INSTALLATION INSTRUCTION MANUAL
This LED Flood light uses the latest in solid state lighting technology for long life,
An excellent alternative to traditional HID lighting. There are multiple installation methods,
An internal power-factor-corrected switch-mode supply allows it to be used on
Suitable for use in the following locations:
For supply connections use wire rated for at least 90°C
“CAUTION – RISK OF SHOCK’’ and “DISCONNECT POWER BEFORE SERVICING”
To avoid the risk of fire, explosion, or electric shock, this product should be installed,
inspected, and maintained by a qualified electrician only, in accordance with all applicable
•Be certain electrical power is OFF before and during installation and maintenance.
•Luminaire must be connected to a wiring system with an equipment-grounding conductor.
•Make sure the supply voltage is the same as the rated luminaire voltage.
•Do not install where the marked operating temperatures exceed the ignition temperature of
the hazardous atmosphere.
•Do not operate in ambient temperatures above those indicated on the luminaire nameplate.
•Keep lens tightly closed when in operation.
LED FLOOD LIGHT, 100-277VAC
Rev A Aug 2015
SERIES:
71531,71532,71533,71541,71542,71543,71544,71545,71551,71552,71553,71554,
71555, 71556, 71557, 71561, 71562, 71563, 71564, 71565, 71573, 71574, 71575, 71576, 71577,
71581, 71582, 71583, 71584, 71585, 71801, 71802, 71803, 71804, 71805, 71806, 71807, 71808,
71809, 71821, 71822, 71823, 71824, 71825, 71831, 71832, 71833, 71835, 71837, 71840, 71841,
71842, 71844, 71846, 71851, 71852, 71853, 71855, 71857, 71861, 71862, 71863, 71864, 71865,
71866, 71868, 71869
low maintenance, and high efficiency.
suitable for different applications.
any nominal 100-277V, 60Hz AC voltage without any variation in light output.
•
Ambient Temp: -20~+40°C
•
Wet Locations
53 Carey Rd Queensbury, NY 12804
Morris Products

For supply connections use wire rated for at least 90°C
Refer to the following diagram when you install the fixture. Seven installation methods available,
Mount directly fix to a wall or other mounting surface or fix to a pole/post with a knuckle, trunion or slipfitter.
1. Mount directly fix to wall or other mounting surface with bracket: 71531, 71532, 71533, 71801, 71802,
71803, 71804, 71805, 71806, 71807, 71808, 71809
1. Use expansion bolts to secure the fixture on mounting surface.
2. Maintain enough slack length in wire leads to ensure adjusting angle unhindered.
Connect wires into wiring terminal:
white wire to“Neutral”terminal
black wire to“Live”terminal
green wire to “Ground” terminal
2. Mounting with a ½” knuckle for Models: 71551, 71552, 71553, 71554, 71555, 71556, 71557, 71821,71822,
Secure service wire or conduit to the wiring compartment cover with 1/2” connector ( not provided ).
Connect white fixture wire to white supply wire, black fixture wire to black supply wire.
Service ground should be attached to green ground screw provided.
Ground must be properly attached to avoid the risk of electrical shock.
Use wire nuts, crimp-on lugs, or other approved devices to connect all wires, make sure connections are secure
and that no loose wire strands are sticking out of connectors
Secure wiring compartment cover to fixture, with black and white connections inside the wiring compartment.
Use UL and CUL Listed flexible steel waterproof conduit in trade sizes 1/2 and UL and CUL Listed
water-proof outlet box cove.
71823,71824,71825
53 Carey Rd Queensbury, NY 12804
Morris Products

3. Mounting with a Slipfitter for Models:
4. Mounting with Wall Mount for Models:
71561, 71562, 71563, 71564, 71565,71840,71841,71842,71844,71846
Step 1
Step 2
Adjust the fixture orientation by opening knockout at
fulcrum and turning the bolt.
Motion sensor or photocell can be installed in KO’s on
slipfitter mounting arm
71581, 71582,71861,71862
Use a tenon post of diameter 2.36” for mounting
and tighten screws completely.
You can open the side cover from the side
knockout
Wall mounting method:
Install mounting plate on junction box, secure wall plate
Morris Products
53 Carey Rd Queensbury, NY 12804

5. Mounting with a Trunion for Models:
71541, 71542, 71543, 71544, 71545,71831,71832,71833,71835,71837
Step 1
Step 2
Adjust the fixture to the required orientation, tighten the
Drill the holes on the square pole or wall
bolts completely
6. Mounting with Pole Arm for Models:
71573, 71574, 71575, 71576, 71577,71851,71852,71853,71855,71857
Secure pole mount arm to pole or wall with mounting hardware. Pole Arm has KO’s in top and bottom
for motion sensor or photocell requirements. Side cover is removable for access to wiring compartment.
53 Carey Rd Queensbury, NY 12804
Morris Products

7.Wall Mount installation
71583, 71584, 71585,71863,71864,71865,71866,71868,71869
Same mounting method as #6 above - wall mounted fixing plate is mounted on the wall
with appropriate mounting hardware.
After installation:
check whether the lighting fixture is firmly secured.
check wiring for correctl connection.
Turn on the power, and check if the lighting fixture works well. If not, please turn off the power
and contact with local dealer.
Morris Products
53 Carey Rd Queensbury, NY 12804

FlatPanel Flood/Area Lights LED DRIVER Dimming Instructions
MORRIS Cat#s 71531 Thru 71585
71801 Thru 71898
Fixture Dimming Parameters
power voltage POWER Model
80W
100W
150W
220W
300W
100-277V EUC-085S200DT No yes No No
100-277V EUG-096S350DT
277-480V ESD-096S360DT
100-277V EUG-150S350DT yes yes yes yes
277-480V ESD-150S560DT
100-277V EUG-240S670DT yes yes yes yes
277-480V ESD-240S660DT
100-277V EUC-320S490DT No yes No No
277-480V ESD-320S620DT
0-5V dimming 0-10V dimming PWM dimming
yes
No yes yes yes
No yes yes yes
No yes yes yes
No
yes yes yes
yes
yes yes
Time dimming
SAFETY INFORMATION
1. Please make wiring according to the nameplate. Incorrect wiring will destroy the product. All the wires are
strictly prohibited to opposite polarity and shortcut. The dimming wires of dimmable driver are strictly
prohibited to connect high voltage (above 24V).
2. In order to avoid the bare wires connect the metal part or high voltage source, the dimming wires must be
isolated by proper method when the dimming function not used, for example wrapped by tape or sealed by
glue.