SEALED COMBUSTION DOWNFLOW GAS FURNACE
FOR INSTALLATION IN: MANUFACTURED (MOBILE) HOMES,
CAUTION: READ ALL SAFETY GUIDES BEFORE INSTALLING THIS FURNACE
Contents Page
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installation Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
High Altitude Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Return Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5
Alcove & Closet Installations . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Air Distribution Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Duct Connector/Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Install Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Roof Jack Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Cut Openings & Install Roof Jack . . . . . . . . . . . . . . . . . . . . . . . .8
Installing in Snow Regions . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Roof Jack On Hi-Pitch Roof . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Transit-mode Roof Jack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-9
Connect Power Supply Wires . . . . . . . . . . . . . . . . . . . . . . . . . .9
Wall Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Connect Thermostat Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-13
Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-15
Final Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Furnace and Air Conditioner Installations . . . . . . . . . . . . . . . . .16
High Altitude Deration Chart . . . . . . . . . . . . . . . . . . . . . . . . . .16
GENERAL INFORMATION
These downflow sealed combustion furnaces install in Manufactured Homes, Recreational Vehicles or modular construction. The furnaces conform to Part 3280 (a) (2) of HUD Manufactured Home Construction and Safety Standards. They must be installed only with listed RJ-Roof Jack, sealed combustion venting system.
NOTE: These instructions are intended to assist qualified individuals experienced in the installation of heating equipment. Some state and local codes require installation personnel to be licensed. Read all instructions before starting the installation.
SAVE THIS MANUAL
NOTICE - A furnace set-up and any adjustment needed is the
responsibility of the installer/retailer/contractor and is not covered by the furnace manufacturers warranty.
CHECKLIST: FURNACE START-UP
1. Has furnace roof jack crown been correctly installed?
2. Has the furnace gas valve and burner orifice been correctly converted to L.P. Gas where applicable?
3. Is the gas line outlet pressure set for the fuel used? NAT Gas is 3.5” W.C. and L.P. Gas is 10.0”W.C.
4. If the home uses a crossover air connector duct, is it installed per the homebuilders installation instruction?
5. Has the furnace been operated through a complete heating cycle?
INSTALLATION INSTRUCTIONS
FINAL PROCEDURE
INSTALL FURNACE DOOR PANELS
A. Install the lower door panel by engaging 2 tabs on bottom cabinet pan into slots on plastic end cap. Then, push in top of door panel until clips on the center divider panel are engaged with latches on door.
B. Install the upper louver door panel in a similar manner, by first engaging tabs on the center divider and then pushing the panel in to engage the clips at top of the cabinet.
FINISH AND TRIM
The alcove or closet installation may be finished and trimmed out as needed.
AIR CONDITIONING SYSTEMS
If an air conditioning system is installed which does not use the blower for air distribution and operates completely independent of the furnace, the thermostat system shall include interlock, which prevents simultaneous operation of the furnace and air conditioner. An interlock system typically contains a switch, which must be turned to either HEAT or COOL to activate either heating or cooling operation. A cooling thermostat may include a positive OFF switch for this purpose.
When used in connection with a cooling unit the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heat exchanger. For installations with a parallel flow arrangement, the furnace must be equipped with a damper or other means to prevent cold air from being discharged up around the heat exchanger.
GAS VALVE CONVERSION INSTRUCTIONS
1. Follow instructions “TO TURN OFF GAS TO APPLIANCE”
2. Remove two bolts securing the gas valve bracket. Pull gas valve valve bracket and burner orifice holder exposing the main burner orifice.
3. Install burner orifice specified on the rating plate for the desired gas. Conversion parts are in a bag attached to the gas valve.
4. Replace valve, bracket/orifice holder, and bolts. Attach ID tag for the desired gas adjacent to the gas valve. Ensure that all connections are tight.
5. Unscrew and reverse the pressure regulating cap so the name of the desired gas is closest to the valve. See illustration.
