Motec LTC, LTCD, LTCD-NTK, LTC-NTK User Manual

Page 1
MoTeC LTC User Manual
Contents
Introduction .............................................................................. 2
Installation ................................................................................ 4
LTC Install ation ..................................................................................4
Lambda Sensor Installation ................................................................4
LTC Manager Software Installation ....................................................6
CAN Bus Interface ................................................................... 7
Configuration ........................................................................... 9
Introduction ........................................................................................9
Setup .................................................................................................9
Calibration ....................................................................................... 16
Firmware ......................................................................................... 19
Operation ................................................................................ 20
Monitori ng LTCs .............................................................................. 20
MoTeC Data Loggers ....................................................................... 24
MoTeC M1 ECUs ............................................................................. 25
MoTeC 'Hundred Ser ies' ECUs ........................................................ 26
Lambda and Air Fuel Rati o............................................................... 28
LTC Operating Tips.......................................................................... 30
Appendices ............................................................................ 31
Appendix A – Specifications ............................................................. 31
Appendix B – Pinout ........................................................................ 32
Appendix C – Dimensions ................................................................ 34
Appendix D – Wiring Det ails ............................................................. 37
Appendix E – LTC CAN Messages ................................................... 39
Appendix F – Lambda t o Air Fuel Ratio Table .................................. 42
Copyright  2016 – MoTeC Pty Ltd
The information in this document is subject to change without notice.
cons equenc es of an y in accur aci es or omis s i ons in t his m an u al.
V1.7 24 February 2017
Page 2
2 Introduction
Introduction
MoTeC LTCs (Lambda to CAN) monitor and control Wideband Lambda sensors and transmit Lambda readings and diagnostics on a CAN bus. There are single channel LTC and Dual channel LTCD avail able to suit either Bosch LSU4.9 or NTK sensors:
#61300 – Single Channel Bosch LSU 4.9 Sensor
#61301 – Dual Channel B osch LSU 4.9 Sensors
#61304 – Single Channel NTK Sensor
#61305 – Dual Channel NTK Sensors
Up to 32 Lambda sensors can be configured on a single CAN bus using LTCs, allowing an E CU or Data Logger to simultaneously monitor multiple Lambda sensors.
Throughout t his manual the LTC, LTCD, LTC-NTK and LTCD-NTK will be refer r ed to as LTC except where details specific t o a particular model are discussed.
Features
Accurate Lambda m easurement even when the exhaust gas temperature is changing rapidly (heating or cooli ng)
Ability to perform free air sensor calibration or use the initial sensor factory calibration. LTC-NTK has the ability to be calibrated against a test gas.
Pre-configured to work in a single LTC or LTCD installation, without requiring configuration with a PC
LTC Manager software to:
o configure and calibrate all LTCs on the CAN bus o display readings and diagnostics o configure the CAN transmission address of each LTC o control free air calibration o update LTC firmware
Compatibility
MoTeC ‘Hundred Series’ ECUs: M400, M600, M800 and M880
MoTeC M1 Series ECUs
MoTeC Data Loggers: ACL, SDL, S DL3, ADL, ADL2, ADL3, CDL3 and all
C Series colour Display Loggers (C187 etc .)
Page 3
MoTeC Introduction 3
Accessories
#57006 Bosch LSU 4.9 Lambda Sensor
#57007 NTK Lam bda Sensor
#61059 MoTeC UTC - USB to CAN, used to comm unicate to the PC
(optional) Note: LT C is not compati ble with MoTeC's CAN cable (part number
61021)
Page 4
4 Introduction
Installation
LTC Installation
The LTC can be mounted t o a flat surface using the two mounting holes. The LTC should be mounted as far as possible from the exhaust to avoid
excessive heat. Note: LT C maximum ambient temperature is 100 °C. Use Connector A to connect the single LTC to the Lambda sensor. Use
connectors A and B t o connect the LTCD to two Lambda sensors. Use the Power/CAN Connector to power the LTC and connect to the CAN bus.
See
Appendices for more details.
Lambda Sensor Installation
Warning: The Bosch LSU 4.9 Lambda sensors are fitted from the factory with
a calibrat ed trim m ing resistor embedded in the sensor connec tor. If the factory sensor connector is cut off and replaced with another type, t he LTC will not operate correc tly.
Note: Unlike the Bosch LSU 4.9 the NTK sensors standard connect or can be
removed and r eplac ed by a non-standard connector without affecting the performance of the sensor or the LTC-NTK. However, the initial factory calibration method will not work as the calibration resistor is built into the origi nal c onnec tor. In this case Free Air cali br ation is required. It is recommended that no wiring modification is made to the NTK sensor or LTC­NTK unless completely necessary.
The Lambda sensor should be fitted to the exhaust system with the sensor tip protrudi ng into the exhaust gas flow. The following c onsi der ations should be taken into acc ount when fitting the sensor:
Place the sensor on an angle between 10 and 90 degrees to the vertical with the tip of t he sensor pointing down to prevent condensati on build up between the sensor case and the sensor cer amic.
Do not place the sensor in a vertical position; excess heat soak will prevent pr oper oper ation.
Place the sensor at least 1 metre from the exhaust ports to av oid excessive heat (recommended).
Place the sensor at l east 1 metre from the open end of the exhaust system to avoid incor r ect r eadings due to outside oxygen (recommended)
Page 5
MoTeC Installation 5
o Where necessary for short er ex haust systems the sensor could be
placed closer to the engine.
