Figure 1: Front View (Calisto 2 model shown) ................................................................................................................................... 6
Figure 16: Adapting the Transformer Valve ..................................................................................................................................... 29
Figure 17: Attaching the Copper Tubing to the INLET Port ....................................................................................................... 30
Figure 18: Attaching the Copper Tubing to the OUTLET Port ................................................................................................... 31
Figure 19: Monitor with Both Valves Closed .................................................................................................................................... 32
Figure 21: Connecting the Quick Connect Oil Sampling Tube to the monitor ......................................................................... 33
Figure 22: Flushing the Oil RETURN Tube ..................................................................................................................................... 34
Figure 23: Flushing the Oil SUPPLY Tube ....................................................................................................................................... 35
Figure 24: Disconnecting the Quick Connect Oil Sampling Tube from the Monitor .............................................................. 35
Figure 25: Monitor with both Valves Open ...................................................................................................................................... 36
Figure 27: 6-Feet Long A/B Type USB Cable.................................................................................................................................. 43
Figure 28: Calisto Access Status Tab with an Error Code .............................................................................................................. 47
Figure 37: Calisto Access Graphic Plotting Panel – CO for Calisto 2 only ................................................................................. 66
Figure 39: Quick Connect Oil Sampling Tube Connected to a 30cc Syringe ............................................................................. 67
Figure 40: 30cc Syringe Connected to the Monitor SAMPLING Port ........................................................................................ 67
II
DISCLAIMER
The Calisto/Calisto 2 IED (Intelligent Electronic Device) has been carefully designed
and engineered to provide maximum accuracy while continuously monitoring the
concentration of dissolved gases in transformer oil.
It is assumed by Morgan Schaffer that users will read this Installation & Operation Manual
and will understand the operation of the instrument prior to installation of the IED.
All results obtained using the Calisto/Calisto 2 monitor are based upon material and
equipment under the responsibility of the client. Morgan Schaffer assumes no
responsibility and makes no warranty or representation, expressed or implied, as to the
condition, productivity or proper operation of any equipment or other property for
which the Calisto/Calisto 2 monitor may be used or relied upon for any reason
whatsoever.
The Calisto/Calisto 2 monitor is designed to be permanently installed on critical transformers for
continuous measurement of dissolved fault gases in dielectric insulating fluids. Calisto and Calisto 2
monitor hydrogen and moisture. Hydrogen is a reliable indicator of a recent or existing fault, as all
fault types produce it to a greater or lesser extent.
Calisto 2 also monitors carbon monoxide. Carbon monoxide and moisture levels may highlight
undesirable deterioration of the paper/oil system, and conditions conducive to such deterioration.
Calisto 2 provides the key measurements required to monitor the health of the insulation system, in
order that informed service decisions may be taken, and major transformer problems may be
avoided.
III
NOTICE
This manual applies to both Calisto and Calisto 2 monitors. Always consider which one
you are working with. Some sections of this manual apply to Calisto 2 only and are
expressly marked “for Calisto 2 only”. If not stated, the section applies to both Calisto
and Calisto 2 monitors.
An electronic version of this manual is available on the Calisto/Calisto 2 CD supplied with your
monitor and at Morgan Schaffer’s web site www.morganschaffer.com. To access this manual on the
website, click Instruments under Products. Then click either Calisto or Calisto 2 and then Downloads under the Menu (on the right). In order to use the electronic manual efficiently,
proceed as follows after opening Acrobat Reader®:
1. Click Window, Show Bookmarks.
2. Click View, Fit Width.
3. Click View, Continuous.
When necessary, use the Zoom command to view drawing or picture details.
This Installation & Operation Manual provides the required information for installing and setting up a
Calisto monitor version C76-00000 or a Calisto 2 monitor version C85-00000 for operation. All
types of signals, alarm relays and communications are also covered. Users should visit Morgan
Schaffer’s website regularly at www.morganschaffer.com or contact us directly for documentation,
firmware and software updates.
