motortronics XLS-78, XLS-120, XLS-92, XLS-150, XLS-180 Installation & Operation Manual

...
XLS Series Solid State Soft Starter 39 - 1250A
XLS SERIES
Solid State Soft Starter
39 - 1250 A
INSTALLATION & OPERATION
MANUAL
Motortronics
- 23 -
XLS Series Solid State Soft Starter 39 - 1250A
Motortronics
- 24 -
XLS Series Solid State Soft Starter 39 - 1250A
Table of Contents
XLS Series Solid State Soft Starter 39 - 1250A
Chapter 1: Introduction.....................................................1
1.1 General
1.2 Specifications and Performance Features
Chapter 2: Installation.......................................................2
2.1 Receiving and Unpacking
2.2 Location
2.3 Initial Unit Inspection
2.4 Warning
2.5 Mounting and Cleaning
2.6 Power Terminal Wire Range and Tightening Torque
2.7 Dimensions
Chapter 3: Motor Overload Protection............................5
3.1 Thermal Overload Relay
3.2 Overload Relay
3.3 FLA Dial Adjustment
3.4 Manual/Automatic Reset
3.5 Test for Trip Indication
Chapter 4: Connections ................................................... 6
4.1 Power Connections
4.2 Control Connections
Chapter 5: Adjustments ....................................................9
5.1 Introduction
5.2 Acceleration Adjustments
5.3 Deceleration Adjustments
Chapter 6: Start-Up .........................................................1 2
6.1 Start-up Check List
6.2 Sequence of Operation
Chapter 7: Status Indicator LEDs ..................................13
7.1 LED Functions
Chapter 8: Troubleshooting ...........................................14
8.1 Failure Analysis
8.2 SCR Testing Procedure
8.3 Replacing SCR Devices
8.4 Replacing Printed Circuit Boards
Chapter 9: Main Control Board ......................................20
Motortronics
- 25 -
XLS Series Solid State Soft Starter 39 - 1250A
Motortronics
- 26 -
XLS Series Solid State Soft Starter 39 - 1250A
Chapter 1 - Introduction
1.1 General
The XLS Series solid state reduced voltage soft starter is a six SCR design which features a voltage/current ramp with an anti-oscillation circuit for smooth load acceleration. The SCRs are sized to withstand starting currents of 500% for 60 seconds (compared to 350% for 30 seconds from other manufacturers). The XLS Series features smooth, stepless ramp control which reduces motor inrush current and excessive wear on the mechanical drive train components. In addition to having easy to understand diagnostic lights, the XLS Series can be set up for the ideal starting cycle. Starting voltage, ramp time, current limit, and decel control are standard adjustments on the XLS Series. The starting electrical characteristics of the motor can be matched to the mechanical characteristics of the drive train for controlled acceleration of the load, by simply adjusting the unit’s starting torque, ramp time and current limit potentiometers. The XLS Series includes adjustable overload protection, shorted SCR detection and phase loss detection. It is factory wired for 120VAC control voltage (or 240VAC for 415 VAC and 380 VAC units) and three-wire start/stop control. Auxiliary contacts and provisions for interlocking are also included.
1.2 Specifications and Performance Features
Motortronics
- 1 -
XLS Series Solid State Soft Starter 39 - 1250A
Chapter 2 - Installation
2.1 Receiving and Unpacking
Upon receipt of the product you should immediately do the following:
Carefully unpack the unit from the shipping carton and inspect it for
shipping damage (if damaged, notify the freight carrier and file a claim within 15 days of receipt).
Verify that the model number on the unit matches your purchase
order.
Confirm that the ratings sticker on the unit matches or is greater
than the motor’s HP and current rating.
2.2 Location
Proper location of the XLS Series is necessary to achieve specified performance and normal operation lifetime. The XLS Series should always be installed in an area where the following conditions exist:
Ambient operating temperature:
Chassis unit: 0 to 50°C (32 to 122°F) Enclosed unit: 0 to 40°C (32 to 104°F)
Protected from rain and moisture
Humidity: 5 to 95% non-condensing
Free from metallic particles, conductive dust and corrosive gas
Free from excessive vibration (below 0.5G)
Open panel units must be mounted in the appropriate type of
enclosure. Enclosure size and type must be suitable to dissipate heat generated by the soft starter. Contact factory for assistance in sizing enclosures.
