•Please read this document prior to set-up of the unit� Ensure that the product is
suitable for your application without any restrictions�
•If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property can occur�
•Improper or non-intended use may lead to malfunctions of the unit or to unwanted effects in your application� That is why installation, electrical connection, set-up, operation and maintenance of the unit must only be carried out by
qualified personnel authorised by the machine operator�
•In order to guarantee the correct condition of the device for the operating time it
is necessary to use the device only for media to which the wetted materials are
sufficiently resistant (→ Technical data).
•The responsibility whether the measurement devices are suitable for the
respective application lies with the operator� The manufacturer assumes no
liability for consequences of misuse by the operator� Improper installation and
use of the units result in a loss of the warranty claims�
CAUTION
For medium temperatures above 50 °C (122 °F) some parts of the housing can
heat up to over 65 °C (149 °F)� Risk of burns�
► In this case do not touch the unit�
UK
► Protect the housing against contact with flammable substances and uninten-
tional contact�
► Do not press the pushbuttons manually; instead use another object (e�g�
ballpoint pen)�
2 Functions and features
The unit monitors water-based fluids (water, deionised water, cooling water)�
It detects the two process categories volumetric flow and medium temperature�
Pressure Equipment Directive (PED):
The units comply with the Pressure Equipment Directive and are designed
and manufactured for group 2 fluids in accordance with the sound engineering practice� Use of group 1 fluids on request�
3
3 Function
•The unit detects the volumetric flow quantity based on the Vortex measuring
principle�
•It features an IO-Link interface�
•The unit displays the current flow and temperature� It generates 2 output
signals according to the parameter setting:
OUT1/IO-Link: 2 selection options
- switching signal for volumetric flow quantity limit value
- or frequency signal for volumetric flow quantity
OUT2: 4 selection options
- switching signal for volumetric flow quantity limit value
- or switching signal for temperature limit value
- or frequency signal for volumetric flow quantity
- or frequency signal for temperature
4 Installation
► Flow in the direction of the arrow� Observe the installation direction�► Make sure that pipe and sensor have the same internal diameter�► Avoid deposits, accumulated gas and air in the pipe system� Install the unit so
that the measuring pipe is always completely filled with medium�
► Install in front of or in a rising pipe�► Recommended tightening torque: 30 Nm► Avoid disturbances on the inlet and outlet side� To do so, provide for the
following inlet and outlet pipe lengths:
4
1
F
2
DN = nominal width of the pipe
R = radius
DisturbanceInlet pipe length
Outlet pipe length
(1)
Non-ideal bend≥ 5 x DN≥ 1 x DN
Ideal bend
≥
R1.8
x
DN
Multiple bends (2 x 90°)≥ 15 x DN
Reduction of internal pipe diameter≥ 15 x DN≥ 15 x DN
Valve or pump≥ 25 x DN
≥ 0.5 x DN
(2)
► Mount the unit in a way that no mechanical forces are exerted on the pipe� To
UK
do so, use angle brackets if required�
- For direct installation, fix the unit on the surface using 4 self-tapping screws
M4 DIN 7500� Maximum insertion depth in the housing: 5�5 mm�
- For installation using the fixing element: ifm mounting accessories at
www�ifm�com�
► Avoid the following installation positions:
- Directly in front of a falling pipe�
- In a falling pipe�
- At the highest point of the pipe system�
- Directly in front of the spout of the pipe�
- On the suction side of a pump�
5
5 Electrical connection
The unit must be connected by a qualified electrician�
The national and international regulations for the installation of electrical
equipment must be adhered to�
Voltage supply according to EN 50178, SELV, PELV�
► Disconnect power�► Connect the unit as follows:
21
43
BK: black
BN: brown
BU: blue
WH: white
BN
1
WH
2
BK
4
BU
3
+
L
OUT2
OUT1
L
Colours to DIN EN 60947-5-2
Pin 1L+
Pin 3L-
• Switching signal: limit values for volumetric flow
Pin 4
• Frequency signal for volumetric flow quantity
(OUT1)
• IO-Link
• Switching signal: limit values for volumetric flow
Pin 2
(OUT2)
• Switching signal: limit values for temperature
• Frequency signal for volumetric flow quantity
• Frequency signal for temperature
6
6 Operating and display elements
12
3
5
UK
4
1 and 2:switching status LEDs
• LED 1 = switching status OUT1 (lights when output 1 is switched)
• LED 2 = switching status OUT2 (lights when output 2 is switched)
3: TFT display
• Display of current process values (volumetric flow quantity, temperature)
• Display of the parameters and parameter values
4: Buttons [▲] and [▼]
• Select parameters
• Change parameter values (hold button pressed)
• Change of the process value display in the normal operating mode (Run mode)
The parameters are only displayed when selected at ou1 / ou2�
8
7.1.1 Explanation main menu
Switching output with hysteresis function