1
A 3-year warranty covers each new Calisto/Calisto 2 IED. In order to activate this warranty, the user
must fill out the Warranty Registration Form located in the documentation included with each
instrument and fax it to Morgan Schaffer at 001.514.739.0434. An electronic version of this form is
also available on the Calisto/Calisto 2 CD and can be e-mailed to support@morganschaffer.com
once it has been filled out. Upon receiving the registration form, Morgan Schaffer will confirm the
validity period of the warranty. End users may also visit our website and electronically register their
monitor. In the main menu, under Products, click Instruments and then Calisto or Calisto 2. On
the right side of the menu, click Registration. The warranty can be activated at any time within the
6-month period following the shipping date from Morgan Schaffer. Additional information must be
provided by the end-user if registration of the warranty is performed after the activation period.
Extended warranties are available from Morgan Schaffer. Extended warranty confirmations will be
provided at the time of their purchase or when the standard Warranty Registration Form is received.
2
Precise, accurate and continuous hydrogen readings allow detection of transformer incipient
faults at their earliest stage. Hydrogen is a reliable indicator of a recent or existing fault as all fault
types produce it to a greater or lesser extent. Hydrogen’s low solubility in oil and high diffusibility
facilitate its early detection at low concentrations thus providing the earliest warning of the presence
of a fault.
Precise, accurate and continuous moisture readings allow correlations to be established
between moisture in oil and transformer load. They also provide key information on long term
trends of the insulation conditions. In combination with polar products and acids, dissolved water
can significantly affect the dielectric properties of insulating fluids and materials. Monitoring
dissolved water over an extended period of time and undertaking proper action following sudden or
abnormal increases in dissolved water content extends the life expectancy, performance and
serviceability of oil-filled equipment.
Additional continuous measurement of dissolved carbon monoxide in oil differentiates the
Calisto 2 from the Calisto monitor. Carbon monoxide readings can help transformer specialists
assess the remaining life of transformers. Carbon monoxide is often generated in large quantities
when transformer cellulose overheats.
Built-in oil circulation and flow monitoring assure reliability of the readings. Effective on-line
monitoring of dissolved fault gases requires that sensors be in continuous contact with
representative oil from the transformer, in order to react quickly to variations in gas concentrations.
To guarantee accuracy and fast response to developing faults, Calisto/Calisto 2 features an oil
circulation system based on an anti-cavitation reciprocating pump with an outstanding reliability
record. In addition, an integrated oil flow monitor, also designed for maintenance-free operation and
long-term reliability, provides a low-flow warning if the flow drops below a pre-set threshold, as may
occur if a valve is inadvertently closed.
Continuous enclosure and oil conditioning is essential for accurate readings. The most important
source of interference on dissolved gas sensors comes from environmental temperature variations.
Varying ambient and oil temperatures significantly affect the solubility and diffusion rates of
dissolved fault gases, leading to baseline drift and signal variation. This often limits the ability of
IEDs to monitor low levels of fault gases. Calisto/Calisto 2 features passive and thermo-electric
temperature conditioning modules which continuously maintain both enclosure and oil temperatures
constant to pre-set levels. This results in unequalled sensitivity, repeatability and long-term stability,
independent of the environment where the instrument is installed.
Reliable gas extraction and detection technologies are both crucial to produce reliable readings.
As the oil within the Calisto/Calisto 2 is conditioned to a precisely regulated temperature, it is
pumped past a bundle of PTFE capillary tubes which together form the gas probe. Dissolved gases
permeate through the walls of the tubing to form a representative gas sample within the probe.
Gases then diffuse along the capillary tubes to form a gas sample inside the detection cell. Any
change in gas concentrations in the oil will modify the equilibrium within the probe and the cell.
