MovinCool Classic 10 Service Manual

SERVICE MANUAL
CLASSIC 10
SERIAL NUMBER FROM FEBRUARY 2011 (0211) TO PRESENT
DocID: 00G00089E
© 2012 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole or in part, without the written permission of the publisher . DENSO SALES CALIFORNIA, INC. reserves the right to make changes without prior notice. trademarks of DENSO Corporation.
MovinCool®, Office Pro® and SpotCool® are registered
Table of Contents
Table of Contents

Operation Section

1. PRECAUTIONS FOR SAFETY
1.1 Foreword ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Definition of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 General Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2. SPECIFICATIONS
2.1 Exterior Dimension Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3. CONSTRUCTION
3.1 Internal Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4. REFRIGERATION SYSTEM
3
4.1 Refrigeration System Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.4 Capillary Tube. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.5 Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6 Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.7 High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
. . . . . . . . . . . . . . . . . . . . . . . . 16
5. ELECTRICAL SYSTEM
5.1 Circuit Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2 Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.3 Control Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.4 Compressor.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.5 Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.6 Temperature Thermistor. . . . . . . . . .
5.7 Drain Tank Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6. CONNECTION AND SETTING
6.1 Warning Signal Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.2 Fire Alarm Control Panel Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7. OPERATION
7.1 Operation of Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4
Table of Contents

Repair Section

8. TROUBLESHOOTING
8.1 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.2 Self-Diagnostic Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.3 Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.4 Basic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
8.5 Compressor Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8.6 Fan Motor Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8.7 Capacitor Inspection ( For Fan Motor and Compressor ). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8.8 Full Drain Switch Inspection .
8.9 Thermistor Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . 45
8.10 Wiring Connection Inspection .
8.11 Refrigeration System Inspection .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
9. DISASSEMBLY
9.1 Parts Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
9.2 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
9.3 Fan Motor Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.4 Removal of Electrical Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
9.5 Full Drain Switch Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
10. REFRIGERATION SYSTEM REPAIR
10.1 Repair of Refrigeration System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
10.2 Removal of Refrigeration System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.3 Charging the System with R-410A Refrigerant. . . . . . . . . .
10.4 Refrigerant Charging Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
. . . . . . . . 63
. . . . . . . . 69
11. REASSEMBLY
11.1 Reassembly of the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.2 Compressor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.3 Fan Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
11.4 Wiring Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 71
. . . . . . . . 72

1. PRECAUTIONS FOR SAFETY

1.1 Foreword

• This manual has been published to service the MovinCool Classic 10. Please use this service manual only when servicing this unit.

1.2 Definition of Terms

Operation Section
5
WARNING
CAUTION
NOTE Provides additional information that facilitates installation or unit operation.
Describes precautions that should be observed in order to prevent injury to the user during installation or unit operation.
Describes precautions that should be observed in order to prevent damage to the unit or its components, which may occur during installation or unit operation if sufficient care is not taken.

1.3 General Precautions

WARNING
• All electrical work should only be performed by qualified electrical personnel. Repair to electrical components by non-certified technicians may result in personal injury and/or damage to the unit. All electrical components replaced must be genuine MovinCool parts, purchased from an authorized reseller.
• When handling refrigerant, always wear proper eye protection and do not allow the refrigerant to come in contact with your skin.
• Do not expose refrigerant to an open flame.
• The power supply for this unit should be a dedicated single outlet circuit with a UL recognized short-circuit and ground-fault protective breaker to prevent electrical shock
from the unit.
• When brazing any tubing, always wear eye protection, and work only in a well ventilated area.
6
Operation Section

2. SPECIFICATIONS

2.1 Exterior Dimension Diagram

6-M6
DIA. 13.8
5.5
DIA. 4.9
13.8
6.519.5
41.5
11.5
4.0
(Unit: inch)
13.0
16.5
19.3
20.7 8.11.3
25.6
ILL00548-00

