Movincool CLASSIC40 Service Manual

Page 1
Page 2
Page 3
Fig. 1-1 Circuit of Auxiliary Relay
GENERAL DESCRIPTION
1. GENERAL DESCRIPTION
Generally speaking conventional air condition­ers cool the entire enclosed environment. They act as “heat exchangers”, requiring an interior and an exterior unit (condenser) to exhaust exchanged heat to the outdoors.
Unlike conventional air conditioners, the SPOT COOL is a cooling system which directs cool air to particular areas or objects.
SPOT COOL has the following features;
1) Compact Design
The innovative design of SPOT COOL has resulted in one compact design, replacing the need for two separate units.
Fig. 1-2 Air Flow of Spot Cool
2) Easy Installation
With the whole cooling system built into one compact unit, SPOT COOL requires no pipe work for refrigerant and installed easily. In this case, cooling air duct work is required.
3) Energy Conservation
SPOT COOL is economical because it cools only the area or objects which need to be cooled, not the entire room.
1
Page 4
CONSTRUCTION, SPECIFICATIONS and DATA
2. CONSTRUCTION AND SPECIFICATION
2-1. Construction
Fig. 2-1 Construction of Hermetric Rotary Type Compressor
2
Page 5
CONSTRUCTION, SPECIFICATIONS and DATA
1) Basic Construction
The SPOT COOL is compact in construction because the condenser and the evaporator are enclosed in one unit. The interior is divided into two sections. The front face is equipped with the evaporator and control box. The rear section contains the condenser and the compressor.
2) Air Flow (See Fig. 1-2)
1. Air flow for the condenser Air is taken through apertures in the rear face and both sides of unit to cool the condenser and discharged through the exhaust air duct at the top of unit.
2. Air flow for the evaporator Air is taken from the front face of unit, cooled via the evaporator, and blown off from the aperture in the unit top. Using a cooling air duct (option, to be installed on the field), blow cool air against an object to be cooled. All air inlets are provided with air filters.
3
Page 6
CONSTRUCTION, SPECIFICATIONS and DATA
2-2 Specifications
Item Model 30HU
[Rating Condition] DB 35˚C WB28.2˚C
95˚F 83˚F
(60%) [Features]
Power frequency ..................................................... (Hz) 60
Line Voltage .......................................................... (Volt) Three phase 220
Power consumption ............................................... (Kw) 4.7
Current consumption .......................................... (Amp) 70
Power factor ........................................................... (%) 88
Starting current ................................................... (Amp) 70
Power wiring .......................................................(AWG) 12 (4-core)
[Cooling Unit]
Cooling capability ............................................. (Kcal/h) 9830
(Btu/h) 39000 Cooling system Direct expansion [Blower] Type of fan Sirroco fan
Air volume ...........................................................(m3/h) 1800
(ft3/min) 1060
Motor output .......................................................... (Kw) 0.75
[Compressor] Type Hermetic
reciprocating type
Output .................................................................... (Kw) 2.2
Refrigerant R-22
(kg) 2.0
Packed amount of refrigerant ................................ (lbs) 4.4)0
[Safety Device] Overcurrent relays (for compressor, evaporator fanwith motor and condenser fan motor) Compressor overload relay with Fan motor protectors (for evaporator and condenser)with High pressure switch with Anti-freezing thermostat with [Dimensions and Weight]
W x D x H .............................................................. (mm) 12100 x 650 x 985
(inch) 43.3 x 25.6 x 38.8
Weight ..................................................................... (kg) 160
(lbs) 353 [Operating Conditions] Inlet air MAX. 45˚C (113˚F), 50%
MIN. 25˚C (77˚F), 50%
Fig. 2-1 Construction of Hermetric Rotary Type Compressor
4
Page 7
REFRIGERANT SYSTEM
3. REFRIGERANT SYSTEM
The component parts of the refrigerant system include the followings;
• Compressor • Evaporator
• Condenser • Modulating tank
• Capiliary tub • High pressure switch
These parts are all connected by copper piping. All the connections have been brazed.
Fig. 3-1 Refrigerant system of MODEL 30HU
5
Page 8
REFRIGERANT SYSTEM
3-1. Compressor
The compressor used for this unit is a reciprocating type. It is a hermetic compressor which incorpo­rates a drive motor and a compression mechanism in an enclosed vessel.
