MoTeC ESDL3 User Manual

Page 1
MoTeC SDL3 User Manual
Copyright © 2010 – MoTeC Pty Ltd
The information in this document is subject to change without notice.
While every effort is taken to ensure correctness, no responsibility will be taken for the
consequences of any inaccuracies or omissions in this manual.
PN 63037 V 1.2, May 2013
Page 2
SDL3 User Manual
Introduction .............................................................................. 1
Features ................................................................................................ 1
System Overview .................................................................................. 3
Typical Devices used with the Dash Logger .............................. 3
Installation ................................................................................ 6
Mounting and Wiring ............................................................................. 6
Connecting Devices .............................................................................. 7
Inputs .......................................................................................... 7
Outputs ....................................................................................... 9
Communications ....................................................................... 10
Connecting Devices Examples ................................................ 11
Software Installation ........................................................................... 12
Dash Manager Software ........................................................... 12
i2 Data Analysis Software ........................................................ 13
Connecting the Dash Logger to a PC ...................................... 13
Configuration ......................................................................... 15
Configuration Sequence ..................................................................... 15
Configuration File ............................................................................... 15
Channels ............................................................................................. 16
Channel Properties ................................................................... 18
Selecting Channels .................................................................. 19
Connections ........................................................................................ 21
Configuring Inputs .................................................................... 21
Configuring Outputs ................................................................. 21
Configuring Communications ................................................... 21
Calculations ........................................................................................ 22
Special Calculations ................................................................. 22
General Purpose Calculations ................................................. 22
Functions ............................................................................................ 23
Data Logging ............................................................................ 23
Display ...................................................................................... 27
Page 3
MoTeC SDL3 User Manual
Alarms ...................................................................................... 31
Other Functions ........................................................................ 32
Operation ................................................................................ 33
Retrieving the Logged Data ................................................................ 33
Sending and Retrieving Configuration Files ....................................... 33
Zeroing Sensors ................................................................................. 33
Checking Operation ............................................................................ 34
Configuration Versions and Updating ................................................. 34
Upgrading the Dash Logger ..................................................... 35
Password Protection ................................................................ 35
Other Online Activities .............................................................. 35
Appendices ............................................................................ 37
Specifications ...................................................................................... 37
Dash Logger Upgrades ...................................................................... 39
Characteristics .................................................................................... 40
Input Characteristics ................................................................. 40
Output Characteristics .............................................................. 45
SDL3 Pin List by Pin Number ............................................................. 46
SDL3 Pin List by Function .................................................................. 48
Mounting Dimensions ......................................................................... 50
Wiring .................................................................................................. 51
Connector ................................................................................. 51
Wire Specification ..................................................................... 51
PC Connection ......................................................................... 52
CAN Bus Wiring Requirements ................................................ 53
SDL3 Data Logger to ECU wiring (RS232) .............................. 54
Update Rate Summary ....................................................................... 56
Command Line ................................................................................... 58
CAN Bus Bandwidth Limit .................................................................. 60
Comms Error Codes ........................................................................... 61
Windows Keyboard Shortcuts ............................................................ 64
Glossary .............................................................................................. 69
Page 4
Page 5
MoTeC Introduction 1
Introduction
SDL3 - Sport Dash Logger
The SDL3 is a combined sophisticated display and powerful control device in one lightweight unit. With the addition of a Data Logging upgrade it becomes a fully programmable data logger with 16 MB or 120 MB memory (see Dash Logger Upgrades). The screen layout is fully configurable to display a multitude of data channels, warning alarms, lap times, fuel calculations, minimum corner speeds, maximum straight speeds and more. The SDL3 performs calculations, acquiring data from other MoTeC devices such as an ECU, other Dash Logger and input expander modules, which enable it to log a multitude of inputs.
ESDL3 - Enclosed Sport Dash Logger
The ESDL3 is an enclosed version of the SDL3, providing the flexibility to connect a display suitable for your application or to use as a 'black box' type data logger. It functions in the same way and uses the same software as the SDL3.
In the remainder of this documentation when reference is made to the SDL3 Dash Logger, it also applies to the ESDL3 – except when referring to the display.
Features
All MoTeC Dash Loggers come with a range of features as standard and several options available as upgrades to customise and grow your system. These additional features are activated through a simple password system, and can be purchased at any time when you need them.
See Dash Logger Upgrades
General
All-in-one display, logger and controller eliminates the need for separate devices
Suitable for bikes, cars, marine and industrial applications
Compact, durable and reliable unit
Supports wideband Lambda from PLMs or LTCs, using Bosch LSU or
NTK UEGO 5 wire sensors
Straightforward control for lights, fans, pumps
Easily integrated with MoTeC CAN based devices e.g. expanders, lap
timing devices, shift lights and ECUs
Page 6
2 Introduction Logging and Analysis
Optional internal data logging of 16 MB or 120 MB
Fast download via Ethernet
Accommodating over 300 channels derived from a mixture of analogue
and digital inputs, RS232 and CAN data channels
Configurable to use sensors from some existing engine management systems
Data analysis with i2 Standard or optional i2 Pro software
Display
Customisable screen layout, measurement units and warnings
Configurable curved bar graph can display any channel with optional
peak, hold and shift markers
48 user-defined alarms, for example Low Oil Pressure, Low Fuel, Fast Lap
Programmable overrides—particularly useful for showing values such as lap times
Three programmable 'pages' for Warm-up, Practice and Race ensure the driver is shown only the most relevant information at any given time
Adjustable backlight (optional)
Software
Windows-based software designed for setup and management of the display and data logging system
The user can generate a configuration file offline and send the completed configuration to the Dash Logger
Calculations including lap times, lap gain/loss, speed and distance, fuel prediction
Monitor active channels—view all channels live
Sensor zeroing
Details editor including event, venue and vehicle details
Extensive Help screens
To access the newest software features you can download the latest
version from www.motec.com/downloads
Page 7
MoTeC Introduction 3 Compatibility
MoTeC ECUs: M4, M48, M8, M400, M600, M800 and M880
MoTeC Accessories: MDD, E888, SLM, PLM, LTC, BR2, PDM, GPS, etc.
Many non-MoTeC devices
Required Accessories
Refer to Connecting the Dash Logger to a PC
Standard Ethernet cable
Any one of the following Ethernet to Autosport connections:
o #62202 SDL3 loom o #61131 Ethernet cable unterminated, 2 metre o #61132 Ethernet to Autosport pins cable, 1.8 metre
System Overview
The Dash Logger offers extensive possibilities to integrate with ECUs, peripheral devices and accessories to form a complete solution that powers, controls, logs, monitors and communicates virtually any automotive parameter.
Typical Devices used with the Dash Logger
ECUs
The Dash Logger can be connected to all MoTeC engine management systems and some other manufacturers' ECUs either via CAN or RS232. This avoids duplication of sensors and allows the Dash Logger to display and log many ECU parameters.
The typical update rate is about 20 times per second for RS232 and 50 times per second for CAN.
Sensors
The Dash Logger inputs can be connected to a wide variety of sensors. Different types of sensors are available to suit different types of measurements, for example: temperature, pressure, movement etc.
Sensors convert a physical measurement (e.g. pressure) into an electrical signal (e.g. volts).
Different types of sensors generate different types of electrical signals. For example most temperature sensors convert the temperature into a variable resistance which may be measured by an Analogue Temperature input.
Page 8
4 Introduction
However most wheel speed sensors generate a variable frequency signal which must be connected to either a Digital input or a Speed input.
Expanders
E888
The SDL3 supports an E888 Expander, 8 x 10 bit thermocouples only.
Accessories
BR2
A BR2 Beacon Receiver may be connected to the Dash Logger, which allows the Dash Logger to calculate lap times for display and to provide lap information for the data analysis software.
SLM
The SLM Shift Light Module can be used for shift lights, warning lights and other driver alerts.
The SLM includes 8 LEDs that can be programmed to display any colour.
GPS
The Dash Logger supports many GPS (Global Positioning System) devices allowing the Dash Logger to record speed and position information as well as providing lap timing.
This information can be used in the i2 data analysis software to create
track maps, and plot and compare driven lines.
Video
MoTeC’s Video Capture System (VCS) is an integrated in-car camera system, recording video and audio using the MPEG-2 video compression format at broadcast quality. It includes a built in real-time graphics processor that allows sensor data to be overlaid onto the video in real-time without the need for additional hardware. The CAN interface enables communication with other devices, for example to set Auto Start/Stop Recording conditions.
Multiple video streams, from in-car cameras for example, can be linked with logged data for synchronised playback of footage alongside other analysis components. Synchronised video requires a standard video capture device
and the Pro Analysis upgrade to provide access to i2 Pro data analysis
software. Note: Synchronisation can be completed manually or automated by recording
regular sync points onto the audio track of the video camera. This requires the
Page 9
MoTeC Introduction 5
small Video Sync Module (VSM) to be connected to an auxiliary output of the Dash Logger and to the audio input of the camera.