2.2 Technical Specifications

p
g
g
(
)
p
p
)
p
(
g)
g
g
(
)
)
)
p
y
p
y
g
(
)
p
ITEM Electronic Features O Electrical Characteristics
Operating Voltage
e
Ran Startin
FLA
Cooling Capacity and Power Consumption Evaporator: 95 °F (35 °C), 60 %RH
Total Cooling Capacity
Condenser: 95 °F (35 °C), 60 %RH
Power Consum Current Consum EER
Compressor
Output
Evaporator
Air Flow Motor Output*
Condenser
Air Flow Motor Output*
Refrigerant
Refrigerant Control Type Amount
Signal Connection
Fire Alarm Input (Signal Type) •No-voltage contact input
Warning Signal Output
Power Cord
NEMA Plu Gau
Configuration
e x Length
H × D × WnoisnemiD
Weight
Net Shipping
Drain Tank Ca Operating Condition Range
Maximum Duct Length
Sound Level*
acit
Inlet Air Tem
erature
Cold Duct
2
With Condenser Duct Without Condenser Duct
Safety Devices
Compressor Overload Protector Fan Motor Overload Protector Freeze Protection Thermistor Full Drain Tank Switch Automatic Restart
ressor Time Dela
Com High Pressure Interruption* Signal Input/Output
Control Devices
Temperature Control
• Specifications are subject to changee without notice. < NOTE >
*1: One motor rotates both the evaporator and the condenser fans. *2: Measured at 3 feet (1.0 m) from surface of the unit. *3: For unit serial number from November 2011 (1111) to Present.
Max. Min.
1
1
Power Interruption
Operation Section
7
SPECIFICATIONS iDnoitare
ital Programmable
gniStnemeriuqeR egatloV le-Phase, 115 V, 60 Hz
127 V 104 V
A 34tnerruC A 51eziS esuF dednemmoceR
9.7 A A 34ARL
10000 Btu/h
2940 W
)W 0231( h/utB 0054yticapaC gnilooC elbisneS
Wk 50.1noit
A 7.9noit
9.5 % 49rotcaF rewoP
yratoR citemreHepyT
0.70 kW niF etalProtaropavE fo epyT
naF lagufirtneCnaF fo epyT
265 CFM (451 m
3
/h
)aP 28( GWI 33.0erusserP citatS lanretxE .xaM
0.15 kW niF etalPresnednoC fo epyT
naF lagufirtneCnaF fo epyT
740 CFM (1258 m
3
/h) )aP 23( GWI 31.0erusserP citatS lanretxE .xaM
-
illary Tube
Ca
R-410A
1.43 lb
Contact resistance less than 100 ohm
0.65 k
2 A at 30 V (DC/AC) or less (resistive load)
5-15
14 AWG (3-core) × 10 ft (3.0 m)
19.4 × 26.5 × 41.5 in
(493 × 673 × 1054 mm)
156 lb (71 kg)
194 lb (88 kg)
5.0 gal (19 L) HR% 05 ,)C° 04( F° 401.xaM
HR% 05 ,)C° 12( F° 07.niM
40 ft (12.2 m)
tf 06tcuD toH
18.3 m 55 dB (A 58 dB (A
Included Included Included Included Included
3
120 sec Included Included Included
8
Operation Section

2.3 Characteristics

(1) Cooling capacity curve
13.9
Btu/hDry Bulb Temp. °F (°C)
3
11.9
9.9
7.9
Cooling Capacity. x10
6.0
104 (40)
95 (35)
86 (30)
77 (25)
(2) Power consumption curve
at 115 V
6859
(15) (20) (25) (30)
77 86
)C°( F° .pmeT bluB teW
ILL00563-00
1.2
1.1
1.0
0.9
Power Consumption. kWDry Bulb Temp. °F (°C)
0.8
104 (40)
95 (35)
86 (30)
77 (25)
68
(25)
(20) (30) (35)
at 115 V
77
86 95
)C°( F° .pmeT bluB teW
ILL00564-00
(3) Cool air temperature difference curve
27.0 (15)
25.2 (14)
23.4 (13)
(Delta-T) °F (°C)
21.6 (12)
19.8 (11)
18.0 (10)
16.2 (9)
14.4 (8)
12.6 (7)
Between Inlet and Outlet
Temperature Difference
at 115 V
Operation Section
9
40 50 60 70
Relative Humidity. %
ILL00565-00
10
Operation Section

3. CONSTRUCTION

3.1 Internal Structure

Room Thermistor (RTS)
Control Panel
Housing for Condenser Fan
Condenser Fan and Motor
Condenser
Compressor and Accumulator
Condenser Air Outlet
Cooling Air Duct
Housing for Evaporator Fan
Evaporator
Freeze Protection Thermistor (CTS)
Capillary Tube
Drain Tank
High Pressure Switch
Control Box
• Relay Board
• Capacitor
Locking Swivel Caster (Front)
Full Drain Switch
Caster (Rear)
ILL00549-00
Operation Section

