Morningstar EC-10, EC-20M, EC-10M, EC-30M, EC-30 Maintance Manual

...
Solar Charging System Controller
Installation, Operation, and Maintenance Manual
Languages: English, French, German, Spanish
www.morningstarcorp.com
EcoPulse
TM
MODELS
For the most recent manual revisions, see the
version at: www.morningstarcorp.com
ii
TABLE OF CONTENTS
6.30 160
4.33 110
5.51 140
3.54 90
2.04 52
DIMENSIONS [inches (millimeters)]
1.0 Important Safety Instructions.............................1
2.0 General Information......................................... ..6
2.2 Features
...............................................................6
2.3 Optional Accessories
............................................7
3.0 Installation..........................................................8
3.1 General Installation Notes.....................................8
3.2 Configuration
...............................................................9
3.3 Mounting
....................................................................11
3.4 Wiring
.........................................................................13
3.5 Custom Settings
....................................................... 19
3.5.1 Adjusting the Meter Display
....................................19
3.5.2
Directional Key Use and Operation /
Navigating the Meter Map
..................................... 19
3.5.3 Using the Meter Display to Program Charging
Set-points and Load Control......................................19
4.0 Operation.........................................................20
4.1 Battery Charging Information........................ .....20
4.2 Load Information.........................................................22
4.3 LED Indcations............................................................ 22
4.3.1 Power-up.....................................................................22
4.3.2 Status LED...................................................................23
4.3.3 State-of-charge LEDs................................................. 23
Continued
SPECIFICATION SUMMARY
10/M 20/M 30/M
Nominal Battery voltage 12 / 24V 12 / 24V 12 / 24V
Max. PV Open- Circuit Voltage* 60V 60V 60V
Max. Battery Charging Current 10A 20A 30A
Rated Load Current 10A 20A 30A
* Array voltage should never exceed this limit
1
iv
EcoPulse Operator’s ManualImportant Safety Instructions
1.0
TABLE OF CONTENTS (Cont.)
4.4
Protections, Faults & Alarms................................. 24
4.4.1 Protections...................................................................24
4.4.2 LED Fault Indication.....................................................24
4.4.3 Alarms..........................................................................25
4.5 Inspection and Maintenance............................. ..........26
5.0 Warranty.................................................................28
6.0 Technical Specifications......................................... 29
Appendix - Certifications.................................................30
SAVE THESE INSTRUCTIONS.
This manual contains important safety, installation, operating and maintenance instructions for the EcoPulse solar charge controller.
The following symbols are used throughout this manual to indicate potentially dangerous conditions or mark important safety instructions:
WARNING: Indicates a potentially dangerous
condition. Use extreme caution when performing this task.
CAUTION: Indicates a critical procedure for safe
and proper operation of the controller.
NOTE: Indicates a procedure or function that is
important to the safe and proper operation of the controller.
Safety Information
• Read all of the instructions and cautions in the manual before beginning installation.
• There are no user serviceable parts inside the EcoPulse. Do not disassemble or attempt to repair the controller.
1.0 IMPORTANT SAFETY INSTRUCTIONS
3
2
EcoPulse Operator’s ManualImportant Safety Instructions
1.0
• Use properly sized conductors and circuit interrupters.
• This charge controller is to be connected to DC circuits only. These DC connections are identified by the symbol below:
Direct Current Symbol
The EcoPulse controller must be installed by a qualified technician in accordance with the electrical regulations of the country where the product is installed.
A means of disconnecting all power supply poles must be provided. These disconnects must be incorporated in the fixed wiring.
The EcoPulse negative power terminals are common, and must be grounded as instructions, local codes, and regulations require.
Battery Safety
WARNING: A battery can present a risk of electrical shock or burn from large amounts of short-circuit current, fire, or explosion from vented gases. Observe proper precautions.
WARNING: Risk of Explosion. Proper disposal of batteries is required. Do
not dispose of batteries in fire. Refer to local regulations or codes for requirements.
WARNING: Risk Of Electrical Shock.
NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM DC INPUT, AND MAY BE ENERGIZED WITH HAZARDOUS SOLAR VOLTAGE. UNDER CERTAIN FAULT CONDITIONS, BATTERY COULD BECOME OVER­CHARGED. TEST BETWEEN ALL TERMINALS AND GROUND BEFORE TOUCHING.
