unit, MovinCool Office Pro 60
requires no piping and can be easily
transported and installed.
I000501
2.4 Energy Conservation
• MovinCool Office Pro 60 is economical
because it cools only the area or objects which
need to be cooled.
I001905
8
Operation Section
3. CONSTRUCTION
3.1 Exterior Dimensions
(55.0)
(30.2)
(2.6)
(3.6)
(29.9)
(2.6)
(3.6)
(18.7)
(27.6)
(10.0)
(8.5)
(40.8)
(51.6)
(DIA. 15.7)
(6.1)
(2.4)
(65.0)
(62.2)
(Unit: inch)
I001906
3.2 Exterior Components
Operation Panel
Operation Section
9
Cold Air Outlet Grill
Caster
Evaporator Air Inlet Grill
Condenser Air Outlet Duct
Service PanelPower CordCondenser Air Inlet Panel
I001907
10
Operation Section
3.3 Internal Structure
Fan Motor
(Evaporator)
(Behind Fan)
Fan
(Evaporator)
Evaporator
High Pressure
Switch
Capillary Tube
Drain Pan
Condensate Pump
3.4 Basic Construction
Fan
(Condenser)
Compressor
Condenser
Fan Motor
(Condenser)
Drain Switch
Control Box
I001908
• The MovinCool Office Pro 60 is compact in construction because the condenser and the
evaporator are enclosed in one unit. The interior is divided into three sections. The upper front
face is equipped with the evaporator, and the lower front face contains the condensate pump
and optional drain tanks. The rear section contains the condenser, the compressor and the
control box.
Operation Section
3.5 Air Flow
• Air drawn from the right side face passes through the condenser which extracts the heat. This
hot air is blown out through the upper exhaust air duct. Air taken in from the front face is cooled
by the evaporator and then blown through the cool air vent. All the air inlets are equipped with
filters, and the exhaust air duct is protected by metal grill.
Exhaust Air Out
Cool Air Out
11
Evaporator Air In
Condenser Air In
3.6 Compressor and Fans
• The compressor is hermetically sealed. Two sets of a two-speed fan motor with a centrifugal fan
are used to draw air across the evaporator and condenser.
3.7 Condensate Pump
• The condensate pump and a 20 ft (6 m) drain hose are included with the Of fice Pro 60 to provide
continuous operation without the need of the drain tanks. The co ndensate pump has a maximum
head lift of 17 ft (5.2 m) at 230 VAC or 13 ft (4.0 m) at 208 VAC.
3.8 Drain Tanks (optional)
I001909
• A set of two 5.0 gal (19 L) drain tanks are supplied as optional accessory for Office Pro 60. When
drain tanks are used instead of condensate pump , the condensate (water) is collected into both
tanks. The drain switch activates and stops the operation when tanks reach the level of
approximately 8.0 gal (30 L).
The component parts of the refrigerant system include the following:
• Compressor, Evaporator, Condenser, Capillary tube, High Pressure Switch
These parts are all connected by copper tubing. All the connections have been brazed.
Evaporator
Condenser
Compressor
Suction Pipe
Compressor
Discharge Pipe
Condenser
Inlet Pipe
Condenser
Outlet Pipe
Compressor
Compressor
Evaporator
Evaporator
Inlet Pipe
Capillary
Tube
Evaporator
Outlet Pipe
Condenser
Capillary
Tubes
Condenser
Condenser
Fan
Evaporator
Fan
Evaporator
Flow of Refrigerant
Compressor
I001912
Operation Section
5.2 Compressor
• The compressor used for the unit is hermetically sealed. The compressor and the compressor
motor are in one casing.
(1) Compressor theory of operation
• The scroll utilizes an involuted spiral which, when matched with a mating scroll form, generates
a series of crescent-shaped gas pockets between the two members. During compression, one
scroll remains stationary (fixed scroll) while the other form (orbiting scroll) is allowed to orbit (but
not rotate) around the first form. As this motion occurs, the pockets between the two forms are
slowly pushed to the center of the two scrolls while simultaneously being reduced in volume.
When the pocket reaches the center of the scroll form, the gas, which is now at a high pressure,
is discharged out of a port located at the center. During compression, several pockets are being
compressed simultaneously , resulting in a very smooth process. Both the suction process (outer
portion of the scroll members) and the discharge process (inner portion) are continuous.
17
(2) Compressor operation
1㧕3㧕4㧕5㧕2㧕
I001767
1) Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral.
Gas enters the outer openings as one of the spirals orbits.
2) The open passages are sealed off as gas is drawn into the spiral.
3) As the spiral continues to orbit, the gas is compressed into two increasingly smaller pockets.
4) By the time the gas arrives at the center port, discharge pressure has been reached.
5) Actually, during operation, all six gas passages are in various stag es of compression at all times,
resulting in nearly continuous suction and discharge.
< NOTE >
When the compressor shuts off, the compressor motor may run backward for a moment or two
until internal pressures is equalized. This has no effect on compressor durability but may cause
an unexpected sound after the compressor is turned off and should not be diagnosed as a
malfunction.
18
Operation Section
5.3 Condenser
• The condenser is a heat exchanger with copper tubes that are covered with thin aluminum
projections called plate fins.
• Heat is given off and absorbed by air being pulled across the condenser fins by the centrifugal
fan and then expelled through the exhaust air duct.
