Mortex
INSTALLATION INSTRUCTIONS
AIR CONDITIONING & HEAT PUMP INDOOR COILS
INTRODUCTION
Please note that HUD Manufactured Home Construction and Safety Standard Section 3280.714, paragraph (a) and subparagraph
(4) and (5) clearly specifies when a cooling or heat pump coil and air conditioner blower are installed with a furnace or heating
appliance they shall be tested and listed in combination for heating and safety performance by a nationally recognized testing
agency(ies). Additionally, the cooling or heat pump systems to be installed in Manufactured Housing shall be certified, listed and
rated based on US Department of Energy test procedures which are listed by AHRI and shall be tested and listed in combination
for heating and safety performance by a nationally recognized testing agency(ies).
Mortex coils are designed specifically for use with various models of manufactured housing gas or electric furnaces in both down-flow
and up-flow applications. A different pan will be required on up flow oil furnaces.
These instructions are primarily intended to assist qualified individuals trained and experienced in the proper installation of this type of
equipment. Some state codes require installation and service personnel to be licensed. Refer to authorities having jurisdiction for
additional guidance. Remember that the Clean Air Act of 1990 requires technician certification for handling refrigerant.
NOTE: EFFICIENCY AND CAPACITY RATINGS ARE LISTED IN CURRENT AHRI UNITARY DIRECTORY [UNDER SUMMIT
MANUFACTURING] FOR MORTEX COIL MODEL NUMBERS MATCHED WITH OUTDOOR CONDENSING OR HEAT PUMP UNITS.
AIR CONDITIONING COIL MATCHES ARE LISTED IN INDOOR COIL MANUFACTURER AIR CONDITIONING SECTION. HEAT
PUMP COIL MATCHES ARE LISTED IN INDOOR COIL MANUFACTURER HEAT PUMP SECTION. INCORRECTLY MATCHED
SYSTEMS MAY NOT WORK PROPERLY AND MAY VOID MANUFACTURER LIMITED WARRANTY.
Model Nomina
l
No. Tons A B C Wt. Qty. No. Tons A B C Wt. Qty.
96-8Z3(*)-0P 1.5-2.0 18 19 5/8 16 30 20 98-8W7(*)-0P 2.5-5.0 18 19 5/8 24 1/2 48 12
96-8Z4(*)-0P 1.5-2.5 18 19 5/8 18 32 16 98-8W8(*)-0P 2.5-5.0 18 19 5/8 26 1/2 50 8
98-8Z6(*)-0P 1.5-3.5 18 19 5/8 22 34 12 98-8W9(*)-0P 2.5-5.0 18 19 5/8 28 1/2 52 8
98-8Z7(*)-0P 1.5-3.5 18 19 5/8 24 35 12 98-8W11(*)-0P 2.5-5.0 18 19 5/8 32 1/2 56 8
98-8Z9(*)-0P 1.5-3.5 18 19 5/8 28 37 8 98-8W12(*)-0P 2.5-5.0 18 19 5/8 34 1/2 58 8
96-8G2(*)-0P 1.5-3.0 18 19 5/8 14 30 20 97-9E5(*)-0P 2.5-5.0 18 20 1/2 20 1/2 50 16
96-8G3(*)-0P 2.0-3.5 18 19 5/8 16 31 20 98-9E7(*)-0P 2.5-5.0 18 20 1/2 24 1/2 53 12
96-8G4(*)-0P 2.0-3.5 18 19 5/8 18 33 16 98-9E9(*)-0P 2.5-5.0 18 20 1/2 28 1/2 57 8
97-8G5(*)-0P 2.0-4.0 18 19 5/8 20 34 16 96-R33(*)-0P 1.5-2.0 18 19 5/8 13 29 20
98-8G6(*)-0P 2.0-4.0 18 19 5/8 22 35 12 96-R34(*)-0P 1.5-2.0 18 19 5/8 14 30 20
98-8G7(*)-0P 2.0-4.0 18 19 5/8 24 36 12 96-R36(*)-0P 2.5-3.0 18 19 5/8 18 33 16
98-8G8(*)-0P 2.0-4.0 18 19 5/8 26 43 8 96-R46(*)-0P 3.5-4.0 18 19 5/8 18 38 16
98-8G9(*)-0P 2.0-4.0 18 19 5/8 28 46 8 97-L46(*)-0P 3.5-4.0 18 20 1/2 18 40 16
98-8G11(*)-0P 2.0-4.0 18 19 5/8 32 52 8 98-R49(*)-0P 3.5-4.0 18 19 5/8 28 52 8
98-8G12(*)-0P 2.0-4.0 18 19 5/8 34 52 8 98-R28(*)-0P 1.5-2.0 18 19 5/8 21 1/2 36 8
96-893(*)-0P 2.0-4.0 18 19 5/8 16 1/2 36 20 98-R210(*)-0P 1.5-2.0 18 19 5/8 24 3/4 38 8
96-8W4(*)-0P 2.0-5.0 18 19 5/8 18 1/2 38 16 98-R213(*)-0P 2.5-3.0 18 19 5/8 29 3/4 41 8
97-9E4(*)-0P 2.0-5.0 18 20 1/2 18 1/2 38 16 98-R311(*)-0P 3.5-4.0 18 19 5/8 26 1/2 56 8
97-8W5(*)-0P 2.5-5.0 18 19 5/8 20 1/2 45 16 98-R313(*)-0P 3.5-4.0 18 19 5/8 29 3/4 58 8
98-8W6(*)-0P 2.5-5.0 18 19 5/8 22.5 47 12
Dimensions Coil Pallet Model Nomina
l
Dimensions Coil Pallet
(*) Designates Piston Size or TXV Current Production Models
All sweat and quick connect coils are
shipping from factory pressure with nitrogen.