4. REFRIGERATION SYSTEM

4.1 Refrigeration System Construction

The component parts of the refrigeration system include the following:
• Compressor, Evaporator, Condenser, Accumulator, Capillary tube, High Pressure Switch.
The parts above are all connected by copper piping with brazed connections.
Evaporator
11
Condenser
Condenser Inlet Pipe
Compressor Discharge Pipe
Condenser Outlet Pipe
Compressor
Capillary Tube
Accumulator
Condenser
Fan
Motor
Evaporator Outlet Pipe Capillary Tube
Evaporator inlet Pipe
Connecting Pipe (Evaporator to Compressor)
Connecting Pipe (Condenser to Capillary Tube)
Compressor Suction Pipe
High Pressure Switch
Flow of Refrigerant
Accumulator
Evaporator
Compressor
ILL00550-00
12
Operation Section

4.2 Compressor

• The compressor used for the unit is hermetically sealed. The compressor and the compressor motor are in one casing.
(1) Compressor construction
• The construction of a rotary type compressor is divided into two mechanisms; the drive mechanism (compressor motor), and the compression mechanism (compressor). When the rotor shaft of the motor (drive mechanism) turns, the roller (compression mechanism) rotates to compress the refrigerant.
Terminal
Stator
Rotor
Cylinder
Roller
Lubricator
To Condenser
From Evaporator
Accumulator
Strainer
Blade Discharge Valve Oil
I001675
(2) Basic compressor operation
Operation Section
13
• The roller (compression mechanism) is set eccentrically with a certain distance given from the axis of the center of the cylinder. A spring loaded blade is mounted on the cylinder. The
Discharge
Discharge
Valve
Hole
Spring Suction
Hole
Blade
roller turns to compress the refrigerant in the space between the cylinder and eccentrically mounted roller. The blade is in contact with the roller by means of spring force. The blade
Shaft
Roller
Cylinder
I000510
partitions the space between the suction side and the discharge side to keep compressed refrigerant from returning to the suction side. There is no suction valve. The discharge valve is designed not to open until the pressure of the refrigerant within the cylinder reaches or exceeds discharge side pressure. As a result, the discharge valve prevents the backward flow of re
frigerant gas.
14
Operation Section
(3) Operation
1) Start of compression
Discharge
Valve
Roller
Discharge
Valve
Roller
Blade
Blade
1) The cylinder is filled with low pressure gas.
2) Since pressure in the discharge chamber is higher than in the cylinder, the discharge valve is kept closed.
I001676
2) Suction and compression
1) The pressure in the cylinder increases gradually.
2) Refrigerant suction begins on the suction side of the cylinder.
3) The discharge valve remains closed.
I001677
Discharge
Roller
Discharge
Roller
Valve
Valve
Blade
Blade
I001678
I001679
3) Discharge
1) The pressure in the cylinder exceeds that in the discharge chamber, and the discharge valve opens.
2) On the suction side, refrigerant suction continues.
4) Completion of compression
1) When compression is completed, all of the refrigerant has been drawn from the suction chamber.
2) Operation then returns to step 1) (Start of compression) and the above process of suction and compression continues repeatedly in succession.
(4) Compressor lubrication
• The lubrication system is comprised of a
Operation Section
15
hollow shaft, an oil scraper mounted at the end face, hollow shaft, a shaft journal (shaft bearing), and the lubrication groove for the shaft journal. The lubrication groove is wider than the oil hole. When the shaft turns, oil is
Hollow Shaft
Cylinder
Eccentric Shaft
Roller
scraped upward by the oil scraper along the inside diameter of the hollow shaft. The oil is fed through the oil hole by centrifugal force, then supplied to the lubrication groove for each shaft journal, lubricating the bearing. In this lubrication system, oil enters into each bearing
Oil Feed Groove
Oil Hole
Oil Scrapper
separately and returns to the oil reservoir. This system effectively prevents bearing temperature increases, and offers high reliability. In addition, the specially treated shaft journal keeps the bearing from being damaged during high temperature operation.

4.3 Condenser

Rotor
I001680
• The condenser is a heat exchanger with copper tubes that are covered with thin aluminum projections called plate fins.
• Heat is given off and absorbed by air being pulled across the condenser fins by the centrifugal fan and then expelled through the exhaust air duct.
ILL00551-00

4.4 Capillary Tube

High Temp./High Pressure
• The capillary tube is a long thin tube that utilizes line flow resistance as an expansion valve. The length and the inner diameter of the capillary tube are determined according to the capacity of the refrigeration system, operating conditions, and the amount of refrigerant. The high pressure, high temperature liquid refrigerant sent from the condenser expands rapidly as the refrigerant is sprayed out through
the fixed orifice in the capillary tube. As a result, the temperature and state of the refrigerant becomes low and mist-like, and therefore evaporates easily.
Liquid Refrigerant
Low Temp./Low Pressure
Gas and Liquid Mixture
I001887
16
Operation Section

4.5 Evaporator

• The evaporator is a heat exchanger covered
with plate fins. Heat is removed from the air being pulled across the evaporator by the centrifugal fan. The resulting cool expelled through the cooling air ducts.

