MovinCool 24HFU Service Manual

SERVICE MANUAL
24HFU and 24HFU-1
DENSO SALES CALIFORNIA, INC.
REGISTERED TO ISO 9002
FILE NO. A5537
© 2000 DENSO SALES CALIFORNIA, INC.
DSCA P/N: LA990009-0205-E
(800) 264-9573 www.movincool.com
FOREWORD
This manual has been published to service the MovinCool 24HFU and 24HFU-1. Both the Model 24HFU and 24HFU-1 perform the same basic function, however the 24HFU-1 has additional features. Please use this service manual in servicing Models 24HFU and 24HFU-1.
DEFINITION OF TERMS
WARNING
Describes precautions that should be observed in order to prevent injury to the user during installation or unit operation.
CAUTION
Describes precautions that should be observed in order to prevent damage to the unit or its components, which may occur during installation or unit operation if sufficient care is not taken.
NOTE
Provides additional information that facilitates installation or unit operation.
GENERAL PRECAUTIONS
WARNINGS:
• All electrical work if necessary, should only be performed by qualified electrical personnel. Repair to electrical components by non-certified technicians may result in personal injury and/or damage to the unit. All electrical components replaced must be genuine MovinCool, purchased from an authorized reseller.
• When handling refrigerant, always wear proper eye protection and do not allow the refrigerant to come in contact with your skin.
• Do not expose refrigerant to an open flame.
• The proper electrical outlet for MovinCool units must be equipped with a “UL” approved ground-fault breaker to prevent electrical shock from the unit.
• When brazing any tubing, always wear eye protection and brazing tubing in a well ventilated area.
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 2
GENERAL DESCRIPTION
Generally speaking conventional air conditioners cool the entire enclosed environment. They act as “heat exchangers”, requiring an interior unit (evaporator) to blow cool air into the interior and an exterior unit (condenser) to exhaust exchanged heat to the out­doors. Unlike conventional air conditioners, the MovinCool Spot Cooling System is a spot cooler which directs cool air to particular areas or objects. MovinCool Spot Cooling Systems have the following features:
1-1. Compact Design
The innovative design of MovinCool has resulted in one compact unit, replacing the need for two separate units.
Conventional Air Conditioner
1-2. Easy Transportation and Installation
With the whole cooling system built into one compact unit, MovinCool requires no piping and can be easily transported and installed.
1-3. Energy Conservation
MovinCool is economical because it cools only the area or objects which need to be cooled.
Air Flow of MovinCool Spot Cooling System
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 3
CONSTRUCTION AND SPECIFICATIONS
Construction of Models 24HFU & 24HFU-1
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 4
CONSTRUCTION AND SPECIFICATIONS
2-1. Basic Construction
The MovinCool Spot Cooling System is compact in construction because the condenser and the evaporator are enclosed in one unit. The interior is divided into three sections. The upper front face is equipped with the evaporator, while the lower front face contains the drain tank. The rear section contains the condenser, the com­pressor and the control box.
2-2. Air Flow
Air drawn from the right side face passes through the condenser and extracts the heat. This hot air is blown out through the upper exhaust air duct. Air taken in from the front face is cooled by the evaporator and then blown through the cooling air duct which can be turned in any direction. All the air inlets are provided with filters, while the exhaust air duct is pro­tected by wire mesh.
Air Flow
2-3. Compressor and Fans
The compressor is hermetically sealed. One motor is used with two centrifugal fans to draw air across the evaporator and condenser.
2-4. Drain Tank
The capacity of the drain tank is 5.3 gallons (20 liters). The unit is equipped with a full tank lamp and a device to automatically stop the unit’s operation when the drain tank reaches a level of approximately 4.4 ± 0.5 gallons (16.5 ± 2 liters).
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 5
CONSTRUCTION AND SPECIFICATIONS
ITEM/MODEL 24HFU 24HFU-1
[Rating Condition] DB 35˚C WB 28.2˚C DB 35˚C WB 28.2˚C
95˚F 83˚F 95˚F 83˚F
RH 60% RH 60%
[Features]
Power frequency___________ (Hz) 60 60 Line voltage ______________ (Volt) Single phase 230 Single phase 230 Power consumption ________ (Kw) 3.1 3.1 Current consumption _______ (Amp) 14.0 14.0 Power factor ______________ (%) 96 96 Starting current ____________ (Amp) 62 62 Power wiring ______________ (AWG) 12 (3-core) 12 (3-core)
[Cooling Unit]
Cooling capability __________ (Kcal/h) 6,000 6,000
________________________ (Btu/h) 24,000 24,000
Cooling system Direct expansion Direct expansion
[Blower]
Type of fan Centrifugal fan Centrifugal fan Condenser - Air flow ________ (ft Evaporator - Air flow ________ (ft3/min) 706 706 Motor output ______________ (Kw) 0.55 0.55
[Compressor]
Type Hermetic scroll Hermetic scroll Output___________________ (Kw) 1.6 1.6 Refrigerant type R-22 R-22 Refrigerant amount _________ (kg) 0.85 0.85
________________________ (lbs) 1.87 1.87
[Safety Device]
Compressor overload relay With With Fan motor protector With With Drain switch With With Anti-freezing thermostat With With High pressure switch With With Restart relay - power interruption Without With Time delay relay Without With
[Dimensions and Weight]
W x D x H ________________ (mm) 490 x 730 x 1200 490 x 730 x 1200
________________________ (inch) 19.3 x 28.7 x 47.2 19.3 x 28.7 x 47.2
Weight___________________ (kg) 107 107
________________________ (lbs) 235 235
[Operating Conditions]
Intake air temperature range 45˚C (113˚F), RH 50% 45˚C (113˚F), RH ≤50%
[Control Device]
Temperature control Without With
3
/min) 1,200 1,200
to 25˚C (77˚F), RH 50% to 25˚C (77˚F), RH ≥50%
Specifications
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 6
Specifications are subject to change without notice.