Place the sensor away fr om the fl am e front comi ng out of the cylinder head and away fr om areas where one cylinder may have more effect than another.
If possible, do not place the sensor near exhaust slip joints; some designs allow air to enter resulting in inc orrect readings. If the sensor has to be plac ed near a sli p joint, reverse the slip joint s to reduce the i nfluence of introduced ai r.
Exhaust slip joint design
Exhaust flow
Introduced air No air introduced
Incorrect sensor
placement
Correct sensor plac ement
Page 6
6 Introduction
LTC Manager Software Installation
The LTC Manager software is required for confi gur ation and calibration of LTC units. The software must be install ed on Windows XP SP3 or later. The same software package i s used f or the LTC, LTCD, LTC-NTK and LTCD-NTK.
Note: The LTC Manager software is not required if usi ng a singl e LTC or LTCD unit preconfigured by MoTeC.
Install LTC Manager Software
Go to the MoTeC website at www.motec.com and navigate to downloads > software > latest releases > LTC Manager
Save the LTC Manager installation file in your pref er r ed loc ation (for example desktop)
Double cli c k the saved file to run the installer
Follow the installation instruc tions on the Install Wizard
To start the program aft er installation,
double click the LTC Manager icon on the desktop
OR
Click Start > All Pr ogr am s > MoTeC > LTC > LTC Manager
Updating Software
Software updates are available free of char ge, giving access to the latest features for the life of the device. Download the latest software versions from the website and f ollow the software installation instructions to update to the new version.
To update the associated firmware in the device see
Firmware.
Page 7
MoTeC Installation 7
CAN Bus Interface
Gateway Devices
LTC Manager comm unic ates with the LTC devices on the CAN bus via a MoTeC gateway devi c e.
Supported gateway dev ices include:
MoTeC UTC (USB To CAN) connected to the PC via USB.
MoTeC M1 ECU (all models) connected to the PC via Ethernet.
MoTeC Display Loggers (all C Series Display Loggers, e.g. C185, plus
ACL, ADL3, SDL3, CDL3) connected to the PC via Ethernet.
The gateway devic e m ust be sel ec ted in LTC Manager as shown below. For gateway devi c es that have multiple CAN interf ac es (e.g. Display Loggers), the appropriate CAN bus must also be select ed.
The selected gateway and CAN bus are saved and will be used by default the next time LTC Manager is run.
CAN Bitrate Settings
All devices on a CAN bus must be confi gur ed to the same CAN bitrate. The CAN bitrate setting in LTC Manager (Tools > Options) must be set t o
match the bitrate of the connected CAN bus.
100R
100R
LTC
M1
ECU
Display
Logger
LTC
LTC LTC
CAN-HI
CAN-LO
Ethernet
UTC
USB
PC
PC
PC
Ethernet
Page 8
8 Introduction CAN Bitrate Conversion Tool
All LTC dev ic es are initially confi gur ed with a 1Mbps CAN bitrate. For applic ations that require a different CAN bitrate, each LTC on the bus must
be individually convert ed to operate at the new bitrate. Supported bi trates are 1Mbps (default) , 500Kbps, 250K bps and 125Kbps. The bitrat e c onv er si on tool (Tools > Options) allows an LTC t o be converted to
any of the four supported bitrates (1Mbps, 500Kbps, 250Kbps and 125Kbps). Note: During t he bitrate conversion, all devices must be removed from the
CAN bus except for one LTC device and the MoTeC gateway device. This is required as the LTC and gateway device change bitrate during the
conversi on pr oc ess. If any other CAN devic es are present then CAN bus would be in error, preventing all devices fr om communic ating.
Page 9
MoTeC Installation 9
Configuration
Introduction
LTC Manager is used to individually configure and cali brate the connected LTC units. Configuration using LTC Manager is only necessary if installing multiple LTC units or if changes to the default settings are required.
All LTC configur ation and calibrati on oper ations are performed di r ectly on an LTC and configur ations are not stored on disk.
Note: LT C units come pre-configured to suit a single LTC or LTCD unit installation using the initial factory sensor calibration.
The default CA N addr ess f or the LT C is hex 460. The default CA N addr esses for LTCD is hex 460 for Lambda sensor 1 and hex 461 for Lambda sensor 2.
Start LTC Configuration
Connect the unit to the PC (see Appendix D – Wiring Details)
Ensure the unit is powered
Start LTC Manager
o Click the LTC Manager icon on the desktop
OR
o Click Start > All Programs > MoTeC > LTC > LTC Manager.
Select the c or r ect gateway and CAN bus (see
CAN Bus Interf ac e)
The main LTC Manager window displays the live configurati on and status of all LTC units present on the connec ted CAN bus.
Setup
CAN Address
The CAN setup determi nes which CAN addr es s (speci fied in hex) the LTC uses to transmit readings and diagnostic information. The format of the CAN messages is described in.
Appendix E – LTC CAN Messages
Each LTC on a CAN bus must be confi gur ed with a unique CAN address. See
Operation for information on confi guri ng a M oTeC Data Logger or ECU to
receive LTC CAN m essages.
Page 10
10 Introduction LTC 4.9 Unit Setup
To open the LTC Setup window, double click the row in the table
containing the LTC or click the row and click Setup.
