3. Operation of Switch Assembly (cont.)
3-4. Operating in FAN ONLY Mode
1. The unit can also be operated in FAN ONLY mode by pressing FAN HI/LO button (LCD indicates “FAN HI/LO” and “COOL OFF”).
2. The unit can then be turned off by pressing the FAN HI/LO button until fan turns off (FAN ONLY mode speed sequences are HI > LO > OFF).
3-5. Changing from FAN ONLY Mode to COOL Mode
The COOL mode can be activated while the unit is operating in FAN ONLY mode. To do this, simply press the COOL ON/OFF button (LCD indicates “COOL ON”).
Note: The FAN ONLY mode does not operate after the COOL mode has been activated. The unit can only be turned off by pressing the COOL ON/OFF button.
4. Self-Diagnostic Codes of Switch Assembly
LCD Display Description Condition Reset/Remedy
Drain tank is full. When the drain tank is filled
with drain water. (“TANK FL” LED flashes.)
1)Drain away. (LCD indicates “TANK”)
2)Press ON/OFF button.
INSTALLATION MANUAL
For Classic Plus 14 - Serial Number: 1200XXXX140 to 0307XXXX140
1. Inventory
After unpacking, please check to make sure you have the correct part number of the switch assembly. If the switch assembly has incorrect part number or appear damaged, please contact your MovinCool reseller for replacement (See Fig.1). Please keep this
installation manual with the operation manual for future reference.
Classic Plus 14
Switch Assembly
Fig. 1
2. Installation of Switch Assembly
!
WARNING: Disconnect power supply from the unit before performing any service. Beware that some residual voltages may remain in the unit immediately after the power is disconnected.
2-1. Connect the following connectors to the switch assembly (See Fig. 2): A. J201 (10-pin) Wire Harness, relay board to the switch assembly. B. J101 (2-pin) Room Temperature Thermistor. C. J102 (2-pin) Freeze Protection Thermistor. D. J103 (2-pin) Drain Tank Switch.
C
D
B
A
FAN
COOL
FAN
COOL
FAN
COOL
FAN
COOL
TU
HI
ON
Condensate pump
AM
problem
F
SET TEMP
When (optional) condensate pump is damaged or broken.
1)Fix the condensate pump.
2)Reset the system. To RESET: Press ON/OFF and HI/LO buttons on the control box simultaneously
for 5 seconds.
Defect (short or open) of room
SET TEMP
SET TEMP
F
thermistor
F
HI
ON
HI
ON
Defect (short or open of freeze
SET TEMP
F
protection thermistor
HI
ON
When room thermistor (connecting to J101) becomes short or open.
When freeze protection thermistor (connecting to J102) becomes short or open.
Disconnect and reconnect the room thermistor. If it does not work, then change it.
Disconnect and reconnect the freeze protection thermistor. If it does not work, then change it.
Fig. 2
SET TEMP
F
< NOTE >
• Connector J104, J106, and J108 are not used.
Manual P/N: GX484007-3710 First Issue: June 2012
1
HI
FAN
ON
COOL
4
2-2. Install four (4) screws to secure the switch assembly to the stays on the unit (See
Fig. 3 and Fig. 4).
Screws (2)
Screws (2)
Fig. 3 Fig. 4
3. Operation of Switch Assembly (cont.)
3-2. LCD indicators (See Fig. 6)
8
6
3. Operation of Switch Assembly
3-1. Before operating the unit, it is important to familiarize yourself with the basic control functions of the switch assembly (See Fig. 5).
4
2
1
3
Classic Plus 14
5
Fig. 5
1. COOL Mode Button
2. FAN Mode Button Activates/deactivates the high, low, and off fan
3. SET TEMP Buttons ( / )
4. TANK FULL LED Flashes when drain tank is full.
5. NOT USE These buttons are covered by the unit top cover.
Activates/deactivates the COOL mode/turns the unit off.
speed. Temperature scale illuminates to indicate the
current LED temperatures being displayed are either in °C or °F.
7
Fig. 6
6. FAN HI/LO Illuminates to indicate selected fan speed.
7. COOL ON/OFF Illuminates to indicate cool on or off.
8. °C or °F Temperature displayed in either Fahrenheit or
Celsius (See Note).
Note: ROOM TEMP display range is from 16 °F (-9 °C) to 109 °F (42 °C). When the display value is greater than 99 °F, it displays values of +0 (for 100 °F),
+1 (for 101 °F), and +9 (for 109 °F).
(This only applies to Fahrenheit values.)
3-3. Operating in COOL Mode
1. The unit can be operated in COOL mode by pressing the COOL ON/OFF button (LCD indicates “COOL ON”).
Note: In COOL mode the unit can only be turned off by pressing the COOL ON/OFF button.
2. Change the fan speed by pressing the FAN HI/LO button.
3. Change the temperature set point by pressing the SET TEMP buttons ( / ).
Note: When turning the unit on, the set point and fan speed are determined by the last operating mode.