• External solar and battery disconnects are required.
• Disconnect all sources of power to the controller before installing or adjusting the EcoPulse.
• There are no fuses or disconnects inside the EcoPulse Do not attempt to repair.
Installation Safety Precautions
• Mount the EcoPulse indoors. Prevent exposure to the elements and do not allow water to enter the controller.
• Install the EcoPulse in a location that prevents casual contact. The EcoPulse heatsink can become very hot during operation.
• Use insulated tools when working with batteries.
• Avoid wearing jewelry during installation.
• The battery bank must be comprised of batteries of same type, make, and age.
• UL/IEC 62109 certified for use in negative ground or floating systems only
• Do not smoke near the battery bank.
• Power connections must remain tight to avoid excessive heating from a loose connection.
5
4
EcoPulse Operator’s ManualImportant Safety Instructions
1.0
CAUTION: When replacing batteries, use properly specified number, sizes, types, and ratings based on application and system design.
WARNING: Do not open or mutilate batteries. Released electrolyte is harmful to skin, and may be toxic.
Servicing of batteries should be performed, or supervised, by personnel knowledgeable about
batteries, and the proper safety precautions.
• Be very careful when working with large lead-acid
batteries. Wear eye protection and have fresh water available in case there is contact with the battery acid.
• Remove watches, rings, jewelry and other metal
objects before working with batteries.
• Wear rubber gloves and boots
• Use tools with insulated handles and avoid placing
tools or metal objects on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Carefully read the battery manufacturer's
instructions before installing / connecting to, or removing batteries from, the EcoPulse.
• Be very careful not to short circuit the cables
connected to the battery.
• Have someone nearby to assist in case of an
accident.
• Explosive battery gases can be present during charging. Be
certain there is enough ventilation to
release the gases.
• Never smoke in the battery area.
• If battery acid comes into contact with the skin,
wash with
soap and water. If the acid contacts the eye, flood with fresh water and get medical attention.
• Be sure the battery electrolyte level is correct before starting charging. Do not attempt to charge a frozen battery.
• Recycle the battery when it is replaced.
General Information
EcoPulse Operator’s Manual
7
6
2.0
2.1 Features
1 - Charging Status / Error LED 2 - Meter Display (optional)
3 - Battery Status / Fault LED Indicators 4 - Solar Positive and Negative Terminals 5 - Remote Temperature Sensor Terminals (RTS)
6 - Battery Positive and Negative Terminals 7 - DIP Switches
8 - Load Positive and Negative Terminals 9 - Heatsink 10 - Meter Directional Buttons 11 - Local Temperature Sensor 12 - Mini-screwdriver for DIP switch adjustments
and RTS screws
2.0
GENERAL INFORMATION
Figure 2.1. EcoPulse Features
1
2
3
7
8
9
4
5
6
10
12
11
2.2 Optional Accessories
The following accessory is available for purchase separately from your authorized Morningstar dealer:
Remote Temperature Sensor (Model: RTS)
The RTS measures battery temperature for accurate temperature compensation, and is recommended when the ambient battery temperature differs from the ambient controller temperature by +/- 5ºC or more. When installed, the EcoPulse will automatically use the RTS for battery temperature compensation.
Installation
EcoPulse Operator’s Manual
9
8
3.0
3.0 INSTALLATION
3.1 General Installation Notes
• Read through the entire installation section first before beginning installation.
• Do not install in locations where water can enter the controller.
• Loose power connections and/or corroded wires may result in resistive connections that melt wire insulation, burn surrounding materials, or even cause fire. Ensure tight connections.
• F
or good service life, extreme temperatures and
marine environments should be avoided.
WARNING: Solar and battery fuses or DC breakers are required in the system. These
protection devices are external to the EcoPulse controller, and must be a maximum of 15 Amps for the EcoPulse-10/M, 30 Amps for the EcoPulse-20/M, and 40 Amps for the EcoPulse-30/M.
WARNING: All breakers must be properly rated for wire ampacity, which may require less than the maximum breaker sizes referenced above.
WARNING: Minimum over-current protection device interrupt ratings must be 2000A
for 12V systems, and 4000A for 24V systems.
NOTE: Carefully observe the LEDs after each connection. The LEDs will indcate proper polarity, and a secure co nnection.
