The energy efciency of the package of products provided for in this document may not correspond to its actual energy efciency once installed in a
building, as the efciency is inuenced by further factors such as heat loss in the products in relation to the building size and its characteristics
A+++
3
4
Morco GB24 & GB30 Series II
Combination Boiler
Destination Country:
BE = Belgium
CH = Switzerland
CZ = Czech Republic
DE = Germany
ES = Spain
FR = France
GB = UK
GR = Greece
IE = Ireland
IT = Italy
NL = Netherlands
PL = Poland
PT = Portugal
SI = Slovenia
2 General Specications ...................................................................................................................................10
3 Technical Data ...............................................................................................................................................12
4 General Installation Requirements.................................................................................................................14
10 Combustion Ratio Check ...............................................................................................................................36
To reset boiler, turn mode control knob to reset position and immediately turn knob back to required setting.
Introduction
The Morco GB Series IIis a wall mounted, room sealed, condensing
combination boiler, featuring full sequence automatic spark ignition
and fan assisted combustion.
Due to the high efciency of the boiler, condensate is produced from
the ue gases and this is drained to a suitable disposal point through
a plastic waste pipe at the base of the boiler. A condensate ‘plume’
will also be visible at the ue terminal.
The Morco GB Series IIis a combination boiler providing both central
heating and instantaneous domestic hot water.
Safety
Current Gas Safety (Installation & Use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this boiler
must be installed by a Gas Safe Registered Engineer, in accordance
with the above regulations.
In other countries the installation must be carried out by a qualied
and competent Gas Installer. In the approved country the boiler is
installed, this must be in accordance with their current rules in force.
It is essential that the instructions in this booklet are strictly followed,
for safe and economical operation of the boiler.
Electricity Supply
This appliance must be earthed.
Supply: 230 V ~ 50 Hz. The fusing should be 3A.
Minimum Clearances
Clearances of 165mm (6 1/2”) above, 100mm (4”) below,
2.5mm (1/8”) at the sides and 450mm (17 3/4”) at the front of
the boiler casing must be allowed for servicing.
Bottom clearance
Bottom clearance after installation can be reduced to 5mm.
This must be obtained with an easily removable panel, to
enable the consumer to view the system pressure gauge, and
to provide the 100mm clearance required for servicing.
To light the boiler. Refer to Boiler Controls
1. CHECK THAT THE ELECTRICITY SUPPLY TO BOILER IS
OFF.
2. Set the mode knob control (A) to ‘Off’.
3. Set the Domestic Hot Water temperature control (B) and
Central Heating temperature control (C) to ‘max’.
4. Ensure that all hot water taps are turned off.
5. Switch ON electricity to the boiler and check that all
controls, e.g. timer and room thermostat, are ON (refer to
mechanical timer instructions - Page 8).
6. Set the mode knob control to winter (
If there is a central heating demand the boiler will commence
the ignition sequence.
Note. In normal operation the boiler status display (D) will
show codes:
).
Important Notes
This appliance must not be operated without the casing correctly
tted and forming an adequate seal.
If the boiler is installed in a compartment then the compartment
MUST NOT be used for storage purposes.
If it is known or suspected that a fault exists on the boiler then it
MUST NOT BE USED until the fault has been corrected by a Gas
Safe Registered Engineer or in other countries a qualied and
competent Gas Installer.
Under NO circumstances should any of the sealed components on
this appliance be used incorrectly or tampered with.
This appliance can be used by children from 8 years and above
and persons with reduced physical, sensory or mental capabilities
or lack of experience and knowledge if they have been given
supervision or instruction concerning use of the appliance in a safe
way and understand the hazards involved. Children shall not play
with the appliance. Cleaning and user maintenance shall not be
made by children without supervision.
Children should be supervised to ensure that they do not play with
the appliance.
In cases of repeated or continuous shutdown a Gas Safe Registered
Engineer, or in other countries a qualied and competent Gas Installer,
should be called to investigate and rectify the condition causing this
and carry out an operational test. Only the manufacturers parts are to
be used for replacement.
Standby - no demand for heat.
CH being supplied.
DHW being supplied.
DHW preheat.
During normal operation the burner on indicator (E) will remain
illuminated when the burner is lit.
Note : If the boiler fails to light after ve attempts the fault
code
RESET PROCEDURE
To reset boiler, turn the mode control knob (A) to reset position
and immediately turn knob back to required setting. The boiler
will repeat the ignition sequence if a heat demand is present.
If the boiler still fails to light consult a Gas Safe Registered
Engineer, or in other countries a qualied and competent Gas
Installer.
will be displayed.
6
SECTION 1 - USERS INSTRUCTIONS
Operation
Winter conditions - i.e. CH and DHW required.
Ensure the mode knob control (A) is set to winter ( )
The boiler will re and supply heat to the radiators but will give
priority to DHW on demand.
Summer conditions - i.e. DHW only required.
Set the mode knob control to Summer ( ).
Set the CH external controls to OFF.
Note. The pump will operate briey as a self-check once every 24
hours, regardless of system demand.
Pre-heat is enabled if the pre-heat indicator (F) is lit. To switch
pre-heat on or off move the DHW/Pre-heat control knob (B) fully
clockwise and then return it to the required DHW temperature
setting.
Control of water temperature
Domestic Hot Water
The DHW temperature is limited by the boiler controls to
64oC maximum at low draw-off rate, adjustable via the DHW
temperature control (B).
Due to system variations and seasonal temperature uctuations
DHW ow rates/temperature rise will vary, requiring adjustment
at the draw off tap : the lower the rate the higher the temperature,
and vice versa.
Approx. ow temperatures for the boiler thermostat settings are:
Knob Setting Flow Temperature
Minimum 40oC (104oF)
Maximum 64
o
C (147oF)
To shut down the boiler
Set the mode knob control to OFF
To relight the boiler
Repeat the procedure detailed in ‘To light the boiler’.
Frost protection
If the holiday home or park home is to be left unoccupied during
cold periods when there is a threat of freezing, the domestic hot
and cold water circuits must be drained as follows:
- Turn off the cold water supply
- Open all hot and cold water taps
- Open all drain plugs in the hot and cold water system (do not
drain the central heating circuit, which should have been lled
with antifreeze if installed in a caravan holiday home or park
home).
Refer to the Holiday Home or Park Home owner’s handbook for
the drain plug positions and further instructions on draining down.
Please note there are no drain plugs on the boiler. Leave all taps
and drain plugs open until next use to allow any residual water to
continue to drain.
When installed in a Caravan Holiday Home or Park Home the
heating circuit and radiators should be lled with an approved
antifreeze (see section 4.8). The level of antifreeze should be
checked annually by a competent person. If the home is occupied
during very cold and freezing weather, the central heating should
be run continuously and the room stat or thermostatic radiator
valves set at a minimum of 15ºC.
If the home is unoccupied for even a short period, the hot and
cold water system must be drained down. This is the only way to
guarantee against frost damage.
Central Heating
The boiler controls the central heating radiator temperature to a
maximum of 80oC and a minimum of 45ºC, adjustable via the CH
temperature control (C).
The boiler is a high efciency combination boiler which is most
efcient when operating in condensing mode.
The boiler will operate in this mode if the CH temperature control
(C) is set to the ‘e’ position (economy mode). This control should
be set to maximum for very cold periods
BOILER CONTROLS
Legend
A. Mode Control Knob
B. DHW/Preheat Control Knob
C. CH Control Knob
D. Boiler Status
E. Burner ‘on’ Indication
F. Pre Heat on/off Indication
G. Mechanical Timer
H. Pressure Gauge
J.K.Condensate Drain
Gas Isolation Valve
(on position shown)
H
off
ABCD
ALL FROST DAMAGE IS OUTSIDE OF THE WARRANTY.
Boiler Overheat Protection
The boiler controls will shut down the boiler in the event of
overheating. Should this occur, a fault code
will be displayed.
Refer to fault chart.