Lambda Measurement
PLM
The PLM Professional Lambda Meter measures the air fuel ratio over a wide range of mixtures with fast response time. It is compatible with Bosch LSU and NTK UEGO Lambda sensors and displays the Lambda readings via the integrated display.
LTC/LTCD
The LTC Lambda to CAN (Dual) meters provide accurate Lambda measurements even when the exhaust gas temperature changes rapidly. They are compatible with the Bosch LSU 4.9 Lambda sensor and transmit Lambda readings via the CAN bus.
Remote Displays
A remote display device may be connected to the Dash Logger to allow display of any value that the Dash Logger calculates, such as lap times and warning alarm messages.
The Dash Logger supports MDD displays which are connected via CAN.
PDMs
Power Distribution Modules are designed to replace conventional relays, fuses and circuit breakers by providing electronically switched power to the various electrical systems in the vehicle. This simplifies wiring and switch requirements, while increasing reliability.
Full diagnostic information, including output currents and error status can be transmitted via CAN to the Dash Logger.
Several models are available to suit vehicles with different complexity ranging from 15 to 32 outputs and 12 to 23 inputs.
Other Devices
Many other devices can be connected to the Dash Logger.
Page 10
6 Installation
Installation
This section provides information on how to install the Dash Logger in the vehicle and connect it to other devices. It will also provide information on how to install the software.
Mounting and Wiring
The Dash Logger has three threaded mounting posts. For further details see Mounting Dimensions
Mounting Tips
Avoid twisting the case: use washers between the unit and the mounting panel to ensure that the unit is mounted only at the mounting points and do not over tighten the mounting screws.
Vibration isolation may be desirable if the vehicle vibrates severely.
Mount so that the connector may be easily accessed.
Orientation: for best contrast, the display should be viewed at an angle of
approximately 20 degrees, However the Dash Logger will give good contrast between 0 and 40 degrees. Display reflections should also be considered when determining the mounting angle.
The SDL3 uses a 37 pin Autosport connector. See Connector List By Function for full details.
and SDL3 Pin
Wiring Tips
To ensure that the connector is sealed, plug unused holes with filler plugs. A heat shrink boot may also be used if desired.
Use 22# Tefzel wire (Mil Spec M22759/16-22) (5 A max at 100 C)
Tefzel wire is difficult to strip unless the correct stripping tool is used.
Be careful not to nick the wires as this may result in wire failure or poor
crimping.
Page 11
MoTeC Installation 7
Some sensor connectors may not be available with 22# terminals, in which case doubling the wire over gives the equivalent of an 18# wire. This is suitable for many of the common sensor terminals.
Use the correct crimping tool for all contacts to ensure a reliable connection.
Power the Dash Logger via a separate switch and a 5 ampere fuse, to ensure the PC can communicate with the Dash Logger without the need to power the rest of the vehicle.
The Dash Logger ground must have a direct connection to the vehicle battery.
Dash Logger is connected to other devices via the CAN bus.
Connecting Devices
Peripheral devices can be directly connected to the Dash Logger's input and output pins. The Dash Logger can also send or receive data from other devices via either RS232 or CAN communications.
Inputs
Input Types
A range of sensors is available to suit different types of measurement, e.g. temperatures, pressures, speed. Each type of measurement generates a different electrical signal that requires a suitable input type.
Each sensor needs to be connected to the type of input designed to suit that type of sensor.
MoTeC devices have the following input types available:
Analogue Voltage Inputs
Analogue Temperature Inputs
Digital Inputs
Wheel Speed Inputs
In addition to sensors connected to the inputs, the Dash Logger has internal sensors available for battery voltage, device temperature and G-force.
Analogue Voltage Inputs
Analogue Voltage inputs are normally used to measure the signals from analogue voltage type sensors, i.e. sensors with variable voltage outputs, such as:
Page 12
8 Installation
o Rotary or linear potentiometers o Signal conditioned 3 wire pressure sensors o Thermocouple amplifiers o Accelerometers
These inputs can also be used to measure two wire variable resistance sensors if an external pull-up resistor is connected from the input to the 5 V sensor supply.
Additionally, on/off switch signals may be connected, which may also require an external pull-up resistor.
Analogue Temp Inputs
Analogue Temperature inputs are identical to Analogue Voltage inputs, except that they contain a 1000 ohm resistor which is connected internally from the input pin to the 5 V sensor supply. This allows the Analogue Temperature inputs to be used with two wire variable resistance sensors, such as:
o Two wire thermistor temperature sensors o Two wire variable resistance pressure sensors
Some voltage output sensors can also be used if they can drive the 1000 ohm resistor without causing an error in their reading (e.g. MoTeC Thermocouple Amplifier).
Additionally, on/off switch signals may be connected.
Digital Inputs
Digital inputs can be used for the external switches required to operate the display. These inputs have a 4700 ohm resistor connected internally from the input pin to the 5 V sensor supply so that a switch can be simply connected between the input pin and 0 V.
They can also be connected to a brake switch or other switch. Digital Inputs include the following measurement methods:
o Frequency: The frequency of the input signal is measured o Period: The time between successive pulses is measured o Pulse width: The low time of the pulse is measured o Count: Counts the number of pulses o Phase Difference: Calculates the phase difference between two digital
inputs
o Beacon: For connection of a lap beacon
Page 13
MoTeC Installation 9
Speed Inputs
Speed Inputs are identical to Digital Inputs except that they can also be configured to suit Variable Reluctance (Magnetic) sensors, such as some wheel speed sensors. Because the amplitude of the signal from these sensors varies with speed of rotation, variable trigger levels are required, which must vary with the frequency of the input signal.
The Speed Inputs can also be used with Hall Effect type wheel speed sensors.
The Pulse Width method measures the high time of the pulse rather than the low time as measured by the Digital Inputs.
Input Specifications
For full specifications refer to Input Characteristics
Expanders
If additional sensors are required, input expanders can be used, such as E888. Sensors can be connected to the expander inputs and communicate via either RS232 or CAN. See Configuring Communications
Outputs
Auxiliary Outputs are used to control various vehicle functions e.g.
o Gear Change Lights o Warning Lights o Thermatic Fan o Gear Box Oil Pump
Note: Devices that consume more than the maximum current (e.g. motors)
should be driven via a relay or a MoTeC PDM (Power Distribution Module).
Output Specifications
Full specifications can be found in Output Characteristics.
Expanders
If additional outputs are required, output expanders can be used, e.g. PDM. Expander outputs can perform the same tasks as the device outputs and can be driven by communication via either RS232 or CAN. See Configuring Communications.
Page 14
10 Installation
Communications
Communications are used to send and receive data from one device to another. There are two communication protocols: RS232 and CAN. Generally older devices use RS232 and newer devices use CAN.
CAN (Controller Area Network) Communications
This protocol enables communication between all devices connected to the same bus. The CAN bus allows for communicating at high speeds. The Dash Logger has two independent CAN communications ports that can be connected to other devices with a compatible CAN port. The bus speed for each interface can be set independently.
Typical devices communicating over CAN:
o 'Hundred series' ECU: M400, M600, M800, M880 o Shift Light Module: SLM o Lambda meters: LTC, PLM o Expanders and input modules: E888 o Displays: SDL o Beacon receiver: BR2
These devices communicate at 1 Mbit/sec, so any other devices connected on the CAN bus must also communicate at 1 Mbit/sec. If a device communicates at another speed, it should be wired to the other CAN bus, and the speed of that CAN bus must be set to match the speed of the device.
RS232 Serial Communications
This is a one to one protocol, communicating from one device to one other device. Typical devices communicating over RS232:
o M4, M48 ECUs o Radio telemetry device o Gobal positioning system: GPS
Note: The Dash Logger can only communicate with devices for which it has
the appropriate communications protocol defined.
Page 15
MoTeC Installation 11
Connecting Devices Examples
Device Connect via Remarks
Sensors
External Buttons for:
- Display mode
- Display next line
(and optional previous line)
- Alarm acknowledge
- Lap number reset
- etc.
External LED Lights
SLM Shift Light Module
K-type Thermocouples
Inputs:
The appropriate input type depends on the sensor type
Inputs:
Digital or Speed inputs
Outputs:
Auxiliary output
Communications:
CAN
Inputs:
Analogue Voltage or Analogue Temperature input
MoTeC supplies datasheets with wiring details for all sensors via the website
Wire between Dash Logger input and Dash Logger 0 V. If wired to an Analogue Voltage input connect an external pull-up resistor between the input pin and the 5 V sensor supply.
Wire between one of the Auxiliary Outputs and battery positive and include a current limiting resistor
Connect via TCA (Thermo Couple Amplifier)
ECU M4, M48, M8
ECU 'hundred series': M400, M600, M800, M880
Communications:
CAN
Communications:
RS232
Communications:
CAN
Connect via E888
Uses the Telemetry feature of the ECU to send data to the Dash Logger
Ensure the ECU and Dash Logger are connected on the same CAN bus
Page 16
12 Installation
Software Installation
This section provides information on Dash Manager software, and i2 Data Analysis software.