3.2 Configuration
The DIP switch block shown below is used to set the operating parameters for the EcoPulse.
Switch 1: Lighting Control
With DIP 1 ON, a light connected to the load terminals will be ON from dusk-dawn.
Switches 2, 3: System Voltage
Three (3) system voltage configurations are available as shown in the table below:
System Voltage Switch 2 Switch 3
Auto OFF OFF
12 OFF ON 24 ON OFF
NOTE: Before connecting the battery, measure the open-circuit voltage. It must be over 10 Volts tostart the controller. (Cont.)
Installation
EcoPulse Operator’s Manual
11
10
3.0
Switch 7: Battery Equalization
Mode Switch 7
Manual Equalization OFF
Auto Equalization ON
NOTE: Regardless of DIP 7 setting, manual EQ can be initiated using the on-board meter command, "Start Equalize". For non-meter versions, DIP 7 only enables or disables auto equalization - manual EQ
is not available.
Switch 8: Current Switching
Mode Switch 8
PWM switching OFF
Slow switching ON
The default (PWM) switching setting (OFF / down) operates at 300Hz. If load or system noise is an issue, DIP 8 can be set (ON-up) for slow switching at 1Hz. Standard PWM switching is recommended when system noise is not a problem.
3.3 Mounting
Inspect the controller for shipping damage. Mount the EcoPulse to a vertical surface (4-#8 stainless steel self-tapping screws are included). Tighten the mounting screws using care not to crack the plastic case. Do not install directly over an easily combustible surface since the heat sink may get hot under certain operating conditions.
NOTE: The heat sink must be in a vertical position (fins up and down).
Table 3.1. Battery charging settings for each selectable battery type
If the system voltage DIP Settings Switches are set to Auto-detect, battery voltage over 15.5V will be detected as a 24V nominal battery, and the unit will charge accordingly.
The 12/24V auto selection is done only at start-up, and the detected system voltage will never change during operation. It is recommended to set DIPs 2 and 3 to the correct system voltage setting. Only use the default auto-detect setting if the nominal system voltage is not known.
Switches 4, 5, 6: Battery Type Selection
Preset EcoPulse battery charging options are shown in table 3-1 below. All voltage settings listed are for nominal 12 Volt batteries. Multiply the voltage settings by two (2) for 24 Volt systems.
NOTE: These settings are general guidelines for use
at the operator’s discretion. Consult the battery manufacturer for optimal battery charge settings.
DIP
S
witch
S
etting s 4
-5-6
B
attery T
ype
A
bsorp.
S
tage
(
volts)
F
loat
S
tage
(
volts)
E
qualiz e S
tage
(
volts)
A
bsorp. T
ime
(
mins)
E
qualiz e
T
ime
(
mins)
E
qualiz e
T
imeout
(
mins)
E
qualiz e
Equali ze
Equali ze
I
nterva l (
days)
Equali ze Interv al
(days)
Equali ze Interv al
(days)
off-off-off 1 - Sealed* 14.00 13.50
150
off-off-on 2 - Sealed* 14.15 13.50 14.40 150 60 120 28
off-on-off 3 - Sealed* 14.30 13.50 14.60 150 60 120 28
off-on-on 4- AGM/Flooded 14.40 13.50 15.10 180 120 180 28
on-off-off 5 - Flooded 14.60 13.50 15.30 180 120 180 28
on-off-on 6 - Flooded 14.70 13.50 15.40 180 180 240 28
on-on-off 7 - L-16 15.40 13.40 16.00 180 180 240 14
on-on-on 8 - Custom Custom Custom Custom Custom Custom Custom Custom
Custom Custom
Custom
* “Sealed” baery type includes gel and AGM baeries
Custom
LVD (volts)
LVR (volts)
Custom
12.30
13.80
12.10 13.60
11.90
13.40
11.50
13.00
11.70
13.20
11.30
12.80
11.50
12.60
Installation
EcoPulse Operator’s Manual
13
12
3.0
For proper air flow, allow at least 15 cm (6 in) of space above and below the controller, and 50 mm (2 in) at the sides - see Figure 3-1 below. Install in an area protected from direct rain and direct sun.
If the controller is installed in an enclosure, some ventilation is recommended. Do not locate in an enclosure where battery gases can accumulate.