Flame Failure
Should this occur a fault code will be displayed. Refer to fault
chart.
continued . . . . . .
status burner
max
min
reset
mode
preheat
9
1
20
1
2
2
2
I
23
24
1
2
3
4
5
6
e
min
max
18
17
1
6
15
0
0
1
4
1
3
1
2
1
1
10
9
8
7
preheat
E
F
Series IIGB24
G
J
K
7
SECTION 1 - USERS INSTRUCTIONS
PRESSURE GAUGE
1
9
20
2
1
2
2
23
24
1
2
3
4
5
6
7
8
9
10
1
1
12
13
1
4
15
16
17
18
0
0
I
preheat
preheat
min
min
max
mode
reset
off
statusburner
max
e
Loss of system water pressure
The pressure gauge indicates the central heating system
pressure. If the pressure is seen to fall below the original
installation pressure of 1-2 bar over a period of time then a water
leak may be indicated. In this event re-pressurise the boiler.
If unable to do so or if the pressure continues to drop a Gas
Safe Registered Engineer, or in other countries a qualied and
competent Gas Installer should be consulted.
INDICATED BY “F1” (LOW WATER PRESSURE) - THE BOILER
WILL NOT OPERATE IF THE PRESSURE HAS REDUCED TO
LESS THAN 0.3 BAR UNDER THIS CONDITION.
Condensate Drain
This appliance is tted with a siphonic condensate trap system
that reduces the risk of the appliance condensate from freezing.
However should the condensate pipe to this appliance freeze,
please follow these instructions:
a. If you do not feel competent to carry out the defrosting
instructions below please call your local Gas Safe Registered
Engineer, or in other countries a qualied and competent Gas
Installer for assistance.
If you do feel competent to carry out the following instructions
b.
please do so with care when handling hot utensils. Do not attempt
to thaw pipework above ground level.
If this appliance develops a blockage in its condensate pipe, its
condensate will build up to a point where it will make a gurgling
noise prior to locking out an “L2” fault code. If the appliance is
reset it will make a gurgling noise prior to it locking out on a failed
ignition “L2” code.
To unblock a frozen condensate pipe;
1. Follow the routing of the plastic pipe from its exit point on the
appliance, through its route to its termination point.
Locate the frozen blockage. It is likely that the pipe is frozen
at the most exposed point external to the building or where
there is some obstruction to ow. This could be at the open
end of the pipe, at a bend or elbow, or where there is a dip in
the pipe in which condensate can collect. The location of the
blockage should be identied as closely as possible before
taking further action.
2. Apply a hot water bottle, microwaveable heat pack or a warm
damp cloth to the frozen blockage area. Several applications
may have to be made before it fully defrosts. Warm water
can also be poured onto the pipe from a watering can or
similar. DO NOT use boiling water.
3. Caution when using warm water as this may freeze and
cause other localised hazards.
Once the blockage is removed and the condensate can ow
4.
freely, reset the appliance. (Refer to “To Light the boiler”)
5.
If the appliance fails to ignite, call your Gas Safe Registered Engineer,
or in other countries a qualied and competent Gas Installer.
Preventative solutions
During cold weather, set the boiler stat to maximum, (Must return
to original setting once cold spell is over)
Place the heating on continuous and turn the room stat down to 15ºC
overnight. (Return to normal after cold spell).
Escape of gas
Should a gas leak or fault be suspected contact the Gas Supplier
without Delay. TURN OFF ALL GAS SUPPLIES.
Do NOT search for gas leaks with a naked ame.
Cleaning
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains, wipe with a damp cloth
and nish off with a dry cloth.
DO NOT use abrasive cleaning materials.
Maintenance
The appliance should be serviced at least once a year by a Gas
Safe Registered Engineer, or in other countries a qualied and
competent Gas Installer.
MECHANICAL 24 HOUR TIMER
PROGRAMMING THE TIMER
1.
Decide what times you would like the timeswitch to switch ON and OFF.
2. Push segments towards the programme ring for an OFF period and
push away from ring for an ON period. The minimum switching
interval is 15 minutes and this can be increased in 15 minute steps.
3. Bring the timeswitch into the correct condition by manually turning
the programme ring clockwise through a 24 hour cycle.
4. Turn the programme ring clockwise until the correct time of day on
the ring lines up with the time indicator.
Note. The segment dial can be turned when the time controller is
operating. In case of power failure, re-adjust the time controller to the
correct time of day, turning the dial in a clockwise direction.
Permanent Override
By rotating the central switch so that the symbol (
time indicator ( ) the unit will be permanently ON.
With the symbol (
) lining up with the time indicator ( ) the unit acts as
a timeswitch.
With the symbol (
) lining up with the time indicator ( ) the unit will be
permanently OFF.
1) lines up with the
8
Permanently OFF
OFF segment
ON segment
24hr Programme Ring
Timer Control
Permanently ON
Time & Control
Indicator
9
1
18
20
1
2
2
2
23
24
1
2
3
4
5
6
17
1
6
15
1
4
1
3
1
2
1
1
10
9
8
7
Timer control segments
1 Segment = 15 mins
Push towards programme ring = OFF
Push away from programme ring = ON
SECTION 1 - USERS INSTRUCTIONS
POINTS FOR THE BOILER USER
Note. In line with our current warranty policy we would ask that you check through the Troubleshooting guide to identify any problems
external to the boiler prior to requesting a service engineers visit. Should the problem be found to be other than with the appliance we
reserve the right to levy a charge for the visit, or for any pre-arranged visit where access is not gained by the engineer.
TROUBLESHOOTING
NO HOT WATER
Check the mains switch (fused
spur) is turned on and ensure
switch mode control knob (A) is
in the summer or winter position
Is water coming out of the hot
water tap when turned on?
YES
See boiler “Fault Codes”
section. If ‘0’ is displayed then
contact Morco if your appliance
is under warranty or a Gas
Safe Registered Engineer, or in
other countries a qualied and
competent Gas Installer, if out of
warranty.
Contact a Gas Safe Registered
Engineer, or in other countries
a qualied and competent Gas
Installer.
NO
NO CENTRAL HEATING
Check the mains switch (fused
spur) is turned on and ensure
switch mode control knob (A) is
in the winter position
Check the timer is in an “ON”
position and the room thermostat
is turned up
Does the boiler operate and
provide central heating?
YES
Check the time settings on the
programmer are as you require
and adjust if necessary
See boiler “Operation Modes” and
“Fault Codes” section. If “0” is
displayed then contact a Gas Safe
Registered Engineer, or in other
countries a qualied and competent
Gas Installer.
NO
NO HOT WATER OR
CENTRAL HEATING
Check the fused spur is turned
on and ensure switch mode
control knob (A) is in the winter
position
Does the boiler have a display
showing on the front control
panel?
YES
See boiler “Operation Modes”
and “Fault Codes” section
Contact a Gas Safe Registered
Engineer, or in other countries
a qualied and competent Gas
Installer.
NO
OPERATION MODES
DISPLAY CODE ON BOILER
Note. These letters are permanently displayed while in that mode.
DESCRIPTION
The boiler is in standby mode awaiting either a central heating call or hot water demand.
The boiler has a call for central heating but the appliance has reached the desired
temperature set on the boiler.
The boiler has a call for hot water but the appliance has reached the desired temperature set on
the boiler.
The boiler is operating in central heating mode.
The boiler is operating in hot water mode.
The boiler is operating in pre heat mode.
The water in the cental heating circuit is less than 5ºC. If heating is switched on, this display
code will change to “c”.
9
SECTION 2 - GENERAL SPECIFICATIONS
1 Expansion Vessel
2 Pump
3 Auto Air Vent
4 Water Pressure Switch
5 Flow Thermistor
6 Return Thermistor
7 Divertor Valve
8 Fan
9 Venturi
10 DHW Plate Heat Exchanger
11 Ignition Electrode
12 Flame Detection Electrode
13 Gas Valve
14 Siphon / Trap
15 DHW Flow Turbine
16 System Pressure Gauge
17 Sump Cover
Schematic Diagram
8
11
5
9
13
4
17
3
6
2
1
14
12
16
7
15
10
2.1 GENERAL SPECIFICATIONS
The Morco GB Series IIrange of boilers are wall mounted, full
sequence, automatic spark ignition low water content, fanned
ue, high efciency condensing combination boilers.
Note. Due to the high efciency of the boiler a plume of water
vapour will format the terminal during operation. The boiler is
supplied for use with Propane only at 37mbar (30 mbar for DE)
supply pressure. It is particularly suitable for caravan holiday
home and park home use.
Maximum heat output in either heating or hot water for the GB24
is 24.2kW (82,570 Btu/hr)
Maximum heat output in heating mode for the GB30 is 24.3 kW
(82,570 Btu/hr) with 30.3 kW (103,384 Btu/hr) available for hot
water production.