3-1-1. Construction
The reciprocating type compressor consists of a drive section (motor) and a compressin mecha­nism as shown in Fig. 3-2. When the rotor shaft of motor rotates, the crank shaft causes the piston to reciprocate in the cylinder and absorb and compress the refrigerant. Main components are the motor, crank case, bearing, crank shaft, cylinder, piston, etc. The motor and compression mechanism are supported by a spring inside the outer shell so that vibration of the compressor does not transmit directly to the outside. The out shell is on the low pressure side, in which gas flows from the evaporator. This gas cools the motor and compression mechanism.
Fig. 3-2 Construction of Hermetic Reciprocating Type Compressor
6
Page 9
Fig. 3-3 Suction
REFRIGERANT SYSTEM
3-1-2. Operation
1) Suction
When the piston is pushed down, pressure inside the cylinder lowers. When this pressure becomes less than the suction side (low pressure side) pressure, the suction valve at the top of the cylinder is pushed open by the suction side pressure and the refrigerant is sucked into the cylinder. See Fig. 3-3.
2) Compression
The refrigerant in the cylinder is pushed up by the piston. As its capacity reduces, its pressure increases gradually. See Fig. 3-4.
Fig. 3-4 Compression
Fig. 3-5 Discharge
3) Discharge
When the refrigerant pressure in the cylinder becomes higher than the pressure on the delivery side (hight pressure side) of the compressor, the discharge valve opens to deliver the compressed refrigerant to the discharge side. See Fig. 3-5.
3-1-3. Lubrication of Compressor
In the lubrication system, lubricant from the thrust pad hole enters an eccentric hole in the crank shaft. Here, forced by centrifugal force, the lubricant rises the eccentric hole, enters the spiral groove in the shaft, and rises while simultaneously lubricating the bearing and subsequent areas.
Fig. 3-6 Lubrication of Compressor
7
Page 10
REFRIGERANT SYSTEM
3-2. Condenser
The condenser, which serves as a heat exchanger, has thin aluminum projections called spine fins fastened toa copper tube. Heat is exchanged by forcing cooler air across the condenser fins.
3-3. Capillary Tube
The following table shows the specifications of the capillary tube.
Model Qty Purpose of Use I.D, (mm) Length (mm)
30HU 4 FOR COOLING Ø1.4±0.02 445
3-4. Evaporator
The evaporator is a heat exchanger using plate-fins and tubes. It is mounted at the front face of the unit, located on the suction side of the blower.
8
Page 11
Fig. 3-7 Modulating Tank
REFRIGERANT SYSTEM
3-5. Modulating Tank
The modulating tank consists of a copper pipe and tank sections, each being separated from the other. The pipe connects to the evaporator outlet at one end and to the suction pipe of the compressor at the other; the tank connects to the evaporator inlet.
The modulating tank is covered with a heat insulator that eliminates thermal effects from ambient temperature. It varies the quantitiy of refrigerant in the refrigerating cycle for optimum operating condition: it stores part of refrigerant under light load and delivers additiona refrigerant to the cycle under heavy load.
3-6. High Pressure Switch
The high pressure switch prevents the con­denser and compressor from being damaged by an excessively high pressure in the high­pressure end of the refrigerating cycle, i.e., the refrigerant condensing pressure.
Fig. 3-8 High Pressure Switch
The switch is normally closed. The diaphragm detects variations in pressure and, as the pressure increases, the snap disk snaps back to pucsh the pin down, causing the internal contacts to open. This generates a signal to open the auxiliary relay.
Possible causes of this trouble include:
1) The condenser air filter is seriously con­taminated and clogged.
2) Defective condense blower.
9
Page 12
REFRIGERANT SYSTEM
3-7. Piping
The parts of the cooling system are connected by copper pipe.
In the unit, the refrigerant cycle is enclosed. Each connection has been brazed. the circled portion in the figure shows the parts which have been brazed.
Fig. 3-9 Refrigerant System Piping for MODEL 30HU
10
Page 13
4. ELECTRICAL SYSTEM
The component parts of the electrical system include the following:
• Control box • Overcurrent relays
• Control switch • Relays
• Fan motor • Lamps etc.
• Compressor motor
ELECTRICAL SYSTEM
Fig. 4-1 Electrical System for MODEL 30HU
11
Page 14
ELECTRICAL SYSTEM
4-1. Control Box
The interior of the control box is shown in the figure below.
Fig. 4-2 Main Control Box
Fig. 4-3 Sub Control Box
12
Page 15
Fig. 1-1 Circuit of Auxiliary Relay
ELECTRICAL SYSTEM
4-1-1. Auxiliary Relay
When the power is supplied to the unit, this relay is energized across terminals 7 and 8 closed across terminals 5 and 3 and across 6 and 4. These states remain unchanged in all operation modes (FAN or COOL). If one of the errors mentioned below has occurred at the unit, the auxil­iary relay is deenergized across terminals 7 and 8, and opened across terminals 5 and 3 and across 6 and 4. This shuts off power to the fan motor relay and compressor motor relay and accordingly brings the unit to a stop. Also, the relay is closed across terminals 6 and 2 to turn on the warning lamp.