6 in / 150 mm
6 in / 150 mm
2 in /
50 mm
Figure 3-1. Proper Clearances for Passive Cooling
3.4 Wiring
To battery for temperature
sensing
Not used in this illustration
To battery (+)
and (-)
terminals
To load (+)
and (-)
terminals
To properly
sized array
1
5
6
2
3
4
REFER TO FIGURE 3.2 WHEN USING THE FOLLOWING
WIRING INSTRUCTIONS
Figure 3-2. Wiring the EcoPulse
Installation
EcoPulse Operator’s Manual
15
14
3.0
STEP 1: Check Controller Limitations
Verify that the highest temperature compensated solar array open-circuit voltage (Voc), and load current do not exceed the ratings of the EcoPulse version being installed.
STEP 2: Remote Temperature Sensor
WARNING: Risk of Fire.
If no Remote Temperature Sensor (RTS)
is connected, use the EcoPulse within 3m (10ft) of the batteries. Internal Temperature Compensation will be used if the RTS is not connected. Use of the RTS is strongly recommended.
Connect the RTS to the 2-position terminal located (see figure). There is no polarity, so the (+) or (-) can be connected to either screw terminal.
WARNING: Equipment Damage. Never place the temperature sensor inside abattery cell. Both the RTS and the battery will be damaged.
CAUTION: The EcoPulse will use the local temperature sensor for compensation if the RTS is not used.
STEP 3:
Grounding
NOTE: Depending on the country of installation, conductors identified by the color green, or a combination of green / yellow, shall only be used for earthing conductors.
For safety, and effective lightning protection, it is recommended, and may be locally required, that the negative conductor of the charging system be properly grounded. Use only one system earth
ground. For conductor sizing requirements, refer to the U.S. National Electrical Code, or applicable local regulations or code.
STEP 4: Battery Connections
(at battery
OR solar side,
but NOT both)
System Ground
6 in (150 mm)
Max.
Battery (-)
Battery (+)
+
-
12V or 24V
Battery
Fuse or breaker sizing
based on required wire
ampacity
Installation
EcoPulse Operator’s Manual
17
16
3.0
Be sure that DIP switches 2 and 3 are set for 12 or 24V, as described in Section 3.2.
NOTE: Before connecting the battery, measure the open-circuit voltage. It must be over 10Volts to start the controller.
With the battery disconnect open, connect the battery (+) and (-) wires from the battery to controller. DO NOT CLOSE THE
DISCONNECT AT THIS TIME.
STEP 5: Solar Connections
WARNING: Shock Hazard.
The solar PV array can produce open- circuit voltages of up to 60 Vdc when in sunlight, and this DC voltage is supplied to the Power Conversion Equipment (PCE). Verify that the solar input breaker or disconnect has been opened (disconnected) before installing the system wires.
SOLAR (+)
SOLAR (-)
(+)
(
-)
NOTE: For design purposes, array should be nominal 12V for 12V battery, and nominal 24V for 24V battery. Do not exceed 60Voc
Solar
Disconnect
Fuse or breaker sizing
based on required wire
ampacity
With the solar disconnect open, connect the solar (PV) array wires to the EcoPulse solar terminals. Use caution, since the solar array will produce current whenever in sunlight.
DO NOT CLOSE THE
DISCONNECT AT THIS TIME. STEP 6: Load Connections
LOAD (+)
LOAD (-)
Fuse or breaker sizing
based on required wire
ampacity
Turn the loads off, and connect the load wires to the load terminals. DO NOT CLOSE THE FUSE OR BREAKER AT THIS TIME.
STEP 7: Power-Up and Verify System Operation Close the battery disconnect to start the processor,
and activate the controller’s protections. Watch the charging status, and then the three battery state­of-charge (SOC) LEDs blink in sequence (G-Y-R), confirming proper start-up. If they do not light, check the battery polarity (+/–) and battery voltage.
Installation
EcoPulse Operator’s Manual
19
18
3.0
The green, yellow or red LED will light depending on the battery state-of-charge (SOC). Confirm that one of these LEDs is on before going to the next step.
Close the solar disconnect. If the solar input is connected while in sunlight, the charging LED indicator will light. Confirm proper connection by observing the charging LED.