The boiler can be supplied with a standard concentric ue with
additional extensions, ue deector and vertical ue kits available
as optional extras. The only ueS that can be tted are those
detailed in this instruction manual.
The boiler is suitable for connection to fully pumped, sealed
heating systems ONLY. Adequate arrangements for completely
draining the system by provision of drain cocks must be provided
in the installation pipework.
The boiler contains the following components:
Cast Aluminium Heat Exchanger
Domestic Hot Water Plate Heat Exchanger
Diverter Valve
Circulating Pump
Pressure Gauge
Safety Valve and Central Heating Expansion Vessel
Automatic Bypass
Daily Pump and Diverter Valve Exercise
Mechanical 24hr Timer
The boiler temperature controls are visible, located in the control
panel. These enable the user to control both CH and DHW
temperatures independently. There is the additional feature of a
DHW preheat facility. Operating and fault codes are displayed on
the status panel.
10
SECTION 2 - GENERAL SPECIFICATIONS
Turbine
2.2 WIRING DIAGRAM
Fused
at 4AT
bk
g
b
r
1 2 3 4
b
Timer
X1A
X1BX1CX2X3
brb
y/g
1
23456123451234568 79
bk
r
r
g
Main
Supply
Stat
Room
L
N
Plug
Pump
br
y/g
b
y
bk
p
Earth
Divertor
Gas
Spark
Electrode
Valve
Valve
y/g
bk b
v br
bk
y/g
b
Spark
Generator
br
b
bk
y/g
PCB
- blue
- black
- brown
- red
bbkbrrpyw
KEY
- pink
- yellow
- white
- yellow/green
- grey
- orange
- violet
y/ggor
v
X13
X7
X5X6X8
bk
y/g
123
12345123456789
p
y
bk
bk
y/g
Flame
Sensor
Electrode
b br
Fan
1234123456
bk
r
1011
bk
p
bk
p y
bk
b
Return
Thermistor
Service
Connector
Flow
Thermistor
bk
or
bk
r
b
Water
pressure
Flow
Water
Switch
11
SECTION 3 - TECHNICAL DATA
Table 1 General Data
Morco GB Series II
Gas SupplyI
Gas Supply Connection15mm copper compression
Injector Size(mm)3.753.75
Inlet ConnectionDomestic Hot WaterG ½
Outlet ConnectionDomestic Hot WaterG ½
Flow ConnectionCentral HeatingG ¾
Return ConnectionCentral HeatingG ¾
Flue Terminal Diametermm (in)100 (4)
Average Flue Temp-Mass Flow RateDHW63ºC - 11g/s68ºC - 13 g/s
Maximum Working Pressure (Sealed Systems)bar (lb/in
Maximum Domestic Hot Water Inlet Pressure bar (lb/in
Minimum Domestic Hot Water Inlet Pressure* bar (lb/in
2
)2.5 (36.3)
2
) (kPa)10.0 (145) (1000)
2
) (kPa)0.8 (11.6) (80)1.3 (18.9) (130)
Electrical Supply230 V - 50 Hz.
Power ConsumptionW146152
Fuse RatingExternal : 3A Internal : T4H HRC L250 V
Water ContentCentral Heating litre (gal)1.2 (0.26)
Domestic Hot Water litre (gal)0.5 (0.11)
Packaged Weightkg (lb)33.8 (74.4)34.1 (75.2)
Maximum Installation Weightkg (lb)31 (68.3)31.2 (68.8)
Boiler Casing SizeHeight mm (in)700 (27.5)
Width mm (in)395 (15.5)
Depth mm (in)285 (11.2)
*Required for maximum ow rate. Boiler operates down to 2 l/min DHW delivery
2430
- G31 - 37mbar (30mbar for DE)
3p
Table 2 - Performance Data - Central Heating
Boiler Input : Max.Min.24 30 24 30
Boiler Input ‘Q’ Nett CV kW 24.3 24.3 8.0 8.0
Btu/h 82,912 82,912 27,296 27,296
Gross CV kW 26.4 26.4 8.7 8.7
Btu/h 90,077 90,077 29,684 29,684
Gas Consumption m
ft
kg/hr 1.83 2.26 0.58 0.58
Boiler Output :
Non Condensing kW 24.2 24.3 8.00 8.00
o
70
C Mean Water temp. Btu/h 82,570 82,570 27,296 27,296
Condensing kW 25.6 25.6 8.5 8.5
o
40
C Mean Water temp. Btu/h 87,347 87,347 29,002 29,002
* The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from
which it has been calculated have been certied by a notied body.
Note. Gas consumption is calculated using a
caloric value of 95.65 MJ/m3 (2569 Btu/ft3)
gross or 88.0 MJ/m3 (2,360 Btu/ft3) nett
To obtain the gas consumption at a different
caloric value:
a.For l/s - divide the gross heat input (kW) by
the gross C.V. of the gas (MJ/m
3
b. For ft
/h - divide the gross heat input (Btu/h)
3
)
by the gross C.V. of the gas (Btu/ft3)
3
c. For m
/h - multiply l/s by 3.6.
Key to symbols
PMS = Maximum operating pressure of water
= A room sealed appliance designed for connection via ducts to a horizontal
C
13 C33
or vertical terminal, which admits fresh air to the burner and discharges
the products of combustion to the outside through orices which, in this
case, are concentric. The fan is up stream of the combustion chamber.
I
= An appliance designed for use on 3rd Family gas, Group P only.
3P
12
SECTION 3 - TECHNICAL DATA
DATA PLATE
3952.5
2.5
from case
700
Side
flue
dim. A
285
86.5
17
155
CH FLOW
DHW OUTLET
COND. DRAIN
GAS INLET
DHW INLET
CH RETURN
PRV
43.565
28.5 28.5
60.67537.556.4
Underside View - Dimensions to Wall
W A L L
W A L L
99
10399
99103
BOILER DIMENSIONS, SERVICES & CLEARANCES
The boiler connections are made on the boiler bulkhead ttings.
The following minimum clearances must be maintained for
operation and servicing.
Additional space will be required for installation, depending upon
site conditions.
Side and Rear Flue
a. Provided that the ue hole is cut accurately, e.g. with a core
boring tool or hole cutter the ue can be installed from inside
the dwelling where wall thicknesses do not exceed 600mm
(24”). Where the space into which the boiler is going to be
installed is less than the length of ue required the ue must
be tted from the outside.
Installation from inside ONLY
b. If a core boring tool or hole cutter is to be used inside the
dwelling the space in which the boiler is to be installed
must be at least wide enough to accommodate the tool.
In either of the above cases safe external access is
required to allow the addition of sealant to seal the ue to
the aluminium ue collar (RSF 060).
Front clearance
The minimum front clearance when
built in to a cupboard is 5mm from
the cupboard door but 450mm overall
clearance is still required, with the
cupboard door open, to allow for
servicing.
* Bottom clearance
Bottom clearance after installation
can be reduced to 5mm.
This must be obtained with an
easily removable panel, to enable
the consumer to view the system
pressure gauge, and to provide
the 100mm clearance required for
servicing.
Max 30kW
Max 24kW
2. For ue lengths requiring “D” pack extensions (RSF 341), the ue must incline by 26mm per 1 Metre of ue length.
13
SECTION 4 - GENERAL INSTALLATION REQUIREMENTS
0.6m
Zone 0
Recessed
window
Zone 2
Ceiling
3G8913a
2.25m
Zone 1
4.1 RECOMMENDATIONS
Current Gas Safety (Installation and Use) Regulation or Rules in
Force.
The boiler is suitable only for installation in the specied countries
and should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a Gas Safe
Registered Engineer, or in other countries a qualied and
competent Gas Installer. It must be carried out in accordance with
the relevant requirement of the:
• Gas Safety (Installation and Use) Regulations
• Appropriate National Standards
• The Water Fittings Regulations
• Current IEE Wiring Regulations
• Health & Safety Document Nol.635
• The Electricity at work Regulations 1989.
• BS5482 Part 1 Code of Practice for Domestic butane and
propane gas burning installation in permanent dwellings,
residential park homes and commercial premises.
• BSEN1949:2011 Specication for the installation of LPG
Systems for habitation purposes in leisure accommodation
vehicles and other road vehicles.
IMPORTANT
The manufacturer’s notes MUST NOT be taken, in any way as
overriding statutory obligations.