SP1Set point 1 = upper limit value at which OUT1 switches�
rP1Reset point 1 = lower limit value at which OUT1 switches off�
SP2Set point 2 = upper limit value at which OUT2 switches�
rP2Reset point 2 = lower limit value at which OUT2 switches off�
Switching output with window function
FH1Set point 1 = upper limit value at which OUT1 switches�
FL1Reset point 1 = lower limit value at which OUT1 switches�
FH2Set point 2 = upper limit value at which OUT2 switches�
FL2Reset point 2 = lower limit value at which OUT2 switches�
Frequency output
UK
FEP1Process value end point on OUT1�
FrP1Frequency at process value end point (FEP1) on OUT1�
FSP2Process value start point on OUT2 (only if SEL2 = TEMP)�
FEP2Process value end point on OUT2�
FrP2Frequency at process value end point (FEP2) on OUT2�
Extended functions
EFOpening of the lower menu level�
9
7.2 Extended functions – basic settings
Main menu
RUN
EFCFG
rES
Info
CFG
MEM
DIS
- - - -
ou1HnoHncFnoFncFRQ
ou2
dS1
dr1
dS2
dr2
uni
HnoHncFnoFncFRQ
0,0...60 s
0,0...60 s
0,0...60 s
0,0...60 s
m3/hl/min
P-n
dAP
FOU1
FOU2
SEL2FLOWTEMP
PnPnPn
0,0...5,0 s
OFFOnOU
OFFOnOU
*
The parameters are only displayed when oux = Hno, Hnc, Fno, Fnc�
10
rESRestoring the factory settings
InfoDevice information
CFGSubmenu basic settings
MEMSubmenu min/max memory
DISSubmenu display settings
7.2.1 Explanation basic settings (CFG)
ou1Output function OUT1
• Flow: Hno, Hnc, Fno, Fnc, FRQ
ou2Output function OUT2
• Flow: Hno, Hnc, Fno, Fnc, FRQ
• Temperature: Hno, Hnc, Fno, Fnc, FRQ
HnoHysteresis function normally open
HncHysteresis function normally closed
FnoWindow function normally open
FncWindow function normally closed
FRQFrequency output
dS1Switching delay on OUT1 in seconds
dr1Switch-off delay on OUT1 in seconds
dS2Switching delay on OUT2 in seconds
dr2Switch-off delay on OUT2 in seconds
uniStandard unit of measurement for volumetric flow
Only in case of ou
Hno, Hnc, Fno, Fnc
UK
x =
P-nOutput logic: pnp / npn
dAP Measured value damping in seconds (only for volumetric flow)
FOU1Behaviour of output OUT1 in case of an error
FOU2Behaviour of output OUT2 in case of an error
SEL2Standard measured variable for evaluation by OUT2:
Volumetric flow quantity or medium temperature
11
7.3 Extended functions – min / max memory – display
EF
MEM
DIS
Info
CFG
rES
MEM
DIS
Lo.T
Hi.T
Lo.F
0,0 l/min
0,0 l/min
0,0 °C
0,0 °C
Hi.F
coL.FOFF rEdr-cF G-cFGrEn r1ou G1ou
cFH.F
cFL.F
cFH.T
cFL.T
diS.L
L1 L2
diS.B
diS.U
diS.R
d1 d2d3
090 180 270
25 50 75 100 OFF
coL.T
OFF rEdr-cF G-cFGrEn r2ou G2ou
10 l/min
5 l/min
50 °C
0 °C
Main Menu
The parameters are only displayed when selected r-cF oder G-cF�
12
7.3.1 Explanation min/max memory (MEM)
Lo�FMinimum value of the flow measured in the process
Hi�FMaximum value of the flow measured in the process
Lo�TMinimum value of the temperature measured in the process
Hi�TMaximum value of the temperature measured in the process
7.3.2 Explanation display function (DIS)
diS�LStandard layout of the display(L1: flow or L2: flow and temperature)
diS�UUpdate rate of display
diS�RDisplay rotation
diS�BDisplay brightness
coL�FColour configuration volumetric flow
coL�TColour configuration temperature
OFFNo colour change
rEdProcess value always red, irrespective of the output function
GrEnProcess value always green, irrespective of the output function
r1ou / r2ou Process value red in case of switched output OUT1 / OUT2
G1ou / G2ouProcess value green in case of switched output OUT1 / OUT2
r-cF
G-cF
Display red if measured value between limit values cFL���cFH,
irrespective of the output function
Display green if measured value between limit values cFL���cFH,
UK
irrespective of the output function
cFH�FUpper limit value for colour change flow
cFL�FLower limit value for colour change flow
cFH�TUpper limit value for colour change temperature
cFL�TLower limit value for colour change temperature
Only if r-cF or
G-cF is selected�
8 Parameter setting
Parameters can be set before installation and set-up of the unit or during operation�
If you change parameters during operation, this will influence the function
of the plant�
► Ensure that there will be no malfunctions in your plant�
13
The parameters can also be set via the IO-Link interface�
8.1 Parameter setting in general
1� Change from RUN mode to the main menu[●]
2� Selection of the requested parameter[▲] or [▼]
3� Change to setting mode[●]
4� Modification of the parameter value[▲] or [▼] > 1 s
5� Acknowledgement of the set parameter value[●]
6� Return to the RUN mode> 30 seconds (timeout) or
press [▲] + [▼] simultaneously
until the RUN mode is reached�
9 Factory setting
ParameterFactory settingUser setting
SP1
rP1
FH1
FL1
FEP1
FrP1
SP2
rP2
FH2
(FLOW)
(FLOW)
(FLOW)
(FLOW)
(FLOW)
(FLOW)
(FLOW, TEMP)
(FLOW, TEMP)
(FLOW, TEMP)
20 % *
18.5 % *
20 % *
18.5 % *
100 % *
100 Hz
40 % *
38.5 % *
40 % *
FL2
FSP2
FEP2
FrP2
ou1
ou2
14
(FLOW, TEMP)
(TEMP)
(FLOW, TEMP)
(FLOW, TEMP)
(FLOW)
(FLOW, TEMP)
38.5 % *
0 % *
100 % *
100 Hz
Hno
Hno
ParameterFactory settingUser setting
FOU1
FOU2
SEL2
col.F
col.T
(FLOW)
(FLOW, TEMP)
(FLOW, TEMP)
(FLOW)
(TEMP)
OFF
OFF
FLOW
OFF
OFF
dS10 s
dR10 s
dS20 s
dR20 s
unil/min (SVx6xx: gpm)
P-nPnP
dAP0.6 s