It will also explain how to connect the Dash Logger to the PC.
PC Recommendations
MoTeC recommends a dedicated laptop for your race car with the following specifications:
32 bit operating system: Windows XP, Vista or Windows7
Screen size: 1024 x 768
Processor speed: 1-2 GHz Pentium
2 GB RAM
256 MB graphics card
2 USB ports
Ethernet port
Most current laptops will meet the specifications above and this will ensure all MoTeC software will run on it.
Dash Manager Software
Dash Manager software is used for configuration, testing, retrieving the logged data, and for general management of the Dash Logger.
Dash Manager supports configuration of the following connected devices: E888, SLM.
Installing Dash Manager Software
1. Go to the MoTeC website at www.motec.com and navigate to
software/latestreleases/SDL3 Dash Manager software OR Locate the Dash Manager software on the MoTeC Resource Disc
2. Save the selected file in your preferred location (for example desktop)
3. When downloading is finished, double click on the file and select run
4. Follow the instructions on the InstallShield Wizard
5. To start the program after installation, click the Dash Manager icon on
the desktop or click Start > All Programs > MoTeC > SDL3 > SDL3 Dash Manager
Page 17
MoTeC Installation 13 Updating Dash Manager Software
Software updates are available free of charge, giving access to the latest features. Download the latest software version from the website and follow the software installation instructions to update to the new version.
To update the associated firmware in the device, select Upgrade Dash Version from the Online menu. See Configuration Versions and Updating
.
i2 Data Analysis Software
MoTeC's i2 data analysis software is used to analyse the logged data that has
been recorded by the Dash Logger. Any number and combination of graphs,
gauges and reports can be analysed simultaneously. The i2 environment can
be customised to specific user requirements.
There are two levels of analysis functionality available; i2 Pro and i2
Standard. i2 Standard is included with any Data Logging upgrade, while i2 Pro requires
the optional Pro Analysis upgrade. See Dash Logger Upgrades
i2 Pro provides advanced mathematics, multiple overlay laps, and unlimited
components, workbooks and worksheets.
.
Connecting the Dash Logger to a PC
The Dash Logger connects to the Ethernet port on the PC. This requires a connector for the standard Ethernet cable in the loom.
The SDL3 loom #62202 incorporates this connector. Alternatively the connector can be wired into an existing loom using the unterminated Ethernet cable (#61131) or the Ethernet to Autosport pins cable (#61132).
All options are used in conjunction with a standard Ethernet cable. Connection details are described in PC Connection
PC Communications Setup
To enable PC communications, a connection must be setup in the Dash Manager software to match the Dash Logger serial number.
On the Tools menu click Connection Settings and then click Add
Click OK to choose IP (Ethernet). This is the only available connection
type.
Click Search*
In the list with discovered devices, click the required Dash Logger and
click Select
If the PC needs to communicate with more then one Dash Logger, repeat the steps.
Page 18
14 Installation
* The connection uses IPV6, which can be affected by firewall and anti virus applications.
If you have a Dash Logger connected but it is not listed in Discovered Devices, try disabling or uninstalling all anti-virus software.
If the Device is 'discovered' without the anti-virus software, you can turn it back on and put in appropriate exceptions to allow the Dash Logger Manager to communicate with the device.
Only one connection can be active at a time. To switch to a different Dash
Logger, click Make Active. Tip: The current connection is listed at the bottom of the Dash Manager
splash screen (this is the main Dash Manager screen with the picture of the Logger)
For a quick way to switch between connections
In the Dash Manager splash screen, enter the connection number (to enter the splash screen, close all other windows in Dash Manager).
Page 19
MoTeC Configuration 15
Configuration
All aspects of the Dash Logger can be configured, including; which sensor is connected to which input, the calibration of each sensor, what to display and where to display it, what to log and how fast to log it, tacho range, warning alarms, multi stage shift lights, etc.
The configuration is stored in a file on the PC. When starting Dash Manager software, the menu items related to changing the configuration are unavailable. To make them available, load a configuration file either by opening an existing file or by creating a new one.
All changes to the Dash Logger configuration are performed ‘Offline’, i.e. without the PC communicating with the Dash Logger. The changes are saved in the configuration file on the PC. The file must be sent to the Dash Logger before the changes take effect. See Sending and Retrieving Configuration Files.
Tip: When using a laptop in and around a car, it is often not practical to use a
mouse to navigate through the program. Using the keyboard to select options is easier. An overview is given in Windows Keyboard Shortcuts
Configuration Sequence
The configuration is best setup in the following order:
1. Connections (Input Pins & Communications)
2. Calculations (Lap Time, Fuel Prediction etc.)
3. Functions (Logging, Display, Alarms, Auxiliary Outputs etc.)
This simplifies the setup procedure by ensuring that the required channels are available for the functions that use them.
Channels cannot be used until they have been generated by an input, calculation or function.
Configuration File
From the File menu the following options are available:
New – creates a new configuration based on a predefined template
Open – selects an existing file
Right-click the configuration file to Rename, Delete, Send to a disk etc.
Save – saves a newly created configuration with a meaningful name
Save as – can be used to create a copy of an existing configuration file by
giving it a new name
Page 20
16 Configuration
Edit Details – allows for entering event, venue and vehicle details to be
stored with the configuration file
Check Channels – verifies that all channels are correctly generated
Edit Configuration Comments – allows for other comments to be stored
with the configuration file
View Configuration Summary – gives a quick overview of the
configuration file
Convert Logging Image – allows users to manually convert a log file for use in i2
Exit – exits the program
Tip: The most recently used files appear at the bottom of the File menu. This
is often the easiest way to open an existing file.
Backups
Whenever a file is saved, the previous content of the file is saved in the Save Backups directory. The total number of files is limited to 100.
Channels
Channels are used to convey information between the various systems of the Dash Logger.
For example an input pin may feed a channel called ‘Fuel Pressure’. This channel may then be used by another system, such as the Di splay System or Data Logging systems.
The Dash Logger channel scheme allows complete flexibility in channel usage, as any available channel can be used by any other function, i.e. any channel can be logged, displayed, used in conditions, used in alarms, used as an input to the user definable tables, etc.
All systems within the Dash Logger that generate values must feed one of the channels.
Pre-defined Channels
MoTeC has defined an extensive list of channels.
General Purpose Channels
Since the use of all channels cannot be predetermined, a number of general purpose channels have been included for occasions when a suitable predefined channel is not available.
Page 21
MoTeC Configuration 17
These general purpose channels may be required when measuring an uncommon value, or when a general purpose function needs to generate a special output channel. For example, a 3D table may generate an output channel to control a valve of some sort, in which case a general purpose channel may be used and named appropriately.
Page 22
18 Configuration
Channel Properties
Each channel has defined properties, some of which may be modified by the user. Predefining these properties makes the channels easy to use throughout the rest of the software.
Properties that may be modified by the user
o Name
The channel names (and abbreviations) may be changed if necessary. However name changes should be limited to name preferences rather than redefining the purpose of the channel, except for the general purpose channels which may be renamed to suit the current use.
o Abbreviation o Units (e.g. degrees Celsius, degrees Fahrenheit)
The units for a channel can be selected from a predefined list, for example the Engine Temperature channel may have units of degrees Celsius, Fahrenheit or Kelvin. Conversion between units is automatically handled by the software.
Note: The units are used for display purposes only. This means that
the units can be changed at any time without affecting the calibration of the channel.
Fixed properties
o Measurement type (e.g. Temperature)
Defining the measurement type allows the channels to be displayed in any unit suitable for that type, with automatic conversion between the units. For example all temperature channels can be displayed in degrees Celsius, Fahrenheit or Kelvin.
o Resolution
The resolution of all channels is fixed, for example the resolution of the Engine Temperature channel is fixed at 0.1 °C. Fixed channel resolutions ensure that the unit conversion system works properly and that channel comparisons can be performed correctly.
o Suitable logging rates o Suitable display filtering o Minimum and maximum range
Page 23
MoTeC Configuration 19
Selecting Channels
There are two methods of selecting channels, either the Category Method or the Search Method.
Category Method
This method divides all the channels into categories and sub categories, so that the list can be narrowed down to a small list of channels. For example, the ‘Engine Sensors / Cooling’ category shows a list of channels associated with the cooling system of the engine.
When selecting a channel from the complete list of channels, it is usually easiest to use the category selection method, for example when assigning a channel to an input pin.
To expand a category
click on the plus sign (+) next to the category name.
Page 24
20 Configuration Search Method
This method lists all channels in alphabetical order and allows a channel to be found either by typing the first few letters of any word in the channel name, or by scrolling through the list.
Note: The words may be typed out of order so that ‘Engine Oil Temp’ could
be found by typing "temp eng oil" or "oil t eng" or "e o t” This method is most useful when selecting a channel from the available
channels.
For example, if ‘Engine Temperature’ has been assigned to an input pin, it can be easily located in the Search list, since this list normally only contains 50 to 100 items.
