Mortex 96-8Z3-0P, 98-8W7-0P, 96-8Z4-0P, 98-8W8-0P, 98-8Z6-0P Installation Manual

...
Page 1
Mortex
INSTALLATION INSTRUCTIONS
AIR CONDITIONING & HEAT PUMP INDOOR COILS
INTRODUCTION
Please note that HUD Manufactured Home Construction and Safety Standard Section 3280.714, paragraph (a) and subparagraph (4) and (5) clearly specifies when a cooling or heat pump coil and air conditioner blower are installed with a furnace or heating appliance they shall be tested and listed in combination for heating and safety performance by a nationally recognized testing agency(ies). Additionally, the cooling or heat pump systems to be installed in Manufactured Housing shall be certified, listed and rated based on US Department of Energy test procedures which are listed by AHRI and shall be tested and listed in combination for heating and safety performance by a nationally recognized testing agency(ies).
Mortex coils are designed specifically for use with various models of manufactured housing gas or electric furnaces in both down-flow and up-flow applications. A different pan will be required on up flow oil furnaces.
These instructions are primarily intended to assist qualified individuals trained and experienced in the proper installation of this type of equipment. Some state codes require installation and service personnel to be licensed. Refer to authorities having jurisdiction for additional guidance. Remember that the Clean Air Act of 1990 requires technician certification for handling refrigerant.
NOTE: EFFICIENCY AND CAPACITY RATINGS ARE LISTED IN CURRENT AHRI UNITARY DIRECTORY [UNDER SUMMIT MANUFACTURING] FOR MORTEX COIL MODEL NUMBERS MATCHED WITH OUTDOOR CONDENSING OR HEAT PUMP UNITS. AIR CONDITIONING COIL MATCHES ARE LISTED IN INDOOR COIL MANUFACTURER AIR CONDITIONING SECTION. HEAT PUMP COIL MATCHES ARE LISTED IN INDOOR COIL MANUFACTURER HEAT PUMP SECTION. INCORRECTLY MATCHED SYSTEMS MAY NOT WORK PROPERLY AND MAY VOID MANUFACTURER LIMITED WARRANTY.
Model Nomina
l
No. Tons A B C Wt. Qty. No. Tons A B C Wt. Qty.
96-8Z3(*)-0P 1.5-2.0 18 19 5/8 16 30 20 98-8W7(*)-0P 2.5-5.0 18 19 5/8 24 1/2 48 12
96-8Z4(*)-0P 1.5-2.5 18 19 5/8 18 32 16 98-8W8(*)-0P 2.5-5.0 18 19 5/8 26 1/2 50 8
98-8Z6(*)-0P 1.5-3.5 18 19 5/8 22 34 12 98-8W9(*)-0P 2.5-5.0 18 19 5/8 28 1/2 52 8
98-8Z7(*)-0P 1.5-3.5 18 19 5/8 24 35 12 98-8W11(*)-0P 2.5-5.0 18 19 5/8 32 1/2 56 8
98-8Z9(*)-0P 1.5-3.5 18 19 5/8 28 37 8 98-8W12(*)-0P 2.5-5.0 18 19 5/8 34 1/2 58 8
96-8G2(*)-0P 1.5-3.0 18 19 5/8 14 30 20 97-9E5(*)-0P 2.5-5.0 18 20 1/2 20 1/2 50 16
96-8G3(*)-0P 2.0-3.5 18 19 5/8 16 31 20 98-9E7(*)-0P 2.5-5.0 18 20 1/2 24 1/2 53 12
96-8G4(*)-0P 2.0-3.5 18 19 5/8 18 33 16 98-9E9(*)-0P 2.5-5.0 18 20 1/2 28 1/2 57 8
97-8G5(*)-0P 2.0-4.0 18 19 5/8 20 34 16 96-R33(*)-0P 1.5-2.0 18 19 5/8 13 29 20
98-8G6(*)-0P 2.0-4.0 18 19 5/8 22 35 12 96-R34(*)-0P 1.5-2.0 18 19 5/8 14 30 20
98-8G7(*)-0P 2.0-4.0 18 19 5/8 24 36 12 96-R36(*)-0P 2.5-3.0 18 19 5/8 18 33 16
98-8G8(*)-0P 2.0-4.0 18 19 5/8 26 43 8 96-R46(*)-0P 3.5-4.0 18 19 5/8 18 38 16
98-8G9(*)-0P 2.0-4.0 18 19 5/8 28 46 8 97-L46(*)-0P 3.5-4.0 18 20 1/2 18 40 16
98-8G11(*)-0P 2.0-4.0 18 19 5/8 32 52 8 98-R49(*)-0P 3.5-4.0 18 19 5/8 28 52 8
98-8G12(*)-0P 2.0-4.0 18 19 5/8 34 52 8 98-R28(*)-0P 1.5-2.0 18 19 5/8 21 1/2 36 8