5.4 Capillary Tube
• The capillary tube is a long thin tube utilizing
line flow resistance to serve as an expansion
High Temp./High Pressure
Liquid Refrigerant
valve. The length and the inner diameter of the
capillary tube are determined by the capacity of
the refrigeration system, specified operating
conditions, and the amount of refrigerant. The
capillary tube causes the high pressure, high
temperature liquid refrigerant sent from the
Low Temp./Low Pressure
Gas and Liquid Mixture
condenser to expand rapidly as the refrigerant
is sprayed out through the fixed orifice in the capillary tube. As a result, the temperature and
state of the refrigerant becomes low and mist-like respectively, causing it to evaporate easily.
5.5 Evaporator
• The evaporator, like the condenser , is a heat exchanger covered with plate fins. Heat is removed
from the air being pulled across the evaporator by the centrifugal fan and the resulting cool air
is expelled through the cool air vent.
I001887
5.6 High Pressure Switch
• The high pressure switch prevents the
condenser and compressor from being
damaged by excessively high pressure in the
Movable Point
high pressure line of the refrigeration cycle.
The switch is normally closed. The snap disk
Stationary Point
responds to the variations in pressure and, if
pressure is abnormally high, the snap disk
moves down to push the pin down, causing the
Molding by Resin
internal contacts to open. This interrupts the
ground signal at the control board (J104 connector) which turns the compressor off.
• Possible causes of this trouble include:
- The condenser air filter is dirty, restricting air flow.
- The condenser blower is defective.
Pressure of Refrigerant
Case
Snap Disk
Pin
Terminal
Lead Wires
I001768
6. ELECTRICAL SYSTEM
6.1 Circuit Diagram and Control Box
Operation Section
19
AP
G
T1
G
AP
TB1
TB2
CB
RB
MF1
MF2
MC
CF1
CF2
CC
AC 208/230 V 1φ 60 Hz
TB1
TRR1
CF2
12
CF1
12
1L1
3L2
5L3
A1
HI
MF2
IOLF
HI
MF1
IOLF
MCC
MCC
LO
LO
CC
12
2T1
4T2
6T3
A2
G
G
Attachment Plug
Terminal Block
Terminal Block
Control Board
Relay Board
Condenser Fan Motor
Evaporator Fan Motor
Compressor Motor
Capacitor for Condenser Motor
Capacitor for Evaporator Motor
Capacitor for Compressor
MC
IOLC
Condensate Pump
G
J8
J7
J6
J5
J4
J3
J2
J1
MDP
ODSFDS
J10
RB
G
J9
IOLF
IOLC
DS
THS
RTH
G
HPRS
MCC
MDP
FDS
ODS
RTHTHSDS
J101 J102 J103 J104
J201
CB
J105
3
2
J106
J108
HPRS
1
TB2
LL+
EE+
Inner Overload Relay of Fan Motor
Inner Overload Relay of Compressor
Full Drain Warning Switch
Freeze Protection Thermistor
Room Thermistor
Grounding
High Pressure Switch
Relay for Compressor and Condenser Fan Motor
Condensate Pump Motor
Drain Float Switch
Drain Overflow Switch
Compressor
Capacitor
Fan Capacitor
(Evaporator)
Relay
Fan Capacitor
(Condenser)
TB2
Terminal Block
(Signal Connection)
Dip Switch
Relay Board
Relay Board Fuse
Terminal Block
TB1
G
I001913
20
Operation Section
6.2 Basic Operation of The Office Pro 60 Electrical Circuit
• There are two basic components used to control the operation of the Office Pro 60 electrical
system:
- Control panel assembly
- Control box
• The control panel assembly contains the control panel, control board (with inputs for the freeze
and room temperature thermistors), drain switch, high pressure switch and a microprocessor.
(1) Fan mode
High Fan Mode
• When the FAN MODE button on the control panel is pressed, the microprocesso r turns on “F AN
HI” “COOL OFF” indication of LCD and activates both the fan on relay and fan mode relay. This
sends line voltage (208/230 VAC) from the fan on relay to the N.O. (normally open) contacts of
the fan mode relay. This output is connected to the J8 terminal (relay board) where the high
speed wire of the fan motor is connected.
• When this button is pressed again, fan turns to low mode (see below). Press again, fan stops.
• High fan mode is automatically switched
depending on room temperature. When room
(High)
temperature is decreased down to 80 °F
(27 °C) or below, fan mode is switched to
Condenser Fan
HIGH. When room temperature is increased to
88 °F (31 °C) or higher, fan mode is switched
from HIGH to LO.
Room Temperature
(LO)
80 °F
(27 °C)
88 °F
(31 °C)
I001914
Low Fan Mode
• When the FAN MODE button on the control panel is pressed again, th e microprocessor turns on
“FAN LO” “COOL OFF” indication of LCD and activates both the fan on relay and fan mode relay.
This sends line voltage (208/230 VAC) from the fan on relay to the N.C. (normally closed)
contacts of the fan mode relay. This output is connected to the J7 terminal (relay board) where
the low speed wire of the fan motor is connected.
• When this button is pressed again, fan stops.
Operation Section
(2) Cool mode
• In addition to fan mode (as described above), when the COOL ON/OFF button on the control
panel is pressed, the microprocessor turns on “COOL ON” indication of LCD and if the
temperature set point is less than the current room temperature, activate s the compressor relay
(relay board) after 120 sec delay. This sends line volt age (208/230 V AC) t o the J4 terminal (relay
board) and compressor auxiliary relay is excited. Then compressor and condenser fan motor
turn on (Cooling Operation).
• Condenser fan mode is automatically switched
21
depending on room temperature. When room
temperature is approximately. 100 °F (38 °C)
or greater, fan mode is switched LO to HIGH.
When room temperature is approximately.
95 °F (35 °C), fan mode is switched HI to LO.
(LO)
Condenser Fan
(High)
Room Temperature
95 °F
(35 °C)
100 °F
(38 °C)
I001915
Loading...
+ 48 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.