Motor Saver 201, 102, 350, 250, 102-A User Manual

...
INSTALLATION INSTRUCTIONS FOR SYMCOM’S
MOTORSAVER MODELS 102, 201, 250, 350
BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!!
FOLLOW NATIONAL, STATE AND LOCAL CODES!
INSTRUCTIONS D’INSTALLATION POUR LE SYMCOM
MOTORSAVER, MODÈLES 102, 201, 250, 350
S’ASSURER QUE LE COURANT EST COUPÉ AVANT L’INSTALLATION!
INSTRUCCIONES DE INSTALACIÓN PARA LOS MODELOS
MOTORSAVER 102, 201, 250, 350 DE SYMCOM
ANTES DE LA INSTALACIÓN CERCIÓRESE DE QUE ESTÉ DESCONECTADA LA
ENERGÍA ELÉCTRICA ACATE LOS CÓDIGOS NACIONALES, ESTATALES Y LOCALES
2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848
www.symcominc.com
Manufactured by
Visit our website at www.symcominc.com for our
complete catalog and new product listings!
VOLTAGE MONITORS
MONITEUR DE TENSION
EL MONITOR DEL VOLTAJE
CONNECTIONS
1. Mount the MotorSaver®in a convenient location in or near the motor control panel.If the location is wet or dusty, the MotorSaver®should be mounted in a NEMA 4 or 12 enclosure.
2. Connect the three lines of the motor’s 3-phase power supply to L1, L2 and L3 on the MotorSaver’s terminal strip [Pin 3, 4 and 5 on the Model 201] (see Figure 1).
3. Connect the output relay to the circuitry to be controlled (see Figure 1).
SETTINGS
All models are not equipped with the same adjustments. Set the adjustments available on the front of your particular model.
1. LINE VOLTAGE ADJUSTMENT: Rotate the LINE VOLTAGE ADJUSTMENT to the nominal 3-phase line voltage feeding the motor to be protected.
2. TIME DELAY RESTART: Rotate the RESTART DELAY to the desired position. The restart delay is the time between MotorSaver®seeing acceptable power and MotorSaver®closing its output contacts. For compressor applications, the restart delay should be set for the approximate time it takes for the head pressure to bleed off of the compressor .For other applications, the restart delay is typically set at 2 seconds. If the RESTART DELAY is in the MAN (manual) position, the unit will not automatically restar t until it is turned out of the manual position.
3. TRIP DELAY ADJUSTMENT: Rotate the TRIP DELAY ADJUSTMENT to the desired setting. The adjustment does not affect the trip delay on phasing faults. Typically, the TRIP DELAY ADJUSTMENT is set to 4 seconds. In areas where voltage fluctuations are frequent, the TRIP DELAY ADJUSTMENT is set between 10 and 15 seconds.
4. OTHER OPTIONAL ADJUSTMENTS: If your MotorSa v er®is equipped with another optional adjustment, rotate the adjustment screw to the desired setting.
POWER-UP
Turn on the power to the motor. The MotorSaver®then goes through its restart delay and the LED will flash green. After the RESTART DELAY (fixed or adjustable), the MotorSaver®will energize its output contacts and the RUN LIGHT will turn solid green. If the contacts do not energize and the RUN LIGHT does not turn solid green, see the TROUBLESHOOTING section.
TROUBLESHOOTING
If the output relay does not energize and the RUN LIGHT does not turn solid green after waiting for the RESTART DELAY time:
1. Rotate the REST AR T DELAY dial clockwise 1/8 turn, above "2." You may be pointed at "Manual" or close enough to the Manual reset position that the unit will not automatically restart. If the light does not flash green, proceed to step 2.
(A) To control a motor : Connect the normally open contact in series with the magnetic coil of the motor starter as shown.
(B) To sound an alarm: Connect the normally closed contact in series with the alarm as shown.
Figure 1:Typical Wiring Diagram
RUN RESTART DELAY
REVERSE PHASE
HIGH / LOW VOLTAGE
UNBALANCE / SINGLE PHASE
GREEN
GREEN
RED
RED
RED
INDICATOR LIGHT DIAGNOSTICS
WARRANTY
Seller warrants to the buyer that products furnished will be free from defects in material and workmanship, exclusive of corrosion, for a period of five years from the date of shipment from its factor y, provided said products have been installed, maintained and operated in conformance with any applicable specifications and recommendations of the Seller. The sellers liability under this warranty shall be limited to the replacement within the aforesaid time of any defec­tive work or material limited at the Seller’s factor y and shall not be liable for any labor or other repair costs made out­side the Seller’s factor y without the written consent of the Seller. The Seller shall be liable for no other damages or losses. The warranty described in this paragraph shall be IN LIEU OF ANY OTHER WARRANTY EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED W ARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
0.150" (3.81)
2.163" (54.94)
2.913"
(73.99)
4.030" (102.36)
5.250" (133.35)
4.500" (114.30)
.375"
(9.53)
2.900"
(73.66)
SymCom, Inc.