96-893(*)-0P 2.0-4.0 18 19 5/8 16 1/2 36 20 98-R210(*)-0P 1.5-2.0 18 19 5/8 24 3/4 38 8
96-8W4(*)-0P 2.0-5.0 18 19 5/8 18 1/2 38 16 98-R213(*)-0P 2.5-3.0 18 19 5/8 29 3/4 41 8
97-9E4(*)-0P 2.0-5.0 18 20 1/2 18 1/2 38 16 98-R311(*)-0P 3.5-4.0 18 19 5/8 26 1/2 56 8
97-8W5(*)-0P 2.5-5.0 18 19 5/8 20 1/2 45 16 98-R313(*)-0P 3.5-4.0 18 19 5/8 29 3/4 58 8
98-8W6(*)-0P 2.5-5.0 18 19 5/8 22.5 47 12
Dimensions Coil Pallet Model Nomina
l
Dimensions Coil Pallet
(*) Designates Piston Size or TXV Current Production Models
Page 2
CAUTION!
ATTENTION!
NOTE!
All sweat and quick connect coils are
shipping from factory pressure with nitrogen.
They do not
HFC410A. Relieve nitrogen pressure before
opening the refrigerant circuit.
contain any HCFC22 or
Some Mortex coils have a TXV as the metering
device. However, the sensor bulb is not mounted
due to potential heat damage and / or proper bulb
location. Therefore, after the suction and liquid
line have been properly connected to the coil the
bulb can be mounted on the suction. Many times,
due to space limitations in the manufactured
housing applications it will require the sensor
bulb to be mounted vertically. If that is the case
the bulb should be located at least 6” away from
and bend (elbow) and fastened on the tubing side
opposite the plane of the bend. The bulb should
be insulated using the thermal insulation to
protect it from the effects of the surrounding
ambient temperature. (SEE PAGE 7)
GENERAL COIL INSTALLATION NOTES
1.
On a quick connect coil, test for pressure by pushing against the diaphragm located inside the quick connect fitting on the suction manifold. If you are not able to depress the diaphragm, the coil contains a Nitrogen holding charge. To test for pressure on a sweat connect coil, remove the cap or flare nut on the Schrader fitting and depress the core valve located on the suction manifold.
2. The blower and duct system must be properly
All Mortex coils are shipped pressurized with Nitrogen. Coils with sweat or quick connect fittings are shipped with a nitrogen holding charge.
ALL COILS SHOULD BE CHECKED FOR PRESSURE BEFORE LEAVING THE DISTRIBUTOR OR BEFORE INSTALLATION! IF THERE IS NO PRESSURE PRESENT, THE COIL MAY HAVE DEVELOPED A LEAK DURING SHIPMENT AND SHOULD BE RETURNED TO THE POINT OF PURCHASE FOR EXCHANGE.
Sized in order to provide adequate cooling and
heating performance. Select the correct motor speed tap on the furnace blower to give the
Mortex coils and other accessories installed when
air conditioning is added to manufactured
housing furnaces will comply with HUD
regulations requiring third party approvals.
Efficiency and capacity ratings as required by
HUD are listed in the current AHRI directory for Mortex [see Summit Manufacturing] matched with the outdoor units. These coil ratings are based on
air quantities consistent with those that are
encountered in typical manufactured housing air
condition and heat pump applications.
required CFM needed for rated cooling capacity or upgrade the blower assembly to attain the proper CFM. Return air filters of generous size must be provided, in order to avoid contaminating the coil, blower and ductwork, or restricting necessary airflow. Failure to deliver the proper air flow across the indoor coil will cause system and/or component problems, i.e. TXV performance problems.