REFRIGERANT SYSTEM
The component parts of the refrigerant system include the following:
• Compressor • Evaporator
• Condenser • High pressure switch
• Capillary tube • Modulating tank
These parts are all connected by copper piping. All the connections have been brazed.
Condenser
Compressor
Modulating Tank
Evaporator
Capillary T ube
High Pressure Switch
Refrigerant System
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 7
REFRIGERANT SYSTEM
3-1. Compressor
The compressor used for the unit is hermetically sealed. The compressor and the compressor motor are in one casing.
3-1-1. Compressor Theory of Operation
The scroll utilizes an involute spiral which, when matched with a mating scroll form, generates a series of crescent-shaped gas pockets between the two members. During compression, one scroll remains stationary (fixed scroll) while the other form (orbiting scroll) is allowed to orbit (but not rotate) around the first form. As this motion occurs, the pockets between the two forms are slowly pushed to the center of the two scrolls while simultaneously being reduced in volume. When the pocket reaches the center of the scroll form, the gas, which is now at a high pressure, is discharged out of a port located at the center. During compression, several pockets are being compressed simultaneously, resulting in a very smooth process. Both the suction process (outer portion of the scroll members) and the discharge process (inner portion) are continuous.
3-1-2. Compressor Operation
1) Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral. Gas enters the outer openings as one of the spirals orbits.
2) The open passages are sealed off as gas is drawn into the spiral.
3) As the spiral continues to orbit, the gas is compressed into two increas­ingly smaller pockets.
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 8
REFRIGERANT SYSTEM
4) By the time the gas arrives at the center port, discharge pressure has been reached.
5) Actually, during operation, all six gas passages are in various stages of compression at all times, resulting in nearly continuous suction and dis­charge.
NOTE
Upon compressor shut-off, the compressor may run backward for a moment or two until internal pressures equalize. This has no effect on com­pressor durability but may cause an unexpected sound after the compressor is turned off and should not be diagnosed as a malfunction.
3-2. Condenser
The condenser is a heat exchanger whose copper tubes are covered with thin aluminum projections called spine fins. Heat is given off and absorbed by air being pulled across the condenser fins by the centrifugal fan and then expelled through the exhaust air duct.
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 9
REFRIGERANT SYSTEM
3-3. Capillary Tube
The capillary tube is a long thin tube and its line flow resistance serves as an expansion valve. The length and the inner diameter of the capil­lary tube are determined according to the capacity of refrigeration system, operating conditions and the amount of refrigerant. The capillary tube causes the high pressure, high temperature liquid refrigerant sent from the condenser to expand rapidly as the refrigerant is sprayed out through the fixed orifice in the capillary tube. As a result, the temperature and state of the refrigerant become low and mist­like, and therefore it evaporates easily.
Capillary Tube Dimensions
Qty Purpose of Use I.D. (mm) Length (mm)
1 For cooling ∅1.5 ± 0.05 540
3-4. Evaporator
The evaporator, like the condenser, is a heat exchanger covered with spine fins. Heat is removed from the air being pulled across the evaporator by the centrifugal fan and the resulting cool air is expelled through the cooling air ducts.
Capillary Tube
3-5. Modulating Tank
The modulating tank consists of a copper pipe and tank sections, each being separated from the other. The pipe connects to the evaporator outlet at one end and to the compressor at the other; the tank connects to the evaporator inlet. The modulating tank is covered with insulation to reduce thermal effects of ambient temperature. It varies the quantity of refrigerant in the refriger­ating cycle for optimum operating condition; it stores part of refrigerant under light load and delivers additional refrigerant to the cycle under heavy load.
3-6. High Pressure Switch
The high pressure switch prevents the con­denser and compressor from being damaged by excessively high pressure in the high pressure line of the refrigeration cycle. The switch is normally closed. The snap disk responds to variations in pressure and, if pressure is abnor­mally high, the snap disk moves down to push the pin down, causing the internal contacts to open. This generates a signal to open the auxiliary relay. Possible causes of this trouble include:
(1) The condenser air filter is dirty, restricting
air flow.
(2) The condenser blower is defective.