1. Abnormally large current has flown in the evaporator fan motor.
Specifications
Rated Voltage: AC230 volts
Rated current: 10 Amps
UL Recognized; file E43028
2. Abnormally large current has flown in the condenser fan motor.
3. Abnormally large current has flown in the compressor motor.
4. Compressor motor temperature has risen abnormally.
5. High pressure has risen abnormally.
Fig. 1-1 Circuit of Auxiliary Relay
13
Page 16
ELECTRICAL SYSTEM
4-1-2. Fan Motor Relay
This fan motor relay is closed when the unit is in operation of FAN and COOL mode, and supply power to the fan motor of the evaporator. In the following case, the relay opens to cut off power to the fan motor.
When the auxiliary relay is opened by the overcurrent relay OFF, compressor overlaod relay OFF or high pressure switch OFF.
Specifications
Rated Voltage: AC230 Volts
Rated current: 15 amps
UL listed file No.:E43028
Fig. 4-6 Circuit of Fan Motor Relay
4-1-3. Compressor Relay
This compressor relay is closed when the unit is in operation of only COOL mode and supply power to the compressor. In the following case, the relay opens to cut off power to the compressor.
When the auxiliary relay is opened by the high pressure switch OFF, overcurrent relay OFF or compressor overload relay OFF.
When the evaporator is freezed. (Thermo­stat OFF)
Specifications
Rated Voltage: AC230 Volts
Rated current: 30 amps
UL listed file No.:E43028
Fig. 4-7 Fan Motor Relay
Fig. 4-8 Circuit of Compessor Relay
14
Page 17
Fig. 4-9 Compressor Relay
ELECTRICAL SYSTEM
4-1-4. Overcurrent Relay
For three-phase blower motor and com­pressor motor, an overcurrent relay is usually used as a safety device. The overcurrent relay prevents motor coil from burning if overcurent has flown into the motor due to abnormal load applied to the blower motor or compressor motor, extraordinary change in supply voltage, or loss of current in one phase. If overcurrent flows into the heating coil would around the bimetal strip, the bimetal strip curls, thereby opening the output contact (across terminals 95 and 96). This output contact shuts off the auxiliary relay circuit and brings the unit to a stop.
Fig. 4-10 Internal Construction of Over Current Relay
Fig. 1-1 Circuit of Auxiliary Relay
UL recognized: File E78841
Current Setting
For compressor motor 16A
For evaporator fan motor 2.8A
For condenser fan motor 2.0A
15
Page 18
ELECTRICAL SYSTEM
4-2. Control Switch
The control switch is employed to start or stop operation. This switch is of 250V, 20A rating rotary type (3-position).
The switching positions are OFF-FAN-COOL. Each contact is switched by the cam uniting with the shaft.
When the unit is hung from the ceiling, pulling the pull cord allows operation of the control switch.
Switch Terminals OFF FAN COOL
(5) - (2) Conduct OFF OFF
(5) - (1) OFF Conduct Conduct
(5) - (4) OFF OFF Conduct
Fig. 4-12 Control Switch
Fig. 4-13 Control Switch
16
Page 19
Fig. 4-14 Fan Motor
ELECTRICAL SYSTEM
4-3. Fan Motor
The fan motors are of three phase, induction type.
The following table shows the specifications of the fan motors.
When the control switch is set to FAN, the evaporator fan motor rotates. When it is set to COOL, both the evaporator and condenser fan motors rotate.
Model/Spec. Rated Voltage (Volt) Rated Output (Watt)
For Evaporator 220 750
For Condenser 220 400
4-4. Compressor Motor
The compressor motor is a three phase motor. This motor is built in the compressor. (Refer to 3-1.)
Specifications
Rated Voltage: 220V
Rated Output: 2200W
17
Page 20
ELECTRICAL SYSTEM
4-5. Thermostat
When the evaporator has freezed, the contacts of thermostat open to stop the compressor and the ventilating operation is automatically initiated. When the evaporator is unfreezed, the contacts close to restart the compressor and the cooling operation is initiated.
The heat sensing tube of thermostat is mounted at the evaporator outlet tube and is insulated from surrounding air by het insulating material. The setting of thermosate is fixed at -1.5˚C when the contacts are open and at +14.5˚C when the contacts are closed.