The Calisto/Calisto 2 detection cell uses an enhanced version of Morgan Schaffer’s proprietary
high-accuracy thermal conductivity detection (TCD) technology, to provide accurate gas
3
measurements, without any field calibration, for the lifetime of the instrument. The Calisto and
Calisto 2 detection cells take validated measurements for hydrogen and carbon monoxide (Calisto 2
only) every three hours. Validated measurements are continuously zeroed to guarantee long-term
stability and low-level detection accuracy. A continuous measurement of the hydrogen concentration
is also performed for both monitors, to indicate any variation in hydrogen concentration which may
occur between validated readings.
Vacuum tolerance is made possible because of the intrinsic properties of the capillary tubing used
to form the gas sample and because the oil circulating and conditioning systems inside the
Calisto/Calisto 2 can both sustain vacuum. As a result, no action is required to protect the monitor
if the transformer is put under vacuum for degassing purposes.
Precise moisture measurement is achieved using a capacitive thin-film sensor immersed directly
in circulating oil to continuously measure dissolved moisture. Moisture content can be reported in
parts per million (ppm), %RS at 25oC (77°F) or %RS at a specific transformer temperature using the
Expert Series Calisto Precision Oil Temperature Probe.
4
The complete technical specifications of the two instruments are included in Appendix I of this
manual. Prior to installing or commissioning the IED, users should understand the basic principles
of operation of the instrument and identify the main components of the built-in systems. Both
Calisto and Calisto 2 monitors feature substantially the same internal components and user interface
hardware. The detection cells are calibrated differently and are specific to each monitor type.
The instrument is usually installed permanently on a transformer or a pedestal-style mounting stand.
The system requires that oil from the transformer be brought to the IED and then returned to the
transformer. To accomplish this, Calisto/Calisto 2 features separate oil inlet and outlet ports. Oil
circulation is achieved with the use of a small reciprocating pump (nominal flow of 60 ml/min. or
0.95 US gal/hr) located inside the instrument.
Figure 1 on the following page shows the general front view of a Calisto/Calisto 2 which features a
vacuum fluorescent display (ultra bright at day and night) and the three-button display interface.
Figure 2 illustrates the main features visible on the bottom view of a Calisto/Calisto 2, including the
oil inlet/outlet ports and the quick-connect oil sampling port.
Figure 3 illustrates the main components inside a Calisto/Calisto 2.
Calisto/Calisto 2 IED controls the oil temperature and the air temperature inside the enclosure
using heat exchangers and thermo-electric elements. A waterproof long-life cooling fan, located at
the bottom of the enclosure, provides the primary heat removal from the system. A small fan,
located inside the enclosure, provides temperature stability to the electronics and the gas
measurement cell.
When the system is in operation, date and time stamped measurements are stored in the
instrument’s memory at a factory set storage frequency of one reading every 3 hours. This data can
be retrieved and viewed graphically using Morgan Schaffer’s Calisto Access software. Data can also
be viewed at any time on the door display, which provides the most recent validated hydrogen and
carbon monoxide (Calisto 2 only) measurements, in addition to the real-time dissolved moisture
measurements. Other instrument operation and manufacturing parameters can be viewed on the
display. Section 3.3 describes the operation of the display buttons in detail.
5
Figure 1: Front View (Calisto 2 model shown)
Figure 2: Calisto/Calisto 2 - Bottom View
6
Figure 3: Calisto/Calisto 2 - Main Internal Components
7
QTY.
DESCRIPTION
1
Standard Calisto/Calisto 2 monitor
1
6-foot male A/B USB 2.0 cable for local connection
1
Calisto Access interface software CD-ROM
1
Quick Connect Oil Sampling Tube
4
Stainless steel vibration mount assembly
2
Copper tubing – 3/8 O.D. × 25 ft (7.6 m)
1
Thermal cut-off fuse (spare)
2
Brass elbow – ½ NPT (M) – 3/8" Tube
4
Brass nut – 3/8 Tube
4
One-lokTM brass ferrule – 3/8 Tube
1
Shipping box
1
Installation & Operation Manual (softcopy, also available on our website)
1
Factory Test Certificate
1
Declaration of Conformity
8
Calisto Mounting Stand
For a fast and easy installation, Morgan Schaffer has designed a pedestal-style
mounting stand for Calisto/Calisto 2. This stand is highly corrosion resistant
and includes all required hardware to perform the installation in less than one
hour.