Select the Reco mmend ed Address c hec k box and enter one of the
addresses in the dr op down box to communicate wit h MoTeC product s such as Data Loggers or 'Hundred Series' ECUs. The recommended addr ess range for LTC messages is hex 460 to hex 47F.
OR
Select the Custo m Address chec k box and enter an address (in hex) for interfacing with third party equi pm ent.
OR
Select Disabled to prevent an LTC from transmi tti ng CAN messages. While disabled an LTC will not heat the sensor or perf orm Lambda measurements.
Note: Lambda sensors should not be left in t he ex haust system of a running engi ne if they are not being controll ed. A disabled sensor in a running engi ne c an be dam aged.
In the Name area the def ault name will appear. The default nam e matc hes
the selected CA N A ddr ess (LTC1 et c .). If required the user can specify a custom name ( e.g. Left Bank or Cylinder 4) .
Click OK. The configuration updates will be sent to the LTC, this may take
several seconds
Page 11
MoTeC Installation 11 LTC-NTK Unit Setup
To open the LTC Setup window, double click the row in the t able
containing the LTC or click the row and click Setup.
Select the Recommended Address check box and enter one of the
addresses in the dr op down box to communicate with MoTeC products such as Data Loggers or 'Hundred Series' ECUs. The recommended addr ess range for LTC messages is hex 460 to hex 47F.
OR
Select the Custo m Address chec k box and enter an address (in hex) for interfacing with third party equi pm ent.
OR
Select Disabled to prevent an LTC from transmi tti ng CAN messages. While disabled an LTC will not heat the sensor or perf orm Lambda measurements.
Note: Lambda sensors should not be left in t he ex haust system of a running engi ne if they are not being controll ed. A disabled sensor in a running engi ne c an be dam aged.
Page 12
12 Introduction
In the Name area the def ault name will appear. The default nam e matc hes
the selected CA N A ddr ess (LTC1 et c .). If required, the user can specif y a custom name ( e.g. Left Bank or Cyli nder 4) .
Select a Standard Sensor type f r om the dr op down menu
OR Select a Custom Sensor Note: Custom sensor setups are for advanced users and it is not
recomm ended for general use.
Select a Standard Output Tab le, generally Lambda to three decimal places
OR
Use a Cust om Ta ble for another ty pe of f uel, e. g. Diesel.
Click OK. The configurati on updates will be sent to the LTC, this may take
several seconds
LTC-NTK Output Table
The standard output table for the LTC-NTK is for Lambda to three dec im al places. It is possible f or the user to m ak e a custom t able to suit the Air/Fuel ratio of any fuel.
When the Edit button is clicked under Output Table a table of Normalized Current appears. The standard Lam bda v alues appear in the Output column, these num ber s can be modified to reflect Air/Fuel ratio of a specific fuel. See
Appendix F for details of common
fuels.
Custom tables can be sav ed usi ng the Save As button.
Page 13
MoTeC Installation 13 Richer than Standard Lambda Readings
The Lambda reading r ange of t he LTC-NTK c an be ex tended by adding extra sites to the Standard Table. If the Standar d Table is selected (Lambda 3dp), the user can select Custom Table, then Edit, which will expose the curr ent Lambda Calibration Table.
At the lower end of the table, users can enter their own values for richer mixtures. The table will be reordered when Enter is pressed.
The Save As option is recommended in order to save the modified t able with a diff er ent name.
NOTE: MoTeC only recommends rich Lambda values down to 0.63La for the NTK sensor. W hile it is possible to enter current values and their subsequent Lambda values to t he table, this must be based on the user’s own t esting.
The following table is a suggested starting point for richer Lambda r eadings.
Page 14
14 Introduction
This can be added to the MoTeC-prov ided calibration table in the LTC-NTK setup.
Testing should be done to ensure the accuracy of any v alues enter ed
into the table bey ond the MoTeC-provided values.
CAN Colle ct Fu nctionality
CAN Collect func tionality allows one LTC (the CA N Collect M aster ) to collect CAN data from up t o 15 other slave LTCs, and retransmit these Lambda readings on a single CA N addr ess (see
Appendix E – LTC CAN Messages).
Note: A CAN Coll ect M aster dev ic e will c ontinue to transmit the standard LTC messages in addi tion to the special coll ect m aster messages.
CAN Collect functionality requires onl y a single CAN address to be configured on a MoTeC Data Logger to receive up to 16 Lambda readings.
See
Operation for information on confi guri ng M oTeC Data Loggers or ECUs to
use CAN Collect.
Configure Master and Slave Units
To configure an LTC as the CAN Collect Master device, select the CAN Collect Master check box and select a CAN address.
The CAN address for the Master dev ice is the address on which the coll ected Lam bda v alues wil l be retransmitted. This address must end in a zero (i.e. hex 460, 470 etc). The recommended addr ess is hex 460.
To configure an LTC as a CAN Collect Slave device, clear the CAN Collect Master check box and select a CAN address.
The CAN address for a Sl av e devi c e must be confi gur ed with one of the 15 addresses following the master address. For ex am ple, if the collect master address is hex 460, the slave devices must use CAN addresses in the range hex 461 to 46F.
Normalized Ip (mA) Output ( Lambda)
-8.000 0.620
-9.000 0.605
-10.000 0.590
-11.000 0.575
-12.000 0.560
-13.000 0.545
Page 15
MoTeC Installation 15
The Collect column on the main LTC Manager Window shows the configuration of CAN Collect Masters and Sl aves. The Master devic e is al ways shown as LTC unit 1 (Master (1) ) , and t he sl av e dev ic es are shown as LTC unit s 2 to 16 according to the confi gur ed CA N address as shown in this examp le.