Fig. 4-15 Thermostat
18
Page 21
4-6. Wiring
Power supplied cord is applied with 12AWG (4-core) wires.
Proper connections are indicated at all the wire ends. Faston type No. 250 or 187 terminals are used.
ELECTRICAL SYSTEM
Fig. 4-16 Wiring Diagram
19
Page 22
ELECTRICAL SYSTEM
5. DATA
5-1. Exterior Dimensions Diagram
Fig. 5-1 Exterior Demensions of MODEL 30HU
20
Page 23
5-2. Construction diagram
ELECTRICAL SYSTEM
Fig. 5-2 Construction Diagram of MODEL 30HU
21
Page 24
ELECTRICAL SYSTEM
5-3. Cooling Capability Characteristics
1) Cooling Capability curve
Fig. 5-3 Cool Capability Curve
2) Current consumption curve
Fig. 5-4 Current Consumption Curve
22
Page 25
3) Cool air temperature difference curve
ELECTRICAL SYSTEM
Fig. 5-5 Cool Air Temperature Difference Curve
4) Static pressure and air volum curve of cool air
Fig. 5-6 Static Pressure and Air Volume Curve
23
Page 26
24
Page 27
Repair
1. TROUBLESHOOTING .............................................................................. 24
2. INSPECTION OF UNIT ............................................................................ 26
3. DISASSEMBLY ....................................................................................... 27
4. INSPECTION AND REPAIR OF ELECTRICAL SYSTEM .............................. 34
5. INSPECTION AND REPAIR OF REFRIGERANT SYSTEM ........................... 38
6. REASSEMBLY ........................................................................................ 47
25
Page 28
1. TROUBLESHOOTING
Before troubleshooting this system the following inspection should be performed.
a) Inspection of power source voltage and phase sequence
Check the voltage of the power source.
Model 30Hu: Three phase, 220 volt ± 15%, 6-Hz.
Check the operation and condition of the fuse or circuit breaker in the power source.
Check the rotating direction of blower. If the blower rotates in the opposite direction, phase sequence of the power source is reverse. Therefore, exchange two of the power cables connected to the power terminals R, S, and T.
b) Inspection of air filters
Remove the air filters and check the element. If it is dirty, wash it as described in the OPERATION MANUAL.
The following chars are provided as a guide for categorized problem remedies. Detailed information is contained in the following pages.
26
Page 29
27
Page 30
2. INSPECTION OF UNIT
In case of trouble, perform the following inspection before disassembly.
2-1. Inspection of Clogging at Heat
Exchanger of Evaporator and Con­denser.
Check the heat exchanger of the evaporator and condenser for dier and clogging. If they are dirty or clogged, remove and wash each part.
2-2. Examination of Operating Environ-
ment
Check the environment around the unit.
Inlet Air:
Fig. 2-1 Spine Fins of the Condenser
45˚C (113˚F), 50% or lower
25˚ (77˚F), 50% or higher
If the unit is operatied at higher temperature and/or higher himidity than above, change the place of installation. If the unit operated in an environment outside this range, evaporator will be frozen.
2-3. Inspection of Cooling Capacity
Measure the difference in temperature be­tween the inlet of evaporator and the cooling air duct.
If the difference is out of the range given in teh graph at right, perform inspection.
Fig. 2-2 Operating Environment
Fig. 2-3 Inspection of Cooling Capacity
28
Page 31
3. DISASSEMBLY
[MODEL 30HU]
Fig. 3-1 Disassembly of MODEL 30HU
29
Page 32
3-1. Removal of outer panels
1) Removal of following parts
1. Air filters
2. Exhaust duct
3. Front panel
4. Evaporator panel
5. Condenser panel
6. Right side panel
7. Rear panel
2) Remove three screws from the control box and open the control box cover.
3) Remove four screws from the sub-control box and opent the sub-control box cover.
Fig. 3-2 Removal of Parts
4) Remove four lead wires of the power wire from the terminal block. Loosen the two screws fixing conduit and disconnect the power wire.
5) Remove left side panel.
Fig. 3-3 Removal of Control Box Cover
Fig. 3-4 Removal of Power Wire
30
Page 33
3-2. Removal of Electrical Parts
1) Remove the electrical wiring according to the wiring diagram as shown below.
Fig. 4-16 Wiring Diagram
31
Page 34
2) Remove the electrical partsk in the control box and sub-control box.
Fig. 3-6 Removal of Electrical Parts
3) Remove the control switch, power indi­cated lamp and warning lamp as shown.