2.3 Initial Unit Inspection
• Make a complete visual check of the unit for damage which may have occurred during shipping and handling. Do not attempt to continue installation or start up the unit if it is damaged.
• Check for loose mechanical assemblies or broken wires which may have occurred during transportation or handling. Loose electrical connections will increase resistance and cause the unit to function improperly.
• Prior to beginning the installation, verify that the motor and XLS unit are rated for the proper amperage and voltage.
2.4 Warning!
Do not service equipment with voltage applied! The unit can be the source of fatal electrical shocks! To avoid shock hazard, disconnect main power and control power before working on the unit. Warning labels must be attached to terminals, enclosure and control panel to meet local codes.
Motortronics
- 2 -
XLS Series Solid State Soft Starter 39 - 1250A
2.5 Mounting and Cleaning
When drilling or punching holes in the enclosure, cover the electrical assembly to prevent metal filings from becoming lodged in areas which can cause clearance reduction or actually short out electronics. After work is complete, thoroughly clean the area and reinspect the unit for foreign material. Make sure there is sufficient clearance (six inches) all around the unit for cooling, wiring and maintenance purposes. To maximize effective air flow and cooling, the unit must be installed with its heat sink ribs oriented vertically and running parallel to the mounting surface.
Warning!
Remove all sources of power before cleaning the unit.
In dirty or contaminated atmospheres the unit should be cleaned on a regular basis to ensure proper cooling. Do not use any chemicals to clean the unit. To remove surface dust use 80 to 100 psi, clean, dry compressed air only. A three inch, high quality, dry paint brush is helpful to loosen up the dust prior to using compressed air on the unit.
2.6 Power Terminal Wire Range and Tightening Torque
Note: All wiring must be sized according to NEC standards.
Motortronics
- 3 -
XLS Series Solid State Soft Starter 39 - 1250A
y
y
y
y
2.7 Dimensions
Enclosure
XLS-6 to XLS-32 12.8 10.9 5.5 12.3 10.3 0.28
XLS-39 to XLS-120 16.5 10 10 15.9 9 0.28
XLS-150 to XLS-180 20 20.1 12 18.5 17.5 0.44
PANEL
NEMA1
NEMA 4/4X
NEMA12
XLS-220 to XLS-288 27 20.1 11.2 25.5 17.5 0.44 XLS-360 to XLS-550 29.5 20.1 11.5 25.5 17.5 0.44
XLS-718 to XLS-1006 45 33 12.8 43.3 31.3 0.44
XLS-1150 to XLS-1250 33 33 15.2 31.2 31.2 0.44
XLS-6 to XLS-32
XLS-39 to XLS-120 16.5 10 10 15.9 9 0.28 XLS-150 to XLS-180 32.3 24.3 13.3 31.3 18 0.44 XLS-220 to XLS-288 38.3 24.3 13.3 37.3 18 0.44 XLS-360 to XLS-550 44.3 30.3 13.3 43.3 24 0.44
XLS-718 to XLS-1006 50.2 36.3 15.5 49.3 30 0.4
XLS-1150 to XLS-1250
XLS-6 to XLS-11 11.7 8.9 9 9 8.4 0.28
XLS-18 to XLS-78 15.7 12.2 10 12 11 0.28
XLS-92 to XLS-120 24 24 12.9 22.5 22.5 0.5 XLS-150 to XLS-288 36 30 16.9 34.5 28.5 0.5 XLS-360 to XLS-550 48 36 16.9 46.5 34.5 0.5
XLS-718 to XLS-1006 72.1 48.1 20
XLS-1150 to XLS-1250
Model
Number
Overall
Dimensions
Mounting
Dimensions
ABCDEF
Not Available Not Available
Contact Factor
Contact Factor
Contact Factor
Floor Mounted
Contact Factor
Motortronics
- 4 -