Page 16
16 Introduction
Calibration
Warning: The Bosch LSU 4.9 Lambda sensors are fitt ed from factory with a
cali br ated t rimming resistor embedded in t he sensor connect or , if the factory sensor connector is cut off and replaced with another type the LTC will not operate correc tly.
Note: Unlike the Bosch LSU 4.9 the NTK sensors standard connector can be
removed and r eplac ed by a non-standard connector without affecting the performance of the sensor or the LTC-NTK. However, the initial factory cali br ation method will not work as the calibration resistor i s buil t into the origi nal c onnec tor. In this case Free Air calibration is required. It is recomm ended that no wiri ng m odification is made to the NTK sensor or LTC­NTK unless completely necessary.
Calibration Methods
Initial fact ory calibration
The default c alibration method uses the known characteristics of a new sensor that has been f ac tory trimmed.
Free Air Calib rat io n
As a sensor ages, the sensor calibration may change. To maintain accurate readings, the LTC allows for re-calibration using the k nown oxygen concentrat ion of free air. The free air calibration procedure takes several readings with the sen sor in free air to calculat e new calibrat ion values.
To perform an accur ate free air calibration, the lambda sensor must be removed from the exhaust and placed in an open air environment.
It is recommended to perform the cali br ation outside of a workshop or dyno room as there may be large am ounts of hydrocarbons in the atm osphere. Contaminated air will result in an incor r ect c alibr ation or a failure to calibrate. Wind shoul d also be avoided as it can affect the free air calibration.
Reference Gas Calibration (LTC-NTK only)
Referenc e gas samples for different lam bda c an be purchased (not avail able from M oTeC) for use as a means of calibrating the LTC-NTK. This method is provided for but is unlikely to be implemented by most users.
Calibrate the LTC 4.9 Unit
Click Calibrate… to open the Gain Calibration window
Page 17
MoTeC Installation 17
Select one of the t hr ee options available:
o Initial F actory S ensor Calibration. Thi s is the default value and
can be used in most cases.
o Entered Free Air Calibration. A calibration value from a previous
Free Air Calibration can be entered.
o Free Air Calib rat io n. A calibration is performed with the sensor in
free air. To perform the free air calibration:
- Click Perform Air Calibration Note: The calibration process may take several minutes during
which the cali br ation progress window is display ed.
- The new calibr ation value is displayed. This value should be
recorded against the serial number of the sensor to enter this calibration when the sensor is used with another LT C unit.
- To apply the new calibr ation click OK.
Click OK to save the calibration method and settings to the LTC.
Tip: Spare sensors can be air calibrated before an event and tagged with t he
14 digit calibr ation number. This number c an be used in the entered Free Air Calibration option for quick replacem ent of a sensor during the event.
Page 18
18 Introduction Calibrate the LTC-NTK Unit
Click Calibrate… to open the Gain Calibr ation window
Select one of the four options available:
o Initial F actory S ensor Calibration. Thi s is the default value and
can be used in most cases.
o Entered Gain Factor. A gain factor fr om a previous Free Air
Calibr ation or Reference Gas Calibration can be entered.
o Reference Gas Calibration. A Reference Gas Cal ibration is not
recomm ended for normal use as it required cali br ated testi ng gas.
o Free Air Calib rat io n. A calibration is perform ed with the sensor in
free air. To perform the free air calibration:
- Click Star t F r ee Ai r Cali br ation Note: The calibration process may take several minutes during
which the cali br ation progress window is display ed.
- When the calibration is complete the new calibration value is displayed. This value should be recorded against the serial number of the sensor to ent er this calibration when the sensor is used with another LTC unit.
- To apply the new calibr ation click OK.
Page 19
MoTeC Installation 19
Click OK to save the calibration method and settings to the LTC.
Tip: Spare sensors can be air calibrated before an event and tagged with t he
4 digit calibr ation number. This number c an be used in the Entered Gain Factor calibration option f or qui c k replacement of a sensor during the event.
Firmware
Each version of the LT C Manager software includes a matching firmware version that m ust be sent to the LTC in order to operate correctly.
The Config Status column in the main LTC Manager window will indicate if the firmware version requires updating.
Update the Firmware
Select the LTC row in the main LTC Manager window
Click Update Firmware.
A progress windo w will be displayed while the firmware is sent to the LTC.
Page 20
20 Operation
Operation
Monitoring LTCs
The main LTC Manager window shows live readings, diagnostics and LTC state inf ormation for all connected LTCs.
Sensor Type
The Sensor Type colum n shows the sensor ty pe. For an LTC 4.9 the sensor type will always be LSU4.9 and for an LTC-NTK the sensor type will be the configur ed type.
Serial Num
The Serial Num colum n shows the uni que serial numbers of all connec ted LTCs. An LTCD will be displ ay ed as two LTCs with the same serial num ber but the designat or s A and B to ident ify the two sensors.
Name
The Name column shows the assigned names of all connected LTCs. The displayed name is configured in the Setup dialog.
Readings
The Readings col um n shows live readings of all connected LTCs. The readings can be configured to display as either Lam bda or AF R (Air Fuel Ratio) for a num ber of different fuels.