Fig. 3-7 Removal of Control Switch
32
Page 35
3-3. Removal of blower assembly (for evaporator)
Fig. 3-8 Blower Assembly
33
Page 36
1) Remove five wing nuts and remove the fan casing.
2) Remove the set bolt using a box wrench and their remove the sirocco fan.
NOTE:
Tightening torque for set bolt.
Fig. 3-9 Removal of Blower Housing
170~190kg-cm (12.5~13.7 ft-lb)
3) Remove four nuts and remove the blower motor.
Fig. 3-10 Removal of Sirocco Fan
Fig. 3-11 Removal of Blower Motor
34
Page 37
3-4. Removal of blower assembly (for condenser)
Fig. 2-1 Construction of Hermetric Rotary Type Compressor
1) Remove the nut (left handed screw) and fan.
NOTE:
Tightening torque for nut.
450±50kg-cm (33± 3.7 ft-lb)
Fig. 3-13 Removal of Fan
2) Remove four nuts and remove the blower motor from bracket.
Fig. 3-14 Removal of Blower Motor
35
Page 38
4. INSPECTION AND REPAIR OF ELECTRICAL SYSTEM
4-1. Inspection of Control Switch
At each position of the control switch, there should be continuity across the following terminals..
Switch Position Conducting Terminals
OFF 2 - 5
FAN 1 - 5
COOL 1 - 5, 4 - 5
If there is no switch continuity, replace the control switch.
4-2. Inspection of Warning Lamp and
Power Indicated Lamp.
Make a test circuit as shown in Fig. 4-2. If the lamp fails to light up, replace it.
4-3. Inspection of Fan Motor
Measure resistance between the each termi­nals of the fan motor. (Except grounding terminal.)
Fig. 4-1 Inspection of Control Switch
Fig. 4-2 Inspection of Lamps
Condenser fan motor: 16.2 ± 2 (at 20˚C)
Evaporator fan motor: 5.9 ± 0.6 (at 20˚C)
If the resistance is not these standard values, replace the fan motor.
Fig. 4-3 Inspection of Condenser Fan Motor
Fig. 4-4 Inspection of Evaporator Fan Motor
36
Page 39
4-4. Inspection of Thermostat
Check for coninuity across two terminals of the termostat. At normal temperature, (17˚C or higher) there is continuity across two terminals.. If continuity is interrupted across the terminals, replace the thermostat.
4-5. Inspection of High Pressure Switch
Check for continuity across two terminals of the high pressure switch. At normal pressure when the unit is stopped, there is continuity across two terminals. If continuity is inter­rupted across the terminals, replace the high pressure switch.
NOTE: Cut off pressure - 27.5kg/cm2G
(391PSIG)
Fig. 1-1 Circuit of Auxiliary Relay
Fig. 1-1 Circuit of Auxiliary Relay
Reset pressure - 20.5kg/cm2G
(291 PSIG)
4-6. Inspection of Comprssor Motor
Measure resistance across the terminals (R, S, T) of the compressor motor.
Resistance: 1.13± 0.15 (at 20˚C)
1.07 (from Oct., 1986)
If the resistance is not this standard values, replace the compressor.
4-7. Inspection of Over Load Relay.
The compressor has a built-in over load relay. Check for continuity across tow terminals of the overload relay.
Fig. 1-1 Circuit of Auxiliary Relay
At normal temperature, there is continutiy across two terminals. If continuity is inter­rupted across the terminals, replace the compressor.
Make check at the ambient temperature of 45˚C or less and more than 1 hour after operation has been stopped.
37
Page 40
4-8. Inspection of Compressor Relay
Check for continuity across the terminals when the test button is depressed and/or released.
Depressed:
All couples of terminals are conducted.
Released:
All couples of terminals are not conducted.
Measure the resistance across terminals A and B.
Standard resistance: 650 ~ 800
When the resistance is out of this range, replace the compressor relay.
4-9. Inspection of over current relays
Check for continuity across the terminals 1 ­2, 3 - 4 and 5 - 6. These couples of terminals are conducted via little resistance. At normal condition (Non power source), there is conti­nuity across terminals 96 and 95.
Fig. 4-8 Inspection of Compressor Relay
If these continuities are interrupted, replace the overcurrent relay.
NOTE
1. Do not turn the dials of over current relays.
These dials of over current relays. These dials have been factory adjusted.
2. These over current relays are automateic
resetting type.
Fig. 4-9 Inspection of Over Current Relays
38
Page 41
Fig. 4-10 Inspection of Fan Motor Relay
4-10. Inpsection of Fan Motor Relay.
