Congratulations on purchasing the MovinCool portable air conditioner. This
manual explains how to install and operate the MovinCool Classic Plus 14, and
Classic Plus 26 portable air conditioning units. Please read this operation manual
thoroughly to familiarize yourself with the features of the unit and to ensure years
of reliable operation.
You may also find it useful to keep this operation manual on hand for reference.
Components and/or procedures are subject to change without prior notice.
Definition of Terms
WARNING: Describes precautions that should be observed in order to
prevent injury to the user during installation or unit operation.
CAUTION: Describes precautions that should be observed in order to
prevent damage to the unit or its components, which may occur during
installation or unit operation if sufficient care is not taken.
Note: Provides additional information that facilitates installation or unit operation.
5
GENERAL WARNINGS & CAUTIONS
1.All electrical work, if necessary, should only be performed by qualified
electrical personnel. Repair to electrical components by non-certified
technicians may result in personal injury and/or damage to the unit. All
electrical components replaced must be genuine MovinCool parts, purchased
from an authorized reseller.
2.The proper electrical outlet for MovinCool units must be equipped with a UL
approved circuit breaker.
3.Because of potential safety hazards under a certain condition, we strongly
recommend against the use of an extension cord.
However, if you still elect to use an extension cord, it is absolutely necessary
that it is a UL listed, 3-wire grounding type appliance extension cord, having a
3-blade grounding plug and a 3-slot receptacle that plugs into the appliance.
The marked rating of the extension cord should be 115 V, 15 A for Classic Plus
14, and 230 V, 20 A for Classic Plus 26 or equivalent.
4.The Classic Plus 14 is equipped with a 10 ft (3.0 m) UL approved LCDI power
cords. The Classic Plus 26 is equipped with a 6 ft (1.8 m) UL approved LCDI
power cord. For replacement, fixed location (hardwire) or power cord
lengthening (extension cord) cords are required, contact your MovinCool
reseller or a qualified electrician for approved replacement methods.
5.Never fold or place heavy objects on the power cord.
This could result in damage to the power cord causing electrical shock or fire.
6.Do not place water or any other liquid on the unit. This can cause damage to
the unit and increase the risk of electrical shock.
7.Do not sit or stand on the unit.
6
INVENTORY & ASSEMBLY
Inventory
After unpacking your MovinCool unit, please check to make sure you have the
following items:
1.Classic Plus 14 or Classic Plus 26 MovinCool Unit (1)
2.Cool Air Outlet Ducts (2)
3.Screws (8)
4.Operation Manual/Product Registration (1)
Note: If any of these items were not included in the box or appear damaged,
please contact your MovinCool reseller for replacement.
COOL AIR
OUTLET DUCT(S)
MOVINCOOL UNIT
SCREWS
OPERATION MANUAL /
PRODUCT REGISTRATION
7
INVENTORY & ASSEMBLY (cont.)
)
Assembly
CAUTION: Before assembling make sure the unit is on a flat, level
surface and the casters are in the LOCKED position.
(Both the Classic Plus 14 and Classic Plus 26 MovinCool units have
locking swivel casters in the front only.)
UNLOCKED
LOCKED
Install each cool air outlet duct using 4 screws each as shown.
Note: Do not over tighten the screws when installing the cool air outlet ducts. This
could damage the base on the cool air outlet duct assembly.
COOL AIR OUTLET
DUCT (2)
SCREW (4 PER DUCT
8
INSTALLATION
Choosing an Installation Site
CAUTION: Following are some precautions to consider before
choosing your installation site. Please review carefully as improper
installation may result in personal injury or damage to the unit.
1.Do not use the unit in areas where leakage of flammable gas may occur.
2.Do not use the unit in areas where it is exposed to rain or water.
3.Do not use the unit in an atmosphere of excessively corrosive gas or vapor.
4.Do not use in areas where the temperature is outside the allowable operating
range.
5.Do not install the unit in sloping areas. The unit may move or topple over even
if the casters are set to the LOCKED position.
6.Install the unit in areas that can with-stand the weight of the unit. The Classic
Plus 14 unit weighs approximately 201 lb (91 kg), and the Classic Plus 26 unit
weighs approximately 234 lb (106 kg) when the drain tank is full of water.
7.Allow 18.0 in (457 mm) of unobstructed airflow for both the air inlets and
outlets.
8.Do not use the unit at condition above 113 °F (45 °C) 50 %RH.
9
INSTALLATION (cont.)
Moving the Unit
Unlock the casters and push the MovinCool unit to a flat level surface and set the
casters back to the LOCKED position.
UNLOCKED
LOCKED
10
INSTALLATION (cont.)
Plugging in the Unit
1.Check the prongs and surface of the power cord plug for dust/dirt. If dust and/
or dirt are present, wipe off with a clean, dry cloth.
2.Check the power cord, plug and prongs for damage or excess play. If any
damage or excess play is found, contact your MovinCool reseller or a qualified
technician for repair.
WARNING:
1.If the power cord or plug is damaged, repair should only be
performed by qualified electrical personnel.
2.Do not connect/disconnect the power cord or attempt to operate
buttons with wet hands. This could result in electrical shock.
CAUTION:
1.Classic Plus 14 ONLY: The AC outlet (115 VAC Single Phase, 60 Hz)
needs to be rated at 15 A or higher. Do not share the outlet with any
other instrument or equipment.
2.Classic Plus 26 ONLY: The AC outlet (208/230 VAC Single Phase,
60 Hz) needs to be rated at 20 A or higher. Do not share the outlet
with any other instrument or equipment.
Note:
1. Make sure the AC outlet is free of dirt, dust, oil, water, or any other foreign
matter.
2. The Classic Plus 14 is equipped with a UL approved LCDI cord and an
approved NEMA plug configuration (5-15). The appropriate outlet must be
used for this plug type.
3. The Classic Plus 26 is equipped with a UL approved LCDI cord and an
approved NEMA plug configuration (6-20). The appropriate outlet must be
used for this plug type.