MovinCool CM12 User Manual

OPERATION MANUAL
CM12
Unit Serial Number Range: 0211XXXXC12 to 0315XXXXC12
(From February 2011 to March 2015)
READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT
INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS.
SECCIÓN EN ESPAÑOL
SECTION EN FRANÇAIS

SERIAL NUMBER LOCATION AND IDENTIFICATION

Nameplate Label
COOLING AMPS. WITH PUMP
COMPR. OUTPUT
REFRIGERANT/TOTAL CHARGE
DESIGN PRESSURE LO/HI
PART NO./WEIGHT
Nameplate Label Position
SERIAL NO.
Month
Year
▲▲  XXXX ###
Model
Sequential Number
© 2015 DENSO PRODUCTS AND SERVICES AMERICAS, INC. All rights reserved. This book may not be reproduced or copied, in whole or in part, without the written permission of the publisher. DENSO PRODUCTS AND SERVICES AMERICAS, INC. reserves the right to make changes without prior notice. MovinCool®, Office Pro® and SpotCool® are registered trademarks of DENSO Corporation.
OPERATION MANUAL
CM12

Table of Contents

SERIAL NUMBER LOCATION AND IDENTIFICATION ...................................2
FOREWORD ...................................................................................................... 5
Definition of Terms................................................................................ 5
GENERAL WARNINGS & CAUTIONS.............................................................. 5
INVENTORY....................................................................................................... 6
INSTALLATION ................................................................................................. 7
Unit Overview ........................................................................................ 7
Clearance Requirement ........................................................................ 8
Mounting the CM12 to a Roof Structure..............................................9
Power Supply Requirements.............................................................. 10
Service Panel Access ......................................................................... 10
Power Connection............................................................................... 11
Drain Hose Connection....................................................................... 11
Packing Attachment............................................................................ 13
Wall Thermostat Connection (Millivolt System ONLY) .................... 13
Warning Signal Connection (Output Signal)..................................... 14
Fire Alarm Control Panel Connection (Input Signal)........................ 15
DIP Switch Configuration and Setting...............................................15
Ducting With Typical Drop Ceiling..................................................... 16
FEATURES ...................................................................................................... 17
INSPECTION & MAINTENANCE.....................................................................
Cleaning Air Filters ............................................................................. 17
Cleaning Condenser Air Intake .......................................................... 17
Ground Fault Breaker Testing............................................................17
TROUBLESHOOTING ..................................................................................... 18
Buzzer Pattern ..................................................................................... 18
CM12: Installation Check Sheet ......................................................... 20
TECHNICAL SPECIFICATIONS...................................................................... 21
17

FOREWORD

Congratulations on purchasing the MovinCool air conditioner. This manual explains how to assemble, install and operate the MovinCool CM12 air conditioning unit. Please read this operation manual thoroughly to familiarize yourself with the features of the unit and to ensure years of reliable operation.
You may also find it useful to keep this operation manual on hand for reference. Components and/or procedures are subject to change without prior notice.

Definition of Terms

WARNING: Describes precautions that should be observed in order to prevent injury to the user during installation or unit operation.
CAUTION: Describes precautions that should be observed in order to prevent damage to the unit or its components, which may occur during installation or unit operation if sufficient care is not taken.
Note: Provides additional information that facilitates installation or unit operation.

GENERAL WARNINGS & CAUTIONS

1. All electrical work should only be performed by qualified electrical personnel. Repair to electrical components by non-certified technicians may result in personal injury and/or damage to the unit. All electrical components replaced must be genuine MovinCool parts, purchased from an authorized reseller.
2. Disconnect power before any electrical installation.
3. Installation should be conducted by qualified technician only. DENSO and DENSO affiliate are not responsible for injuries and/or damages caused by improper installation.
4. Do not place water or any other liquid on the unit. This can cause damage to the unit and increase the risk of electrical shock.
5. Do not sit or stand on the unit.
6. Do not place hands or any object in the cool air outlet or exhaust duct. Touching the fan, which is rotating at a high speed, is very hazardous.
5