Check for continuity across the terminals when the test button is depressed and when it is released.
Depressed:
All couples off terminals are conducted
Released:
All couples of terminals are not conducted.
(Couples of terminals:
11 - 12, 13 - 14, 15 - 16 and 19 - 20.)
Measure the resistance across termianls A and B.
Standard resistance: 1900~2100Ω.
When the resistance is out of this range, and/ or all couples of terminals are not conducted when the test button is depressed, replace the fan motor relay.
Fig. 4-11 Inspection of Auxiliary Relay
4-11. Inspection of Auxiliary Relay
Check for continuity between the each terminals as follows.
Measure the resistance across terminals 7 and 8.
Standard resistance: 14 ~ 16 kΩ.
When the resistance is out of this range, and/ or continuties are not as above table, replace the auxiliary relay.
4-12. Inspection of Wiring Connection
Refering to 3-2, check for connection of each wire.
39
Page 42
5. INSPECTION AND REPAIR OF REFRIGERANT SYSTEM
5-1. Inspection
When something is wrong with the refrigerant system, it fails to cool sufficiently. the possible cause of this failure is clogging, leakage or insufficient refrigerant. In such a case, inspect the system according to the following procedure.
5-1-1. Inspection of Refrigerant Clogging
Check the component parts of the refrigerant system and the pipes connecting them for clog­ging. If clogged with refrigerant, only the clogged part is frosted partially. In such a case, change the part in question.
5-1-2. Inspection of Refrigerant Leak
Carefully check all connections, and each component for leaks whenever the refrigerant system is installed or repaired.
Use the gas leak tester to inspect the system.
Fig. 5-1 Gas Leak Tester
40
Page 43
The gas leak tester should be used in the following way.
1) Check the amount of propane liquid in the container.
2) Install the propane container to the gas leak tester body by turning it fully clockwise.
3) When lighting the tester, insert the match into the ignigting hole of the tester and turn the adjust­ing handle slowly counterclockwise. This will ignite the gas leak tester.
4) The reactor (copper ring) must be red heat, but the flame must be kept as small as possible. The smaller the flame, the more sensitive.
5) Hold the tip of the sensing tube at each suspected leak.
6) Watch for a change in the flame color. If there is no leak, the flame will be almost colorless. The slightest leak will be indicated by a brightly colored flame
Color of flame:
When leak is very small Color of flame is light green.
When leak is large Color of flame is bright blue.
When leak is very large Color of flame is purple.
NOTE:
a) Always hold the tester vertically when detecting a leak.
b) Use adequate ventilation, burned R-22 is poisonous and should not be inhaled.
c) Never make a gas leak check near flammable materials.
5-1-3. Insufficient Refrigerant
In case there is a leak, clogging or trouble in the refrigerant system of the Spot Cool replace or repair the part in question. All the connections of the refrigerant system have been brazed. When removing or reassembling these connections, they must by brazed.
5-2. Repair of Refrigerant System
In case there is a leak, clogging or trouble in the refrigerant system of the Spot Cool replace or repair the part in question. All the connections of the refrigerant system have been brazed. When removing or reassembling these connections, they must be brazed.
5-2-1. Correct Brazing Work
It is desirable to use a slightly reducing flame. Normally, often used is an oxy-acetylene flame which is easy to judge and adjust the condition of the flame. Unlike gas welding, a secondary flame is used for brazing.
It is necessary to preheat the base metal proerly depending on the shape, size or thermal con­ductivity of the brazed fitting.
The most important point in flame brazing is to bring the whole brazed fitting to a proper brazing temperature. It is also important to take care not to cause overflow of brazing filler metal, oxidiza­tion of brazing filler metal, or deterioration due to the overheating of flux.
41
Page 44
(1) Proper Fitting, Proper Clearance
In general, the strength of brazing filler metal is lower than that of the base metal. So, the shape and clearance of the brazed fitting are quite important.
As for the shape of the brazed fitting, it is necessary to maximize its adhesive area. The clearance of the brazed fitting must be minimized to pour brazing filler metal into it by use of capillary attraction.
Fig. 5-2 Brazed Fitting and Its Clearance
(2) Cleaning of Brazing Filter Metal and Pipe
When the refrigerant cycle is exposed by heating, brazing filler metal may be found sticking to the inside and outside of the pipe. Brazing filler metal may also be compounded with oxygen int he air to form oxide film. Fats and oils may stick to the pipe.
In such conditions, complete brazing cannot be made. It is necessary to get rid of brazing filler metal completely by using sand paper or a solvent such as trichlene.