3. It is essential that the indoor coil and outdoor
unit be properly matched and charged with the proper amount of refrigerant. Incorrect
charge levels will result in inefficient operation. See more details in installation instructions for the outdoor unit.
4. For optimum performance and efficiency of air conditioning or heat pump coils, adjust system charge and/or superheat/subcooling as recommended by outdoor unit manufacturers. Procedures will differ between manufacturers.
5. It is recommended that the coil be sprayed with liquid detergent thoroughly and rinsed thoroughly before installation to assure proper drainage of condensate from the coil fins to eliminate water blowoff and to assure maximum coil performance. If not sprayed, approximately 50 hours of break in time is required to achieve the same results.
Page 3
6. Always be sure coil is installed level or sloped slightly toward primary and secondary (the higher of the two) drain fittings. If mandated by code, connect both drain lines to open drain, but never to a closed sewer. Pitch drain lines away from drain pan. Always water before operating. This step is mandatory in all manufactured housing installations. Reduction in size of the drain lines is not recommended and many times not allowed.
7. A WATER TRAP IS RECOMMENDED ON ALL
COIL APPLICATIONS, BUT IS REQUIRED PULL THROUGH INSTALLATIONS ON ELECTRIC FURNACES. FAILURE TO PROVIDE CAN RESULT IN IMPROPER DRAINAGE OR POTENTIAL SHOCK HAZARD.
It is mandatory to use an emergency auxiliary drain pan with any coil or air handler installed in an attic or above a finished ceiling. It must have its own drain line (a water trap is not necessary) with its output into an open drain (not a closed sewer). It should allow easy visual inspection so that if condensate flow is seen the homeowner knows that the coil drain pan lines are plugged and need maintenance.
8.
Refrigerant piping is critical on any coil installation when the outdoor unit is to be located below the level of the coil. For proper piping design considerations, refer to the guidelines furnished by the manufacturer of the outdoor unit.
9. Check all field installed refrigerant connections with electronic leak detector, halide torch, or soap bubbles.
10. Refer to installation instructions provided with the outdoor unit, gas or electric furnace, and line sets for completion of system installation.
INSTALLATION WITH ELECTRIC FURNACE:
Typical electric furnace installation consists of a coil without cabinet installed on top of a downflow furnace or the coil inside a cavity on either a downflow or upflow furnace.
The following Mortex installation kits are unique to manufactured housing air conditioning and these kits are required to complete the installation.
1. Filter-Electrostatic (95-1741-UES) is required when using Mortex coil models on all electric furnaces without cavities. [See #3 below}
2. A Coil Support Bracket (99-3420-03) and coil
support with Insulation Kit (99-3420-02) is required to support coils in Coleman furnaces.
3 Coil & Filter Cabinets (97-BCC-02N) are
recommended and may times required for Nordyne furnaces as a preferred option.
Installation procedure:
1. Turn off electrical power to the furnace by turning off breaker in house panel. CAUTION:
Furnace may be connected to more than one supply circuit. Do not use furnace disconnect only. Check power at furnace to insure power is off.
ATTENTION!
, test drain lines with
ON
2. Remove filter at top of furnace cabinet (Nordyne or Coleman only).
3. Remove refrigerant line knockout at top of furnace (Mortex & Nordyne only).
4. Install insulation if needed.
5. Attach drain pan gasket provided with coil to underside of coil pan and center evaporator coil on furnace. See figure A on page 5.
6. Attach filters to sides of coil.
7. Route low voltage wiring, refrigerant lines and drain tubing through floor penetration.
WARNING: If drain hose is below 40 Deg F
during installation warm before expanding and/or forming.
8. Form 3” deep trap using (field supplied) tape
and (provided) flexible drain hose and connect
to coil pan drain securing with clamp provided. See figure B on page 5. The most efficient use of drain material is to form a “P” trap under the house. All pull through furnaces must have a
condensate trap in the drain line.