4.2 BOILER LOCATION
The boiler must be installed on a at and vertical wall, capable of
adequately supporting the weight of the boiler and any ancillary
equipment.
The boiler may be tted on a combustible wall and insulation
between the wall and the boiler is not necessary unless required
by National Standards.
For Electrical Safety reasons there must be no access available
from the rear of the boiler.
The boiler must not be tted outside.
BATHROOM INSTALLATIONS
This appliance is rated IP20.
The boiler may be installed in any room or internal space, although
particular attention is drawn to the requirements of the current
IEE (BS.7671) Wiring Regulations and the electrical provisions
of the building regulations applicable in Scotland, with respect to
the installation of the boiler in a room or internal space containing
a bath or shower. For IE reference should be made to the current
ETCI rules for electrical installations and I.S. 813:2002.
If the appliance is to be installed in a room containing a bath or
shower then, providing water jets are not going to be used for
cleaning purposes (as in communal baths/showers), the appliance
must be installed beyond Zone 2, as detailed in BS.7671.
COMPARTMENT INSTALLATIONS
A compartment used to enclose the boiler should be designed
and constructed specially for this purpose.
An existing cupboard or compartment may be used, provided
that it is modied for the purpose.
• The position selected for installation MUST allow adequate
space for servicing in front of the boiler.
4.3 FLUE TERMINAL POSITION
Pluming will occur at the terminal so avoid locations where this
will cause a nuisance.
The boiler MUST be installed so that the terminal is exposed to
external air.
It is important that the positions of the terminal allows the free
passage of air accross it at all times.
Minimum acceptable spacing from the terminal to obstructions
and ventilation pump are specied in the table below.
For Caravan Holiday Homes; if the height of the ue terminal
from any ground, decking or steps is under 1.5m then a suitable
terminal guard should be tted.
For Residential Park Homes, please refer to BS 5440 Part 1.
Terminal Guards are available from boiler suppliers.
TFC Flue Guard - Model K6 Round Plastic Coated.
www.tfc-group.co.uk
Table 4 - Balanced Flue Terminal Position
Flue Terminal Positions
1. Directly below, above or alongside an opening
window, air vent or other ventilation opening. 300mm (12”)
4. Below balconies or a car port roof. 25mm (1”)*BS5440-1 2008 200mm (8”)
5. From vertical drain pipes or soil pipes. 25mm (1”)*BS5440-1 2008 150mm (6”)
6. From an internal or external corner or to a 25mm (1”)*boundary along side the terminal. BS5440-1 2008 300mm (12”)
7. Above adjacent ground, roof or balcony level. 300mm (12”)
8. From a surface or a boundary facing the terminal. 600mm (24”)
9. From a terminal facing a terminal. 1,200mm (48”)
10. From an opening in a car port
(e.g. door or window) into dwelling. 1,200mm (48”)
11. Vertically from a terminal on the same wall. 1,500mm (60”)
12. Horizontally from a terminal on the wall. 300mm (12”)
Vertical Terminals
13. Above the roof pitch with roof slope of all angles. 300mm (12”)
Above at roof. 300mm (12”)
14. From a single wall face. 300mm (12”)From corner walls. 300mm (12”)
15. Below velux window 2000mm (79”)
16. Above or side of velux window 600mm (24”)
* Only one reduction down to 25mm is allowable per installation
otherwise BS5440-1 2008 dimensions must be followed.
Min. Spacing*
14
SECTION 4 - GENERAL INSTALLATION REQUIREMENTS
4.4 AIR SUPPLY
It is NOT necessary to have a purpose provided air vent in the
room or internal space in which the boiler is installed. Neither is
it necessary to ventilate a cupboard or compartment in which the
boiler is installed, due to the low surface temperature of the boiler
casing during operation.
4.5 ELECTRICAL SUPPLY
WARNING
This appliance MUST be earthed.
Wiring external to the boiler MUST be in accordance with the
correct IEE Regulations and any local regulations.
The boiler has been pre-tted with a 3 amp fused approved
moulded 3 pin plug and ying lead, for use with 230V 50Hz.
The plug should be used with an unswitched/shuttered socket
outlet complying with BS1363.
4.6 GAS SUPPLY
A propane gas supply at 37mbar is required (30 mbar for DE).
Ensure that regulator is of sufcient capacity to carry the
maximum boiler input plus the full demand for any other installed
appliances.
Ensure the connection between supply/cylinder to caravan holiday
home or park home is designed so that no pressure drop occurs.
Ensure the pipework is of sufcient size to prevent a pressure
drop greater than 2.5mbar between the nal pressure regulator to
the caravan holiday home or park home and all appliances when
the installation is subjected to the anticipated maximum load.
IMPORTANT
The complete installation MUST be tested for gas soundness.
4.7 CONDENSATE DRAIN
A condensate drain is provided on this boiler.
The drain MUST be connected to an approved drainage point.
All pipework and ttings MUST be made of plastic. No other
materials may be used.
Suitable protection against freezing should be undertaken.
4.8 WATER SYSTEMS - GENERAL
This boiler is designed for connections to fully pumped sealed
system only.
IMPORTANT - A minimum length of 1 metre of copper pipe
MUST be tted to both central heating and DHW ow and return
connections from the boiler before connection to any plastic piping.
Central Heating System
IMPORTANT - The sealed central heating system must be lled
at all times with an antifreeze / inhibitor and water mix that is
compatible with aluminium heat exchangers. The concentration
levels of the antifreeze / inhibitor should be at least 25% in order
to provide adequate corrosion protection. This level also provides
protection against frost from -7.5ºC to -11ºC (depending on the
product used). The maximum allowable level of antifreeze /
inhibitor is around 40%.
The only products approved are as follows:
- Fernox Alphi 11
- Sentinel X500
Failure to use these products may result in damage to the boiler
and / or the radiators in the heating system.
4.9 REQUIREMENTS FOR SEALED WATER
SYSTEMS
At maximum CH output 24.2kW at a 20ºC differential and ow rate
17.3 l/min a 3.4m wg head is available for the system
Set all radiators to give around 20ºC temperature differential.
The boiler does not normally need a bypass but at least some
radiators of load at least 10% of the minimum boiler output.
These radiators should be tted with lockshield valves only.
A sealed system MUST only be lled by a competent person using
an approved lling loop (or other approved method) between the
mains water supply pipe and the central heating return pipe.
Once used, the lling loop should be disconnected and capped off.
4.10 EXPANSION VESSEL
The boiler is tted with an 8 litre expansion vessel which is
sufcient for a cold ll capacity of up to 143 litres.
For other system volumes refer to table below.
Safety valve setting bar 3.0
Vessel charge pressure bar 0.5 to 0.75
System pre-charge pressure bar None 1.0
System volume Expansion vessel
(litres) volume (litres)
For other system volumes
multiply by the factor across 0.063 0.074
4.11 PRESSURE RELIEF VALVE
A pressure relief valve set at 3 bar is tted to the boiler. The
connection is shown in the dimensions and connection details.
The discharge pipework must be suitable for use with 3bar water
at 110ºC without damage to property and persons.
The run and exit point of the pipework should not leave a hazard
or be prone to freezing up.
4.12 DHW SYSTEMS
Check that the mains supply pressure is within the units stated in
the technical data section in this manual
A pressure reducing valve should be tted if above 10 bar.
In areas of low mains water pressures the domestic hot water
regulator may be removed (by a suitably qualied person). The
boiler will require the ow rate to be set to give a temperature of
35ºC at the tap furthest from the boiler.
In hard water areas where mains water exceeds 200ppm total
hardness, the tting of a scale reducing device is recommended
(with the requirements of the local water company).
The use of articially softened water, however, is not permitted.
The boilers are suitable for connection to most types of washing
machine and dishwasher appliances.
15
SECTION 5 - INSTALLATION INSTRUCTIONS
5.1 BOILER PACKAGING
The boilers are supplied in different packagings:
• Boiler
• Flue System (separate)
• Hardware Pack (separate)
5.2 FITTING/MOUNTING THE BOILER
Decide where the boiler is to be xed on the wall, taking into
account installation requirements detailed in previous section.
1. Screw the wall mounting plate to the wall choosing one of the
two sets of slots in left and right bank. Ensuring that at least
one of the screws is tted into a top slot.