HIGH ALTITUDE DERATE CHART- MAIN BURNER ORIFICE SIZE
NATURAL GAS
ELEVATION 60,000 BTUH FURNACE 70,000 BTUH FURNACE 75,000 BTUH FURNACE 90,000 BTUH FURNACE
PART NO ORIF DIA. DRILL SIZE PART NO ORIF DIA. DRILL SIZE PART NO ORIF DIA. DRILL SIZE PART NO ORIF DIA. DRILL SIZE
SEA LEVEL 72AG-147 0.1470 26 72AG-159 0.1590 21 72AG-161 0.1610 20 72AG-180 0.1800 15
2,000 72AG-144 0.1440 27 72AG-154 0.1540 23 72AG-161 0.1610 20 72AG-177 0.1770 16 3,000 72AG-140 0.1405 28 72AG-154 0.1540 23 72AG-159 0.1590 21 72AG-173 0.1730 17 4,000 72AG-140 0.1405 28 72AG-152 0.1520 24 72AG-157 0.1570 22 72AG-173 0.1730 17 5,000 72AG-140 0.1405 28 72AG-149 0.1495 25 72AG-154 0.1540 23 72AG-169 0.1690 18 6,000 72AG-136 0.1360 29 72AG-147 0.1470 26 72AG-152 0.1520 24 72AG-166 0.1660 19 7,000 72AG-136 0.1360 29 72AG-144 0.1440 27 72AG-149 0.1490 25 72AG-161 0.1610 20 8,000 72AG-128 0.1285 30 72AG-140 0.1405 28 72AG-147 0.1470 26 72AG-161 0.1610 20 9,000 72AG-128 0.1285 30 72AG-140 0.1405 28 72AG-144 0.1440 27 72AG-157 0.1570 22
10,000 72AG-128 0.1285 30 72AG-136 0.1360 29 72AG-140 0.1405 28 72AG-152 0.1520 24
LP-PROPANE GAS
ELEVATION 60,000 BTUH FURNACE 70,000 BTUH FURNACE 75,000 BTUH FURNACE 90,000 BTUH FURNACE
PART NO ORIF DIA. DRILL SIZE PART NO ORIF DIA. DRILL SIZE PART NO ORIF DIA. DRILL SIZE PART NO ORIF DIA. DRILL SIZE
SEA LEVEL 72AG-089 0.0890 43 72AG-099 0.0995 39 72AG-101 0.1015 38 72AG-113 0.1130 33
2,000 72AG-086 0.0860 44 72AG-098 0.0980 40 72AG-099 0.0995 39 72AG-110 0.1100 35 3,000 72AG-086 0.0860 44 72AG-096 0.0960 41 72AG-098 0.0980 40 72AG-110 0.1100 35 4,000 72AG-086 0.0860 44 72AG-096 0.0960 41 72AG-096 0.0960 41 72AG-106 0.1065 36 5,000 72AG-082 0.0820 45 72AG-093 0.0930 42 72AG-096 0.0960 41 72AG-106 0.1065 36 6,000 72AG-082 0.0820 45 72AG-093 0.0930 42 72AG-093 0.0930 42 72AG-104 0.1040 37 7,000 72AG-081 0.0810 46 72AG-089 0.0890 43 72AG-093 0.0930 42 72AG-101 0.1015 38 8,000 72AG-078 0.0780 47 72AG-089 0.0890 43 72AG-089 0.0890 43 72AG-101 0.1015 38 9,000 72AG-078 0.0780 47 72AG-086 0.0860 44 72AG-089 0.0890 43 72AG-098 0.0980 40
10,000 72AG-076 0.0760 48 72AG-086 0.0860 44 72AG-086 0.0860 44 72AG-096 0.0960 41
Reference: NFPA No. 54, ANSI Z 223.1 National Fuel Gas Code Table shows 4% Input Reduction per 1,000 feet elevation. For Canadian High Altitude (2,000-4,500 feet), reduce gas pressure to burner manifold (manifold Ps.) to 3.0" W.C., and 9.0" W.C. for LP (Propane) Gas
G17D, G18D
Sizes 060-090
WARNING-RISK OF FIRE OF ELECTRICAL SHOCK
Only qualified service personnel shall be used to install and provide maintenance of this furnace.
P/N: 61GF0011
Page 2
3
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
2
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
“B” Cabinet “A” Cabinet
CAUTION
• ELECTRIC POWER - turn off all electrical power to furnace before performing any maintenance or service on unit. Failure to take this precaution may result in personal injury due to electrical shock.
•
SERVICE - a qualified service technician should service this unit. Fuel burning appliances can generate toxic flue products. Modification of the appliance can cause carbon monoxide in deadly amounts. To prevent a safety hazard, maintain this appliance in a safe operating manner and do not modify.
•
DO NOT modify vent or operate the unit with a blocked vent or inlet air pipe.
•
DO NOT re-drill a burner orifice. If the orifice size must be changed, use only a new orifice.
•
DO NOT use matches, lighters, candles, or other sources of open flame to check for gas leaks.
•
PROPER maintenance for this unit requires certain mechanical skills and tools. If you are at all uncertain, contact your Heating Service Co. for maintenance and service.
•
CONSULT with a service technician for any problems or questions you may have pertaining to this appliance.
•
ALWAYS inspect the appliance before starting a new heating season, paying special attention to vent pipes and fuel lines.
SAFETY CONSIDERATIONS
NOTE: The words “Shall” or “Must” indicate a
requirement, which is essential to satisfactory and safe furnace performance.
The words “Should or “May” indicate a recommendation which may be helpful or enhance performance.
INSTALLATION STANDARDS
CODE COMPLIANCE
The installer shall become familiar with and follow all local codes and regulations which govern the installation of this furnace. Where applicable, local codes may take precedence.
• Federal Manufactured Home Construction and Safety Standards – HUD Title 24, Part 3280.
• National Fuel Gas Code – ANSI-Z223.1/NFPA-54
• Unit electrical wiring and grounding shall comply with National Electrical Code – ANSI/NFPA-70.
• “Manufactured Housing” – NFPA-501 and “Fire Safety Criteria for Mobile Home Installations – NFPA 501A.
• “Recreational Vehicles” – ANSI-119-2/NFPA-501C
HIGH ALTITUDE INSTALLATION
For elevation above 2,000 feet derate furnace input 4% for each 1,000 feet of elevation above sea level. Furnace deration is accomplished by reducing the burner orifice size. See DERATING CHART for orifice size and CONVERSION INSTRUCTIONS, Page16.
INSTALLATION CLEARANCES
These furnaces are design certified for the following minimum clearances from combustible materials in alcove or closet installations.
Locate furnace to ensure adequate room for service access to all vent connections, controls and the heat exchanger. A front clearance of 18” minimum (24” recommended) shall be provided by a closet door or spacing away from a facing wall or partition.
For installation on combustible flooring (except carpeting) using manufacturers supplied floor base P/N 87FB0005 and duct connector Series P/N 86AA001-.