Insert the load fuse, or close the breaker, and turn the load on to confirm a proper connection.
STEP 8: To Power-Down
WARNING: Risk of Damage. ONLY disconnect the battery from the EcoPulse AFTER the solar input has been disconnected. Damage to the controller may result if the battery is removed while the EcoPulse is charging.
• To prevent damage, power-down must be done in the reverse order as power-up.
3.5 Custom Settings
3.5.1 Adjusting the Meter Display
The display setting options are adjustable by using the directional keys to locate and edit a desired display setting.
3.5.2 Directional Key Use and Operation / Navigating the Meter Map
A lit key indicates a valid direction in the meter map. The current location is indicated on the display with a column heading, and a bold descriptor.
3.5.3 Using the Meter Display to Program Charging Set-points and Load Control
From the top level monitoring screens, scroll down to the Main Menu - “Custom Programming” - screen. Select the desired category, and edit the variable or setting as instructed in the meter display.
Operation
EcoPulse Operator’s Manual
21
20
4.0
4.0 OPERATION
4.1 Battery Charging Information
4-Stage Charging
The EcoPulse has a 4-stage battery charging algorithm for rapid, efficient, and safe battery charging. Figure 4-1 below, shows the sequence of stages.
Figure 4.1. EcoPulse Charging Algorithm
Bulk Charge Stage
During Bulk charging, the battery is not at 100% state of charge and battery voltage has not yet charged to the Absorption voltage set-point. The controller will deliver 100% of available solar power to recharge the battery.
NIGHT
NIGHT
BULK
CHARGE
ABSORPTION
FLOAT
EQUALIZE
VOLTAGE
TIME
Absorption Stage
When the battery has recharged to the Absorption voltage set-point, constant voltage regulation is used to maintain battery voltage at the Absorption set-point.
Float Stage
After the battery is fully charged in the Absorption stage, the EcoPulse reduces the battery voltage to the Float voltage set-point. The purpose of float is to protect the battery from long-term overcharge.
Equalization Stage
WARNING: Risk of Explosion. Equalizing vented batteries produces explosive gases. The battery bank must be properly ventilated.
CAUTION: Equipment Damage.
Equalization increases the battery voltage to levels that may damage sensitive DC loads. Verify all system loads are rated for the temperature compensated Equalize voltage before beginning an Equalization charge.
Operation
EcoPulse Operator’s Manual
23
22
4.0
CAUTION: Equipment Damage.
Excessive over-charging and gasing too vigorously can damage the battery plates and cause shedding of active material from the plates. An equalization that is too high, or too long, can be damaging. Review the requirements for the particular battery being used in your system.
Equalization (EQ) charging raises the battery voltage above the standard absorption voltage so that the electrolyte gases.
4.2 Load Information
CAUTION: Do not wire an AC inverter of any size to the load terminals of the EcoPulse
- damage to the load control circuit may result. Wire inverters directly to the battery or battery
bank.
4.3 LED Indications
KEY:
G = green G - Y - R = flashing sequentially Y = yellow G / Y = flashing together R = red G / Y - R = G and Y flashing together,
alternating with R flash
4.3.1 Power-up
Normal power-up: Status LED flashes G, then SOC LEDS flash G - Y - R, then SOC LEDs indicate battery charge status with a single battery status LED.
Failed bootload: Status LED flashes G, then SOC LEDS flash G - Y and stop on solid Y.
4.3.2 Status LED
Table 4.1 below lists the Status LED indications.