Page 25
MoTeC Configuration 21
Connections
Configuring Inputs
1. On the Connections menu, click Devices
2. Select the device (e.g. SDL3) and then click the Input pins tab
This will list all inputs available for this product
3. Select the input and click Channel (or double-click the input)
4. Assign a measurement channel to the input and click OK
5. The channel needs to be calibrated using one of two options:
Select Load Cal if a pre-defined calibration is available
OR Double-click the input to enter a calibration
Other tasks:
Change Cal – to change the calibration
Spd Levels – only for speed inputs
Settings – to set default
Configuring Outputs
1. On the Connections menu, click Devices
2. Select device (e.g. SDL3) and then click the Output Pins tab to list all
outputs available for this product
3. Select the output and click Change (or double-click the output)
4. Select a mode to make appropriate settings available
5. Follow the directions on the screen and when all settings are done
click OK
Configuring Communications
1. On the Connections menu, click Communications
2. Select an available communications section (CAN or RS232)
3. Click Select and choose one of the available communications
templates
Comms templates
Communication templates are available for most connected MoTeC devices. When MoTeC releases new products, new communication templates will also be released. These will be incorporated in the latest software versions. See
Page 26
22 Configuration
Dash Manager Software on how to update to a new software version to make the latest communication templates available.
Calculations
The Dash Logger has special and user definable general purpose calculations
available. They are set up from the Calculations menu.
Special Calculations
Lap Time and Numberclick on the tabs to set up Lap Time, Lap
Speed, Running Lap Time, Split Lap Times, Lap Number, Laps Remaining
Speed and Distance – click on the tabs to set up Ground Speed, Drive
Speed, Wheel Slip, Lap Distance, Trip Distance, Odometer
Lap Gain/Loss –- to set up a continuous indication how far behind or
ahead the vehicle is compared to a reference lap
Gear Detection – to set up Current Gear
Fuel Prediction – click on the tabs to set up Fuel Used, Fuel Usage,
Fuel Remaining, Laps Remaining, Fuel Used per Lap
Speed Min/Max – to perform Min/Max Speed calculation (Peak/Trough
detection)
General Purpose Calculations
Tables – to set up 2D and 3D Lookup Tables
Timers – to set up General Purpose Timers
User Conditions – to activate items such as a Thermatic Fan or
Gearbox Oil Pump
Page 27
MoTeC Configuration 23
Functions
Data Logging
Data logging allows sensor readings and calculated values to be stored in the
Dash Logger's memory for later analysis using the i2 Data Analysis software.
To configure logging
1. On the Functions menu, click Logging
2. Select the relevant tabs to set up the logging parameters
Power
The Dash Logger power can be turned off at any time without losing the logged data, because it uses FLASH memory that does not require an internal battery to keep it alive.
Logging Memory
The SDL3 has optional Data Logging upgrades providing 16 MB or 120 MB of logging memory. See Dash Logger Upgrades.
Start and Stop Logging Conditions
To avoid logging unnecessary data, logging can be started and stopped by user definable conditions.
For example logging might start when the vehicle exceeds 50 km/h, and stop when the engine RPM is below 500 rpm for 10 seconds.
The Dash Logger provides the normal logging type; this will continuously log data to memory whenever the Start Condition is true and the Stop Condition is false.
Memory Usage
When the logging memory is full the Dash Logger may be configured to either stop logging, or to overwrite the oldest data, which ensures that the most recent data is always available. This is referred to as cyclic logging.
For most applications it is recommended that cyclic logging is used.
Logging Time
The maximum logging time is dependent on the logging memory size, the number of items logged and the rate at which they are logged. The Manager software will report the total available logging time.
Page 28
24 Configuration Logging Setup Files
The logging list can be saved and loaded from a file. This allows multiple logging setups to be used.
Logging Rate
The logging rate sets how often each channel is logged and can be set individually for each channel.
The rate at which the values are logged must be fast enough to record all variations in the reading. If the value is logged too slowly, the readings can be totally meaningless. For example, suspension position may need to be logged at 200 times per second or more.
However, if a value is logged faster than necessary it will not improve the accuracy of the logged data. It will just reduce the total logging time available. For example, the engine temperature only needs to be logged at once per second.
CAN Bus Bandwidth Limit
High logging rates also increase the amount of data that is being received from the measurement devices which increases the amount of data on the CAN bus. This can lead to exceeding the CAN bus bandwidth limit. See CAN Bus Bandwidth Limit
Note: The Dash Manager software will warn if the bandwidth is likely to be
exceeded.
Maximum Logging Rate
The maximum logging rate is limited to the update rate of the particular channel. This varies significantly depending on the source of the channel. For example, some communications devices may only update at 50 Hz. Also some internal calculations may be limited to 100 Hz.
Update Rate
Each input is measured at a maximum rate which is dependent on the capabilities of the measuring device and may also vary between inputs on that device. See Update Rate Summary
Anti-Alias Filter
If a channel is logged at a rate slower than its specified update rate then an optional anti-alias filter can be applied.
The anti-alias filter is used to average out any variations in the signal between logged values. This ensures that unrepresentative values are not logged.
Page 29
MoTeC Configuration 25
The anti-alias filter is implemented by averaging the channel values between logging events. For example, if a channel has an update rate of 1000 Hz and it is logged at 100 Hz then the preceding 10 samples will be averaged each time it is logged.
The anti-alias filter is normally turned on by default when a channel is added to the logging list, but may be turned off if required. For normal purposes it is recommended that the anti-alias filter is left turned on.
Note: For some channels the anti-alias filter cannot be turned on because the
averaging performed by the filter would cause incorrect values. This is the case for on/off channels and channels where the bit values have a particular meaning, for example error group channels.
Real Time Value (ADL2, SDL)
For channels that come from an ADL2 or an SDL, the logging anti-alias filter also affects the real-time value of the channel. This is the value that all other parts of the system see, such as the various calculations.
Note: The anti-alias filter is limited to 50 Hz for real time values even if the
channel is logged at a lower rate. For example, a channel logged at 10 Hz will be filtered and updated at 10 Hz in the logging and 50 Hz for the real time value.
Note: Channels that are not logged are updated at 50 Hz.
Real Time Value (For devices other than ADL2, SDL)
The real time value from other devices and from internal calculations is not anti-aliased at the logging rate, however the value can be anti-aliased in the logging.
Phase Shift
The anti-alias filter will cause a phase shift (time delay) of half the logging rate. For example, a channel logged at 100 Hz is logged every 10 milliseconds, so it is delayed by 5 milliseconds.
For most purposes this time delay is not an issue. Channels logged at the same rate are delayed by the same amount, which
negates this effect when comparing these channels. This applies to all channels whether they are generated internally from a
calculation or whether they are generated externally from devices such as a display device.
Page 30
26 Configuration Track Map
For the i2 Data Analysis software to plot a track map, either a GPS should be
connected or a number of separate sensors that will provide the required information.
Track Map using GPS
Ensure GPS Latitude and GPS Longitude are logged.
Track Map using Sensors
The following sensors are required and must be logged:
Lateral G force (internal sensor)
Wheel Speed
Lap Beacon (the ‘Beacon’ Channel must be logged)
Optionally Longitudinal G force (internal sensor)
A Longitudinal G force sensor should be used if the vehicle has only one wheel speed sensor. This allows the analysis software to eliminate wheel lockups which is essential when creating or using a track map.
Page 31
MoTeC Configuration 27
Display
The Dash Logger display is a high contrast, high temperature, custom made LCD display.
The display contains a Bar Graph, three Numeric Displays, a Centre Numeric Display and a Bottom Alpha / Numeric Display.
To configure the display
On the Functions menu, click Display
Select the relevant tabs to set up the display
Display Modes
The display has three main modes of operation; Race, Practice and Warm-up. The mode is changed by pressing a button that is wired to the system.
Race Mode
Page 32
28 Configuration
The Race display is normally used to display minimal information, e.g. RPM, Lap Time, Fuel Remaining or Laps Remaining.
The bottom alpha/numeric display can be used to display additional information as needed.
Practice Mode
The Practice display is used to display basic information, plus information to help the driver improve lap times, e.g. Lap Time, Lap Gain/Loss, Maximum Straight Speed, Minimum Corner Speed or Corner Exit Speed.
The bottom alpha/numeric display may be used to display additional information as needed.
Warm-up Mode
The Warm-up display is used to display important engine sensor readings during engine warm-up, e.g. RPM, Battery Voltage, Engine Temperature, Oil Pressure, Oil Temperature and Fuel Pressure.
The bottom alpha/numeric display can be used to check many other warm­up values.
Page 33
MoTeC Configuration 29 Bar Graph
The 70 segment bar graph has a user definable range and is typically used as a tacho, however it can be used to display any other value. When used as a tacho it may be configured for up to 19000 RPM.
A fully programmable shift point can be displayed, which can also be gear dependent.
The operation of the bar graph can be different for each of the display modes (Race, Practice and Warm-up), this allows a lower range to be used in Warm­up mode.