4.6 Accumulator

• The accumulator is mounted on the suction
gas piping between the evaporator and the compressor. The accumulator separates the liquid refrigerant from the gas refrigerant, allowing only the gas refrigerant to enter the compressor. In the accumulator, suction gas is led into a cylindrical vessel where the speed of the gas is decreased. This process separates the refrigerant contained in the gas by the force
air is
ILL00552-00
From Evaporator
To Compressor
I000514
of gravity, causing the refrigerant to accumulate at the bottom of the vessel. As a result, the compressor is protected from possible damage caused by liquid refrigerant intake.

4.7 High-Pressure Switch

• The high-pressure switch prevents the condenser and compressor from being damaged by excessive high pressure in the
Movable Point
high-pressure line of the refrigeration cycle. The switch is normally closed. The snap disk
Stationary Point
responds to the variations in pressure and, if pressure is abnormally high, the snap disk moves down to push the pin down, causing the
Molding by Resin
internal contacts to open. This interrupts the ground signal at the relay board which turns the compressor off.
Pressure of Refrigerant
Snap Disk
Pin
Case
Terminal
Lead Wires
I001768
Operation Section

5. ELECTRICAL SYSTEM

5.1 Circuit Diagram

For Unit Serial Number from February 2011 (0211) to October 2011(1011)
17
Dip Switch
ON
OFF (Default)
2
3
14
#1 : ON: Fan Stop Mode (Fan Auto)
OFF: Fan Operate Mode (Fan On) #2 : N/A #3 : N/A
#4 : ON: The Buzzer Sound Disabled
TB2 L­L+ E-
On Board Controller
CB
CN9
11
1 5
1
CN8
E+
Control Box
Output Signal
Fine Alarm Input
CN23
CN25
1
11
CN17
1
5
13
520D1520D2
Dip Switch
1ON234
CN13
CN12
CN11
13 3
1
CN22
2
12
11521135
52ID
CN16
1
MF
IOLF
CN21
52CT
F1
CN15 52CM
1243
R
G
CN24
MC
SC
CCCF
1
2
RB
T1
COM
R
115V
5
CN01
G
OLC
1 2
Ground (G)
T R
TB1
G
CN
AP
AC115V 1PHASE 60Hz
TB1 Terminal Block1 TB2 Terminal Block2 RB Relay Board MF Fan Motor MC Compressor Motor CF Capacitor for Fan Motor CC Capacitor for Compressor OLC Overload Protector
CTS
RTS Drain Tank SW
CN Connector for Option
Drain Pump
CTS Freeze Protection Thermistor RTS Room Thermistor G Ground CB Control Board
HPRS High Pressure Switch
HPRS
Jumper Line
ILL00553-00
18
Operation Section
For Unit Serial Number from November 2011 (1111) to Present
Dip Switch
ON
OFF (Default)
2
3
14
#1 : ON: Fan Stop Mode (Fan Auto)
OFF: Fan Operate Mode (Fan On) #2 : N/A #3 : N/A
#4 : ON: The Buzzer Sound Disabled
MF
IOLF
R
G
MC
S
C
OLC
1
2
G
On Board Controller
CB
TB2
Output Signal
L­L+ E­E+
Fine Alarm Input
CN9
11
1 5
1
CN8
Control Box
CN23
CN25
1
11
CN17
14
1
CN13
1
520D1520D2
Dip Switch
ON
2
3
CN11
CN12
1
3
3
CTS RTS Drain Tank SW
CF
12 1
11521135
CN22
CN21
52ID
CN165CN15
312
12
1
52CT
F1
CN24
52CM
4 3
COM 115V
CC
RB
1
5
CN01
1
5
CN03
2
Ground (G)
T R
CN-HP
T
R
TB1
G
CN-PUMP
HPRS
AP
AC115V 1PHASE 60Hz
Jumper Line
TB1 Terminal Block1 TB2 Terminal Block2 RB Relay Board MF Fan Motor MC Compressor Motor CF Capacitor for Fan Motor CC Capacitor for Compressor OLC Overload Protector
CN-PUMP CTS
RTS G CB HPRS
Connector for Option Drain Pump
Freeze Protection Thermistor Room Thermistor
Ground
Control Board High Pressure Switch
ILL00554-00
Operation Section