Example of fixing
2. Lift the boiler onto the wall mounting plate, locating it over the
two tabs.
5.4 INTERNAL WIRING
The boiler has been pre-tted with a 3 amp fused approved
moulded 3 pin and ying lead for use with 230V 50Hz.
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualied persons in
order to avoid a hazard.
The plug should be used with an
unswitched/shuttered socket outlet
complying with BS1363.
The boiler comes pre-tted with
a link wire between the room
thermostat/Timer connections on
the terminal strip. This creates a
permanent call for heat and must
be removed when adding a room
thermostat.
ROOM THERMOSTAT - WIRING
To t a room thermostat proceed as follows:
1. Ensure that the electrical supply to the boiler is isolated before
proceeding.
4
Cable
Clamp
Note. If present, remove the bottom end support packaging
and ensure all plastic plugs are removed from CH & DHW
connections.
5.3 WIRING INSTRUCTIONS
WARNING: THIS APPLIANCE MUST BE EARTHED
Connections must be made in such a way that allows complete
isolation of the electrical supply, e.g. double pole switch with
3mm contact separating in both poles.
2. Remove the two screws beneath the ap on the front of the
boiler and lower the front panel.
3. Remove the pre-tted link wire between the Room stat/timer
terminals.
4. Pass the cable through a grommet, secure with the cable
clamp and connect the room stat as shown in the diagram
below.
5. If room stat has a neutral connection, connect this to terminal
N (load) in the fused spur.
6. Carry out all necessary electrical checks.
7. Raise the front panel and relocate the two screws under the
small ap.
8. Check operation of room stat if possible.
L
N
ROOM
STAT/
TIMER
230VAC Feed
230VAC Return
N
Room
Stat
16
SECTION 5 - INSTALLATION INSTRUCTIONS
CH FLOW
DHW OUTLET
COND. DRAIN
GAS INLET
5.5 WATER AND GAS CONNECTIONS
Ensure all boss blanking plugs are removed before making any connections.
Each valve must be tted to the correct boss as shown in diagram below
Do not subject any of the isolating valves to heat as the seals may be damaged.
Ensure that the green bre washer is used on the CH ow connection.
IMPORTANT - The gas service cock is sealed with a top hat washer - DO NOT subject to heat.
Pressure Relief Valve (PRV) - Located at the bottom right hand side of the boiler connection via a 15mm diameter stub pipe.
Use a replaceable connection to ease the replacement of the valve if required.
Ensure a safe discharge point using temperature and pressure resistant materials.
DHW INLET
CH RETURN
PRV
5.6 AIR / FLUE SYSTEMS
The ue system is part of the appliance and is approved as such. Only use the ue systems supplied by Morco.
The standard ue kit (RSF303) for the Morco GB range is a 600mm as shown below. There is also a 900mm kit available (RSF305).
Turret
100
60
600
60
The minimum cut length is 138mm (includes 30mm into elbow)
The maximum allowable length using extensions (RSF341) is:
GB24 Series II - 8m (minus any ue kit options)
GB30 Series II - 7m (minus any ue kit options)
Part No. RSF303
17
SECTION 5 - INSTALLATION INSTRUCTIONS
WALL
Aluminium Flue
Collar (RSF 060)
Fill with
sealant
17mm min
Internal Sealing
Flubber
Fill with
sealant
5.7 DETERMINING THE FLUE LENGTH
IMPORTANT. The boiler must be installed in a vertical position in accordance to the installation instructions.
STANDARD FLUE KITS
Horizontal Flue Terminal RSF303 (600mm long) - contains: Flue turret, non telescopic single piece ue incorporating a terminal
and inner rubber wall seal.
Extension Kit RSF341 - contains: 1 metre length of ue pipe (Functional length 950mm), 1 support bracket.
When extension kits are used the ue duct must incline 1.5 degrees away from the appliance, to allow the condensate to drain back to
the boiler and out of the condensate drain. It is recommended that a support bracket is tted on every 1 metre of pipe work used and the
bracket is located as close to the collar as possible. The bracketing must ensure a 1.5 degree fall back to the appliance.
Only use water as a lubricant during assembly.
The horizontal ue kit terminal is classed as part of the maximum ue length.
Once the ue is installed it is IMPORTANT that the white air duct protrudes from the aluminum ue collar (RSF 060) by at
least 17mm. The gap between the aluminium ue collar (RSF 060) and the white air duct MUST be sealed with sealant to
create an adequate seal.
It is IMPORTANT that all attachments are tted in accordance with the installation instructions provided in this manual.
The TURRET supplied in the Horizontal Flue Kits (RSF303 & RSF305) has an upper combustion sample point with a screw cap seal
and a lower air sample point with an air stopper seal. Ensure all caps & seals are in place.
Additional Termination Kits available for use with these Horizontal Flue Kits (RSF303 & RSF305)
Flue Deector Kit (RSF300) The resistance is the equivalent of 1 metre of ue pipe and therefore must be deducted from
any maximum ue length
Total Maximum Permissible Horizontal Concentric Flue Length combining both Horizontal Flue Kits and Extension Kits
(Measured from centreline of the turret to the outside face of the aluminium ue collar (RSF060))
24 kW appliancesTotal Maximum: 8 metres - minus any ue kit options
30 kW AppliancesTotal Maximum: 7 metres - minus any ue kit options
Total Maximum Permissible Vertical Flue Length
24 & 30kW AppliancesTotal Maximum: 7.5 Metres - minus any 90º bends
Minimum Horizontal Flue Lengths (Centre line of turret to outside face of the aluminium ue collar (RSF060))
Rear Flue - 191mm
Side Flue - 236mm (with minimum 2.5mm clearance)
18
SECTION 5 - INSTALLATION INSTRUCTIONS
5.8
DETERMINING THE FLUE LENGTH
FIGURE 1
REAR FLUE
Cut ue length = distance from edge of turret to outside of
wall dimension A + 47mm.
Note. Minimum dimension A which can be accommodated is
91mm.
A
REAR
Fit
to wall
WALL
SIDE FLUE
Cut ue length = distance from edge of turret to outside of
wall dimension B + 47mm.
Note. Minimum dimension B which can be accommodated is
136mm (with minimum clearance of 2.5mm).
B
SIDE
Fit
to wall
WALL
Minimum clearance 2.5mm
Flue length measured from outer terminal lip
NOTES
Centre of turret to edge of turret = 100mm
Turret has a ue insertion of 30mm
The white outer ue tube must protrude the wall by 17mm.
From centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mm
1. Measure from the outer terminal lip to end of outer ue. Mark the
required cut length (A or B + 47mm) around the circumference of the
outer ue and cut following the mark to ensure its cut square.
2. Dress the cut end to make sure all burr’s are removed and the cut
edge is in its original shape.
3. Mark the inner tube 10mm longer than the outer tube around its
circumference and cut following the mark to ensure its cut square.
4. Remove all burrs and place a light chamfer on the outer edge to aid
assembly.
10mm
Mark cut length =
A or B + 47mm from terminal lip
A or B + 47mm
19
SECTION 5 - INSTALLATION INSTRUCTIONS
Flue Outlet
C
A
A - Duct Assembly
B - Flue Turret
C - Turret Clamp
D - Seal
Flue Outlet
D
B
Retaining
screw
Clamp Lugs
Sample points
WALL
Aluminium Flue
Collar (RSF 060)
Fill with
sealant
17mm min
Internal Sealing
Flubber
Fill with
sealant
5” hole
5.10 INSTALLING THE FLUE
FITTING FLUE THROUGH THE WALL
1. Ensure the seam and the outlet terminal are
at the top and tted as shown.
2. Once the ue is installed it is IMPORTANT
that the white air duct protrudes from the
aluminium ue collar (RSF 060) at least
17mm.
Note. If less than 50% of the length of the ue is
internal the ue should be tted from outside.
3. Fit the internal sealing ubber to the ue
(leave loose) and check protrusion externally
of the white air duct is 17mm.
4. Fit the turret as below
FITTING THE TURRET - Ensure the condensate trap / siphon is lled with water
1. Ensure the rubber seal is tted correctly on the appliance manifold and that all ue seals are undamaged.
2. Hold the ue rmly and push the turret on until it has travelled 30mm on to the ue pipe and is fully engaged. Make sure the
ue has not rotated or moved forward during tting and the ue seam is upper most.