Numeric Displays
The three numeric displays–left, right and top right–can be programmed to display any value, which may be different for each of the display modes (Warm-up, Practice and Race).
Each of the three numeric displays has a different number of digits and is therefore suited to displaying different values. For example the top right display can only show values up to a maximum of 199 and is therefore not suitable for displaying Lap Times, but is suitable for values such as Lap Number, Fuel Remaining or Engine Temperature.
The numeric displays can show any channel value plus up to two override values. Override values show each time their value is updated. This is useful
Page 34
30 Configuration
for values that are updated periodically. The override values are shown for a programmable period of time. For example, a numeric display could normally show the Running Lap Time (which is continuously updating), then be overwritten by the Lap Time for 10 seconds each time the Lap Time is updated.
Enunciators for common displayed values are provided above the numeric displays (e.g. ET for Engine Temperature, OP for Oil Pressure).
Centre Numeric Display
The centre numeric display is normally used to display the current gear but can be used for other purposes.
Bottom Alpha/Numeric Display
The 13 digit bottom alpha/numeric display can display up to 20 lines of information that can be scrolled up or down using external buttons. Each of the 20 lines can display up to 3 channel values at a time.
The values shown may be different for each of the three display modes. Similar to the numeric displays, the bottom alpha/numeric display can show
up to four override values. The bottom alpha/numeric display will also show any active alarm messages,
which will override all other values until the alarm is cleared.
Page 35
MoTeC Configuration 31 Display Formatting
Units
All display units can be changed to suit the driver preferences, for example, show temperatures in Fahrenheit rather than in Celsius.
Note: This is independent of the units used for other purposes.
Decimal Places
The number of decimal places can be reduced for display purposes, for example the engine temperature is measured to 0.1 °C but is better displayed with no decimal places. This is normally done automatically.
Alarms
When an alarm is activated, a message is shown on the bottom line of the display. To draw the driver's attention to the display, it is recommended to activate a warning light.
The message can be defined as required and can include the current sensor reading or the sensor reading when the alarm was triggered.
The alarms remain active until they are acknowledged, either by a driver activated switch or automatically after a defined period of time.
The warning alarm limits are fully programmable and may include up to 6 comparisons to ensure that the alarms are only activated at the correct time. For example, an engine temperature alarm may activate at 95 °C if the ground speed has been above 50 km/h for 30 seconds. The speed comparison avoids the alarm showing during a pit stop due to heat soak. Additionally another comparison could be set at a higher temperature to cover all other situations.
The comparison values can be automatically incremented or (decremented) when an alarm occurs. For example the engine temperature alarm may be set at 95 °C with and increment of 5 °C, so that the second time the alarm activates at 100 °C. A limit may be set on the number of times the comparison
Page 36
32 Configuration
value is allowed to increment. An alarm may return to its original value after a period of time, in case the alarm condition was temporary.
The alarms can be dependent on the current display mode (Warm-up, Practice or Race).
Other Functions
The Dash logger can perform many other functions accessible from the
Functions menu including the following:
Shift Lights – to control up to 4 staged shift lights
Shift Light Module – to configure MoTeC's SLM
Engine Log Setup – to set up the engine log
Page 37
MoTeC Operation 33
Operation
When operating the Dash Logger, any of the activities of the Online menu of
the Dash Logger Manager software can be performed. This requires the PC to communicate to the Dash Logger.
Note: All other menu items perform offline activities.
Retrieving the Logged Data
On the Online menu, click Get Logged Data
A PC is used to unload the logged data from the Dash Logger. The logged data is then stored on the computer's hard disk.
After each unload the user has the option to clear the logging memory. The unload may be interrupted part way through if necessary by
disconnecting the computer. The partial unload will contain the most recently logged data and will be stored on the computer's hard disk. In this case the Dash Logger memory is not cleared and logging will continue as normal at the end of the existing data. Next time the logged data is unloaded both the new data and the previously partly unloaded data will be retrieved.
Sending and Retrieving Configuration Files
On the Online menu, click Send Configuration to send the currently
open configuration file
Note: When a configuration file is sent to the Dash Logger the existing data is retrieved and stored in the From Dash Backups directory to use
in case the data in the Dash Logger needs to be restored. The maximum number of files is 10.
On the Online menu, click Get Configuration to retrieve the current
configuration file This will only be necessary if the original file is not available on the PC.
Zeroing Sensors
Some sensors require regular zeroing, for example Steering Angle, Suspension Position, Ride Heights, G Force Sensors and Throttle Position. Dash Manager software provides a feature for easy zeroing of all these sensors.
Page 38
34 Operation
Checking Operation
Monitor Channels
The currently active channels can be monitored to check the operation of all functions and measurements.
On the Online menu, click Monitor Channels
To show any channel on an oscilloscope style screen, click Utilities
and then Oscilloscope
Simulate
The Simulate feature allows most input channels to be manually changed so that the Dash Logger operation can be checked under abnormal conditions, e.g. High Engine Temp. This is extremely useful for checking that the Dash Logger is working as expected.
On the Online menu, click Simulate
Test
A number of tests are provided to check the operation of the Dash Logger, such as the Display test.
On the Online menu click the appropriate test
Configuration Versions and Updating
On the Online menu, click Upgrade Dash Version
The software inside the Dash Logger (firmware) can be updated by the user at any time to take advantage of the latest features.
Matching Versions
The firmware version must match the version of the Dash Manager software on the PC in order to communicate. Dash Manager will show a warning if the versions do not match.
Tip: To check the version of Dash Manager, click About MoTeC SDL3 Dash Manager on the Help menu.
The firmware version is displayed on the bottom line of the display for 2 seconds when the Dash Logger is powered.
Matching Configuration File
The configuration file must also match the software and firmware versions used. The display will show a warning if the file does not match.
Page 39
MoTeC Operation 35
Configuration files can be updated by choosing the option to automatically update the configuration file while updating the software (firmware). It can also be done manually by upgrading the configuration file and sending it to the Dash Logger:
On the File menu, click Open
In the Files of type box select the new version file extension.
The file will be converted to the new version format and saved with the same file name but with the new version file extension.
Note: The old file is not changed.
On the Online menu, click Send Configuration to send the
configuration file to the Dash Logger
Upgrading the Dash Logger
Several options are available as upgrades to customise and grow your system.
The currently enabled options can be listed and new options can be activated through a password acquired from MoTeC.
To upgrade the Dash Logger
On the Online menu, click Enable Dash Options
Password Protection
On the Online menu, click Set Access Passwords
Several Dash Logger capabilities can be protected from unauthorised access by using the password protection.
Note: Ensure you keep passwords secure. The unit needs to be returned to
MoTeC for unlocking if the passwords are lost.
Other Online Activities
Many other activities are accessible from the Online menu including the
following:
Reference Lap – to send a reference lap to the Dash Logger used in the
lap gain/loss system.
View – to view:
o configuration settings e.g. Engine Logs o GPS Beacon Definitions o saved details e.g. Running Totals o Device Halt Counts
Page 40
36 Operation
Retrieve – to retrieve Engine Log
Communication –to list the current Connections Settings
Miscellaneous
o Erase Logged Data without unloading o Serial Number to view the Serial and Hardware Number;
the Serial Number is required when ordering upgrade passwords, the Hardware Number is for MoTeC internal use
o Change Display Mode to switch between Practice, Warm-up and
Race mode
Page 41
MoTeC Appendices 37
Appendices
Specifications
Specifications listed as optional are available as upgrades to customise and
grow your system. These additional features are activated through a simple password system, at any time when you need it. An overview of the
upgrades can be found in Dash Logger Upgrades
Logging
Optional 16 MB or 120 MB logging memory
Logging rates up to 500 samples per second
Fast Ethernet download
Display
70 segment bar graph
13 digit alphanumeric text bar
48 user-defined, scrollable message lines with programmable overrides
3 programmable 'pages' for Practice, Warm-Up and Race
.
Inputs
8 x Analogue voltage inputs, some are high resolution inputs
4 x Analogue temperature inputs
2 x Digital inputs
4 x Speed inputs with voltage measuring capability
Compatible with up to two E888 expanders (8 Thermocouples only)
Outputs
4 x PWM, digital or switched outputs
Internal Sensors
3-axis G sensor
Dash temperature sensor
Sensor supply voltage
Battery voltage
Page 42
38 Appendices Communications
2 x CAN with individually programmable CAN bus speeds
o Maximum data range 1 Mbit/sec o Recommended terminating impedance 100 ohm
1 x RS232
Physical
Dimensions 180 x 91 x 18 mm excluding connector
Weight 385 g
1 x 37 pin Autosport connector
Power Supply
Operating voltage: 8 to 32 volt DC
Operating current: 0.15 ampere typical (excluding sensor currents)
Reverse Battery protection
Battery Transient protection
Operating Temperature
Internal Temperature Range -10 to 80 °C
Ambient Temperature Range -10 to 70 °C
Sensor Supply Current
5 V Sensor supply: 0.2 ampere maximum
8 V Sensor supply: 0.3 ampere maximum
Page 43
MoTeC Appendices 39
Dash Logger Upgrades
For the SDL3 Dash Logger the following upgrades are available:
Adjustable Backlight
Improves readability at night time or at low visibility conditions. This option must be specified at time of purchase.