(3) Use of Dry Nitrogen Gas
During brazing, the inside of the pipe undergoes oxidative reaction due to the brazing flame. Con­duct dry nitrogen gas (11/min;adjust with the flow regulator) through the pinch-off tube of the refrig­erant cycle to prevent oxidization.
(4) Take care not to allow dirt, water, oil, etc. to enter into the pipe. (5) Vertical Joint
Heat the whole brazed fitting to a proper brazing temperature. Make the brazing filler metal contact with the fitting so that the brazing filler metal starts flowing by itself. Stop heating the fitting as soon as the brazing filler metal has flown into the clearance. Since the brazing filler nmetal flows easily into the portion heated to a proper temperature, it is essential to keep the whole fitting at a proper brazing temperature.
Fig. 5-3 Vertical Down Joint
Fig. 5-4 Vertical Up Joint
42
Page 45
5-2-2. Removal of Refrigerant Cycle Relatives
CAUTION:
1. When removing the brazed portion, protect the other parts with a steel plate, asbestos, etc. to keep the other parts from the flame.
2. Before removing the refrigerant cycle from the brazed portion, be sure to cut off the end of pinch-off tube and bleed the cycle of gas.
3. In this case, also bleed the refrigerant cycle of N2 gas through the open pinch-off tube in order to prevent oxidization.
Fig. 5-5 Refrigerant Cycle of MODEL 30HU
[Exchanger and Brazing Removing Portions]
Exchanger Brazing Removing Portions
Compressor A-B
Condenser A-C
Capillary tube D-F
Evaporator D-E
NOTE:
1. Evaporator include the capilliary tube.
2. Hold the compressor body, not the tubes, when carrying the compressor.
43
Page 46
5-3. Charging the System with R-22
Be sure to purge the system and charge the system with refrigerant to the specified amount in the following.
CAUTION:
1) When handling refrigerant (R-22), the following precautions should be observed. A) Always wear eye protection while handling refrigerant. B) Keep the refrigerant container blow 40˚C (104˚F). C) Do nnot handle refrigerant in an enclosed room. D) Do not handle refrigerant near an open flame (especially never while smoking a cigarette). E) Discharge refrigerant slowly, when purging a system. F) Be careful the liquid refrigerant does not contact skin.
2) If liquid refrigerant strikes eye or skin. A) Do not rub the eye or skin. B) Splash large quantities of cool water on the eye or skin. C) Apply clean petroleum jelly to the skin. D) Rush to physician or hospital for immediate professional treatment. E) Do not attempt to treat it yourself.
5-3-1. Connection of Gauge Manifold
(1) Cut off the crushed end of the pinch-
off tube at the high pressure side of the refrigerant cycel with a pipe cutter.
(2) Fit the process tube fitting to the
pinch-off tube on both sides.
Fig. 5-6 Mounting of process tube Fitting
44
Page 47
Fig. 5-7 Connection of Gauge Manifold
(3) Connect the charging hoses (red one
on high pressure side, and blue one on low pressure side) of the gauge manifold to the process tube fittings.
NOTE: Connect the hoses using care not to mistake the high pressure side for the low pres­sure side and vice versa.
(4) Connect the charging hose (green) at
the center of the gauge manifold to the vacuum pump.
5-3-2. Purging
(1) Open the high pressure valve (HI) and
the low pressure valve (LO) of the gauge manifold.
Fig. 5-8 Purging
(2) Turn on the vacuum pump to start
purging. (Purge the system for approx. 15 minutes.)
(3) When the negative pressure gauge
reading (degree of vacuumization) reaches 750 mmHg or larger, close the high pressure valve and the low pressure valve of the gauge manifold and turn off the vacuum pump.
5-3-3. Checking Airtightness
(1) Leave the high pressure valve and the
low pressure valve of the gauge manifold closed for five minutes or more, and confirm that the gauge pointer does not return to zero.
(2) In case the gauge pointer returns
gradually to zero, there must be a leak somewhere. In such a case, first correct the brazed portion. Purge the system once more, and confirm there is no leak.
Fig. 5-9 Checking Airtightness
45
Page 48
5-3-4. Checking Gas Leak
(1) Remove the charging hose (green)
from the vacuum pump, and connect the hose to the refrigerant cylinder (R22).
NOTE: Before this stip, fit the mouthpiece for refrigerant cylinder (service tool: No. 945502050) to the outlet of the refrigerant cylinder.
(2) Loosen the nut on the gauge manifold
sid e fo the charging hose (green). Open the valve of the refrigerant cylinder to purge air from inside the charging hose. (As soon as a “hissing” sound is heard, tighten the nut as it was before.)