3. Push the turret into the manifold ensuring the upper plastic lip is ush with the top of the manifold.
4. Fully engage the clamp location section into the manifold location holes. Rotate down on to turret ange.
5. Secure clamp to appliance using securing screw.
6. Ensure all sample points are accessible and all sample plugs and caps are tted.
7. Fully engage the ue into the turret and slide internal ubber to wall.
8. The gap between the aluminium ue collar (RSF 060) and the white air duct MUST be sealed with sealant to create a seal.
20
SECTION 5 - INSTALLATION INSTRUCTIONS
Flue
Deector
WALL
115
115
5.11 FLUE EXTENSIONS (RSF341) - OPTIONAL
INNER PIPE ASSEMBLY INSTRUCTIONS
1. Make sure that ‘top hat’ on the collar (A) ts over the
rectangular form on the inner plastic pipe (B).
AB
Top Hat
Rectangular
2. Ensure that the at base of the collar (C) is
positioned on the bottom lip of the pipe (D).
For side outlet refer to section 1.2 before connecting.
3. Slide the pipe and collar assembly back into the outer
housing (E), note that this can only be done at the female
end of the outer housing.
E
4. When tting support brackets (F) make sure they are
positioned on the female side of the neck as shown.
C
D
5.12 FLUE DEFLECTOR KIT (RSF300) - OPTIONAL
The ue deector elbow can be tted to the ue outlet of the standard
terminal kits RSF303 or RSF305 to deect the ue products horizontally
to the left or the right only.
1. Refer to the boiler Installation and Servicing Instructions for tting of
the boiler and its ue system.
Note. The resistance of the deector is equivalent to 1 metre of ue
length. Ensure this is used when calculating the maximum allowable
ue length.
2. Choose the direction required to deect the ue products
(horizontally left or right only).
3. Push the deector elbow onto the angled ue outlet of the terminal
in the desired position and ensure the deector is pushed up to the
shoulder to fully engage the rubber seal. Drill the terminal through
the hole in the deector with a 3.2mm (1/8") drill and secure the
deector with the self tapping screw provided.
Note. Only use water as a lubricant during assembly. Do not use
mineral based oils.
F
5.13 90º KIT RSF315 (OPTIONAL)
This optional kit can be used on both horizontal and
vertical ue kits
1. Use dimensions below for calculating total length
2. When cutting extensions or ue kits always allow
sufcient (+ 30mm air duct + 14mm ue duct) to
allow for correct engagement in the tting
3. 1 elbow reduces the maximum available length by
1m
Note. Only use water as a lubricant during assembly .
Do not use mineral based oils.
21
SECTION 5 - INSTALLATION INSTRUCTIONS
5º & 14º
MAX LENGTH:
7.5m**
MIN LENGTH:
0.950m
Flue Terminal
RSF050
14º
RSF050
5º
1
Assembly A
5
3
Vertical
connector
4
5.14
FITTING THE OPTIONAL ROOF FLUE KIT (RSF345) (Pitched)
Note.
A 5º or 14º pitched roof plate (not supplied) is required before
proceeding with the installation of this kit.
This kit is suitable for both 5º and 14º pitched roof terminations,
using a concentric ue to run vertically from the top of the boiler and
terminating above roof level.
Connection to the top of the boiler is made using a vertical connector
(supplied in the kit - RSF346).
WEATHER PROOFING
Where the ue passes through the roof line an adequate seal must be
made. This is achieved by using a suitable sealant.
ACCESSORIES
Flue Duct Extension Kits are available for ue lengths extending
beyond 1m. These packs contain 1m extension ducts and may be
cut to the desired length. If 90º elbows are used (RSF315) they will
reduce the overall height by 1m per elbow.
5.15
ASSEMBLING THE ROOF FLUE KIT
Terminal Position Minimum Dimension
Directly below an opening,
air brick, windows, etc. 300 mm
Below plastic / painted gutters 300 mm
Painted surface 300 mm
Below eaves or balcony 500 mm
Below velux windows 2000mm
Above or side of velux windows 600mm
1. Position the roof plate (supplied separately) over the hole cut in the roof and insert ue
terminal from the roof end.
ASSEMBLY A
2. Ensure that if the length needs to be adjusted to allow an additional 30mm added to
the outer air tube length 14mm added to the inner ue length. This allows correct
engagement into the vertical connector.
Note. Ensure a square cut. remove all burrs and sharp edges.
3. Fit the vertical connector (supplied in the kit) and secure the vertical connector by
applying downward pressure on the connector.
4. Position the clamp on the top face of the ue manifold and push it horizontally
backwards. Locate both clamp lugs into the ue manifold and secure to the ue
manifold clamp with the M5 retaining screw.
5. “Push” assembly A into vertical connector.
Notes. Ensure turret sample points are servicable and all caps and plugs are tted.
Ensure condensate siphon/trap is lled with water.
6. Finally ensure the roof plate is correctly sealed to the roof.
22
SECTION 5 - INSTALLATION INSTRUCTIONS
Sink/basin/
bath or
shower
Boiler
with 75mm
sealed
condensate
trap
Min Ø 19mm
Internal pipe
Internal soil & vent stack
Boilers without 75mm sealed
condensate trap must be fitted with
a 75mm trap and visible air break
75
≥ 100
≥ 100
5.16
CONDENSATE DRAIN
47
137
Condensate
Drain
156
This appliance is tted with a siphonic 75mm sealed condensate
trap system that requires lling before operating the appliance for
the 1st time or after maintenance.
All condensate pipework should conform to the following:
a. Where a new or replacement boiler is being installed, access to
an internal ‘gravity discharge’ termination should be one of the
main factors considered in determining boiler location.
b. Plastic with push t or solvent connections.
c. Internal plastic pipe work a minimum of 19mm ID (typically
22mm OD)
d. External plastic pipe must be a minimum of 30mm ID (typically
32 OD) before it passes through the sleeved wall.
e. All horizontal pipe runs, must fall a minimum of 45mm per metre
away from the Boiler.
f. External & unheated pipe work should be kept to a minimum
and insulated with Class “O” waterproof pipe insulation.
g. All installations must be carried out in accordance to the
relevant connection methods as shown in the “Condensate
installation diagrams” & BS6798:2009
h. Pipe work must be installed so that it does not allow spillage
into the dwelling in the event of a blockage (through freezing)
i. All internal burrs should be removed from the pipe work and any
ttings.
NB. Clip runs to prevent pipework disconnecting due to
vibration etc.
In order to minimise the risk of freezing during prolonged very cold
spells, one of the following methods of terminating condensate
drainage pipe should be adopted.
Internal Drain Connections
Wherever possible, the condensate drainage pipe should be routed
to drain by gravity to a suitable internal foul water discharge point
such as an internal soil and vent stack or kitchen or bathroom
waste pipe etc. See Figs 1 and 2.
Condensate Pump
Where gravity discharge to an internal termination is not physically
possible or where very long internal pipe runs would be required
to reach a suitable discharge point, a condensate pump of a
specication recommended by the boiler or pump manufacturer
should be used terminating into a suitable internal foul water
discharge point such as an internal soil and vent stack or internal
kitchen or bathroom waste pipe etc. (g 3).
External Drain Connections
The use of an externally run condensate drainage pipe should
only be considered after exhausting all internal termination options
as described previously. An external system must terminate at a
suitable foul water discharge point or purpose designed soak away.
If an external system is chosen then the following measures must
be adopted:
The external pipe run should be kept to a minimum using the most
direct and “most vertical” route possible to the discharge point, with
no horizontal sections in which condensate might collect.
- For connections to an external soil/vent stack see Fig 4.
Insulation measures as described should be used.
- When a rainwater downpipe is used, an air break must be
installed between the condensate drainage pipe and the
downpipe to avoid reverse ow of rainwater into the boiler
should the downpipe become ooded or frozen, see Fig 5.
- Where the condensate drain pipe terminates over an open
foul drain or gully, the pipe should terminate below the grating
level, but above water level, to minimise “wind chill” at the open
end. The use of a drain cover (as used to prevent blockage by
leaves) may offer further prevention from wind chill. See Fig 6.
- Where the condensate drain pipe terminates in a purpose
designed soak away (see BS 6798) any above ground
condensate drain pipe sections should be run and insulated as
described above. See Fig 7
Unheated Internal Areas
Internal condensate drain pipes run in unheated areas should be
treated as external pipe.