Precision Oil Temperature Probe – Standard Edition
The Precision Oil Temperature Probe was specifically developed to meet
client demands to report the %RS in oil at a specific transformer temperature
in a truly accurate and reliable way. The 610 mm (24 in.) temperature probe is
customized at the moment of the installation of the monitor and does not
require any specifications from the client at the time of the order. Refer to
Appendix I for the complete technical specifications.
Stainless Steel Braided Flex Lines
The Stainless Steel Braided Flex Lines are a popular customizable option for
the Calisto/Calisto 2 configuration that has the advantage of being highly
resistant to corrosion and easy to install. Refer to Appendix I for the
complete technical specifications.
Ethernet Outdoor Connectivity Kit
Calisto/Calisto 2 features an Ethernet port isolated to 1500 V. The Ethernet
Outdoor Connectivity Kit includes all the necessary parts to bring a
communication cable from the monitor to a control box switch/hub in an
easy and reliable way. Refer to Appendix I for the complete technical
specifications.
9
Other available options:
Insulation kit (for -50 to 55°C [-58 to 131°F] operation)
IEC 61850 Ethernet communication kit
900 MHz radio modem over RS-485
2.4 GHz radio modem over RS-485
Quick-connect dust plug
Calisto MultiTrack software
Extended warranty up to 5 years
On-site commissioning assistance
10
WARNING
IED’s should only be installed by qualified personnel familiar with their operation and
associated hazards. Improper electrical or hydraulic circuitry may result in personal
injury and/or instrument damage and may void the warranty.
Two persons are recommended for lifting the equipment.
NOTICE
Calisto/Calisto 2 is designed for industrial use and shall not be connected to the public
low-voltage distribution system.
Section 2.0 Installation applies to both Calisto and Calisto 2 monitors.
CAUTION
All IEDs are filled with new transformer mineral oil when shipped. DO NOT OPEN INLET AND OUTLET VALVES PRIOR TO INSTALLATION.
The following steps must be undertaken to properly install a Calisto/Calisto 2 IED on a
transformer:
Mounting of the monitor on a transformer or structure
Electrical connections: power, alarms, signals and communication
Attachment of oil circulation lines between transformer valves and IED
Flushing of the oil lines with oil to remove air
The following tools are usually required for a standard installation:
Pipe cutter (for copper oil lines only)
Pipe wrench, 5/8 and 11/16 wrenches (or adjustable wrenches)
Knife
Small screwdriver (flat)
Large screwdriver (flat)
Installation kit for Calisto/Calisto 2
11
This section will provide guidelines on where to install the monitor on the transformer. Two
different scenarios will be discussed. One will be based on the Calisto/Calisto 2 being shipped
directly from a new transformer manufacturer or transformer rewinder (Factory Installed) and the
other is based on a field retrofit.
Calisto/Calisto 2 must be solidly bolted to a suitable support approximately 1.2 m (4 ft) above
ground level to allow easy access to the internal oil sampling valves. A minimum of 60 cm (24 in.) is
required for air circulation under the unit.
The mounting structure should be positioned to protect the monitor from extreme vibrations. A
typical location would be the side of the transformer control box. Vibration mounts (4) are provided
with each monitor and should be used to provide the instrument with additional protection against
possible vibrations. If the monitor is field installed, the use of a post bolted to the concrete base of
the transformer is an ideal configuration. The Calisto/Calisto 2 mounting hole locations are shown
in Figure 4. Standard dimensions are in inches and dimensions in brackets are in millimetres.
Figure 4 : Calisto/Calisto 2 - Mounting Diagram
12
NOTICE
The IED is designed to be installed vertically (as shown in this manual). The unit
MUST NOT BE MOUNTED IN ANY OTHER ORIENTATION.