9. Connect refrigerant lines per instructions with line set. Make sure to lubricate quick connect threads with refrigeration oil for proper mating. Refer to outdoor unit installation instructions for additional information on line set hook-ups and proper torque values.
10. W ith the coil in place seal off any openings at top or bottom of furnace to prevent air leakage or air bypass (use silver backed tape provided, if needed).
11. Turn power on to furnace.
12. Replace front door.
INSTALLATION WITH GAS FURNACE:
Do not install any coil containing refrigerant in a gas
furnace which is to be operated during the heating
season without attaching the refrigerant lines to the
coil. Possible coil damage will result from excessive
pressure build up during heating operation.
Typical downflow gas furnace installation consists of a coil without cabinet installed in the cavity of a downflow furnace. Coil with plastic pan is not suitable for upflow oil furnaces.
Installation procedure:
1. Turn off electrical power to furnace.
2. Remove the lower front panel of the furnace,
and re-route any gas piping in front of coil compartment as required to install coil.
Contractor must comply with all local, state, and
federal codes and regulations when working with
gas piping. Personal injury or death may result from
3. Remove the coil cover panel(s).
4. Remove knockouts in front left bottom of
furnace for routing of refrigerant lines, low voltage wiring, and condensate drain.
5. Attach drain pan gasket provided, see figure
“A”, page 5, to underside of coil pan and center coil in coil cavity.
ATTENTION!
WARNING!
improper installations!
Page 4
6. Connect drain hose to condensate pan fitting, securing with clamp. See figure “B”, page 5.
7. Remove knockouts from coil cover panel(s), cut fiberglass insulation covering openings and reinstall cover.
8. Install silver backed tape provided to cover openings in interior panel door and over refrigerant lines to seal around lines
9. Connect refrigerant lines and make sure all connections are tight and without leaks.
10. Reconnect the gas piping if it was disconnected and seal off any openings at bottom of furnace. National, state and local codes must be followed.
11. Install filter if not located in furnace door.
12. Turn on gas/electrical supply and make final system check.
13. Replace front door.
SPECIAL CONSIDERATIONS FOR SELECTING
HEAT PUMP COILS
The selection of indoor heat pump coils is much more critical than selection of indoor coils for air conditioning units. The differences are as follows:
1. Only indoor coils with expansion/check valve flow
control devices may be used with outdoor heat pump units. These devices permit reversing refrigerant flow in the coils when changing from cooling to heating. All Mortex expansion valves and pistons have a built-in check making them heat pump capable when matched with the proper AHRI rated outdoor unit. CAP TUBE OR
FIXED RESTRICTOR COILS MUST NOT BE USED WITH HEAT PUMP.
2. Matching of indoor coils for heat pumps
demands that the heat rejection capacity, internal volume, and equivalent metering device of the matched coil be at least equal to that of the smallest internal volume matched coil recommended by outdoor unit manufacturer for that outdoor unit.
3. It is important that selection be based on
Mortex recommendation for a specific coil with a specific metering device to be used with an outdoor heat pump unit of a specific make, series, and model number.
4. Failure to conform to proper selection
requirements will affect efficiency, charging, and reliability and may result in damage to the system or system components.
5. The matching of specific indoor heat pump coils with specific outdoor heat pump units as certified in the heat pump section of the current AHRI Directory will assure proper and efficient operation of heat pump systems. See www.ahri.org.
SPECIAL INSTRUCTIONS FOR CHARGING
HEAT PUMP COILS
Specific detailed instructions for refrigerant charging of a heat pump system as recommended by the outdoor unit manufacturer should be followed. These instructions will differ between manufacturers, but in general are as follows:
WITH EXPANSION/CHECK VALVE IN INDOOR COIL, USE LIQUID LINE SUBCOOLING METHOD IN COOLING MODE. Measure following values from
system: liquid line pressure at gauge and liquid line temperature. Compare measurements to refrigerant T&P chart. Allow 20-30 minutes to insure the
system has stabilized before verifying that the charge is correct. Adjust charge to achieve outdoor unit manufacturer’s recommended liquid line subcooling.