Ensure the customer is aware of the effects created by a frozen
condensate and is shown where this information can be found in
the user manual.
Figure 1 - Connection of Condensate Drainage Pipe to
Internal Soil & Vent Stack
Boiler
with 75mm
sealed
condensate
trap
Boilers without 75mm sealed
condensate trap must be fitted with
a 75mm trap and visible air break
Min Ø 19mm
Internal pipe
75
Soil & vent stack
Minimum
connection
height up to 3
≥ 450
storeys
Figure 2 - Connection of a Condensate Drainage Pipe
Downstream of a Sink, Basin, Bath or Shower Water Trap to
Internal Soil Vent Stack
continued . . . . .
23
SECTION 5 - INSTALLATION INSTRUCTIONS
≥ 25 Below grate
C
ONDENSATE DRAIN - CONT’D.......
Figure 3 - Connection of a Condensate Pump Typical
Method (see manufacturers detailed instructions)
Boiler
with 75mm
sealed
condensate
trap
Min Ø 19mm
Internal pipe
Condensate pump
(Install in accordance with manufacturers instructions)
Visible air break
75
Figure 5 - Connection of a Condensate Drainage Pipe to an
External Rainwater Downpipe (only combined foul/rainwater
drain)
Figure 4 - Connection of Condensate Drainage Pipe to
External Soil & Vent Stack
Boiler
with 75mm
sealed
condensate
trap
Min Ø 19mm
Internal pipe
Boilers without 75mm sealed
condensate trap must be fitted with
a 75mm trap and visible air break
75
Min Ø 30mm
Internal pipe
Water/weather
proof insulation
Soil & vent stack
Minimum
connection
≥ 450
height up to 3
storeys
Figure 6 - Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to
External Drain, Gulley or Ranwater Hopper
Boiler
with 75mm
sealed
condensate
Min Ø 19mm
Internal pipe
Min Ø 30mm
Internal pipe
trap
Terminated
and cut at 45º
43mm 90º male/
female bend
Water/
weather proof
insulation
combined foul/
rain water drain
External air
break
Air gap
68mm Ø PVCU
Strap on fitting
Figure 7 - Connection of a Condensate Drainage Pipe to an
External Purpose Made Soak Away.
Boiler
with 75mm
sealed
condensate
trap
Min Ø 19mm
Internal pipe
75
Min Ø 30mm
Internal pipe
Water/Weather
proof insulation
Max 3m external
pipework
Boiler
with 75mm
sealed
condensate
trap
Min Ø 19mm
Internal pipe
Sink, basin, bath or
shower with integral
overflow and 75mm trap
Visible air break
≥ 100
75
at plug hole
Minimum 30mm
internal pipe
Water/
weather proof
insulation
45º pipe
termination
24
Boilers without 75mm sealed
condensate trap must be fitted with
a 75mm trap and visible air break
2 rows of three Ø12mm holes
25mm centres, 50mm from
the bottom of the tube, facing
away from the house
≥ 300
≥ 500
≥ 25
Limestone
chippings
SECTION 6 - COMMISSIONING INSTRUCTIONS
Gas
Supply
Gas
Pressure
Test
Point
Before commissioning the boiler, the whole gas installation including
the meter (if tted) MUST be purged and tested for gas soundness.
Purge air from the gas installation by the approved methods only.
WARNING. Whilst effecting the required gas soundness test
and purging air from the gas installation, open all windows
and doors, extinguish naked lights and DO NOT smoke.
Ensure that the ue has been installed correctly and no vents are
blocked. Before commencing commissioning, ensure that the CH
system and DHW and cold water system have been ushed. The
CH system needs to be treated with water treatments that are
approved for use with aluminium alloy heat exchangers.
GENERAL
Please Note: The combustion for this appliance has been
checked, adjusted and preset at the factory for operation on
the gas type dened on the appliance data plate. As part of the
commissioning process, the combustion of this appliance must be
checked. A owchart to assist is provided on page 37.
DO NOT adjust the air/gas ratio valve.
Having checked:
- That the boiler has been installed in accordance with these
instructions.
- The integrity of the ue system and the ue seals, as
described in the Flue Installation section.
Proceed to put the boiler into operation as follows:
6.2 CENTRAL HEATING CIRCUIT
Fill the siphon in the condense pipework prior to operating.
In order for the boiler to function correctly, the pressure in the
central heating circuit must be between 1 and 1.5 bar on the
pressure gauge.
Both the boiler and central heating installation must be purged of
any air. The boiler has an auto air vent integral to the pump which
must be loose prior to commissioning.
Add an approved ushing solution to one of the radiators.
Fill the central heating circuit using one of the approved methods
to 1 bar.
Open radiator vent screws and turn off when water appears.
Turn off the lling method and disconnect.
With the system hot, examine all water connections. The system
pressure should not exceed 2.5 bar.
Turn off gas, water and electricity when draining down.
Rell and vent the system, add inhibitor and anti-freeze in the
required concentration and check for water leaks.
Check that the condensate operates and the pipework for any
leaks.
6.3 INITIAL OPERATION
Ensure central heating circuit is full and vented, and pressure
gauge is reading 1.0 bar.
CHECK THE OPERATIONAL (WORKING) GAS INLET
PRESSURE
Set up the boiler to operate at maximum
rate by opening hot tap to maximum
ow.
With the boiler operating in the
maximum rate condition check that
the operational (working) gas pressure
at the inlet gas pressure test point
complies with the requirements - refer to
“Gas Supply” on page 15.
Ensure that this inlet pressure can be
obtained with all other gas appliances in
the property working at maximum.
6.1 DOMESTIC HOT WATER
Turn on the main cold water supply.
Fill and vent the installation by turning on and off the various hot
water taps in the installation.
Check hot water taps in the installation.
Check for and repair leaks as necessary.
6.4 DOMESTIC HOT WATER MODE
Turn the “mode” control knob to tap/radiator icon . Ensure all
external controls are calling for heat. Set the integral timer to ON.
Display reads “C” then “C”
Ensure all radiators warm up evenly. The CH temperature can be
controlled in between max 80ºC and min 45ºC (ow temp).
Check the DHW functions by turning on a hot water tap.
Close the DHW tap and set the integral timer and external
controls to off.
Display will read “0”.
Legend
A. Mode Control Knob
B. DHW/Preheat Control
C. CH Control
off
when burner is lit.
D. Boiler Status
E. Burner ‘on’ Indication
F. Pre Heat on/off Indication
max
e
E
status burner
reset
mode
A
min
preheat
min
max
BCD
preheat
F
25
SECTION 6 - COMMISSIONING INSTRUCTIONS
THE DISPLAY
The user control has one neon and one display to inform the
user about the status. The display will show the status of the
boiler. The neon will show the status of the ame. If no ame
is detected the neon is off. When the ame is detected the
neon will be lit permanently.
Below is a list with display function in normal operation.
0 Standby, no demand for heat present.
Boiler is active for central heating.
Boiler is active for domestic hot water.
Boiler is heating up the plate heat exchanger.
CH circuit water less than 5ºC.
Below is a list with display in fault condition. If the display is
ashing with “L” or “F” with alternate numbers / letters refer to
page 34.
Boiler is in lockout for a specic error. Display will be
blinking, alternating with a number or letter to show which
error is detected.
Boiler has a fault for a specic error. Display will be
blinking, alternating with a number or letter to show which
error is detected.
Service mode
6.5 FINAL CHECKS
Re-light and test for gas soundness.
Set the CH and DHW temperature knobs to the desired settings.
Ensure that the integral timer and/or room thermostat are set to
the required settings.
6.6 HANDING OVER
After completing the installation and commissioning of the system
the installer should:
• Hand the Users Instruction to the owner and emphasise their
responsibilities under the relevant national regulations.
• Explain and demonstrate the lighting and shut down
procedures.
• Explain the operation of the boiler and the use and
adjustment of the system controls to ensure the greatest
possible fuel economy, consistent with the owners heating
and hot water requirements.
• Advise the user of the precautions necessary to prevent
damage to the system and to the building in the event of the
system remaining in operation during frosty condition.
• Explain the function of the boiler fault mode. Emphasise that
if a fault is indicated, refer to Fault Codes in the User Guide.
• Explain and demonstrate system controls, integral timer
functions and boiler reset procedure.
IMPORTANT - Stress the importance of an annual service by
a competent gas registered engineer.