Note: t he displ ay units do not affect the units of the tr ansmitted readings i n CAN messages.
Page 21
MoTeC Operation 21
Configure display units
Select Tools > Options.
Choose a predefi ned stoichiometric AFR for one of various fuels
OR
Define a c ustom AFR by enteri ng a stoichiometric point bet ween 1.0 and 100.0.
Display live readings in larger format
Select View > Readings or press F5. This lar ger format display provides a usef ul m eans of monitori ng several sensor val ues whil e tuning.
Sensor State
The Sensor Stat e c olum n shows the operat ing state of all connected LTCs.
Sensor State Description
Starting LTC hardware is performing a self calibr ation Heating
The Lambda sensor is outside the tem per ature range
required for measurement Running Lambda measurement is active Cooling
A heater short cir c uit or a failure to reach operating
temperatur e has occur r ed. The sensor is allowed to
cool befor e another attempt at heating.
Page 22
22 Operation
Diagnostics
The Diagnostics column shows fault s and diagnosti c information for all connected LTCs.
Diagnostic Description
Heater short circuit (GND)
A short circuit to ground has been detec ted in the
heater wiri ng Heater short
circuit (Batt+)
A short circuit to bat tery+ has been detected in the
heater wiri ng Heater open
circuit
An open circ uit has been detected in the heater wiring
Failed t o achi ev e heat
The measured sensor temperature is not responding
to sensor heating. This fault may indicat e a fault with
the sensor wiring. Sensor short
circuit
A short circuit has been detec ted in the sensor wiring
Corrupt Firmware
The LTC firmware is corr upt. Upgrade the firmware to
restore operation. Incompatible
Firmware
The LTC firmware is i nc om patible with LTC Manager.
Upgrade the firmware to restore operati on.
LTC Temp
The LTC Temp column shows live internal temperat ur e readi ngs of all connected LTCs.
Note: The tem per ature column shows the temperat ur e of t he LTC unit , not the sensor temper ature.
CAN Address
The CAN Address column shows the conf igured CAN addresses (in hex) of all connected LTCs.
To configure the CAN addresses see
Setup.
Collect
The Collect column shows the configured CAN Coll ect functionality of all connected LTCs. To configure the CAN Collect functionality see
Setup.
A configured CAN Collect Master device is always shown as Master ( 1) . Any LTC unit configur ed with a CAN address within the 15 CAN addresses
following a Collect Master address will be shown as Slave (x).
Page 23
MoTeC Operation 23
The number in the c ollec t column (e.g. (3)) refers to the LTC number ( 1 to 16) in the messages transmitted by a Collect Master LTC.
For more inf ormati on about CAN Collect, see
CAN Collect Functionality
Config Status
The Confi g Status col um n shows any issues rel ating to the confi gur ation of the connected LTCs.
Config Status Description
OK Config is OK Disabled The LTC has been disabled under the Setup options.
A disabled LT C will not measure or transmit readings.
Incompatible Config
The configuration in the LTC is not compatible wit h the firmware i n the LT C. A new configuration can be sent to the LTC by changing the Setup or Calibration.
Corrupt Config
The configuration in the LTC is corrupt. A new configur ation can be sent to the LTC by changing the Setup or Cali br ation.
CAN Address Conflict
Multiple LT C units have been configured with t he same CAN address. Each LTC m ust be c onfigured with a unique address.
Device Type
The Devic e Ty pe colum n shows the model of the connected LTC (LTC4.9 or LTC-NTK).
Firmware Version
The Firmware Versi on c olumn shows the version of the firmware in eac h of t he connected LTCs.
Page 24
24 Operation
MoTeC Data Loggers
MoTeC Data Loggers incl ude CA N c ommunication templates to rec eiv e LTC messages fr om up to 16 LTCs.
Received Lambda readings and diagnostic s can be displayed and logged. Refer to the Dash Manager sof tware for more inform ation.
There are two methods for receiving LTC CAN messages with a logger device: o Using One CAN Template Per LT C
Select the m atching template (e.g. LTC #1 (CAN ID 460)) to rec eiv e all avail able r eadings and diagnostics fr om an LTC. T he select ed template must match the LTC CA N address specif ied in LTC Manager.
Receiving full LTC messages provides the most information about an LTC and requires one CAN section per LTC in the communications setup.
o Using LTC CAN Collect T empl at e
Select the LTC Collect 16 Channel CAN templat e to receive Lambda readings f r om up to 16 LTCs. T he LTCs must be configured in LTC Manager f or CAN Collect functionalit y using addres s hex 460 for the CAN Collect M aster .
Receiving CAN collect messages provides only Lam bda r eadings from each LTC but only r equir es one CAN section in the communications setup for up to 16 Lambda readi ngs.
For more information see
CAN Collect Func tionality.
Refer to Dash Manager help for details on loadi ng CAN templ ates.
Page 25
MoTeC Operation 25
MoTeC M1 ECUs
MoTeC M1 series ECU pack ages can support up to 32 LTCs. LTC configuration is found in M1 Tune under Exhaust > Lam bda where LTCs can be enabled for Banks, Collectors and individual cylinders.
LTC devic es are configured in M1 Tune by setting the CAN bus, Index and LTC Type.
The Index specifies the CAN ID (e.g.. 0x460) used to receive LTC CAN messages. The Index for each confi gur ed LTC must be unique and must match the configured LTC device.