INVENTORY

CM12 UNIT OPERATION MANUAL /
PRODUCT REGISTRATION
CLIP
PACKING I (2.8 in x 32.0 in x 0.2 in)
PACKING II (1.0 in x 33.0 in x 0.2 in)
After unpacking your MovinCool unit, please check to make sure you have the following items:
1. CM12 MovinCool Unit (1)
2. Operation Manual/Product Registration (1)
3. Clip (1)
4. Packing I (1)
5. Packing II (1)
Note: If any of these items were not included in the box or appear damaged, please contact your MovinCool reseller for replacement.
6

INSTALLATION

COLD AIR EXHAUST (10.0 in DIA. FLANGE)
DRAIN PIPE FOR PUMP
CONDENSER (HOT) AIR EXHAUST
EVAPORATOR (ROOM) AIR INTAKE (10.0 in DIA. FLANGE)
MOUNTING
BRACKETS CONDENSATE PAN DRAIN FOR MAINTENANCE
SERVICE PANEL
OVERRIDE (STOP) SWITCH
POWER CORD CONNECTION
CONDENSER AIR INTAKE
SIGNAL WIRE

Unit Overview

WARNING: Remove protective cardboard from condenser intake after installation.
7
INSTALLATION (cont.)
WALL
All dimensions are in inches. Unit Weight: 123 lb (56 kg)
WALL
CEILING
INTAKE
EXHAUST
Minimum
clearance
40.0 in
from wall
Minimum
clearance
40.0 in
from wall
Ø0.6
Ø10.0
15.3
7.5
15.8
4.1
8.7
17.6
19.9
34.8
33.6
32.0
15.7
2.7
2.8
0.6
Top of the unit should not contact any building structure or object.
2.0
10.0
9.2

Clearance Requirement

8
INSTALLATION (cont.)
1/2 in THREADED ROD (MIN. 123 lb (56 kg) LOAD CAPACITY)
SEE MOUNTING DETAIL
VIBRATION ISOLATOR (MIN. 123 lb (56 kg) LOAD CAPACITY)
1/2 in THREADED ROD
(MIN. 123 lb (56 kg)
LOAD CAPACITY)
1/2 in NUT
1/2 in WASHER
MOUNTING BRACKET
1/2 in WASHER
1/2 in NUT
1/2 in JAM NUT

Mounting the CM12 to a Roof Structure

WARNING: Be sure that the supporting roof structure is capable of supporting the weight of the unit, mounting hardware and the accessories (Roof structure should be capable to support four times of total weight or more. Unit weight is 123 lb (56 kg).
Be sure to securely anchor the top ends of the suspension rods. Make sure all nuts are tight. Be sure to follow all applicable codes.
The CM12 unit is usually mounted above the ceiling and must be securely mounted to the roof structure. The ceiling support of the existing building may require reinforcements.
Use field-supplied threaded 1/2 inch suspension rods, washers, nuts and vibration isolators.
The recommended clearance between ceiling grids and building the structural member is the unit height plus 3.0 inch (76 mm).
ALL MOUNTING HARDWARE FIELD PROVIDED
Install the four field-supplied rods by suspending them from suitable building structure members. Locate the rods so that they will align with four mounting holes in the mounting bracket that are part of the unit base.
WARNING: Wear gloves to
Tightening torque for nuts: 3.02
avoid injury during installation.
ft•lbf (4.1 N•m)
CAUTION: Make sure the unit is level (must be less than 2° incline).
9
INSTALLATION (cont.)
CIRCUIT BREAKER WITH GROUND-FAULT PROTECTIVE
FUSE 20 A MAX.
RTG
RTG
TERMINAL BLOCK OF CM12
GROUND TERMINAL

Power Supply Requirements

• The CM12 requires a single-phase 115 V, 60 Hz power supply to operate.
• The power supply should be a dedicated single outlet circuit with a UL approved short-circuit and ground fault protective breaker with a fuse size of 20 A maximum.