Electronic mounting and installation drawings are included in the CD provided.
In most cases the factory will install the monitor on Unistrut® brackets that are welded to the main
transformer tank. Calisto/Calisto 2 is generally installed at eye level and two additional ½ inch valves
are welded directly to the main tank near the monitor for the oil supply and return.
In most cases the top oil fill valve and the main drain valve are located on the same side of the main
tank. It is best to install the monitor near the bottom drain valve. Of course this location will vary as
needed based on the oil line requirements discussed later in this section.
Typically Unistrut® brackets are used to make a base for mounting the Calisto/Calisto 2. The
mounting structure can be designed to clamp on to various components of the transformer tank, on
the main control cabinet, on a post installed in the ground or on a concrete base. A Morgan Schaffer
Calisto Mounting Stand is available as an optional accessory. Contact Morgan Schaffer for more
information.
A complete Installation Manual is included with the Morgan Schaffer Calisto Mounting Stand
accessories. Refer to this manual when mounting a Calisto/Calisto 2 on the stand.
13
WARNING
Electrical shock hazard. Only persons with electrical safety training and certification
should install the equipment or open the enclosure once the equipment has been
installed.
NOTICE
It is recommended to select a shielded cable suitable for outdoor use for all
communication and signal wiring. For any configuration, the installer must follow these
guidelines:
Minimize the length of cable from the hub to the interface board (avoid loops).
Protect against mechanical stress on wires and connectors attached to the
interface board.
The following section explains in detail the monitor interface board and how to connect the mains
power, safety ground, alarm relays, analog signals, and communication cables to a Calisto/Calisto 2
monitor.
The Calisto/Calisto 2 monitor features a 4-hub detachable electrical entry plate made of stainless
steel. All entry holes are 22 mm (7/8 in.) in diameter and can accept most ½ in. entry hub fittings.
Four waterproof rubber entry hole plugs are provided with the instrument to cover unused holes.
Opening the Calisto/Calisto 2 enclosure door will provide access to the monitor interface board.
Figure 5 shows the main components of the Calisto/Calisto 2 interface board. All connections to
the monitor are made using this board.
Items 1, 12 and 11 are respectively the mains power connectors, the thermal cut-off fuse and the
over-current fuse.
Items 10 and 2 are the programmable NO/NC dry-contact relays with their respective connectors.
Items 4, 5, 6 and 7 are respectively the RS-485, RS-232, 4-20 mA analog input and 4-20 mA analog
output connectors.
14
Calisto Interface Board Components:
12. Thermal cut-off fuse terminals
Items 8, 9 and 3 are respectively the USB type B port, the Ethernet port and the Ethernet shield
earth jumper. The USB port is for local connection only, used during servicing or maintenance of
the instrument.
1.Main supply terminals
2.Programmable relays with activity LEDs (5)
3.Ethernet shield earth jumper
4.RS-485 communication port
5.RS-232 communication port
6.4-20mA analog input terminals
7.4-20mA analog output terminals (3rd channel is for
Calisto 2 only)
Install the protective earth conductor to the earth ground terminal before making any
other connections. When uninstalling the unit, remove all other connections before
removing the protective earth connection.
Protective earth connection is essential to guarantee client safety. To install the protective earth
conductor to the earth ground terminal, secure the protective earth conductor tightly using the two
screw terminals provided. It is the client’s responsibility to ensure the integrity of the ground cable
and client-side ground connection.
The Calisto/Calisto 2 monitor is designed to accept any supply voltage from 100 to 240 VAC with
frequencies in the range of 50 to 60 Hz. Mains power connections are made to connector 1 (neutral)
and connector 2 (line) using either solid or stranded conductors (See Figure 6). Connections must be
made in accordance with the connector ratings provided in the table below.
Figure 6: Calisto/Calisto 2 - Power Connections
To connect the mains power, loosen completely each screw terminal, insert the conductor to the
bottom of the terminal slot, and then tighten the screw.