Top . . . . . . . . . . . . . . . . . . . . . . . . . . .6 in.
Sides . . . . . . . . . . . . . . . . . . . . . . . . . .0 in.*
Back . . . . . . . . . . . . . . . . . . . . . . . . . .0 in *
Alcove-front of furnace . . . . . . . . . . . . .18 in
Closet- front of furnace . . . . . . . . . . . . . .6 in**
Duct . . . . . . . . . . . . . . . . . . . . . . . . . . .0 in.
Vent/Roof Jack . . . . . . . . . . . . . . . . . . .0 in.
* If the return air opening is below the top of
the furnace, clearance to the side or rear shall be 6”.
** See Return Air for clearances less than 6”.
PART NO. DESCRIPTION NOTES 90-RJF1729-AL Body, Roof Jack, Gas-FLAT Height 'A'- 73 in.- 85 in. 90-RJF2551-AL Body, Roof Jack, Gas-FLAT Height 'A'- 81 in. - 107 in. 90-RJS1729-AL Body, Roof Jack, Gas-SLOPE 3/12 Height 'B'- 81 in. - 101 in. 90-RJS2551-AL Body, Roof Jack, Gas-SLOPE 3/12 Height 'B'- 97 in. - 123 in. 90-RJS3868-AL Body, Roof Jack, Gas-SLOPE 3/12 Height 'B'- 110 in. - 140 in. 90-RJS6399-AL Body, Roof Jack, Gas-SLOPE 3/12 Height 'B'- 135 in.- 171 in. 90-RJCRWN-AL Crown, Roof Jack, Gas Use w/ Gas Roof Jack Body 90-TRM-RNG Ceiling Trim Ring, Roof Jack Trim out to inside RJ- pipe 90-RJTRC Kit, Transit- Roof Jack--Cap & Labels for transport-remove on site 90-OUTXT16-AL Roof Jack Outdoor Extension-Gas 16" Extend pipes/crown-16 in. 90-INSXT10-AL Roof Jack Inside Extension-Gas 10" Extend inside pipes-10 in. 90-RJS56 5-6/12 Slope, Roof Saddle Adapter Add to RJS 3/12 Roof Jack 90-DCUO-OI 86AA0013 Duct Conn + 87FB0005 Flr Base Floor to Duct- 1 in.-4 in. 90-DCUO-O2 86AA0014 Duct Conn + 87FB0005 Flr Base Floor to Duct- 6 in.-8 in.*STD 90-DCUO-O3 86AA0015 Duct Conn + 87FB0005 Flr Base Floor to Duct- 8 in.-12 in. 90-CABEXT4 White, Top, Cabinet Extender Plate Fill alcove 76" top opening 90-BLWRELAY Blower Relay/Wiring Kit Convert Furn for A/C 87-1008-3/12A1 A/C Blower, 3 Speed-1/3 HP 2-4 Ton A/C 87-1008-4/16A1 A/C Blower, 4 Speed-3/4 HP 2-5 Ton A/C
PRODUCT CODE
ACCESSORIES
G1 8D075 B - A 3/12
G=GAS NOM CFM-HI SPEED, W/COIL
DASH @ 0.3" W.C Ext SP (DUCT)
1=SERIES 10-1010, 12-1180, 16-1620
7=75, 8=80 AFUE 1,2,3,4- MOTOR SPEEDS
D=DNFLO, MANUFTR-MOD A=A/C BLOWER & RELAY
H=HEAT or 3T BLW READY, NO RELAY
060,070,075,090 BTUH INPUT A=56", B=72" TALL FURN CABINET
80 AFUE- AUTOMATIC HOT SURFACE IGNITION
Model No. G18D060A-H2/10 G18D075A-H2/10 G18D090A-H2/10 G18D060B-A3/12 G18D075B-A3/12 G18D090B-A3/12 Input, BTUH 60,000 75,000 90,000 60,000 75,000 90,000 Output, BTUH 48,000 61,000 72,000 48,000 61,000 72,000 AFUE, % 80.0 81.0 80.0 80.0 81.0 80.0 With A-Coil Cabinet NO NO NO YES YES YES Ignition Type Auto-Elect Auto-Elect Auto-Elect Auto-Elect Auto-Elect Auto-Elect Air Temperature Rise, Range-F 40-70 45-75 50-80 40-70 45-75 50-80 Blower-Heat or Heat/Cool Heat Heat/Cool -4T Designed Max Outlet Air Temp-F 165 Max. External SP (Duct), In. W.C. 0.30 Factory Equipped Fuel Natural Gas High Altitude For elevations above 2,000 feet, reduce input 4% for each 1,000 ft. elevation above sea level Furnace Flue Pipe Must Use RJS or RJF Roof Jack Gas Connection 1/2" NFPT Electric Service 120VAC, 60Hz, 1 Ph Fuse or Circuit Breaker 15 Amp Thermostat Circuit 24VAC, 60Hz, 40VA Filters 2-16"x20"x1"