Color Indication Operating State
None Off (with heartbeat) Night
Green
On Solid
( with heartbeat)
Charging
Red Flashing Error
Red
On Solid
( with heartbeat )
Critical Error
Table 4.1. Status LED Definitions
4.3.3 State-of-Charge LEDs
Battery SOC LED Indications are shown in Table 4.2 below:
Condition Indication
Absorption G flash - every sec Float
G flash - every 2 secs
Equalize
G flash - 2 / sec
Low voltage disconnect warning
R flash - every sec
Low voltage disconnect
R solid
Table 4.2. Battery SOC LED Indications
Operation
EcoPulse Operator’s Manual
25
24
4.0
4.4 Protections, Faults and Alarms
4.4.1 Protections
Solar, battery and load transient surges
Power-up against any active faults Reverse Polarity - battery and array
Solar Short-Circuit Solar High Voltage Disconnect High Heatsink Temperature - Load disconnect Load Short-Circuit Load Over-Current
Heatsink Temperature Limit RTS Terminals
Battery Sense Terminals
4.4.2 LED Fault Indications Solar Over-current
Error status LED: Flashing red. Battery status LEDs: R/Y-G sequencing
Load Over-current
Error Status LED: Flashing red. Battery status LEDs: R/Y-G sequencing
Solar Short Circuit
Charging Status LED: OFF
Battery Reverse Polarity
No LED indication, the unit is not powered
Load Short Circuit
Error status LED: Flashing red. Battery status LEDs: R/G-Y sequencing
Solar High Voltage Disconnect
Charging Status LED: R flashing
Remote Temperature Sensor (RTS)
Error status LED: Flashing red. Battery status LEDs: R/Y - G/Y sequencing
Battery / Load High Voltage disconnect (HVD)
Error status LED: Flashing red. Battery status LEDs: R-G sequencing
High Heatsink Temperature
Error status LED: Flashing red. Battery status LEDs: R-Y sequencing
Settings (DIP) Switch Changed
Error status LED: Flashing red. Battery status LEDs: R-Y-G sequencing
Custom Settings Edit Error status LED: Flashing red. Battery status LEDs:
R-Y-G sequencing
Internal Power Supply Out of Range
Error status LED: Solid red. Battery status LEDs: R-Y-G sequencing. Contact your Morningstar dealer for service
4.4.3 Alarms
High Temperature Current Limit RTS Open
Heatsink Temperature Sensor Open or Shorted Battery Sense Out of Range, or Disconnected Uncalibrated
Operation
EcoPulse Operator’s Manual
27
26
4.0
4.5 Inspection and Maintenance
Table 4.3 below lists the recommended maintenance schedule to keep your EcoPulse performing optimally.
Schedule Maintenance Items
2 weeks after installation
Re-tighten power terminal connections to specified torque values.
3 months after installation
Re-tighten power terminal connections to specified torque values.
Monthly, or After Each
Equalization
Inspect the battery bank. Look for cracked or bulging cases, and corroded terminals.
For wet cell -flooded type batteries, make sure the water level is correct. Wet cell water levels should be
check monthly according to the manufacturer’s recommendations.
Table 4.3. Maintenance Schedule (Cont.)
Schedule Maintenance Items
Monthly, or After Each
Equalization
Inspect the battery bank. Look for cracked or bulging cases, and corroded terminals.
For wet cell (flooded type) batteries, make sure the water level is correct. Wet cell water levels should be checked monthly or according to the manufacturer’s recommendations.
Annually
Clean the heatsink fins with aclean, dry rag.
Inspect all wiring for damage or fraying.
Inspect for nesting insects.
Re-tighten all wiring terminal connections to specified torque values.
Inspect the system earth grounding for all components. Verify all grounding conductors are appropriately secured to earth ground.
Table 4.3. Maintenance Schedule (End)
EcoPulse Operator’s Manual
29
6.0
Warranty and Policies28
LIMITED WARRANTY Morningstar Solar Controllers and Inverters
The EcoPulse is warrantied to be free from defects in material and workmanship for a period of TWO (2) years from the date of shipment to the original end user. Morningstar will, at its option, repair or replace any such defective units.
WARRANTY EXCLUSIONS AND LIMITATIONS:
This warranty does not apply under the following conditions:
Damage by accident, negligence, abuse or improper use PV or load currents exceeding the ratings of the product Unauthorized product modification or attempted repair Damage occurring during shipment Damage results from acts of nature such as lightning and weather extremes
THE WARRANTY AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE AND IN LIEU OF ALL OTHERS, EXPRESS OR IMPLIED. MORNINGSTAR SPECIFICALLY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. NO MORNINGSTAR DISTRIBUTOR, AGENT OR EMPLOYEE IS AUTHORIZED TO MAKE ANY MODIFICATION OR EXTENSION TO THIS WARRANTY.
MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO LOST PROFITS, DOWN-TIME, GOODWILL OR DAMAGE TO EQUIPMENT
OR PROPERTY.