They do not
HFC410A. Relieve nitrogen pressure before
opening the refrigerant circuit.
contain any HCFC22 or
Some Mortex coils have a TXV as the metering
device. However, the sensor bulb is not mounted
due to potential heat damage and / or proper bulb
location. Therefore, after the suction and liquid
line have been properly connected to the coil the
bulb can be mounted on the suction. Many times,
due to space limitations in the manufactured
housing applications it will require the sensor
bulb to be mounted vertically. If that is the case
the bulb should be located at least 6” away from
and bend (elbow) and fastened on the tubing side
opposite the plane of the bend. The bulb should
be insulated using the thermal insulation to
protect it from the effects of the surrounding
ambient temperature. (SEE PAGE 7)
GENERAL COIL INSTALLATION NOTES
1.
On a quick connect coil, test for pressure by pushing
against the diaphragm located inside the quick connect
fitting on the suction manifold. If you are not able to
depress the diaphragm, the coil contains a Nitrogen
holding charge.
To test for pressure on a sweat connect coil, remove
the cap or flare nut on the Schrader fitting and depress
the core valve located on the suction manifold.
2. The blower and duct system must be properly
All Mortex coils are shipped pressurized with
Nitrogen. Coils with sweat or quick connect
fittings are shipped with a nitrogen holding
charge.
ALL COILS SHOULD BE CHECKED FOR
PRESSURE BEFORE LEAVING THE
DISTRIBUTOR OR BEFORE INSTALLATION!
IF THERE IS NO PRESSURE PRESENT, THE
COIL MAY HAVE DEVELOPED A LEAK
DURING SHIPMENT AND SHOULD BE
RETURNED TO THE POINT OF PURCHASE
FOR EXCHANGE.
Sized in order to provide adequate cooling and
heating performance. Select the correct motor
speed tap on the furnace blower to give the
Mortex coils and other accessories installed when
air conditioning is added to manufactured
housing furnaces will comply with HUD
regulations requiring third party approvals.
Efficiency and capacity ratings as required by
HUD are listed in the current AHRI directory for
Mortex [see Summit Manufacturing] matched with
the outdoor units. These coil ratings are based on
air quantities consistent with those that are
encountered in typical manufactured housing air
condition and heat pump applications.
required CFM needed for rated cooling capacity
or upgrade the blower assembly to attain the
proper CFM. Return air filters of generous size
must be provided, in order to avoid contaminating
the coil, blower and ductwork, or restricting
necessary airflow. Failure to deliver the proper air
flow across the indoor coil will cause system
and/or component problems, i.e. TXV
performance problems.
3. It is essential that the indoor coil and outdoor
unit be properly matched and charged with
the proper amount of refrigerant. Incorrect
charge levels will result in inefficient operation.
See more details in installation instructions for the
outdoor unit.
4. For optimum performance and efficiency of air
conditioning or heat pump coils, adjust system
charge and/or superheat/subcooling as
recommended by outdoor unit manufacturers.
Procedures will differ between manufacturers.
5. It is recommended that the coil be sprayed with
liquid detergent thoroughly and rinsed thoroughly
before installation to assure proper drainage of
condensate from the coil fins to eliminate water
blowoff and to assure maximum coil
performance. If not sprayed, approximately 50
hours of break in time is required to achieve the
same results.