75 AFUE- STANDING PILOT IGNITION NOTE: Blower Drives- H2/10, A3/12 , A4/16 listed with all G17D-G18D furnace models.
Model No. G17D060B-H2/10 G17D070B-H2/10 G17D090B-H2/10 G17D060B-A3/12 G17D070B-A3/12 G17D090B-A3/12 Input, BTUH 60,000 70,000 90,000 60,000 70,000 90,000 Output, BTUH 48,000 55,000 71,000 48,000 55,000 71,000 AFUE, % 76.0 75.0 76.0 76.0 75.0 76.0 With A-Coil Cabinet YES YES YES YES YES YES Ignition Type Pilot Pilot Pilot Pilot Pilot Pilot Air Temperature Rise, Range-F 45-75 45-75 50-80 45-75 45-75 50-80 Blower-Heat or Heat/Cool Heat/3T Blower Ready, No AC Controls Heat/Cool -4T Designed Max Outlet Air Temp-F 165 Max. External SP (Duct), In. W.C. 0.30 Factory Equipped Fuel Natural Gas High Altitude For elevations above 2,000 feet, reduce input 4% for each 1,000 ft. elevation above sea level Furnace Flue Pipe Must Use RJS or RJF Roof Jack Gas Connection 1/2" NFPT Electric Service 120VAC, 60Hz, 1 Ph Fuse or Circuit Breaker 15 Amp Thermostat Circuit 24VAC, 60Hz, 40VA Filters 2-16"x20"x1"
Page 3
5
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
4
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
INSTALLATION INSTRUCTIONS
RETURN AIR
ALCOVE INSTALLATION
The furnace may be installed free standing or in an alcove with a free flow of air back to the furnace. A minimum of 18” shall be provided at the front for return air and service access.
CLOSET INSTALLATION - 6 in.
NOTE: If return air is through a side wall, there must be a minimum of 6-in. clearance from side wall to furnace in addition to 6-in. minimum clearance from inside of closet door to front of furnace.
If a louvered door complying with the minimum air require­ments is used, the front clearance may be reduced to 1”.
CLOSET INSTALLATIONS Additional Requirements
Concerning under floor or ceiling return air systems, the following items (1-10) must be adhered to:
1. The return-air opening into the closet, regardless of location, is to be sized not less than specified on the appliance rating plate.
2. If the return-air opening is located in the floor of the closet (versus the vertical front or side wall), the opening is to be provided with means to prevent its inadvertent closure by a flat object placed over the opening.
3. The cross-sectional area of the return duct system (when located in the floor or ceiling of the manufactured home) leading into the closet is to be not less than that of the opening specified on the appli­ances rating plate.
4. The total free area of openings in the floor or ceiling registers serving the return-air duct system is to be not less than 150% of the size opening specified on the appliance rating plate. At least one such register is to be located where the likelihood of its being covered by carpeting, boxes, and other objects is minimized.
5. Materials located in the return duct system have a flame spread classification of 200 or less.
6. Non-combustible pans having one-inch upturned flanges are located beneath openings in the floor return duct system.
7. Wiring materials located in the return duct system conform to Article 300-22 (B&C) of the National Electric Code, ANSI / NFPA-70.
8. Gas piping is not run in or through the return duct system.
9. The negative pressure in the closet, as determined by test with the air-circulating fan operating at high heating speed and the closet door closed, is to be not more negative than minus 0.05-inch water column.
10. For floor return systems, the manufactured home manufacturer or installer shall affix a prominent warning where it is easily read when the closet door is open.
The marking shall read:
HAZARD OF ASPHYXIATION
DO NOT COVER OR RESTRICT FLOOR
OPENING, or equivalent
WARNING
RETURN AIR
ALCOVE
A minimum of 18” front clearance to a facing wall or partition is needed for service access and return air.
Provide a removable panel above the furnace for access to roof jack and pipe connections on top of the furnace.
CLOSET - 6” CLEARANCE
A minimum of 250 sq. in free open area return opening is required to the closet. The return opening may be anywhere on or above the closet door. If the return is through a side wall, and the opening is below the top of the furnace, a minimum of 6-in. clearance from side wall to furnace must be provided in addition to 6-in minimum clearance from inside of closet door to furnace.
If a 5T A/C will be installed, the return shall be increased to 390-sq. in. open area.
SPECIAL-CLOSET, 1” CLEARANCE
For closet installations with less than 6-in. clearance from inside of closet door to furnace, a louvered closet door must be used with a min. of 250 sq. in open area directly in line with the furnace top louver panel as shown. A fully louvered closet door may be used.
If a 5T A/C will be installed, the return shall be increased to 390 sq. in open area directly in line with the furnace louver panel.
ALCOVE INSTALLATION
CLOSET INSTALLATION
*SPECIAL - 1”- 6” CLOSET INSTALLATION
Page 4
7
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
6
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
INSTALLATION INSTRUCTIONS
AIR DISTRIBUTION SYSTEMS
The supply duct system must be designed so that static pressure in the duct does not exceed the static pressure list­ed on the furnace rating plate. Location, size and number of registers should be selected on the basis of best air distribution and floor plan of the home. A manual to review before selecting a duct system is Manufactured Housing Duct Systems: Guide to Best Practices by Manufactured Housing Research Alliance (MHI-MHRA).
Typical duct systems are shown below: FIG. A, B, C
DUCT CONNECTOR / BASE INSTALLATION
The furnace may be on combustible flooring (expect carpeting) when installed with 86AA001­Duct Connector and 87FB0005 Floor Base.