The LTC Type must match the connected LTC Device. Type LTC refers to a LTC4. 9 dev ic e Type LTCN refers to a LTC-NT K device
See the package help in M1 Tune for details on lambda setup.
Page 26
26 Operation
MoTeC 'Hundred Series' ECUs
MoTeC ‘Hundred Series’ ECUs (M400, M600, M800, M880) can be configured to receive Lambda m easurements from up to 12 LTCs using the existing PLM CAN templates i n the ECU Manager software. The M84 ECU can rec eiv e two channels of Lam bda with CAN addresses 460 and 461.
Received Lambda readings can be used in engine control and logged. Refer to the ECU Manager sof tware for more information.
Note: The ECU only stor es the Lambda r eadings from the LTC messages; LTC diagnostic information is not stored.
Configure Hundred Series ECU Communications for LTC
Select Adjust > General Setup > Communicati on > CAN Set up
For singl e LTC configuration:
o Select a spare CAN data sl ot in the range CAN 1 to CAN 6 o Enter 1 - PLM Rec eiv e for CA N Data
Enter the LTC CAN Address in decimal*
. The address must match
the CAN address specified in LTC Manager.
For CAN Collect configuration:
The LTCs must be configur ed in LTC Manager for CAN Collect functionality using address hex 460 f or the CAN Collec t Master .
o Enter 1 - PLM Rec eiv e for CA N 6 Data o Enter the LTC CAN address in decimal* for CAN 6 address.
The address must match the CAN address specified in LTC Manager f or the CA N Collect Master LTC. The recommended address is 1120.
* Important: CAN addresses in ECU Manager are in decimal, while the CAN addresses in LTC Manager are in hex
. e.g. 1120 decimal = 460 hex
Configur e M84 EC U Com m unications for LTC
Select Adjust > General Setup > Communication > CAN Setup
For singl e or dual LTC c onfiguration:
o Enter a CAN Address of 1120 (460 Hex ) into the PLM CAN
Address
Assign Lambda measurements to a Hundred Series channel
Lambda measurements from the LTCs must be assigned to an ECU c hannel before they can be used for engine control or logging.
Page 27
MoTeC Operation 27
Select Adjust > Sensor Setup > Input Setup... to open the Input Pins Setup
dialog.
Attach an LTC reading to a channel, using the following parameters
Input Source Predefined Calibration
PLM 1 to PLM 12 #81 Lambda: PLM over CAN
Example 1: LT C1 readi ng assigned t o c hannel Lambda 1
Example 2: LT C1 to LTC4 readings assigned to Lambda Cyl channels
Assign Lambda measurements to a M84 channel
For an M84 the Lambda Input Sour c e is fixed so only the Calibration needs to be chosen – Predefined “#81 Lambda: PLM over CAN”
Page 28
28 Operation
Lambda and Air Fuel Ratio
Lambda gives a measure of the Air to Fuel Ratio (AFR) that is independent of the type of fuel being used.
Lambda 1.00 Stoichiometric ratio: no excess fuel and no excess air Lambda > 1.00 Lean: exc ess ai r Lambda < 1.00 Rich: excess fuel
Stoichiometric Air Fuel Ratio for various fuels
Lambda Air Fuel Ratio Petrol Alcohol LPG Diesel
1.0 14.7 6.4 15.5 14.5
Calculations with Lambda
Fuel
Stoichiometric AFR
Measured value
Calculated value
Petrol 14.7 AFR = 14 Lambda = 14/14.7 = 0.95 Diesel 14.5 Lambda = 1.1 AFR = 1.1 x 14.5 = 16
See Appendix F – Lambda to Air Fuel Rati o Table for a quick reference table.
Engine Tuning wi t h Lambda
When tuni ng the engine, the target Lambda (or AFR) is dependent on the tuning objective. The following table can be used as a guideline.
Tuning objective Lambda
Maximum power 0.84 to 0.90 Economy 1.05 Emissions 1.00
Normally the engine is tuned for maximum power at full load and for emissions or economy at light loads.
The exact requi r em ents for a specific engine and fuel can only be found by experimentation. On turbo engi nes ext r a fuel may be desirable to reduce exhaust tem per atures and help avoid knock. If the vehicle is fitted with a catalytic c onv er ter, extra fuel may be requir ed to ensure the c atalyst does not overheat when not operating at Lambda 1.00
Page 29
MoTeC Operation 29
Lambda Sensor
Sensor Warm-up
The internal heater in the Lambda sensor is powerf ul enough to allow accurate measurem ent when gas temperature is at room temperat ur e. The sensor will take approximately 20 seconds to heat up.
The maximum continuous
operati ng temperature of the sensor is 850 °C.
Sensors should not be used at higher temperatures for a prolonged period, although t he sensor can be heated to 930 °C for a maximum of 10 minutes.
This may however reduce t he accuracy.
Sensor Lifetime
The sensor lif etime is dependent on the type of fuel being used and the volume of gas fl ow ov er the sensor.
Sensor lifetime will be reduced by contami nants such as silicon, lead, oil, etc. Thermal cycli ng and ex posure t o exhaust fumes without any heating control activ e will also age the sensor more rapidly.
Manifold seal ants can contaminate sensors. Use seal ants that are sensor­friendly to prevent reduced sensor lifetime.