Fig. 5-10 Purging Air inside Charging Hose
(3) Open the high pressure valve of the
gauge manifold. Charge the system with refrigerant until the low pressure gauge indicates 75 PSIG. (4 kg/cm2G). After charging is complete, close the high pressure valve.
(4) Check carefully for gas leak inside the
refrigerant cycle using the gas leak tester.
(5) Correct (braze) leaking portions, if any.
CAUTION:
Before checking for gas leak, fully confirm that there is nothing flammable in the area to cause an explosion or fire. Since contact of refrigerant with an open fire generates toxic gas (phosgene), take care not to breathe it.
Fig. 5-11 Charging with Refrigerant for Gas
Leak Check
46
Page 49
5-3-5. Purging (Repeat)
(1) Close the valve of the refrigerant
cylinder. Then remove the charging hose (green) from the refrigerant cylinder, and connect it to the vacuum pump.
NOTE: Keep the high pressure valve and the low pressure valve of the gauge manifold closed.
(2) In the procedure of above “5-3-2.),
purge the system until the low pres­sure gauge indicates 750mmHg or larger. (For 15 minutes or more.)
(3) After purging is complete, close the
high pressure valve and the low pressure valve of the gauge manifold..
Fig. 5-12 Purging (Repeat)
Fig. 5-13 Purging Air Inside Charging Hose
CAUTION:
Be sure to purge the system twice or more using the repetitive vacuum method.
Purge the system an additional time on rainy or humid days.
5-4. Refrigerant Charging Work 5-4-1. Refrigerant charging
(1) Remove the charging hose (green)
from the vacuum pump, and connect it to the refrigerant cylinder (R-22).
(2) Loosen the nut on the gauge manifold
side of the charging hose (green). Open the valve of the refrigerant cylinder, and purge the air from inside the charging hose.
NOTE: At this time, tighten the nut as soon as the air comes out with a “hissing” sound.
47
Page 50
(3) Place the refrigerant cylinder on a
scale. (weighting capacity: 70lbs; graduated in 0.2 oz.)
(4) Open the high pressure valve of the
gauge manifold and the valve of the refrigerant cylinder.
Charge the system with refrigerant to the specified amount, looking at the graduations of the scale.
[Specified Charging Amount of Refrigerant]
If the system cannot be charged with specified amount of refrigerant under this condition, follow the steps below:
1. Close the high-pressure valve of manifold.
Fig. 5-14 Charging with Refrigerant
2. Run the system.
3. Slowly open the low pressure valve while looking at the scale reading.
4. When the scale reads the specified amount, immediatey close the low­pressure valve.
5. Bring the system to a stop.
CAUTION:
The charging amount of refrigerant has a great effect on the colling capacity of the cooler for business use. Charge to the specified amount, always looking at the scale graduations.
(5) Close the high pressure valve of the
gauge manifold and the valve of the refrigerant cylinder.
48
Page 51
5-4-2. Removal of Gauge Manifold
(1) Pinch off the pinch-off tube with a
pinch-off tool.
(2) Remove the gauge manifold and the
process tube fitting. Crush the end of the pinch-off tube.
(3) Braze the end of the pinch-off tube.
(4) Make sure that gas leak is not ob-
served at the pinched off portion and the brazed end.
6. REASSEMBLY
Reassemble the unit in the reverse order of removal.
Fig. 5-15 Removal of Gauge Manifold
Fig. 6-1 Compressor Mounting
Described below are the parts that need special care in reassembling the unit. Perform wiring in reference to the wiring diagram.
(1) Compressor Mounting
Mount the compressor on the frame, using cushion, collar steel, spring washer, plate washer and nut.
(2) Blower Assembly Mounting
1. Mounting of blower fans (for evaporator).
Tightening Torque:
1.3 ± 0.7 lb•ft (1.8 ± 0.1 kg•m).
NOTE:
1) After reassembling, the gap between evapo­rator fan and casing should be 0.06 inches (1.5 mm) or more.
2) After reassembling, the gap between con­denser fan and exhaust duct should be 2.0 inches (5 mm) or more.
(3) Wiring Notice
Fig. 6-2 Blower Assembly Mounting
Fix the wires with clamps so that they do not come into contact with the edges of struc­ture, etc. Set the wire with clamps at the same posi­tions they were before removal.
(4) Perform Test
Perform the inspection of cooling capacity in 2-3., and check for abnormal noise or abnor­mal vibration.
49
Page 52
50
Page 53
Page 54
Loading...