1. Cut a 14-1/8 x 14-1/8 opening in floor. Fig. D.
FIG.D Duct Connector Opening, Fuel & A/C Lines
2. Orient duct connector to align 11x13 tabbed opening with floor duct. See FIG. E
FIG. E- 86AA001- Duct Connector
1. Place duct connector tab end down, thru floor opening to rest on top duct surface.
2. Use eight (8) oval holes on tab surfaces as locators and mark for 11x13 duct opening; remove duct connector.
3. Connect marks with straight lines and cut out the duct opening slightly outside the lines.
4. Attach four (4) foam tape gaskets (provided) to duct connector alongside tabs for a 11x13 perimeter seal.
5. Replace duct connector/gaskets through floor opening.
6. Bend tabs down into the duct opening and fold back 180 degrees, securing duct connector. Add screws if needed.
7. Slit the 4 corners of the connector extending above the floor. Bend sides over onto the floor surface. Fig. F
8. Install floor base over floor opening with 13x13 flanges down. Nail to floor thru 4 holes. Fig. G
INSTALL FURNACE
Prior to installing furnace, fuel and A/C line openings may be cut in. See FIG.D
1. Remove upper and lower furnace doors.
2. Slide furnace onto floor base and push back until cabinet is against rear flange of floor base.
3. Secure furnace to floor with fasteners/screws at right and left front inside corners of cabinet.
4. Attach pipe strap at top of furnace to alcove or closet framing, or fasten through furnace front edge cabinet sides to wood framing.
RJ - SERIES ROOF JACK
G17D and G18D are sealed combustion furnaces tested and listed for use
only with RJ - Series Roof Jack
Venting System.
Furnace exhaust gases vent outdoors through the inner pipe of the RJ - Series “pipe-within-a-pipe” vent system. The space between the outer and inner pipes is used to bring in outside combustion air for the burner.
WARNING: Do not install furnace with any other type of venting system.
A HAZARDOUS CONDITION
MAY RESULT.
FIG. H - RJ SERIES ROOF JACK
FIG. A - Single trunk duct with in-line registers
FIG. B - Double duct with in line registers and crossover duct
FIG. C - Graduated Single Trunk with perimeter registers
FLOOR BASE
DUCT CONNECTER
FOLD-OVER TABS
14-1/8" X 14-18" FLOOR CUTOUT
11" X 12" DUC
T
OPENING
MAIN TRUNK
FIG. F FIG. G
THE SEALED COMBUSTION VENT SYSTEM CONSISTS OF: FURNACE SERIES FURNACE SERIES
ROOF JACK BODY AND ROOF JACK CROWN G18D-A , 56" H G17D-B, G18D-B, 72" H
PART NO. FOR: FLAT OR "A" "B"
ROOF JACK BODY SLOPE ROOF ADJUSTABLE HEIGHT ADJUSTABLE HEIGHT
90-RJF1729-AL FLAT 73"- 85 " 89" - 101" 90-RJF2551-AL FLAT 81"- 107" 97" - 123" 90-RJS1729-AL 3/12 73" - 85 " 89" - 101" 90-RJS2551-AL 3/12 81" - 107" 97" - 123" 90-RJS3868-AL 3/12 94" - 124" 110" - 140" 90-RJS6399-AL 3/12 119" - 155" 135" - 171"
PART NO. MUST USE
ROOF JACK CROWN WITH:
90-RJCRWN-AL ROOF JACK BODY
Page 5
9
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
8
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
INSTALLATION INSTRUCTIONS
CUTTING ROOF JACK OPENING
A proper installation of the roof jack requires that openings in roof and ceiling be on the same vertical centerline as the furnace flue collar. See FIG. I
FIG. I - ROOF CUT-OUT
Mark the center point on the ceiling and scribe a 4” radius (8” diameter) around this mark. If furnace is in place during this step, cover the furnace and flue opening to prevent debris from entering flue.
INSTALLING ROOF JACK
The roof jack body should be secured to the furnace before the roof flashing is secured to the roof.
1. Insert roof jack body into opening in the roof.
2. From above, center the roof jack body aligning with the furnace collar.
3. From inside the home, pull down 4-3/16” D flue pipe seating the pipe fully and firmly over the furnace flue collar.
4. Next pull down the 7” D combustion air pipe seating it over the mating furnace collar. Rotate the combustion air pipe lining up to the screw hole on the 7” furnace collar.
5. Check and make sure the combustion air pipe is fully seated.
Then drive a #10 sheet metal screw attaching
pipe firmly to furnace collar.
6. Install optional ceiling trim ring, 90-TRM-RNG
7. On the roof, caulk liberally under the roof jack flashing.
8. Drive nails or screws through the flashing onto the roof surface about 1- 1 _ inches apart. Caulk again to ensure a leak tight joint.
9. Install roof jack crown and fasten to roof jack body with three (3) screws (provided) using pre-punched holes.
INSTALLATION IN SNOW REGIONS
When the combustion air inlet to the roof jack is blocked with snow, the furnace will not operate properly due to the depleted combustion air supply.
Therefore, if the furnace will be located in regions where snow accumulation on the roof exceeds 7” or in H.U.D. Snow Load Zones, a roof jack extension- Par
t No. 90-
0UTXT16-AL- is recommended.
ROOF JACK ON HI-PITCH ROOF
To install the RJS (3/12) Series Roof Jack on roofs which have a slope between 4.5/12 - 6/12, install a Par
t No. 90-RJS56 Roof Saddle, Fig. J. The combined assembly of the RJS Roof Jack and Roof Saddle will conform to the higher roof pitch. If roof pitch is greater than 6/12, field fabricate a suitable adapter, or consult with factory.