Service Panel Access

1. Access service panel by
removing 4 screws.
Tightening torque for screw: 1.10 ft•lbf (1.5 N•m)
2. Remove the service panel.
10
INSTALLATION (cont.)
POWER CORD
DRAIN PIPE
CONDENSATE PAN
DRAIN FOR MAINTENANCE

Power Connection

Connecting Power Supply to Unit

The following are recommended wire sizes and electrical ratings:
Cord Type: SJT (3 wires) or equivalent
Wire Gauge: 14 AWG
Voltage Rating: 300 V minimum
Heat Resistance: 140 °F (60 °C)
1. Remove service panel from the right side of CM12 unit.
2. Route power cord wires through the opening of the left grommet connector located below service panel. Tighten the grommet connector at about 0.15 ft•lbf (0.2 N•m) torque.
3. Connect the neutral wire (white color label “R”) to the center screw connection of terminal block. Tighten screw at about 0.96 ft•lbf (1.3 N•m) torque.
T
G
R
4. Connect the line wire (black color label “T”) to the left screw connection of terminal block. Tighten screw at about 0.96 ft•lbf (1.3 N•m) torque.
5. Connect the ground wire (green color label “G”) to brass screw located below terminal block. Tighten screw at about 0.96 ft•lbf (1.3 N•m) torque.
WARNING: All electrical work, if necessary, should only be performed by qualified personnel. Repair to electrical components by non-certified technicians may result in personal injury and/or damage to the unit.

Drain Hose Connection

The CM12 is equipped with an internal condensation removal pump. Maximum lift is 4 feet (1.2 m).
1. Use the provided 1/2 inch (13 mm) female connection on the unit for the evaporator coil condensate drain. The drain line must be located so it will not be exposed to freezing temperatures. The drain should be the full size of the drain connection. (Connect the drain hose to the condensation drain or the janitor closet.)
2. A 1/2 inch (13 mm) ID (5/8 inch (16 mm) OD), PVC tubing is required for the drain. Insulate the drain hose; condensation may occur during humid conditions. (Field supplied material)
11
INSTALLATION (cont.)
RED STOPPER
MAX. 3 ft
(0.9 m)
MAX. 4 ft (1.2 m)
1/4 inch (6 mm) PER FOOT OR MORE
Drain Hose Connection (cont.)
1. Plug in the 1/2 inch (13 mm) drain hose with the lose clip into the drain pipe. Make sure the hose is all the way in and flush with the grommet.
2. Position the clip to the top of the drain pipe near the unit as shown.
3. Pull out the red stopper and secure hose. Make sure there are no kinks or bends. When using the gravity drain, make sure the hose is connected as a decline.
Note: Do not use more than 4 feet (1.2 m) of drain hose vertically. This is maximum lift of the condensation pump.
To insure proper drainage, locate the drain hose to the highest vertical position, no more than 4 feet (1.2 m) high, and run the hose to the drain, run the drain hose on a downward slope at a minimum rate of 1/4 inch (6 mm) per foot.

Check following items:

1. No kinks or bends on the drain hose
2. No trap in the drain hose
3. The end of the drain hose should be highter than the water level at the drain
4. No dripping from the drain hose at the clamping area
DRAIN HOSE ARRANGEMENT
SLOPE
ABOVE DRAIN
CM12
NO TRAP TO DRAIN HOSE
When uninstalling the unit, empty the drain pan by draining out the water through the drain pan drain pipe.
WATER
12
CM12
NO TRAP
NO POOL
INSTALLATION (cont.)
Wall Thermostat Connector Name
CM12 WIRES
Label Name Color
Function
RC
Y
G
G1
RC
Y
G
G1
Brown
Red
Orange
Yellow
Common
Cool On/Off
Fan On/Off
Fan Hi/Lo

Packing Attachment

Apply include “Packing I” (provided) and “Packing II” (provided) to the cold air outlet flange to prevent condensation in high humidity environments.
1. Release the liner on Packing I and apply to outside flange cylinder of the ring as shown.
2. Release the liner on Packing II and apply to edge of Packing II as shown.
PACKING I
PACKING II