When using leaded fuel, sensor element contamination will reduce t he sensor lifetime substantially. Typic ally sensor lifetime for high performance engines is at least 500 hours i n unleaded fuel and 50 hours in leaded f uel. Longer lifetimes can be expected for less demanding applications. These fi gur es are a conserv ative estimate as the sensors are designed t o be ac c ur ate for 50,000 km of operati on in a road car.
Incorrect placement in the exhaust can over heat the sensor and significantly reduce the sensor l ife. For the Bosch LSU 4.9 the sensor impedanc e ( Ri) is an indic ation of sensor temperature. I n normal operation Ri should be approximately 300 ohms. If Ri is less than 250 ohms then the sensor is bei ng overheated. Ri is included in the transmitted CAN messages. Due to the diff er ent control system for the NTK sensor the Ri param eter is not applicable.
At the end of its life the sensor becomes slow to respond and does not read rich properl y . Regular performanc e of the Free Air Calibr ation (see
Calibration)
will mai ntain the accuracy of the sensor over its lifetime.
Page 30
30 Operation
LTC Operating Tips
If the engine misfires for any reason, i ncl uding an over-rich mixture, the LTC may falsely read Lean. This is due to excess air being present in the exhaust gasses, caused by incomplete combustion.
Other areas that can give misleading readings include at high RPM, closed throttl e when the mix ture won’t burn completely. Following overrun fuel cut when the sensor has becom e satur ated with oxy gen it can take up to several seconds to resume acc ur ate readings. Engine misfires include hitting the rev­limiter , be it a fuel or ignition cut or a combination of both, and can give a similar r esul t wit h time being required to pur ge the sensor of ex c ess oxy gen or fuel.
Engines with hi gh ov erl ap c am shafts running at low speed may pump air through the engine resulting in a false l ean r eading, Th erefore the LTC may need to read leaner than would ot her wise be expected.
Page 31
MoTeC Appendices 31
Appendices
Appendix A – Specifications
Sensor Type
Bosch LSU 4.9 Lam bda sensor (LTC4.9)
NTK LZA09 Lambda Sensor
Power Supply
11 V - 16 V DC
110 mA typical current plus the sensor heater
current.
Heater current is ty pic ally 0.5 A - 1 A (up to 2 A
on startup)
Communications
1 Mbit/sec CAN
Physical
Dimensions 38 x 26 x 14 mm excluding wiring looms and connector s
Weight 62 grams
Mounting holes spacing 32 mm (Ø3.2 mm)
Max Temperatures
Max ambient t em per ature at device 100 °C
Max internal device temperature 125 °C
Page 32
32 Appendices
Appendix B – Pinout
Bosch LSU version (LTC 4.9)
LTC Connector A LTCD Connecto r A and B
Bosch LSU 4.9 sensor connect or Mating connect or : supplied on sensor
Pin No Wire Colour Description
1 Red Ip 2 Yellow Sensor 0 V 3 White Heater ­4 Grey Heater + 5 Green Ipr 6 Black Vs
Power/CAN Connector
DTM 4pin (M) (#68055) Mating connect or : DTM 4pin (F) (#68054)
Pin No Wire Colour Description
1 Black Battery ­2 Green CAN Lo 3 White CAN Hi 4 Red Battery +
Page 33
MoTeC Appendices 33
NTK version (LTC-NTK)
LTC-NTK Connector A
NTK sensor connector Mating connect or : supplied on sensor
Pin No Wire Colour Description
1 Blue Heater + 2 Yellow Heater - 3 Orange Rc 4 Black Sensor 0V 5 N/C 6 Grey VS 7 White IP 8 Black Sensor 0V
Power/CAN Connector
DTM 4pin (M) (#68055) Mating connect or : DTM 4pin (F) (#68054)
Pin No Wire Colour Description
1 Black Battery ­2 Green CAN Lo 3 White CAN Hi 4 Red Battery +
Page 34
34 Appendices
Appendix C – Dimensions
Page 35
MoTeC Appendices 35
Page 36
36 Appendices
Page 37
MoTeC Appendices 37
Appendix D – Wiring Details
Power Connections
Care must be taken f or power and ground wir ing for the LTC. Each sensor can draw over 3 Amps when cold if multiple channels of Lambda are used thi s current draw will increase dramatically. Wiring size should be suitable for the number of LTCs used.
Tip: To wire the LTC to power, connect either t o the igniti on switc h f or fast sensor start up or connect to the fuel pump relay to prev ent acci dental battery drainage
CAN Connections
Refer to the example below for details on wiring t he LTC CAN bus. This examples show multiple options (USB and E thernet) for the PC interfac e. See section
CAN Bus Interface for details on PC interfacing.
General CAN Bus Wiring Requirements
The CAN bus should consist of a twisted pair trunk wit h 100R termi nating resistors at each end. The preferred cable for the trunk is 100R data cable. The maximum length of the bus is 16 metres (50 ft)
CAN devices (such as MoTeC Data Loggers, ECUs etc) may be connected to the trunk with up to 500 mm (20 in) of twisted pair wires.
An optional CAN connector for the UTC may al so be connected t o the trunk with up to 500 mm (20 in) of twisted wire and should be wit hin 500 mm of one end of the trunk.