16
The Calisto/Calisto 2 nominal power is 320W. The main supply switch may be used to turn the unit
WARNING
Electrical shock hazard. Alarm relays may be connected to hazardous live voltage even
if the mains power is OFF or disconnected.
ON or OFF. A circuit breaker must also be dedicated to the unit for this purpose. Although the
Calisto/Calisto 2 is equipped with an internal over-current fuse, it is strongly recommended that a
suitable fuse or breaker be installed in the mains supply external to the unit, with rating appropriate
to the supply voltage and nominal power.
Calisto/Calisto 2 features 5 programmable dry-contact relays. Each relay can be connected in a
normally open (NO) or normally closed (NC) configuration.
All 5 relays are located on the monitor interface board as shown in Figure 7.
Figure 7: Calisto/Calisto 2 - Alarm Relays and Connections
17
The table below describes the alarm relay connections pinout assignment:
CONNECTOR NO.
MARKING
CONNECTION TYPE
1
RLY1_NC
Relay 1 normally closed (NC)
2
RLY1_COM
Relay 1 common
3
RLY1_NO
Relay 1 normally open (NO)
4
RLY2_NC
Relay 2 normally closed (NC)
5
RLY2_COM
Relay 2 common
6
RLY2_NO
Relay 2 normally open (NO)
7
RLY3_NC
Relay 3 normally closed (NC)
8
RLY3_COM
Relay 3 common
9
RLY3_NO
Relay 3 normally open (NO)
10
RLY4_NC
Relay 4 normally closed (NC)
11
RLY4_COM
Relay 4 common
12
RLY4_NO
Relay 4 normally open (NO)
13
RLY5_NC
Relay 5 normally closed (NC)
14
RLY5_COM
Relay 5 common
15
RLY5_NO
Relay 5 normally open (NO)
16
SHIELD
Shield to earth ground
17
SHIELD
Shield to earth ground
18
SHIELD
Shield to earth ground
RATING
NOMINAL VALUE/RANGE
Connection range
0.34 – 2.5 mm2 stranded
Connection range (UL/CSA)
22 – 141 AWG stranded
Wire strip length
9 mm (~3/8 in.)
Wire insulation ratings
300V,
90ºC (194ºF) or better
Flammability
VW-1 or better
Screw type
M2.5
1
Connectors 2, 5, 8, 11 and 14 are all commons and can be looped together into one single common
if all signals must route to the same location.
Connectors 16, 17 and 18 can be used to terminate an alarm cable shield to the earth ground.
The relay connections must be made in accordance with the following connector ratings:
To connect the relay connections, loosen completely each screw terminal, insert the conductor in
the terminal slot until the bottom is reached, and then tighten the screw.
Using gauge 14 conductors to wire the relays may dictate the use of a larger diameter protective conduit, thus enlarging
one of the electrical entry holes. Two entry holes can also be dedicated to the alarm relay wiring as an alternative.
18
Recommended use of the alarm relays:
AC CONNECTIONS
Characteristic
Nominal value/range
Min./Max. switching voltage
5V/400VAC
Rated resistive load
16A/250VAC
Min switching current
5mA
Coil-contact dielectric strength
5000VAC
DC CONNECTIONS
Characteristic
Nominal value/range
Min./Max. switching voltage
5V/300VDC
Rated resistive load
16A/24VDC
1A/48VDC
0.4A/100VDC
0.3A/(150-300)VDC
Min switching current
5mA
Coil-contact dielectric strength
5000VAC
For more information on how to configure the alarm relays, refer to Section 4.2.6 Setting Alarm
Limits and Section 4.2.7 Relay Output Configuration of this manual. The factory default alarm relay
configurations can also be found at Section 4.2.7.
The Calisto monitor features two 4-20 mA analog outputs, one for dissolved hydrogen and one for
moisture. Calisto 2 features one additional 4-20 mA analog output dedicated to carbon monoxide.