Wall Thermostat Connection (Millivolt System ONLY)

Preparation for Wall Thermostat Connection

1. Use with a single stage wall thermostat. Thermostat type: Millivolt System
2. Set the wall thermostat to cooling system mode, since most wall thermostats are designed for both heating and cooling.
3. Prepare the wire harness for connection from the unit to the thermostat. The recommended wire size is: Wire Type: Thermostat cable / Solid wire 16 ~ 26 AWG
4. Identify the thermostat connectors labeled G, G1, Y, and RC. G (Fan On/Off), G1 (Fan Speed Hi/Lo), Y (Cooling On/Off) and RC (Cooling Transfer - Common)
Connecting Thermostat to CM12 Unit
13
INSTALLATION (cont.)
CM12 UnitThermostat
(Millivolt System)
Orange Wire
G
Y
RC
G1
Red Wire
GYWRCRHOB
Brown Wire
Yellow Wire
Remove Factory-Installed Jumper
Use only with thermostat that has Fan Hi-Lo Speed control.
Note: Use thermostat that is compatible with millivolt system. Do not connect thermostat to AC power source.
5. Install the wall thermostat to the proper location inside the room where it can be conveniently accessed. Do not install the wall thermostat where unusual heating condition may occur (i.e. hot stove, hot pipe, fireplace, direct sunlight, and etc.)
Most thermostats provide these basic functions:
Fan Mode: On / Auto (Select the desired fan mode) System: Cool / Heater (Select Cool only)

Warning Signal Connection (Output Signal)

The CM12’s controller is equipped with a warning signal output relay type (Form­C, normal open dry contact), which can be used to monitor the failure condition.
Relay contactor is closed when the following condition has occurred:
a. Condensation Overflow b. Temperature Sensor fails c. Cooling Function fails
The relay output contactor is rated 5 A at 30 VDC or 5 A at 250 VAC (resistive load), and it is compatable with various warning devices such as alarm speakers, light indicators, and etc.

Connecting Warning Signal From CM12

1. Connect the warning device to CM12 signal wires label L+ and L-.
2. Use recommended warning signal wire size from 16 AWG to 26 AWG for a solid wire, or 16 AWG to 22 AWG for a stranded wire.
14
INSTALLATION (cont.)
1234
NO
“OFF” POSITION
250V 5A
OUTPUT: 12.6V-0.37A
GA09301-G ST
INPUT: 230V 115V 0
CN01
CN15CN16CN14CN02CN03CN04
CN17
CN25
CN23 CN22 CN21
4
3
52CH
RTSCTSODS
SW2
4-POSITION DIP SWITCH

Fire Alarm Control Panel Connection (Input Signal)

The CM12’s controller is equipped with a normal open input signal, which can be connected directly from the fire alarm control panel. When receiving the signal from the fire alarm control panel, the unit turns off and does not turn back on until power source is reset or turns the wall thermostat off and on.

Connecting Fire Alarm Control Panel to CM12

1. Connect the fire alarm signal wires to CM12 signal wires label E+ and E-.
2. Use recommended fire alarm signal wire size from 16 AWG to 26 AWG for a solid wire, or 16 AWG to 22 AWG for a stranded wire.

DIP Switch Configuration and Setting

The CM12’s controller is equipped with a 4-position DIP switch, which defaults in the OFF position. The DIP switch can be set to configure the following functions:
a. When the switch position #1 is ON, the evaporator and condenser fan
motor turn on. This function is used for test purposes and verification.
b. When switch position #2 is ON, the compressor, evaporator and condenser
fan motor turn on. This function is used for test purposes and verification.
c. When switch position #3 is ON, the compressor delay timer function is
disabled.
15
d. When switch position #4 is ON, the buzzer sound function is disabled.
INSTALLATION (cont.)