RESTART
DELAY
(SECONDS)
70
2
MAN
150
220
300
C
IND. CONT. EQ
LISTED
784X
U
L
®
IND. CONT. EQ
LISTED
784X
U
L
®
GEN. PURPOSE RATING
10 A at 240 VAC
PILOT DUTY RATING
480 VA at 240 VAC
RUN LIGHT
MODEL 102
P/N- MS102 - A
220 440
208
416 200 400
190 380
230 460
240 480
LINE VOLTAGE
ADJUST
(VAC)
L1
L2
L3
190-480 VAC, 3Ø, 50/60 HZ
Rapid City, SD
BOTTOM
2.375
(60.331)
1.75
(44.545)
TOP
SIDE
3.15
(80.010)
.5
(12.700)
LINE VOLTAGE ADJUST
190/380
200/400
208/416 220/440
230/460
240/480
RUN LIGHT
(VAC)
DIMENSIONS FOR MODELS 102, 250, 350
DIMENSIONS FOR MODEL 201
SIDE
FRONT
2. Tur n off the 3-phase power. Swap any two leads: L1 and L2; L2 and L3; L3 and L1. You have a 50-50 chance of connecting L1, L2 and L3 up correctly the first time.Turn on the 3-phase power.
3. If the MotorSaver
®
still seems to be malfunctioning, measure the three line-to-line voltages.Calculate the average of the voltages. If the average voltage is 10% above (high voltage protection standard on Model 250 only) or 10% below the voltage adjust setpoint, the MotorSaver®is functioning properly, saving your motor from abnormal power conditions.
4. If the average of the three line voltages is within ±10%, calculate the voltage unbalance using the NEMA method shown below:
% voltage unbalance = (max. deviation / average of the three voltages) x 100
EXAMPLE: Find the largest deviation from the average voltage and divide it by the average for the NEMA unbalance.
L1 - L2 = 460VAC, L2 - L3 = 466 VAC, L3 - L1 = 490 VAC Average = (460 + 466 + 490)/3 = 472 490 is the largest deviation from the average voltage. Max. deviation = 490 - 472 = 18
% voltage unbalance = (18/472) x 100 = 3.8% If the percent voltage unbalance is greater than 4.5%, MotorSaver®is functioning properly, saving your motor from abnormal power conditions.
5. If the percent voltage unbalance is less than 4.5%, contact SymCom at 1-800-843-8848 OR 1-605-348-5580 and we will be happy to help you.
SPECIFICATIONS MODEL 102-A MODEL 201-A MODEL 250-A MODEL 350
Line Voltage Ranges 190 - 480VAC 190 - 480VAC 190 - 480VAC 190 - 240VAC (200V Model)
380 - 480VAC (400V Model)
475 - 600VAC (600V Model)
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Operating Points
Low Voltage
Trip (% of setpoint) 90% 90% 90% 90%
Reset (% of setpoint) 93% 93% 93% 93%
High Voltage
Trip (% of setpoint) N/A (Standard)
Option 9 (110%)
N/A (Standard)
Option 9 (110%)
110% N/A (Standard)
Option 9 (110%)
Reset (% of setpoint) N/A (Standard)
Option 9 (107%)
N/A (Standard)
Option 9 (4 Seconds)
N/A (Standard)
Option 9 (107%)
107% N/A (Standard)
Option 9 (107%)
Voltage Unbalance (NEMA)
Trip (% of setpoint) 6% 6% 6% 6%
Reset (% of setpoint) 4.5% 4.5% 4.5% 4.5%
Trip Delay Time (Nominal)
Low Voltage 4 Seconds (Standard) 4 Seconds 4 Seconds 4 Seconds (Standard)
Option 3 (2 - 30 Seconds)
High Voltage 4 Seconds N/A (Standard)
Options 3 & 9 (2 - 30 Seconds)
N/A (Standard)
Option 9 (4 Seconds)
Unbalance & Phasing Faults 2 Seconds 2 Seconds 2 Seconds 2 Seconds
Restart Delay Time
After a Fault 2 Seconds (Standard)
Option 2 (2 - 300 Seconds)
2 Seconds 2-300 Seconds 2 Seconds (Standard)
Option 2 (2 - 300 Seconds)
From complete power loss 2 Seconds (Standard)
Option 2 (2 - 300 Seconds)
2 Seconds 2-300 Seconds 2 Seconds (Standard)
Option 2 (2 - 300 Seconds)
Manual Reset N/A (Standard)
(Available with option 2)
N/A (Standard) Standard N/A (Standard)
(Available with option 2)
Output Contact Rating
Pilot Duty (SPDT) 480VA @ 240VAC or
10A General Purpose 10A General Purpose
480VA @ 240VAC or
15A Gen. Purp. or 1 hp @ 240VAC (200V Unit)
470VA @ 600VAC (400 or 600V Unit)
2-15A Gen. Purp. or 1 hp @ 240VAC (Option 8)
Pilot Duty (DPDT) 480VA @ 240VAC or
10A General Purpose
2500V for 10 ms 2500V for 10 ms 2500V for 10 ms 2500V for 10 ms
Power Consumption 5 Watts (max.) 5 Watts (max.) 5 Watts (max.) 5 Watts (max.)
Weight 14 oz. 9 oz. 14 oz. 1.5 lbs.
Ambient Operating Temperature
Ambient Storage Temperature
-40 to 70 ºC
-40 to 80 ºC
-40 to 70 ºC
-40 to 80 ºC
-40 to 70 ºC
-40 to 80 ºC
-40 to 70 ºC
-40 to 80 ºC
Internal Transient Protection
Using IEC 1000-4-5:1995
Loading...
+ 8 hidden pages