Data Logging 16 MB
Allows recording of all input data to a 16 MB internal logging memory.
Memory 120 MB
Increases the internal memory to 120 MB. (Requires the Data Logging 16 MB upgrade).
Pro Analysis
Provides access to advanced i2 Pro data analysis software with multiple
graph overlays, X-Y plots, advanced maths functions, synchronised video (automatic alignment), and flexible layouts to accommodate virtually any user preference.
Page 44
40 Appendices
Characteristics
Input Characteristics
Analogue Voltage Inputs
Suitable for
Measure Voltage Range
Input Resistance Resolution
Measurement Methods
Update Rate Filter Calibration Accuracy
Potentiometers Voltage output sensors Variable resistance sensors with pull-up resistor
Inputs 1—4: 0 to 5.46 V All other Inputs: 0 to 15.0 V Note: Voltages outside this range may affect the readings on other inputs.
100k ohms to 0 V
Inputs 1—4: 1.33 mV All other Inputs: 3.66 mV
Ratiometric Absolute Variable Resistance Off/On
1000 times/second
240 Hz 1st order
Gain 0.05% max (Ratiometric method) Gain 0.15% max (Absolute method) Offset  6 mV max Linearity  6 mV max Temperature Stability 60 ppm/C max Calibration Schedule 12 months
Page 45
MoTeC Appendices 41
t
Analogue Temp Inputs
Suitable for
2 wire variable resistance sensors and some voltage output sensors
Measure Voltage Range
0 to 15.0 V
Note: Voltages outside this range may affect
the readings on other inputs.
Input Resistance
1000 ohms pull-up to 5 V sensor supply +100 k to 0 V
Resolution Measurement Methods
3.66 mV
Ratiometric Absolute Variable Resistance Off/On
Update Rate Filter Calibration Accuracy
1000 times / second
290 Hz 1
s
order
Gain: 0.05% max (Ratiometric method) Gain:
0.15% max (Absolute method) Offset: ± 6 mV max Linearity: ± 6 mV max Temperature Stability: 60 ppm/°C max Calibration Schedule: 12 months
Page 46
42 Appendices Digital Inputs
Suitable for
Pull-up Resistor Voltage Range Positive Trigger
Threshold Negative Threshold Hysteresis Update Rate Filter Time Constant Measurement Methods
Switch to 0 V Logic signal and open collector device (e.g. Hall Switch)
2200 ohms to 3.3 V
0 to 15 V
2.4 V max
0.6 V min
0.4 V min
100 times / second
22 usec
Frequency
Resolution 0.1 Hz Maximum Frequency 3200 Hz Rising Edge Triggered
Period 1 usec
Measures period between rising edges Resolution 1 usec Maximum 32 msec
Period 100 usec
Measures period between rising edges Resolution 100 usec Maximum 3.2 sec
Pulse Width 1 usec
Measures pulse low time Resolution 1 usec Maximum 32 msec
Pulse Width 100 usec
Measures pulse low time Resolution 100 usec Maximum 3.2 sec
Page 47
MoTeC Appendices 43 Speed Inputs
Hall mode Suitable for
Pull-up Resistor Voltage Range Trigger Threshold
Magnetic mode
Suitable for
Input Resistance
Voltage Range
Programmable Trigger Levels
A 2200 ohm pull-up resistor is connected to 2.7 V
Switch to 0 V Logic signal Open collector device (e.g. Hall Switch)
2200 ohms to 2.7 V
0 to 15 V
Selectable between -1.33 V and 4.68 V
The pull-up resistor is disengaged and the trigger levels can be varied depending on the input frequency
Two wire magnetic sensor (variable reluctance sensor)
100k ohms to ground (no pull-up)
-80 V to +80 V
-1.33 V to 4.68 V
For both modes
Update Rate Filter Time Constant Hysteresis Measurement
Methods
100 times / second
25 usec
0.17 V min
Frequency
Resolution 0.1 Hz Maximum Frequency 3200 Hz Falling Edge Triggered
Period 1 usec
Measures period between falling edges Resolution 1 usec Maximum 32 msec
Page 48
44 Appendices
Period 100 usec
Measures period between falling edges Resolution 100 usec Maximum 3.2 sec
Pulse Width 1 usec
Measures pulse high time Resolution 1 usec Maximum 32 msec
Pulse Width 100 usec
Measures pulse high time Resolution 100 usec Maximum 3.2 sec
Page 49
MoTeC Appendices 45 Analogue Input Sampling
4 times oversampling is scheduled with samples taken every 250 usec, providing measurements every 1 msec. The following inputs are sampled at 250 usec, with microsecond offsets as shown in the table:
Offsets 0.0 usec +1.5 usec
0.0 usec
+9.3 usec
+20.9 usec +30.1 usec +39.4 usec +51.0 usec +60.3 usec +71.9 usec +81.1 usec
+90.4 usec +102.0 usec +111.3 usec +122.9 usec +132.1 usec +141.4 usec
AT1 AV1
AT2 AV2
AT3 AV3
AT4 AV4
N/A AV5
N/A AV6
N/A AV7
N/A AV8
N/A INTTEMP
8VSEN SPD1
5VSEN SPD2
GLAT SPD3
GVERT SPD4
GLONG N/A
N/A BAT+
Output Characteristics
Output Type
Current Output Clamp
Open Collector (Drives to ground) with weak pull-up (10 k) to battery positive
0.5 A max, current limited and thermal overload protected
50 V Flyback Clamp (no clamp diode to supply)
Page 50
46 Appendices
SDL3 Pin List by Pin Number
Pin Name Function
1 AV5 Analogue Voltage Input 5
2 AV6 Analogue Voltage Input 6
3 BAT+ Battery Positive
4 BAT- Battery Negative
5 AUX1 Auxiliary Output 1
6 AUX2 Auxiliary Output 2
7 AUX3 Auxiliary Output 3
8 AUX4 Auxiliary Output 4
9 E-RX- Ethernet Receive -
10 E-TX- Ethernet Transmit -
11 SPD3 Speed Input 3
12 SPD4 Speed Input 4
13 8V Sensor 8 V
14 5V Sensor 5 V
15 AV1 Analogue Voltage Input 1
16 AV2 Analogue Voltage Input 2
17 AV3 Analogue Voltage Input 3
18 AV4 Analogue Voltage Input 4
19 AV7 Analogue Voltage Input 7
20 AV8 Analogue Voltage Input 8
21 AT1 Analogue Temp Input 1
22 AT2 Analogue Temp Input 2
23 SPD1 Speed Input 1
Page 51
MoTeC Appendices 47
Pin Name Function
24 E-RX+ Ethernet Receive +
25 E-TX+ Ethernet Transmit +
26 SPD2 Speed Input 2
27 DIG1 Digital Input 1
28 DIG2 Digital Input 2
29 CAN1L CAN 1 Low
30 CAN1H CAN 1 High
31 AT3 Analogue Temp Input 3
32 AT4 Analogue Temp Input 4
33 TX RS232 Output
34 RX RS232 Input
35 CAN0L CAN 0 Low
36 CAN0H CAN 0 High
37 0V Sensor 0 V
Page 52
48 Appendices
SDL3 Pin List by Function
Pin Name Function Battery Power
4 BAT- Battery Negative
3 BAT+ Battery Positive
Analogue Voltage Inputs
15 AV1 Analogue Voltage Input 1
16 AV2 Analogue Voltage Input 2
17 AV3 Analogue Voltage Input 3
18 AV4 Analogue Voltage Input 4
1 AV5 Analogue Voltage Input 5
2 AV6 Analogue Voltage Input 6
19 AV7 Analogue Voltage Input 7
20 AV8 Analogue Voltage Input 8
Analogue Temp Inputs
21 AT1 Analogue Temp Input 1
22 AT2 Analogue Temp Input 2
31 AT3 Analogue Temp Input 3
32 AT4 Analogue Temp Input 4
Digital Inputs
27 DIG1 Digital Input 1
28 DIG2 Digital Input 2
Speed Inputs
23 SPD1 Speed Input 1
26 SPD2 Speed Input 2
11 SPD3 Speed Input 3
12 SPD4 Speed Input 4
Page 53
MoTeC Appendices 49
Pin Name Function Auxiliary Outputs
5 AUX1 Auxiliary Output 1
6 AUX2 Auxiliary Output 2
7 AUX3 Auxiliary Output 3
8 AUX4 Auxiliary Output 4
8 V Sensor
13 8V Sensor 8 V
5 V Sensor
14 5V Sensor 5 V
0 V Sensor
37 0V Sensor 0 V
CAN Interface
36 CAN0H CAN 0 High
35 CAN0L CAN 0 Low
30 CAN1H CAN 1 High
29 CAN1L CAN 1 Low
Ethernet
9 E-RX- Ethernet Receive -
24 E-RX+ Ethernet Receive +
10 E-TX- Ethernet Transmit -
25 E-TX+ Ethernet Transmit +
RS232
34 RX RS232 Input
33 TX RS232 Output
Page 54
50 Appendices
Mounting Dimensions
SDL3
ESDL3
Note:
All dimensions in [mm]
Ensure product is not stressed when mounted
Dimensions indicate actual product size, allow for clearance when
mounting
Page 55
MoTeC Appendices 51
Wiring
This section provides reference material about the Dash Logger's connector and wiring requirements.