Ducting With Typical Drop Ceiling

RETURN GRILL WITH FILTER REQUIRED
CONDENSER
INTAKE
CONDENSER
EXHAUST
2 ft x 2 ft,
T-bar diffuser
with 10.0 in flange
COOL AIR SUPPLY
(EVAPORATOR)
10.0 in insulated flexible duct
(6 ~ 10 ft each)
2 ft x 2 ft,
T-bar return grill with 10.0 in flange and filter
ROOM AIR
INTAKE
Use a 10.0 inch diameter insulated duct with low friction and air resistance.
The duct should be bent in a large radius. If the bending radius is less than 15.0 inch (381 mm), then use vanes or guides to reduce air resistance.
Make sure the ducts are secured in order to absorb vibration from the unit.
Avoid bending the duct suddenly and have air ducts travel in a strait line for improved performance.
• Following filed supplied hardware requires:
Insulated 10.0 inch diameter ducts
Return air grill with filter for evaporator air intake
Diffuser for cold air
• Maximum external static pressure, 0.40 IWG (100 Pa) for evaporator duct and grills
CAUTION: Do not operate CM12 without the filter installed on the return air grill.
16

FEATURES

CM12 Features

• Built-in condensation removal pump
• Built-in mounting bracket
• Built-in flange for supply and return air (room air) - 10.0 inch diameter, 2.8 inch deep cylinder for easy installation
• Fire alarm control panel connection with automatic shut off
• Automatic shut off and warning signal output and alarm for
Condensation Overflow
Unit Failure (no cooling)
Temperature Sensor Failure

INSPECTION & MAINTENANCE

Cleaning Air Filters

The air filter on the evaporator return grill should be checked weekly for dust buildup. Clean or replace air filter on a weekly basis. If the unit is used in a dusty environment, more frequent cleaning may be required.
A dirty air filter can reduce the air output, resulting in a decrease in cooling capacity.

Cleaning Condenser Air Intake

Inspect and remove dust buildup on the condenser air intake of the unit with a vacuum cleaner periodically to prevent insufficient cooling.

Ground Fault Breaker Testing

The ground fault breaker should be tested at least once a month.
17

TROUBLESHOOTING

PATTERN 1
(Internal thermistor failure)
PATTERN 4
(Fire alarm signal input)
PATTERN 2
(Pump or drain problem)
PATTERN 3
(Refrigeration system problem)
ON
OFF
ON
OFF
ON
ON
OFF
0.5 sec
0.5 sec
0.5 sec
4 sec
4 sec
1 sec

Buzzer Pattern

18
TROUBLESHOOTING (cont.)
Check the following items before calling your MovinCool reseller or a qualified technician.
CONDITION POSSIBLE CAUSE REMEDY
Unit does not operate
Insufficient Cooling / Unit operation interrumpted frequently.
1. Power supply is off Check circuit breaker.
2. Power interruption Unit will turn on automatically when power back (Some thermostats require reset).
3. Blockage of air duct Check duct for any blockages or excessive kinks in ducting.
4. Turn off signal input Check for turn off signal input (fire alarm control panel).
5. Override (Stop) switch is
active
6. Battery ran out on
thermostat
1. Blockage of Condenser air
intake or outlet in the ceiling
2. Dirty Surface of Condenser
Core
3. Dirty / Blocked filters Clean / replace air filter.
4. Excessive evaporator air
ducting
Ensure the switch is in “OPERATE” position.
Change battery.
Check any blockages in the ceiling.
Clean surface of Condenser Core.
Evaporator ducting should not exceed 10 feet (3.0 m) and bend radius should be larger than twice of duct diameter.
Beeping / Alarm coming from unit and unit stops. (Buzzer sound pattern indicated on page 18.)
5. Blockage of Condenser air
intake or outlet in the ceiling
6. Outside of operating range Use within operating temperature
1. Internal thermistor failure
(Sound pattern 1)
2. Pump or drain problem
(Sound pattern 2)
3. Refrigeration system
problem (Sound pattern 3)
4. Receiving fire alarm signal
input (Sound pattern 4)
Remove the blockage.
range.
Replace internal thermistor.
Check for drain connection and blockage, kink or bend on drain hose. (See “Drain Hose Connection” on page 11.)
Turn off power source and contact your MovinCool reseller or a qualified technician.
Reset power source or turn the wall thermostat off and on.
If conditions persist after the above actions have been taken, turn the unit off, disconnect the power and contact your MovinCool reseller or a qualified technician.
19
TROUBLESHOOTING (cont.)