IF WITH PISTON METERING DEVICE IN INDOOR COIL, USE SUCTION LINE SUPER HEAT METHOD IN COOLING MODE. Measure following values from
system: Suction line pressure at gauge and suction line temperature. Compare measurements to refrigerant T&P chart. Adjust charge to achieve outdoor unit
manufacturers recommended Suction line super heat.
NOTE: Micro-channel condensing unit/heat pump outdoor unit. The charging should always be done by superheat, not sub-cooling
.
If the installer encounters a problem using the outdoor manufacturers suggested charging method technician should contact the factory for assistance.
NOTE: Good preventive maintenance on heat pumps is critical to ensure proper airflow across the coils. Low airflow on indoor coils during winter months causes high head pressures and premature compressor damage due to oil breakdown. This problem is normally the result of a dirty air filter. The installer should instruct the homeowner of the importance of keeping filters clean.
CONTACT US FOR HELP OR FOR ANY COMMENTS ON OUR PRODUCTS.
As we strive to better serve our customers like you, we are always ready to help you. We also welcome any comments from our customers concerning quality and improvements that could be made to our products. Thank you for the purchase of our product.
Page 5
Page 6
THERMAL EXPANSION VALVE
INSTALLATION INSTRUCTIONS
A. INTRODUCTION
Thermal expansion valve (TXV) can be used on both heat pump and air conditioning applications. All TV’s have a built-in check valve making them heat pump capable. All are externally equalized with non­adjustable superheat and are available with non-bleed construction. Hard start capability for outdoor units is required when non-bleed valve is used. The external equalizer line attached to the TXV has a female flare nut with built in Schrader valve depressor that attached to the Schrader valve port provided on most coils.
B. INSTALLATION NOTES
With reference to Figure 1, the TXV assembly is to be installed between the flowrator distributor and the existing liquid line attached to the flowrator distributor.
WARNING: COIL IS PRESSURIZED. RELIEVE PRESSURE BEFORE INSTALLING TXV BY DEPRESSING SCHRADER VALVE ON COIL MANIFOLD IF NITROGEN, OR RECLAIM REFRIGERANT IF COIL HAS HOLDING CHARGE.
C. INSTALLATION STEPS ARE AS FOLLOWS:
1. After coil pressure has been relieved, turn
female swivel nut counter-clockwise to remove.
2. Remove the piston from the flowrator
distributor fitting using a small diameter wire or paper clip (ALWAYS REMOVE THE PI8STON FROM THE DISTRIBUTOR BODY WHEN TXV IS INSTALLED).
3. Attach the TXV by connecting the female
swivel nut on TXV outlet to the flowrator distributor (aligning Teflon seal first) and torque swivel nut to 10 – 30 in. lb.
4. Attach liquid line with female swivel nut to
male rotalock fitting on TXV inlet (aligning Teflon seal first) and torque swivel nut to 10 – 30 in. lb.
5. Remove the cap on Schrader valve port on
coil manifold. Attach equalizer tubing with ¼” female flare nut that includes depressor to this male Schrader port. Torque flare nut to 10 – 30 in. lb. If using a different brand TXV, you
must remove the Schrader valve core prior to attaching the equalizer tube.
6. Install the TXV bulb to the suction manifold
of coil or the suction line using the two bulb clamps, or single large clamp, furnished with kit. a. Bulb should be installed on a horizontal run
of the manifold if possible. On line 7/8” OD and smaller the bulb should be installed at 2 or 10 o’clock. With line larger than 7/8” OD, the bulb should be installed in a position of about 4 or 8 o’clock.
b. If bulb installation is made on a vertical run,
the bulb should be located at least 6 inches from any bend, and on the tubing side opposite the plane of the bend. On vertical bulb installations, the bulb should be positioned with bulb capillary tube at the top.
c. The bulb should be insulated using thermal
insulation to protect it from the effect of the surrounding ambient temperature.
7. After completing installation of TXV
(including equalizer tube), it will be necessary to leak check the coil and evacuate the coil through the service access fittings of liquid and suction line valves. SEE COIL AND UNIT INSTALLATION INSTRUCTIONS.
Loading...