FIG. J - 90-RJS56 ROOF SADDLE, HI PITCH ROOF
TRANSIT ROOF JACK - MODE
RJF and RJS Roof Jacks feature a removable top crown. The crown is normally installed at the factory. If road clearance for the home requires that vent caps or crowns remain uninstalled for road clearance, a T
ransit Mode Kit, Part No.
90-RJTRC
is available. The kit, when used, allows for home shipment with the crown shipped inside the home. The kit includes a weather cap and four (4) warning tags.
FIG. K - 90-RJTRC TRANSIT MODE INSTALLATION
INSTALL TRANSIT ROOF JACK
AT MANUFACTURED HOME FACTORY
1. Roof Jack body (less crown) installed per instructions in this manual.
2. Install weather cap from 90-RJTRC kit on RJF or RJS upper body.
3. The 3 warning tags supplied must be attached
as
follows:
• To homes gas line connection point
• To furnace gas control valve
• To furnace wall thermostat
4. Upper crown, in original carton must be stored in a prominent location inside the home until crown installation is made at site location.
AT MANUFACTURED HOME SITE
5. The transit weather cap is removed and
6. 90-RJCRWN-AL crown installed per these instructions. See FIG K. Make sure crown engages RJ-body pipes above the roof and crown is secured with 3 sheet metal screws.
7. Transit system warning tags are discarded.
CONNECT POWER SUPPLY
1. Remove the furnace control panel cover.
2. Insert 115 V wiring through a strain relief bushing on the left side of the furnace.
3. Connect the HOT wire to the BLACK pigtail lead; connect the NEUTRAL wire to the WHITE pigtail lead. Secure the connections with suitable wire nuts and wrap with electrical tape. Refer to Pgs. 11 thru 13 and one of the following Fig’s L,M,N,O,P or Q to select the proper wiring diagram for connections
4. Connect the GROUND wire to a grounding screw in the control panel.
5. Reinstall and secure the control panel cover with screws.
WALL THERMOSTAT
The location of the wall thermostat is important, as it must sense the desired temperature of the entire conditioned space. Choose a location 4-5 feet above the floor, preferably on an inside wall in an area with good air circulation. Stay away from lamps and air registers and do not install behind a door. Choose a location where the temperature will be reasonably representative of other living areas the thermostat is controlling.
CONNECT THERMOSTAT WIRES
When installing a furnace with a cooling coil compartment, use of a five-conductor thermostat cable is recommended. This will allow easy installation of an air conditioning sys­tem at a later date.
1. Insert 24V wires through the small plastic bushing on the left side of the furnace.
2. Connect low voltage wires to the color coded low voltage pigtails at top of the control panel.
3. Connect low voltage wires to the wall thermostat.
NOTE: The use of 18-gauge wire is highly recommended to carry the thermostat load. Use of smaller conductors risks operational problems caused by loose or broken conductors or wire that is too small to carry the load. Any such problems are the responsibility of the installer.
With conductors smaller than 18 gauge, observe the
following guidelines.
Thermostat wire length
-furnace to thermostat- Thermostat wire gauge 0-45 feet 22 0-70 feet 20
GAS PIPING
Supply piping must be sized in accordance with recommendations found in National Fuel Gas Code ANSI Z223.1/NFPA-54. In addition materials used in manufactured homes must comply with requirements contained in HUD Title 24, Section 3280.705 as well as A119.1 and A119.2 for recreational vehicles.
See chart in this manual for minimum sizes for NAT and LP pipe and tubing serving the fur
nace only.
NOTE: The gas inlet on the gas control valve is 1/2-14NPT. The gas line may be installed through the bottom casing or on left or right side of furnace.
WARNING
Any attempt to operate furnace before replacing transit-mode Weather Cap with Roof Jack Crown may result in hazard of fire, explosion or asphyxiation.
WARNING
To avoid electric shock, personal injury, or death, turn off the power at the disconnect or the main service panel before making any electrical connections.
Page 6
11
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
10
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
INSTALLATION INSTRUCTIONS
GAS PRESSURE:
TYPE GAS INLET GAS PRESSURE
PRESSURE TO BURNER NATURAL 7” W.C. 3-1/2” W.C. PROPANE 11” W.C. 10” W.C.
OPERATION - Once system gas piping has been checked for leaks, operate the furnace using the lighting instructions on the front furnace panel, and:
1. Observe burner through viewport and make sure it ignites. The color of the flame when operating on natural gas will turn blue with yellow tips. On Propane, a significantly yellow flame can be expected. If flame is not the proper color call a qualified service technician for service.
2. Let furnace operate until blower cycles on. This takes about 2 to 2 1/2 minutes.
3. Turn thermostat down.
4. Observe burner to make sure it has shut off.
5. Let furnace cool and blower cycle off.
IF FURNACE FAILS TO OPERATE PROPERLY:
1. Check setting on wall thermostat and the position of the HEAT-COOL switch if air conditioning is installed.
2. Check to make sure that electrical power is ON at the furnace and the furnace circuit breaker has not tripped.
3. Make sure that filters are clean and return grills are not obstructed. The supply registers should be open.
4. Be sure that the furnace flue and inlet piping has not been obstructed and is open. If the cause for failure is not obvious, do not attempt to service the furnace yourself. Call a qualified service agency or the gas supplier.
Take care when connecting the gas line to the furnace gas valve. Use suitable wrenches to support the gas valve when tightening fittings to prevent mis-alignment of the attached burner orifice. Do not damage the gas valve as improper heating, explosion, fire or asphyxiation may result.