CM12: Installation Check Sheet

ITEMS
Installation Unit Check and make sure all screws are tight and
unit is secured in place.
Check and make sure inlet / outlet air exhaust are clear without blockage.
Wiring Check and make sure the unit is properly
connected to the dedicated circuit breaker.
Check and make sure all wiring are properly connected and secured.
Check and make sure ground wire is tighten and secured.
DIP Switch Setting Check and make sure all DIP switches
located on relay board are set to “OFF” positions.
Before Test Operation
Test Operation
Drain Hose Connection
Grill Installation Check and make sure that grill is secured and
Wall Thermostat Check and make sure wall thermostat is
Other Remove card board on condenser inlet side.
Maintenance Switch Check and make sure override switch located
Check Operation with Wall Thermostat
Abnormal Noise Check and observe abnormal noise during
Check and make sure that drain hose provided with heat insulator to prevent condensation on hose surface.
properly installed.
connected properly to unit.
below maintenance’s panel is at “OPERATE” position before test operation.
Set wall termostat to Fan On or Fan Only mode to confirm fan only mode operation.
Set wall thermostat to Fan Auto or Cool mode operation. During cool mode operation, check and cinfirm cooling operation after delay timer is expired. (Note: Delay timer vary from 2 ~ 5 min depending on thermostat model used.)
Blowing/Cooling operation.
Drain During cooling operation, check and observe
condensation drip through normal drainage path.
Air Leakage Check for air leakage from duct and duct
connection.
20