Modulating Tank
High Pressure Switch
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 10
REFRIGERANT SYSTEM
Condenser Inlet Pipe
Compressor Discharge Pipe
Condenser Outlet Pipe
Compressor Suction Pipe (insulated)
Evaporator Inlet Pipe
Evaporator Outlet Pipe
Capillary T ube
Connecting Pipe (evaporator to compressor)
Connecting Tube (condenser to capillary tube)
Refrigerant System Piping
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 11
ELECTRICAL SYSTEM • 24HFU
24HFU
Electrical System and Control Box for Model 24HFU
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 12
ELECTRICAL SYSTEM • 24HFU
4-1. Basic Operation of MovinCool Modelp 24HFU Electrical Circuit
The three basic modes of operation are as follows:
Operation in “OFF” position
2) Control Switch in “FAN” position: a. Current also flows through the control
switch (CS) to the fan motor (MF).
b. Current flows through the contact (termi-
nals 19 and 20) of the auxiliary relay and its coil, and remains closed.
1) Control Switch in “OFF” position: a. Current flows through terminals 5 and 2
of the control switch (CS) and to the coil of the auxiliary relay (RX). (A and B.)
b. Two contacts (RX) of the auxiliary relay
are closed by electromagnetic force. The closed contact RX (terminals 19 and 20) allows current to flow directly to the auxiliary relay coil and hold the contact in a closed position.
NOTE
Symbol indicates alternating current.
Operation in “FAN” position
Operation in “COOL” position
3) Control Switch in “COOL” position: a. The contacts of the auxiliary relay remain
closed as mentioned in step 2) b. b. Current flows to the fan motor (MF). c. Current also flows to the anti-freezing
thermostat (THS) contact, to the coil of
the relay for the compressor motor
(MCC) (A and B) and the auxiliary relay
contacts. d. Two contacts of the relay for the com-
pressor motor (MCC) are closed by the
electromagnetic force. Current then
flows to the compressor motor (MC).
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 13
ELECTRICAL SYSTEM • 24HFU
4-2. Control Box
4-2-1. Capacitor
The capacitor is used to boost power output to the fan motor and the compres­sor at start-up. The specifications of each capacitor are shown below.
Capacitor Registrant Voltage Capacitance
(Volt) (mF) For fan motor 440 12.5 For compressor 370 40
4-2-2. Auxiliary Relay
This auxiliary relay is normally closed when the unit is in operation (FAN or COOL), and supplies power to the com­pressor relay and the fan motor. In the following cases, however, the relay opens to interrupt power to the compressor and the fan motor.
When the drain tank is filled with water. (Drain switch OFF.)
When the high pressure becomes excessively high. (High pressure switch OFF.)
When current flows across A and B, terminals 11 and 12, 13 and 14, 15 and 16, 19 and 20 conduct.
Circuit of Auxiliary Relay
Auxiliary Relay
Specifications:
Rated Voltage AC 240V Rated current 15 amps UL Listed File No. E1 12482
4-2-3. Compressor Relay
The compressor relay is closed when the unit is operating in COOL mode, and supplies power to the compressor. How­ever in the following cases, the relay opens to cut off power to the compressor.
When the auxiliary relay is opened. (Drain switch OFF or high pressure switch OFF.)
When the evaporator has frosted. (Thermostat OFF.)
Specifications:
Rated Voltage AC 230V Rated Current 30 amps UL Listed File No. E43028
Circuit of Compressor Relay
Compressor Relay
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 14
Control Switch
Fan Motor
CF1 CF2 RX12
ELECTRICAL SYSTEM • 24HFU
4-3. Control Switch
The control switch is employed to start or stop operation. This switch is a 250V, 20A rating rotary type (3-position). The switching positions are OFF-FAN-COOL. Each contact is switched by the cam uniting with the shaft.
Switch Terminals OFF FAN COOL
(5) - (2) Conduct OFF OFF (5) - (1) OFF Conduct OFF (5) - (4) OFF Conduct Conduct
4-4. Fan Motor
The fan motor is a single phase, induction type motor which drives fans on the evaporator side and the condenser side at the same time.
Specifications:
Rated Voltage AC 230V Rated Output 552 Watts UL Listed File No. E49807
4-5. Compressor Motor
The compressor motor is a single phase motor and is contained within the same housing as the compressor.
Specifications:
Rated Voltage AC 230V Rated Output 1600 Watts
Thermostat
NOTE
An internal overload relay is used to protect the compressor motor and fan motor. This relay is built into the compressor motor and fan motor and will interrupt the flow of current when there is an overcurrent situation or if abnormally high temperature builds up in the compressor motor or fan motor.
4-6. Anti-freezing Thermostat
If the evaporator has frosted, the thermostat contacts open to stop the compressor and the unit continues to operate on “FAN” mode. Once the evaporator has defrosted, the contacts close to restart the compressor and the unit operates in COOL mode. The thermostat heat sensing tube is mounted at the evaporator outlet tube and is insulated from surrounding air by heat insulating material. The thermostat contacts are opened at -1.5˚C and closed at +14.5˚C.
MOVINCOOL 24HFU / 24HFU-1 SERVICE PAGE 15
Loading...
+ 33 hidden pages