Do not use matches, lighters, candles or other open flame to check for leaks. Use a soap or water solution or a leak detector.
Do not pressure test the fuel system at more than 14” W.C. pressure once furnace has been connected to the gas line. Overpressure may void the warranty and damage the valve which could cause an explo­sion, fire or asphyxiation.
WARNING
When converting gas control valve from or to Propane gas, it will be necessary to change the main burner orifice to prevent an underfired or overfired condition. The pressure regulator on the gas control valve must also be converted. See label on lower furnace compartment for full instructions.
If the gas input to the furnace is too high due to excessive gas pressure, wrong size burner orifice, no orifice, high altitude, etc., the burner flame will be sooty especially with Propane gas. This type of furnace operation can produce carbon monoxide, which could result in unsafe operation, explosion, and/or fire and asphyxiation.
WARNING
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the furnace and allow burner to run until furnace cools down and blower shuts off before shutting off electrical supply.
WARNING
WAR NING
DIAGNOSTIC CODES:
STEADY ON -
NORMAL OPERATION
ONE FLASH -
IGNITION FAILURE
TWO FLASHES -
COMBUSTION AIR SWITCH STUCK CLOSED
THREE FLASHES -
COMBUSTION AIR SWITCH FAILED TO CLOSE
FOUR FLASHES -
LIMIT SWITCH OPEN
FIVE FLASHES -
GAS VALVE ENERGIZED WITH NO CALL FOR HEAT
RAPID FLASHES -
REVERSED POLARITY
ELECTRIC SHOCK HAZARD
Disconnect all electric power
before servicing.
1. Incoming wire must be polarized. Observe color coding.
2. If any of the original wires must be replaced, use 105C Thermoplastic type wire or its equivalent.
3. **RED** = Lo Speed - 4 Speed Motor Only
GAS, HOT SURFACE IGNITION - G18D
P/N 61GFC001
Mortex Products, Inc. / FT. WORTH, TX 76016
WAR NING
DIAGNOSTIC CODES:
STEADY ON -
NORMAL OPERATION
ONE FLASH -
IGNITION FAILURE
TWO FLASHES -
COMBUSTION AIR SWITCH STUCK CLOSED
THREE FLASHES -
COMBUSTION AIR SWITCH FAILED TO CLOSE
FOUR FLASHES -
LIMIT SWITCH OPEN
FIVE FLASHES -
GAS VALVE ENERGIZED WITH NO CALL FOR HEAT
RAPID FLASHES -
REVERSED POLARITY
ELECTRIC SHOCK HAZARD
Disconnect all electric power
before servicing.
1. Incoming wire must be polarized. Observe color coding.
2. If any of the original wires must be replaced, use 105C Thermoplastic type wire or its equivalent.
3. **RED** = Lo Speed - 4 Speed Motor Only
GAS, HOT SURFACE IGNITION ­G18D060A-G18D075A-G18D090A
P/N 61GFC002
Mortex Products, Inc.
FT. WORTH, TX 76016
H 2/10, 1/4 HP, 2 SPD BLOWER ­HEATING SPEED SELECTION
G18D060, G18D075-LO OR HI SPEED TAP G18D090-HI SPEED TAP ONLY
FIG. L - G18D060B, G18D075B, G18D090B - A/C READY
WIRING DIAGRAMS
FIG. M - G18D060A, G18D075A, G18D090A - HEATING ONLY
GAS PIPE AND TUBING-MIN SIZES MODEL TYPE LENGTH PIPE TUBING G17D OF SIZE SIZE G18D GAS (FT.) (IN.) (IN.OD)
to 20 3/8 5/8
Natural to 60 1/2 -
060 to 70 - 3/4
to 40 3/8 -
Propane to 70 - 5/8
to 80 1/2 -
to 20 - 5/8
to 50 1/2 -
Natural to 60 - 3/4 072 to 80 3/4 ­075 to 30 3/8 -
Propane to 60 - 5/8
to 80 1/2 ­to 40 1/2 3/4
Natural to 50 - 3/4 090 to 30 3/8 -
Propane to 40 - 5/8
to 60 1/2 3/4
Page 7
13
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
12
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
INSTALLATION INSTRUCTIONS
WAR NING
ELECTRIC SHOCK HAZARD
Disconnect all electric power
before servicing.
1. Incoming wire must be polarized. Observe color coding.
2. If any of the original wires must be replaced, use 105C Thermoplastic type wire or its equivalent.
3. **RED** = Lo Speed - 4 Speed Motor Only
GAS, PILOT, ATMOSPHERIC FURNACE MODELS G17D060, G17D070
P/N 61GFC003
Mortex Products, Inc. / FT. WORTH, TX 76016
WAR NING
ELECTRIC SHOCK HAZARD
Disconnect all electric power
before servicing.
1. Incoming wire must be polarized. Observe color coding.
2. If any of the original wires must be replaced, use 105C Thermoplastic type wire or its equivalent.
3. **RED** = Lo Speed - 4 Speed Motor Only
GAS, PILOT, ATMOSPHERIC FURNACE A/C READY - MODELS G17D060, G17D070
P/N 61GFC004
Mortex Products, Inc.