TECHNICAL SPECIFICATIONS

ITEM SPECIFICATIONS
Electronic Features Control Millivolt Thermostat
(Field supplied)
Electrical Characteristics Voltage Requirement Single-Phase, 115 V, 60 Hz
Operating Voltage Range
Max. 127 V Min. 104 V
Recommended Fuse Size 15 A
Cooling Capacity and Power Consumption
*1
*1
*1
*1
10,500 Btu/h (3,090 W)
7,200 Btu/h (2,100 W)
1.23 kW
11.2 A
Evaporator: 80 °F (27 °C), 50 %RH Condenser: 95 °F (35 °C), 50 %RH
Total Cooling Capacity
Sensible Cooling Capacity
Power Consumption
Current Consumption EER 8.5
*1
*1
*1
*1
9,300 Btu/h (2,730 W)
7,000 Btu/h (2,040 W)
1.22 kW
11.1 A
Evaporator: 72 °F (22 °C), 50 %RH Condenser: 95 °F (35 °C), 50 %RH
Total Cooling Capacity
Sensible Cooling Capacity
Power Consumption
Current Consumption
EER 7.6 Compressor Type of Compressor Hermetic Rotary Evaporator Type of Fan Centrifugal Fan
Air Flow High
Low
324 CFM (550 m 228 CFM (390 m
Max. External Static Pressure 0.16 IWG (40 Pa)
3
3
/h) /h)
Condenser Type of Fan Centrifugal Fan
Air Flow
High
Low
700 CFM (1,190 m
370 CFM (630 m
Max. External Static Pressure 0.12 IWG (30 Pa) Refrigerant Type R-410A
Amount 1.59 lb (0.72 kg) Dimension W x D x H Without Flange
and Mounting Bracket
With Flange and Mounting Bracket
32.0 x 19.9 x 15.2 in
(813 x 505 x 386 mm)
34.8 x 22.7 x 15.8 in
(884 x 577 x 401 mm)
Weight Net 123 lb (56 kg)
21
3
3
/h)
/h)
TECHNICAL SPECIFICATIONS (cont.)
ITEM SPECIFICATIONS
Condensate Pump Capacity
Operating Condition Range
Maximum Duct Length
Maximum Sound Level
*2
Pump Rate 5.0 gal/h (19 L/h)
Max. Head 4 ft (1.2 m)
Evaporator Air
Inlet
Condenser Air
Inlet
*3
Cold Duct 20 ft (6.1 m)
Hot Duct 10 ft (3.0 m)
*4
High 52 dB (A)
Low 52 dB (A)
Max. 95 °F (35 °C), 50 %RH Min. 65 °F (18 °C), 50 %RH Max. 113 °F (45 °C), 50 %RH Min. 65 °F (18 °C), 50 %RH
• Specifications are subject to change without notice.
Note: *1: With two 6-foot (1.8 m) ducts containing one 90° bend each, supply grill and
return grill with filter [0.16 IWG (40 Pa) external static pressure] on high fan speed.
*2: When ambient temperature is lower than 65 °F (18 °C), operation may be
interrupted due to anti-freeze protection activation.
*3: Confirm pressure drop of duct, grills, and filter with manufacture’s
specifications.
*4: Measured at 3 feet (1.0 m) under the ceiling with evaporator duct and ceiling
tile.
22
WARRANTY STATEMENT
DENSO PRODUCTS AND SERVICES AMERICAS, INC. ("DENSO") warrants its MOVINCOOL Products only to the extent stated in its official written warranties. Unless otherwise specifically provided in writing by DENSO, DENSO warrants to the original end-user that the products shall be free of defects in materials or workmanship and will function in accordance with DENSO's published specifications under ordinary intended use and service for a period listed below beginning from the date of purchase on the invoice to the end-user:
CM12 Warranty: 2 Years on the Unit and 3 Years on the Compressor with warranty registration OR 1 Year on the Unit and 3 Years on the Compressor for unregistered units.
DENSO shall, at its sole discretion, repair or replace any defective product covered by this warranty. Such remedy shall be end-user's sole remedy with respect to any particular defect in the products.
This warranty does not cover defects or malfunctions which result from causes beyond DENSO's control, including, without limitation, (i) unusual physical or electrical stress; (ii) accident, neglect, abuse, misuse or other abnormal use; (iii) failure to perform routine maintenance in accordance with DENSO's recommended procedures; (iv) normal wear and tear; (v) repairs or attempted repairs by an unauthorized person; (vi) modifications or alterations to the products; (vii) use with parts or devices not supplied or approved by DENSO; (viii) improper installation or service; (ix) shipping damage to any units or spare parts during shipping. This includes and is not limited to compressors, evaporators and condenser coils. This warranty shall extend only to the original end-user and shall be void if any labels or other identifying marks permanently affixed to products when shipped by DENSO are removed, altered, defaced or obliterated.
TO THE EXTENT PERMITTED BY LAW, THIS WARRANTY, AS LIMITED HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, ON THE PART OF DENSO PRODUCTS AND SERVICES AMERICAS, INC., OR DENSO CORPORATION, WHETHER ARISING FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE, INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS OF A PARTICULAR PURPOSE OR ANY LIABILITY FOR COMMERCIAL LOSSES BASED UPON NEGLIGENCE OR MANUFACTURER'S STRICT LIABILITY. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NEITHER DENSO PRODUCTS AND SERVICES AMERICAS, INC., NOR DENSO CORPORATION WILL, IN ANY EVENT, BE LIABLE FOR LOST PROFITS, COSTS OF PROCESSING, INJURY, GOODWILL, OR ANY OTHER CONSEQUENTIAL DAMAGES OF ANY KIND ARISING FROM BREACH OF THIS WARRANTY.
DENSO PRODUCTS AND SERVICES AMERICAS, INC. reserves the right to make changes without prior notice. MovinCool®, Office Pro® and SpotCool® are registered trademarks of DENSO Corporation.
PURCHASE DATE:
SERIAL NUMBER:
P/N: 484007-3433EN Fourth Issue: March 2015
Loading...