100R
100R
LTC
M1
ECU
Display Logger
LTC
LTC LTC
CAN-HI
CAN-LO
Ethernet
UTC
(optional)
USB
PC
PC
PC
Ethernet
Page 38
38 Appendices
CAN-LO
CAN-HI
100R
100R
CAN
Device
500mm Max
Optional
UTC
Connector
500mm
Max
<< CAN Bus >>
500mm Max
100R Terminating Resistors at each end of the CAN Bus
CAN
Device
CAN
Device
5
4
These wires must be twisted
Minimum one twist per 50mm (2i n)
Short CAN Bus
If the CAN bus is less than 2 metre (7 ft) long, a single termi nation resistor may be used. The resistor shoul d be placed at the opposite end of t he CAN bus to the CAN connector.
Page 39
MoTeC Appendices 39
Appendix E – LTC CAN Messages
Messages 1 and 2 are transmi tted by all LTC units. Messages 5 to 10 are onl y tr ansmit ted from an LTC unit configured as a CAN Collect M aster .
Message 1
Byte Name Scaling
0
Compound ID = 0
N/A
1:2
Lambda
Hi:Lo = x.xxxLa
3:4
Ipn (Normalised pump cell current)
Hi:Lo = xxxx μA
5
LTC Internal Temperature
xxx °C
6 Fault bits
Heater short to Gnd1 Heater short to V B att1 Heater open ci r c uit Heater failed to heat
1
Sensor wire short
1
Internal fault
1
Sensor Control fault2
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5
Bit 6
7 Heater duty cycle xxx%
1
LTC4.9 onl y 2LTC-NT K only
Message 2
Byte Name Scaling
0
Compound ID = 1
N/A
1 Sensor State
START
DIAGNOSTICS1 PRE CAL
1
CALIBRATION POST CAL
1
PAUSED HEATING RUNNING COOLING
1
PUMP START
2
PUMP OFF2
0
1 2 3 4 5 6 7 8 9
10
2:3
Battery Voltage
Hi:Lo = x.xxV
Page 40
40 Appendices
4:5
Ip (Raw pump cell cur r ent)
Hi:Lo = xxxx μA
6:7
Ri (Sensor cell impedence) (0 for LTC-NTK, not applic able)
Hi:Lo = xxxx Ohms
1
LTC4.9 onl y 2LTC-NT K only
Message 3
Byte Name Scaling
0
Compound ID = 2
N/A
1
Firm ware Versi on Lett er
0..25 = A..Z
2:3
Firm ware Versi on Num ber
e.g. 104 = v1.04
4:5
Serial Number
Message 5
Byte Name Scaling
0
Compound ID = 4
N/A
1
Reserved
N/A
2:3
LTC1 (Master LT C) Lambda
Hi:Lo = x.xxxLa
4:5
LTC2 Lambda
Hi:Lo = x.xxxLa
6:7
LTC3 Lambda
Hi:Lo = x.xxxLa
Message 6
Byte Name Scaling
0
Compound ID = 5
N/A
1
Reserved
N/A
2:3
LTC4 Lambda
Hi:Lo = x.xxxLa
4:5
LTC5 Lambda
Hi:Lo = x.xxxLa
6:7
LTC6 Lambda
Hi:Lo = x.xxxLa
Message 7
Byte Name Scaling
0
Compound ID = 6
N/A
1
Reserved
N/A
2:3
LTC7 Lambda
Hi:Lo = x.xxxLa
4:5
LTC8 Lambda
Hi:Lo = x.xxxLa
6:7
LTC9 Lambda
Hi:Lo = x.xxxLa
Page 41
MoTeC Appendices 41 Message 8
Byte Name Scaling
0
Compound ID = 7
N/A
1
Reserved
N/A
2:3
LTC10 Lambda
Hi:Lo = x.xxxLa
4:5
LTC11 Lambda
Hi:Lo = x.xxxLa
6:7
LTC12 Lambda
Hi:Lo = x.xxxLa
Message 9
Byte Name Scaling
0
Compound ID = 8
N/A
1
Reserved
N/A
2:3
LTC13 Lambda
Hi:Lo = x.xxxLa
4:5
LTC14 Lambda
Hi:Lo = x.xxxLa
6:7
LTC15 Lambda
Hi:Lo = x.xxxLa
Message 10
Byte Name Scaling
0
Compound ID = 9
N/A
1
Reserved
N/A
2:3
LTC16 Lambda
Hi:Lo = x.xxxLa
4:5
Reserved
N/A
6:7
Reserved
N/A
Page 42
42 Appendices
Appendix F – Lambda to Air Fuel Ratio Table
Lambda Air Fuel Ratio
Petrol
Alcohol
LPG
Diesel
0.70
10.3
4.5
10.9
10.2
0.75
11.0
4.8
11.6
10.9
0.80
11.8
5.1
12.4
11.6
0.85
12.5
5.4
13.2
12.3
0.90
13.2
5.8
14.0
13.1
0.95
14.0
6.1
14.7
13.8
1.00
14.7
6.4
15.5
14.5
1.05
15.4
6.7
16.3
15.2
1.10
16.2
7.0
17.1
16.0
1.15
16.9
7.4
17.8
16.7
1.20
17.6
7.7
18.6
17.4
1.25
18.4
8.0
19.4
18.1
1.30
19.1
8.3
20.2
18.9
1.35
19.8
8.6
20.9
19.6
1.40
20.6
9.0
21.7
20.3
1.45
21.3
9.3
22.5
21.0
1.50
22.1
9.6
23.3
21.8
1.55
22.8
9.9
24.0
22.5
1.60
23.5
10.2
24.8
23.2
Loading...