FT. WORTH, TX 76016
H 2/10, 1/4 HP, 2 SPD BLOWER ­HEATING SPEED SELECTION
G17D060, G17D070 LO OR HI SPEED TAP
FIG. N - G17D060, G17D070 - W/PILOT, HEATING
FIG. O - G17D060B, G17D070B - W/PILOT, A/C READY
FIG. Q - G17D090B - W/PILOT, A/C READY
FIG. P - G17D090 - W/PILOT, HEATING
WAR NING
ELECTRIC SHOCK HAZARD
Disconnect all electric power
before servicing.
1. Incoming wire must be polarized. Observe color coding.
2. If any of the original wires must be replaced, use 105C Thermoplastic type wire or its equivalent.
3. **RED** = Lo Speed - 4 Speed Motor Only
GAS, PILOT, W/ COMBUSTION BLOWER A/C READY - MODEL G17D090
P/N 61GF0006
Mortex Products, Inc. / FT. WORTH, TX 76016
WAR NING
ELECTRIC SHOCK HAZARD
Disconnect all electric power
before servicing.
1. Incoming wire must be polarized. Observe color coding.
2. If any of the original wires must be replaced, use 105C Thermoplastic type wire or its equivalent.
3. **RED** = Lo Speed - 4 Speed Motor Only
GAS, PILOT, W/ COMBUSTION BLOWER HEATING - MODEL G17D090
P/N 61GFC005
Mortex Products, Inc. / FT. WORTH, TX 76016
WIRING DIAGRAMS WIRING DIAGRAMS
Page 8
15
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
14
Mortex Products, Inc. / FT. WORTH, TX 76106 G17 / G18 Installation Instructions Printed 04/04
INSTALLATION INSTRUCTIONS
REPLACEMENT PARTS
BURNER ORIFICE CHART- (FACTORY INSTALLED)
MODEL 060 070 075 090 NAT GAS 72AG-144, #27 72AG-157, #22 72AG-166, #20 72AG-177, #16 LP GAS 72AG-089, #43 72AG-098, #40 72AG-101, #38 72AG-110, #35
ITEM NO.
1
2
3 4
5 6
7 8
9 10
11 12 13
14 15 16 17
18
19 20
21 22 23 25 26 27 28 29 30 31 32 33
USED ON FURNACE MODEL
G18D060, G18D075, G18D090 G17D090 G18D060, G18D075, G18D090 G17D090 All G18D060, G18D075, G18D090 G17D090 G18D060, G18D075, G18D090 G18D060, G18D075, G18D090 G17D060, G17D070, G17D090 All G17D060, G17D070, G18D060 G18D075, G18D090, G17D090 G18D060, G18D075, G18D090 All G18D All G17D-w/H2/10 Blower All G17D -w/A3/12 or A4/16 Blower All All G17D060, G17D070 G17D090 G18D060, G18D075, G18D090 G18D060, G18D075, G18D090 All All All (Tall) All (Short) All G17D, G18D w/ H2/10 Blower All G17D, G18D w/ A3/12 Blower All G17D, G18D w/ A4/16 Blower All w/ A4/16 Blower -3/4HP All w/ H2/10 Blower-1/4HP All w/ A3/12 Blower-1/3HP All w/ A4/16 Blower-3/4HP All G17D models w/factory A/C blower G17D090 All G17D G17D060, G17D070 All G17D All G17D All G17D All G17D060 See Chart All
PART NO
R68DD0010 R68DD0010 R71CA0006 R71CA0006 R68CA0005 R86GF0050 R86GF0050 R68GF0001 R68GF0006 R68GF0007 R68BKN007 R86GF0051 R86GF0052 R68GF0004 R68DD0009 R68DD0009 R68DD0008 R68GF0002 R68CA0004 R86GF0053 R86GF0054 R86GF0054 R68GF0005 R76AA0002 R86GF0055 R86GF0123 R86GF0119 R65GF0001 R65GF0002 R65GF0003 R86GF0056 R68DE0001 R68DE0002 R68DE0003 R69AB0001 R68AB0002 R68AB0002 R68CA0007 R68CA0006 R68GF0009 R68GF0008 R86GF0057 R86GF0058 R87NBF007
72AG-XXX
R87NNE001
QUAN
1
1 2 ft 2 ft
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
DESCRIPTION
Pressure Switch, -0.20 N.O. Pressure Switch, -0.20 N.O. Silicon Tubing Silicon Tubing Limit Switch, Manual, Upper-180F Boost Blower Assembly, w/ air orifices Boost Blower Assembly, w/air orifices Integrated Control Board, HSI Gas Valve-for HSI Electric Ignition Gas Valve- for Standing Pilot Ignition Valve Bracket & Orifice Holder Heat Exchanger & Gaskets Heat Exchanger & Gaskets Flame Sensor System Switch-SPST System Switch-SPST System Switch-SPDT Tran sformer (115V-24V, 40VA) Limit Switch- Open 140F-Close 110F Burner Assembly Burner Assembly Burner Assembly Hot Surface Igniter Filter (16" x 20" x1") Door Panel-Upper Door Panel-Lower Door Panel- Lower Motor-1/4 HP Motor-1/3 HP Motor-3/4 HP Motor Mount Assembly Capacitor- 10/370V Capacitor- 15/370V Capacitor- 25/370V Blower Wheel-10x8 A/C Blower Relay Comb Boost Blower Relay Fan Switch Vent Limit- Manual Reset Thermocouple Pilot Burner Pilot Tube Door Latch,set Combustion Air Orifice Main Burner Orifice Filter Retainer Bracket