5.2 Control Box

For Unit Serial Number from February 2011 (0211) to October 2011 (1011)
19
T B 2 : T erminal Block2
CF:Capacitor for
Fan Motor
E+ E­L+ L-
RB:Relay Board
TB1:Terminal Block 1
CC:Capacitor for Compressor
ILL00559-00
For Unit Serial Number from November 2011 (1111) to Present
T B 2 : T erminal Block2
CF:Capacitor for
Fan Motor
E+ E­L+ L-
RB:Relay Board
TB1:Terminal Block 1
CC:Capacitor for Compressor
ILL00555-00
20
Operation Section
(1) Capacitor
• The capacitor is used to improve the rotational power of the fan motor and compressor at startup. The specification for each capacitor is shown below.
ILL00561-00
Model Capacitor
For unit serial number from February 2011 (0211) to March 2011 (0311)
For unit serial number from April 2011 (0411) to Present
Rated
Voltage For Fan Motor 450 V 16 μF For Compressor 450 V 55 μF For Fan Motor 250 V 25 μF For Compressor 450 V 55 μF
Capacitance
Operation Section
(2) Relay board
• The relay board contains the dip switch, the compressor and fan relays, and a step-down transformer that reduces the line voltage from 115VAC to approx. 14 VAC. This voltage is then rectified from 14 VAC to 12 VDC and used for relay coil activation. The 12 VDC voltage is sent to the control panel assembly, and further being reduced to 5 V for the system logic.
21
CN23
CN25
CN17
CN12CN13
4-Position Dip Switch
CN04CN11
“OFF” Position
1) Power supply requirements
CN21CN22
CN24
Relay Board Fuse (5A)
CN01
CN15CN16CN14CN02CN03
ILL00556-00
• This unit requires a single-phase 115 V, 60 Hz power supply.
2) Relay board fuse
• The relay board fuse is the only serviceable component on the relay board assembly. This fuse provides protection against damage to the step-down transformer. The fuse must be replaced with the exact same part, or a suitable equivalent.
Specifications:
- 5 A, 250 VAC
CAUTION
Failure to use the exact same fuse may result in damage to the unit and/or components, and will also void the unit warranty.
22
*1
Operation Section
3) Input signal
• The relay board receives inputs from the control panel, sensors, and external devices to perform device control.
Control Panel Input
Symbol Indication Function Connector
SW1 ON/OFF Button On/off control for unit operation. Turns the unit on and off.
SW2 FAN Button
SW3
SW4
SET TEMP Button
SET TEMP Button
Changes the fan control mode between continuous and automatic on/off control.
Increases the set temperature.
Decreases the set temperature.
CN17
Sensor Input
Symbol Type
RTS Room Thermistor
CTS
Freeze Protection
Thermistor
Characteristic “Short” Detection “Open” Detection
5 k ohm at 77 °F (25 °C)
5 k ohm at 77 °F (25 °C)
Specification
181 °F (83 °C) or more
181 °F (83 °C) or more
-29 °F (-34 °C) or less
-29 °F (-34 °C) or less
Connector
CN11
CN12
External Input Signal Specification
Symbol Signal Specification Function Connector
On: Activates “Defect control”
(Contact: Normally open) LED shows “AL”, Output signal “ON” On board buzzer sound
CN15
AUX2
Fire Alarm Input
On: Between 10 to 20
mA at DC12 V
(Off: No signal)
TANK
FULL S/W
AUX1
HPRS
*1 : For unit serial number from November 2011 (1111) to Present
Tank Full
Switch
External Pump Failure
High Pressure
Switch
On: Between 10 to 20
mA at DC12 V
(Off: No signal)
On: Between 10 to 20
mA at DC12 V
(Off: No signal)
On: Between 0.4 to 1.0
mA at DC 5V
(Off: No signal)
Off: Activates “Defect control”
LED shows “FL”, Output signal “ON” Off:
1) From 1 to 180 seconds - Compressor stops.
2) After 180 seconds - Compressor stops. LED shows “AS”, Output signal turns “ON”
(Contact: Normally closed)
Off: Activates “Defect control”
(Contact: Normally closed)
1) Activates 3 times in 24 hours: LED shows blinking “HP”.
2) Activates 10 times in 24 hours: LED shows “HP”, Output signal “ON”
CN16
CN13
CN03
Loading...
+ 51 hidden pages