All analog outputs are isolated to 1500 V.
The analog output screw-terminal plug-in connector is located on the monitor interface board (Refer
to Figure 8). Although pin 8 and 9 are present in a Calisto monitor, no signal from this output can
be used as Calisto does not report carbon monoxide.
Figure 8: Calisto/Calisto 2 - Analog Output Connector
It is recommended to un-plug the connector to simplify wiring the connections, and to screw the
connector in place after the connections are made.
19
The analog output connector pinout has the following configuration:
PIN NO.
OUTPUT
DESCRIPTION
1
SHLD
Shield to earth ground
2
SHLD
Shield to earth ground
3
N/A
Unused 4 Moisture (H2O)
Positive (+)
5
Moisture (H2O)
Negative (-)
6
Hydrogen (H2)
Positive (+)
7
Hydrogen (H2)
Negative (-)
8
Carbon monoxide (CO)
Positive (+) (Calisto 2 only)
9
Carbon monoxide (CO)
Negative (-) (Calisto 2 only)
RATING
NOMINAL VALUE/RANGE
Connection range
0.34 – 1.5 mm2 solid/stranded
Connection range (UL/CSA)
22 – 16 AWG
Wire strip length
6.5 mm (~1/4 in.)
Wire insulation ratings
150V (300V preferred2),
90ºC (194ºF) or better
Flammability
VW-1 or better
Screw type
M2.0
2
NOTICE
The analog input can only be used with self-powered 4-20 mA devices and must not be
powered by an external source.
The analog output connections must be made in accordance with the following connector ratings:
The load resistance can be anywhere from 0 Ohm to a maximum of 500 Ohms including resistance
of the wires. The maximum length of the wires depends on the overall resistance of the load and the
acceptable noise level.
The setup of the analog outputs is done using the Calisto Access software. Refer to Figure 33:
Calisto Access Default Set-Up for more information.
Calisto/Calisto 2 features one 4-20 mA analog input that can be used to provide a reading of the
transformer oil temperature to the unit. The 4-20 mA analog input is loop-powered to +13.5 VDC
and isolated to 1500 V.
To preserve 1500V functional I/O isolation, 300V rated voltage is preferred.
20
The analog input screw-terminal plug-in connector (Refer to Figure 9) is located on the monitor
PIN NO.
MARKING
DESCRIPTION
1
SHLD
Shield to earth ground
2
Unused 3 -
4-20 mA negative (-)
4
+
4-20 mA positive (+)
RATING
NOMINAL VALUE/RANGE
Connection range
0.34 – 1.5 mm2 solid/stranded
Connection range (UL/CSA)
22 – 16 AWG
Wire strip length
6.5 mm (~1/4 in.)
Wire insulation ratings
150V (300V preferred3),
90ºC (194ºF) or better
Flammability
VW-1 or better
Screw type
M2.0
3
interface board.
Figure 9: Calisto/Calisto 2 - 4-20 mA Analog Input Connector
It is recommended to un-plug the connector to simplify wiring the connections, and to screw the
connector in place after the connections are made.
The 4-20 mA analog input connector pinout has the following configuration:
The 4-20 mA analog input connections must be made in accordance with the following connector
ratings:
If the Precision Oil Temperature Probe option for Calisto/Calisto 2 was purchased with your
instrument, refer to the Precision Oil Temperature Probe Manual. An electronic version of this manual
can be found on our website www.morganschaffer.com.
The analog input temperature range is configured via the Calisto Access software.
Calisto/Calisto 2 features one RS-485 communication port isolated to 1500 V. The RS-485 uses a
differential balanced line over twisted pair and can thus span relatively large distances, up to 4000 ft
(1200 m). It is highly recommended to select an industrial grade shielded twisted pair cable of
minimum 0.34 mm2 (22 AWG) to set up a communication via RS-485.
To preserve 1500V functional I/O isolation, 300V rated voltage is preferred.
21
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.