Connector
SDL3 connector Mating connector
37 pin Autosport connector
#68089
Wire Specification
Wire
Wire to suit Dash Logger connector: 22# Tefzel, Mil Spec : M22759/16-22
M22759/16 Wire Ratings (for various wire gauges)
Insulation Material: Tefzel Conductor: Tin Plated Copper Voltage Rating: 600 V Maximum Temperature: 150 °C
Wire Gauge [AWG]
22 0.38 5 0.045 14.0
20 0.61 6 0.028 8.5
18 0.96 9 0.018 5.5
Cross Sectional Area [mm2]
Max Current at 100 °C Ambient [A]
Resistance [ohm/m]
Resistance [ohm / 1000 ft]
16 1.2 12 0.014 4.3
14 1.9 18 0.009 2.7
12 3.0 24 0.006 1.8
Crimp Tool
Crimp Tool: M22520/2-01 Positioner for Crimp Tool: M22520/2-07 Crimp Contacts are type 22D (needed to set the crimp tool correctly)
Page 56
52 Appendices Wire Stripping Tool
Recommended: Ideal Industries 45-2133 stripping tool with LB1195 wire stop
Heatshrink Boots
Straight:
Raychem 202K142,
Hellerman 155-42-G
Right Angle:
Raychem 222K142,
Hellerman 1155-4-G
PC Connection
Ethernet Wiring Schematic:
SDL3 Ethernet Connector Pin Function Pin Function
24 Ethernet RX+ 1 Ethernet TX+
9 Ethernet RX– 2 Ethernet TX–
25 Ethernet TX+ 3 Ethernet RX+
10 Ethernet TX– 6 Ethernet RX–
Pin numbering
Plug Socket
Wire
CAT5 UTP Ethernet cable
Page 57
MoTeC Appendices 53 Cable
An Ethernet RJ45 socket, connecting to a standard Ethernet cable, is provided on:
#62202 SDL3 loom
#61131 Ethernet cable, unterminated, 2 metre
#61132 Ethernet to Autosport pins cable, 1.8 metre
CAN Bus Wiring Requirements
The CAN bus should consist of a twisted pair trunk with 100R (0.25 watt) terminating resistors at each end.
o If the CAN bus is less than 2 metres (7 ft) long, a single termination
resistor may be used.
The preferred cable for the trunk is 100R data cable.
The maximum length of the bus is 16 metres (50 ft)
CAN devices (such as MoTeC Dash Loggers, ECUs etc.) may be
connected to the trunk with up to 500 mm (20 in) of twisted wire.
Page 58
54 Appendices
SDL3 Data Logger to ECU wiring (RS232)
The following details the methods for connecting the Data Logger to the various MoTeC ECUs via RS232. In all cases this is done using the serial data stream generated by the Telemetry function of each ECU.
In the case of the M800, M880 and M4e the Data Logger may be directly wired to the ECU because these ECUs use RS232 interface levels. On the M48, M4 (pre M4e) and the M8, a Computer Interface Module (CIM) or a PCI cable is required to convert the signals to RS232.
M800 / M880
Note:
The data to the Data Logger will be interrupted while a PC is connected (DOS software only)
The 9 pin connector is not required, if using the Windows calibration software.
Data may be sent to the Data Logger via the CAN bus as an alternative to the serial connection.
M4e
Note:
Older M4 ECUs require a different connection method
The data to the Data Logger will be interrupted while a PC is connected.
Page 59
MoTeC Appendices 55 M48, M4 (p re M4e) and M8
The M48, M8 and M4 (pre M4e) require the use of a CIM module or a PCI Cable to convert the logic level signals used by these ECUs into RS232 levels.
Using a CIM Module
Contact MoTeC for the CIM module drawing for full wiring details.
Note:
The data stream to the Data Logger will be interrupted while a PC is connected.
Page 60
56 Appendices
Update Rate Summary
Device Input Type Maximum Update
Rate (per second)
ADL3 Analogue Voltage Inputs 1000
ADL3 Analogue Temperature Inputs 1000
ADL3 Digital Inputs and Speed Inputs 100
ADL3 RS232 and CAN Communications 50 max *
ADL3 CAN comms fast receive 1000
ACL RS232 Communications 200 *
ACL General CAN communications 200 *
SDL3 Analogue Voltage Inputs 500
SDL3 Analogue Temperature Inputs 500
SDL3 Digital Inputs and Speed Inputs 100
SDL3 RS232 and CAN Communications 50 max *
SDL3 CAN comms fast receive 500
VIM AV Fast Inputs 5000
VIM AV Differential Voltage Inputs 1000
VIM AV High Resolution Inputs 500
VIM AV Special Inputs 2000
VIM Speed Inputs 100
ADL2/SDL
ADL2/SDL Other Analogue Voltage Inputs 500
ADL2/SDL Analogue Temperature Inputs 500
ADL2/SDL Lambda Inputs 100
ADL2/SDL Digital & Speed Inputs 100
SDL Internal G Sensors 100
E888
E888/816
Analogue Voltage Inputs 1 to 4 (ADL2/SDL) and 11 to 14 (ADL2)
Thermocouple Inputs (First Device / Second Device)
Analogue Voltage & Digital Inputs (First Device / Second Device)
1000
100 / 50
200 / 50
Page 61
MoTeC Appendices 57
* RS232 and general CAN communications update rate depends on how frequently the data is sent from the device. Typically the update rate from an M4, M48, M8 or M800 ECU is about 20 times per second using RS232 and about 50 times per second for the M800 using CAN.
Page 62
58 Appendices
Command Line
Usage:
sportdash3.exe -c[connection] -d -x -l -e -t -s [config file name]
[config file name] (Optional) Fully qualified path to the configuration file. (eg "c:\motec\dash\config\bathurst.d30")
Note: the path must included the file extension (eg .d30)
Options :
Each of the following options can be given as "/[character]" or "­[character]". They are shown here as "-[character]".
-c[Connection Name] (Optional) Select a preconfigured connection by name as configured in the dash
connections dialog. (eg -c"Primary CAN Connection").
Note: There must not be a space between the c and the connection name.
-d (Optional) Causes the debug console to be displayed. Only available for debug builds.
-x (Optional) Causes the app to terminate when one the following tasks has been
performed.
Page 63
MoTeC Appendices 59 Tasks :
One or more of the following may be specified.
-l (Optional) Perform a “Get Logged Data” operation.
-e (Optional) Perform a “Get Engine Log” operation.
-t (Optional) Perform a “Get Tell-tale Values” operation.
-p (Optional) Perform a “Print Summary” operation.
Note: The configuration file must be specified using a fully qualified path
including the file extension. (e.g. -p "c:\motec\dash\config\bathurst.d30")
Note: There must be a space between -p and configuration file name.
-s (Optional) Perform a “Send Configuration” operation.
Note: The configuration file must be specified using a fully qualified path
including the file extension. (e.g. -s "c:\motec\dash\config\bathurst.d30")
Note: There must be a space between -s and configuration file name.
-u (Optional) Perform an “Upgrade Dash Version” operation.
Page 64
60 Appendices
CAN Bus Bandwidth Limit
The total available CAN bandwidth on a single CAN bus is 1 Mbit/sec. The bandwidth used by the total of all devices on a particular CAN bus must
not exceed approximately 90% of this value (900000 bits/second) If the total bandwidth required exceeds this specification then some devices
should be connected to the second CAN bus.
Note: Dash Manager will warn if the bandwidth is likely to be exceeded.
E888
Device on first CAN Address: Bandwidth = 145000 (bits/sec) Device on second CAN Address: Bandwidth = 55000 (bits/sec)
Other Devices
Device Bandwidth
BR2, SLM , PLM Negligible
SDL, ADL2, MDD, M800 ECU TBD
Page 65
MoTeC Appendices 61
Comms Error Codes
The "Comms CAN x Diagnostic" and "Comms RS232 Diagnostic" channels can be used to diagnose communications problems.
Multiple errors are shown by error codes added together. For example: A RS232 error of 9 = parity + overrun.
The error values have the following definitions:
RS232 Errors
Errors generated by RS232 communications.
1 PARITY Parity bit incorrect. The comms parity setup is
wrong, or there is electrical interference causing errors in the data.
2 FRAMING Not seeing the stop bit. The baud rate or stop
bit setup is wrong or there is electrical interference causing errors in the data.
4 NOISE Glitch in the data. Electrical interference is
causing glitches in the signal. (the Dash Logger does not generate this error)
8 OVERRUN A byte was received before the previous byte
was read indicating that the processor was too busy to read the message.