5.0 WARRANTY
R17-8/16
EC-10/M EC-20/M EC-30/M
Electrical:
Nominal battery voltage All: 12 or 24 Volts Battery voltage range All: 10-35 Volts Max. Battery Current 10A 20A 30A Max. PV open-circuit voltage All: 60 Volts Load Current Rating 10A 20A 30A Self Consumption <15mA (non-meter) <20mA (meter)
Mechanical:
Dimensions: 6.01(W) x 4.14(L) x 2.17(D) in. 153(W) x105(L) x 55(D) mm
Weight (lb/kg): Non-metered: 0.75 / 0.34 1.1 / 0.48 Metered: 0.90 / 0.40 1.2 / 0.54
Wire Size Range: Power Terminals 2.5 - 16 mm2 / #14 - 6 AWG Maximum Torque 35 in-lb
Battery/Temp. Sense 0.25 - 1.0 mm
2
/ #24 - 16 AWG
Enclosure IP20, Type 1
Battery Charging:
4-Stage Charging: Bulk, Absorption, Float, Equalize Temperature compensation Coefficient: -30mV / ºC / 12 Volt Temperature compensated set-points: Absorption, Float, Equalize, HVD
Environmental:
Maximum Operating Altitude 2000 meters Operating Temperature -40ºC to +45ºC Storage Temperature -40ºC to +80ºC Humidity 100% n.c.
Tropicalization Conformally coated PCBs; Marine-rated terminals
6.0 TECHNICAL SPECIFICATIONS
Certifications
30
• EN 61000-6-2: 2005/AC:2005 EMC Immunity
• EN 61000-6-4: 2007 +A1:2011 EMC Emissions
• Industry Canada: CAN ICES-3 (B)/NMB-3(B)
• IEC 62109-1: 2010 Safety of Power Converters in PV Systems (TUV Pending)*
• JAS-ANZ Certification (TUV-Australia Pending)*
• Restriction of Hazardous Substances Directive 2011/65/EU (RoHS 2)
• Electromagnetic Compatibility Directive 2004/108/EC
• FCC (Title 47 of CFR), Part 15 Subpart B Class B digital device
EcoPulseTM and MeterBus
TM
are trademarks of
Morningstar Corporation MODBUSTM and MODBUS TCP/IPTM are trademarks of
Modbus IDA. www.modbus-ida.org
© 2017 Morningstar Corporation. All rights reserved.
* For current certifications, please go to: support.morningstarcorp.com, and use the, “What Are You Looking For?” menu to choose, "Corporate Documents". Then look for the product Certificate of Conformity.
MS-001990 v2.3
TUVRheinland
®
CERTIFIED
APPENDIX - CERTIFICATIONS
REACH
ALL
COMPONENTS
COMPLIANT
Registration, Evaluation and
Authorization of Chemicals
www.morningstarcorp.com
EcoPulse
TM
Le présent document est un manuel abrégé. Pour consulter
lemanuel intégral du produit, veuillez vous référer à la version
papier en anglais ou à la version électronique sur:
www.morningstarcorp.com
Dieses Handbuch wurde gekürzt. Das vollständige
Produkthandbuch finden Sie in der gedruckten englischen
Version des Handbuchs oder in elektronischer Version unter:
www.morningstarcorp.com
Este es un manual resumido. Para consultar el manual completo
del producto, consulte la versión impresa en inglés del manual
ola versión que se encuentra en: www.morningstarcorp.com
Régulateur de charge solaire
Solarladesystem-Regler
Controlador del sistema de carga solar
Manuel de l’utilisateur...32
Bedienerhandbuch.........63
Manual del operador......94
EC-10 EC-10M EC-20 EC-20M EC-30 EC-30M
33
Manuel de l’utilisateur de l’EcoPulse
1.0
32
6.30 160
4.33 110
5.51 140
3.54 90
2.04 52
DIMENSIONS [pouces (millimètres)]
SYNTHÈSE DES SPÉCIFICATIONS
10/M 20/M 30/M
Tension nominale de la batterie 12/24V 12/24V 12/24V
Tension maximale en circuit
ouvert du système PV*
60V 60V 60V
Courant maximal de charge
de la batterie
10A 20A 30A
Courant de charge nominal 10A 20A 30A
* La tension du générateur ne doit jamais excéder cette limite.
CONSERVEZ CES INSTRUCTIONS.