512 NO DATA A valid message header was not found - either
there is a wiring fault or comms is setup incorrectly.
1024 CHECKSUM A valid message header was found, but the
checksum was wrong. If seen in combination with other errors there is electrical noise. If only checksum errors occur there may be a software incompatibility between the Dash Logger and the other device.
2048 WRONG DATA Could not decode the protocol.
General CAN Errors
Errors generated by general CAN communications.
2 FRAMING Only generated when used with an
E888/E816 expander. Inconsistent message length.
Page 66
62 Appendices
8 OVERRUN Receive or transmit overrun error. In the
receive case a byte was received before the previous byte was read indicating that the processor is too busy to read the message. In the transmit case the transmit buffer is full which could happen if the CAN bus is too busy.
256 BAD CONFIG The device configuration is not valid (e.g.
overlapping CAN addresses)
512 NO DATA A valid message header was not found -
either there is a wiring fault or comms is setup incorrectly, (problem could be at either end). E.g.: transmit and receive CAN IDs do not match.
1024 CHECKSUM Only generated when used with an Async
Expander. See RS232 errors
2048 WRONG DATA Only generated when used with an Async
Expander or E888/E816 Expander. Async Expander: Could not decode the protocol. E888/E816: Compound ID incorrect.
4096 BUS WARNING More than 96 errors have occurred on the
CAN bus. Check wiring and termination resistors. The CAN bus may still be operational.
8192 BUS OFF More than 255 errors have occurred on the
CAN bus. CAN communications is suspended when this error occurs. Check wiring, termination resistors and the CAN baud rate. Also check that CAN HI and CAN LO are correct (not swapped).
16384 CAN TRANSMIT CAN bus transmit warning
"VIMCOM" Errors
Errors generated by "VIMCOM" devices (SVIM, Dash Loggers).
Note: VIMCOM devices are connected via CAN.
Dash Logger Errors (SDL3)
These errors are generated by the Dash Logger's communications system.
2 FRAMING Incorrect number of samples received.
Page 67
MoTeC Appendices 63
256 BAD CONFIG Configuration mismatch between Dash
Logger and device. Resend the configuration.
512 NO DATA VIMCOM packets have not been found.
Either there is a wiring fault or Dash Logger Connections is setup incorrectly.
2048 WRONG DATA VIMCOM packet has bad length.
4096 BUS WARNING More than 96 errors have occurred on
the CAN bus. Check wiring and termination resistors. The CAN bus may still be operational.
8192 BUS OFF More than 255 errors have occurred on
the CAN bus. CAN communications is suspended when this error occurs. Check wiring, termination resistors and the CAN baud rate. Also check that CAN HI and CAN LO are correct (not swapped).
VIMCOM Device Errors.
These error codes are sent once by the VIMCOM device on resuming data transmission and therefore indicate why data was previously not being transmitted.
4097 STARTUP Device has restarted (normally due to
power up). Data is not sent until sync is achieved.
4098 HALT Data not sent due to deliberate halt. For
example configuration or firmware being sent.
4099 OVERRUN Data not sent due to transmit buffer
overrun (possibly due to CAN bus too busy)
4100 SYNC TIMEOUT Data not sent due to Dash Logger sync
message timeout (sync not received from Dash Logger)
4101 CAN ERROR Data not sent due to error on CAN bus
4102 SYNC
EXCEEDED
Data not sent due to excessive sync error (synchronisation too far out)
Page 68
64 Appendices
Windows Keyboard Shortcuts
When using a laptop in and around a car, it is often not practical to use a mouse to navigate through the program.
Using the keyboard to select options is easier.
Main Menu
To access the main menu, press ALT + the key for the underlined letter in the menu, followed by the underlined letter of the item in the drop down menu. E.g. ALT + F, N for F
Alternatively press and release ALT, select the desired menu item using the arrow keys, press ENTER to activate it.
Closing a Window
Press ENTER for OK or Close (only when the OK or Close button has a bold line around it)
Press ESC to Cancel or Close
ile New.
Getting Help
1. Press F1 to get help on the current window or item
2. Select Help from the Main Menu to access the main help system.
Page 69
MoTeC Appendices 65 Selecting an Item in a Window
To access the various items in a window, press ALT + the key for the underlined letter of the item of interest, e.g. to select the ‘F press ALT + F
Alternatively use the TAB key to move through the dialog box (use SHIFT + TAB to move backwards). The selected control is usually indicated by a dotted line around it, or by highlighting the text or item selected within the control.
lash Light’ item
Using the Selected Item
The method of using the selected item (or control) depends on the type of control. The common controls are detailed below:
Command Button
Command buttons are generally used to show another screen or perform a particular function.
Press ALT + the key for the underlined letter (S navigate to the command button. To select, press ENTER or SPACEBAR.
), or use the TAB key to
Page 70
66 Appendices
Check Box
A check box is used to tick on or off a particular option. Press ALT + the key for the underlined letter (F
navigate to the Check Box. To select, press SPACEBAR.
Group Box
The Group box is used to select an item from a group of options. Press ALT + the key for the underlined letter (F,
key to navigate to the Group box. To select, use the arrow keys.
Text Box
A text box is used to enter a value or text. Press ALT + the key for the underlined letter (M
navigate to the Text box, type in the new value or text. Use BACKSPACE or DELETE to remove unwanted characters.
), or use the TAB key to
A or D), or use the TAB
) or use the TAB key to
Page 71
MoTeC Appendices 67
List Box
A list is used to select from a number of options. Press ALT + the key for the underlined letter (M
navigate to the List Box. To select, use the arrow keys.
Drop-down List Box
) or use the TAB key to
A Drop-down list box is used to select from a number of items, but only the selected item is shown until a new item needs to be selected.
Press ALT + the key for the underlined letter (L navigate to the Drop down List Box. To select the desired item, use the arrow keys, and press ENTER to close the list.
Tabs
Tabs are used to select the different tab pages of a screen. To select the next tab, press CTRL + TAB. To select the previous tab,
press CTRL + SHIFT +TAB.
) or use the TAB key to
Page 72
68 Appendices
Tree Structure
A Tree Structure is used to select items from a hierarchical list The UP ARROW key moves the cursor up (selects the item above) The DOWN ARROW key moves the cursor down (selects the item below) The RIGHT ARROW key expands; expandable branches indicated by a
plus sign (+) The LEFT ARROW key collapses; collapsible branches indicated by a
minus sign (-)
Page 73
MoTeC Appendices 69
Glossary
MoTeC Devices
ACL Advanced Central Logger
ADL2 Advanced Dash Logger - second generation
ADL3 Advanced Dash Logger - third generation
BR2 Beacon Receiver
BTX Beacon Transmitter
CIM Computer Interface Module
CLS Central Logging System
DBW4 Drive By Wire expander
E816 Input/Output Expander
E888 Input/Output Expander
i2 MoTeC data analysis software
i2 Pro MoTeC data analysis software, professional version
IEX Ignition EXpander
LTC Lambda to CAN module
LTCD Lambda to CAN Dual module
M2R ECU dedicated to run 2 rotor engines
M4 ECU for engines with up to 4 cylinders or up to 2 rotors
M400 ECU for modern engines with up to 4 cylinders or up to 2 rotors
M48 ECU for engines with up to 8 cylinders and 2 rotors
M600 ECU for modern engines with up to 6 cylinders or up to 3 rotors
M800 ECU for modern engines with up to 12 cylinders or up to 4 rotors
M800 Plug-In
M880 ECU for modern engines with up to 12 cylinders or up to 4 rotors
MDC Mitsubishi Diff Controller
MDD Mini Digital Display
MLS ECU dedicated to run Chevrolet LS1 and Lexus/Toyota V8s
PCI Cable PC Interface cable
ECU for direct replacement of a factory ECU
Page 74
70 Appendices
PDM15 Power Distribution Module with 15 outputs
PDM16 Power Distribution Module with 16 outputs
PDM30 Power Distribution Module with 30 outputs
PDM32 Power Distribution Module with 32 outputs
PLM Professional Lambda Meter
RTC Real Time Clock
SDC Subaru Diff Controller
SDL Sport Dash Logger
SDL3 Sport Dash Logger - third generation
SGA Strain Gauge Amplifier
SLM Shift Light Module
SUU Software Update Unit
TCM Traction Control Module
VIM Versatile Input Module
Other
Calibration
CAN Controller Area Network - communication protocol
CDI Capacitive Discharge Ignition
ECU Engine Control Unit
GPS Global Position System
MAF Mass Air Flow
MAP Manifold Absolute Pressure
PID Proportional, Integral and Derivative gain
PWM Pulse Width Modulated.
RPM Revolutions Per Minute
RS232 Recommended Standard 232, communication protocol
RX Receive
TDC Top Dead Centre
TX Transmit
The process of converting an electrical value into a physical value e.g. Volts into kilometres per hour
Page 75
MoTeC Notes 71
Page 76
72 Notes
Loading...