Le présent manuel contient des consignes de sécurité ainsi que des instructions d’installation, d’utilisation et d’entretien importantes concernant le régulateur de charge solaire EcoPulse.
Les symboles suivants sont utilisés tout au long du présent manuel pour signaler les situations potentiellement dangereuses ou souligner les consignes de sécurité importantes:
ATTENTION: signale une situation potentiellement dangereuse. Faites preuve d’une extrême prudence pour effectuer cette tâche.
MISE EN GARDE: signale une procédure essentielle pour l’utilisation sûre et adéquate du régulateur.
REMARQUE: signale une procédure ou une fonction importante pour l’utilisation sûre et adéquate du régulateur.
Informations relatives à la sécurité
• Veuillez lire l’intégralité des instructions et des mises en garde contenues dans le présent manuel avant de procéder à l’installation.
• L’EcoPulse ne contient aucune pièce susceptible d’être réparée par l’utilisateur. N’essayez pas de le démonter oude le réparer.
1.0 CONSIGNES DE SÉCURITÉ IMPORTANTES
FRANÇAIS
35
34
Manuel de l’utilisateur de l’EcoPulse
Consignes de sécurité importantes
1.0
• Utilisez des conducteurs et des interrupteurs de circuit adaptés.
• Ce régulateur de charge doit être raccordé exclusivement à des circuits DC. Ces raccordements DC sont identifiés àl’aide du symbole suivant:
Symbole du courant continu
Le régulateur EcoPulse doit être installé par un technicien qualifié conformément à la réglementation relative aux équipements électriques en vigueur dans le pays d’installation.
Un dispositif de sectionnement doit être mis en place pour l’ensemble des pôles d’alimentation. Ce dispositif doit être incorporé au câblage fixe.
Les bornes d’alimentation négatives de l’EcoPulse sont ordinaires et doivent être mises à la terre conformément aux instructions, aux codes locaux et à la réglementation.
Consignes de sécurité relatives à la batterie
ATTENTION : les batteries peuvent présenter un risque d’électrocution ou de brûlure en raison des quantités importantes de courant de court-circuit ainsi qu’un risque d’incendie ou d’explosion lié aux gaz libérés. Veuillez prendre les précautions requises.
ATTENTION: risque d’explosion. Veillez à mettre au rebut les batteries de manière
appropriée. Ne jetez pas les batteries au feu. Veuillez vous référer à la réglementation ou aux codes locaux pour connaître les exigences en matière de mise aurebut.
ATTENTION: risque d’électrocution.
AUCUNE BORNE ACCESSOIRE OU D’ALIMENTATION N’EST ISOLÉE ÉLECTRIQUEMENT DE L’ENTRÉE DC. ELLES PEUVENT DONC ÊTRE SOUMISES À UNE TENSION SOLAIRE DANGEREUSE. DANS CERTAINS CAS DE DÉFAILLANCE, LA BATTERIE POURRAIT SUBIR UNE SURCHARGE. EFFECTUEZ UN TEST ENTRE TOUTES LES BORNES ET LA MISE À LA TERRE AVANT TOUTE MANIPULATION.
• L’utilisation d’un sectionneur solaire et d’un sectionneur de batterie externes est requise.
• Débranchez toutes les sources d’alimentation du régulateur avant d’installer ou de régler l’EcoPulse.
• L’EcoPulse ne contient pas de fusibles ni de sectionneurs. N’essayez pas de le réparer.
Consignes de sécurité lors de l’installation
• Montez l’EcoPulse à l’intérieur. Installez-le à l’abri des éléments et des infiltrations d’eau.
• Installez l’EcoPulse à l’abri de tout contact accidentel. Le dissipateur thermique de l’EcoPulse peut devenir très chaud lors du fonctionnement.
• Utilisez des outils isolés pour travailler sur les batteries.
• Évitez de porter des bijoux lors de l’installation.
• Le banc de batteries doit être composé de batteries du même type, de la même marque et du même âge.
• Certifié UL/CEI62109 pour utilisation avec mise à la terre négative et systèmes flottants uniquement.
• Ne pas fumer à proximité du banc de batteries.
• Les branchements électriques doivent demeurer serrés afin d’éviter toute chaleur excessive due à un branchement lâche.
FRANÇAIS
Loading...
+ 45 hidden pages