26
SECTION 7 - ROUTINE SERVICING INSTRUCTIONS
Flue Sampling Point
Air Sample
Point
Ensure all caps and seals
are re-fitted after use
7.1
SERVICING SCHEDULE
For the very latest copy of literature for specication, maintenance practices and parts replacement, visit our website www.morcoproducts.co.uk
where you will be able to download the relevant information.
WARNING. Always turn OFF the gas supply at the gas service cock, and switch OFF and disconnect the electricity supply to
the appliance before servicing.
Combustion testing must be carried out by a competent person using a combustion analyser conforming to BS7927.
To ensure the continued safe and efcient operation of the appliance it is recommended that it is checked at regular intervals and
serviced as necessary. The frequency of servicing will depend upon the installation condition and usage but should be carried out at
least annually.
It is the law that any service work must be carried out by a Gas Safe Registered Engineer, or in other countries a qualied and
competent Gas Installer.
INSPECTION
1. Light the boiler and carry out a pre-service check, noting any
operational faults.
2. Check the ue terminal (and terminal guard if tted) is
undamaged and clear of any obstruction.
3. Check all water and gas joints for signs of leakage. Remake
any suspect joints ensuring a gas tightness check is carried
out if applicable and the water system is correctly relled,
vented and re-pressurised.
CLEANING PROCEDURE
Note. In order to carry out either servicing or replacement of
components the boiler upper and lower front panels must
be removed. Refer to Frame 7.2.
1. Clean the main burner. Refer to Frame 7.4.
2. Clean the heat exchanger & condensate trap/siphon. Refer to
Frames 7.5 & 7.6.
Check the main injector for blockage or damage. Refer to
3.
Frame 7.3.
4. Check that the ue terminal is unobstructed and that the ue
system is sealed correctly.
The cleaning procedures are covered more fully in Frames 7.3-7.7
and MUST be carried out in sequence.
IMPORTANT.
5. After completing the servicing or exchange of components
always test for gas tightness.
6. When work is complete the front panels MUST be correctly
retted, ensuring that a good seal is made.
Do NOT OPERATE the boiler if the upper front
panel is not tted.
7. If, for any reason, the condensate trap/siphon has been
removed ensure the trap is relled with water before
reassembling.
8. Check the gas consumption if on metered installations.
Check combustion by connecting the ue gas analyser to the
9.
ue gas sampling point as shown in the diagram and measure
CO & CO2. (Refer to Section 10, page 37).
If the CO/CO2 ratio is greater than 0.004 AND the integrity of
the complete ue system and combustion circuit seals have
been veried and the inlet gas pressure have been veried,
then contact Morco.
GENERAL
Please Note: During routine servicing, and after any maintenance
or change of part of the combustion circuit, the following must be
checked:
- The integrity of the ue system and the ue seals,
- The integrity of the boiler combustion circuit and the relevant seals
- The operational (working) gas inlet pressure at maximum rate.
Turn on one or more DHW taps.
- The combustion performance.
COMPETENCE TO CARRY OUT THE CHECK OF
COMBUSTION PERFORMANCE
Please Note: BS 6798:2009 Specication for installation and
maintenance of gas-red boilers of rated input not exceeding 70kW
net advises that:
- The person carrying out a combustion measurement should have
been assessed as competent in the use of a ue gas analyser and
the interpretation of the results.
- The ue gas analyser used should be one meeting the
requirements of BS7927 or BS-EN50379-3 and be calibrated in
accordance with the analyser manufacturers requirements, and
- Competence can be demonstrated, for example, by satisfactory
completion of the CPA1 ACS assessment (UK Only), which
covers the use of electronic portable combustion gas analysers in
accordance with BS7967, Parts 1 to 4.
SERVICE MODE
To access the service mode:
Using the central heating potentiometer, starting from the 11 o’clock
position, move the thumb piece to the maximum position, back to the
11 o’clock position and then nally nish at the maximum position.
The letter “S” will now be displayed.
To toggle to maximum DHW output move the thumb piece up to
the 11 o’clock position and then back to maximum. A minimum of 3
seconds will reset the boiler back to normal mode.
27
SECTION 7 - ROUTINE SERVICING INSTRUCTIONS
7.2
BOILER UPPER & LOWER FRONT PANEL REMOVAL / REPLACEMENT
REMOVAL
1. Lift the lower front panel access panel.
2. Unscrew the two xing screws, close the access panel to
retain the two screws and hinge the lower front panel down
into the service position.
3. Remove the two upper front panel xing screws, lift the
panel and remove.
2&6
1&7
REPLACEMENT
4. Hook the upper panel onto the top retaining clips.
5. Retain the upper panel with the two xing screws
previously removed ensuring a good seal is made.
6. Swing the lower front panel up and retain with the two
screws.
7. Close the lower front panel access panel.
3&5
7.3
FAN AND VENTURI ASSEMBLY REMOVAL AND CLEANING
1. Disconnect the electrical leads from the fan.
2. Remove the clip from the gas control valve
outlet and ease the pipe upwards rotate and
then ease down to remove.
3. Remove the extended nut on the fan
mounting bracket.
4. Lift off fan and venturi assembly.
5. Inspect the injector for blockage or damage.
6. Inspect fan outlet sealing gasket and
replace if necessary.
Injector
3
5
2
1
28
SECTION 7 - ROUTINE SERVICING INSTRUCTIONS
7.4
BURNER REMOVAL AND CLEANING
1. Ensure the sump is fully drained
2. Undo the two screws and remove the sump cover retaining the lower
ue manifold.
3. Lift the manifold to clear the bottom sealing gasket and remove
manifold.
4. Remove the 2 burner front xing screws and loosen the 2 rear
extended nuts by at least ten turns.
5. Lift off the burner from the combustion chamber. To facilitate the
removal angle the burner as shown.
IMPORTANT
The burner head is a ceramic plaque construction. Care must be taken
to ensure that the burner is not placed down upon its face as this
may cause damage to the ceramic.
6. Brush off any deposits that may be on the ceramic with a SOFT brush.
7. Inspect the sealing gasket around the burner for any signs of damage.
Replace as necessary.
5
3
2
4
2
7.5
CLEANING THE CONDENSATE TRAP/SIPHON
Note: Ensure condensate trap is fully drained before removal.
1. Pull off the rubber pipe at the siphon.
2. Turn the siphon clockwise to disengage and lift to remove.
3. Flush out all deposits with clean water.
4. Reassemble in reverse order
Note. When reassembling ensure the trap is full of water
4
1
29
SECTION 7 - ROUTINE SERVICING INSTRUCTIONS
7.6
CLEANING THE HEAT EXCHANGER
Note: Ensure the condensate trap/siphon
is fully drained before cleaning. Refer to
Frames 7.5.
1. Remove ignition and ame detection
electrodes. Refer to Frames 7.9 & 7.10.
2. It is advisable to replace the sump cover
prior to the water ush process.
3. Thoroughly ush the heat exchanger
by pouring water into the top of the
combustion chamber ensuring the full top
area is covered.
4. Remove the sump cover and clean loose
deposits from the sump.
5. Inspect the ignition and detection
electrodes. Ensure that they are clean
and in good condition - replace if
necessary.
6. Re-t the ignition and ame detection
electrodes. Ensure that earth wire is
connected to the electrode
7. Check that the ignition and detection gaps
are correct. Refer to Frames 7.9 & 7.10.
1
Ignition Electrode
Earth Wire
Flame Detection
3
7.7
REASSEMBLY
Reassemble the boiler in the following order:
1. Ensure that the condensate trap/siphon is full of water.
2. Ret the burner ensuring the sealing gasket is correctly
positioned and free from damage (tighten the 4 xing screws
in the sequence A,B,C,D, shown below).
3. Ret the fan / venturi assembly ensuring the retaining tabs
are correctly positioned and the sealing gasket is correctly
positioned and free from damage.
4. Reconnect the fan electrical leads.
D
B
5. Remove the sump cover and ret the lower ue manifold
as shown.
6. Ret the sump cover.
7. Ret the boiler upper and lower front panels.
IMPORTANT. Ensure that the boiler upper front panel
is correctly tted and that a good seal is made. Replace
seals as necessary.
8. Turn on the gas supply at the gas service cock.
9. Reconnect the electrical supply.
5
30
A
C
SECTION 7 - ROUTINE SERVICING INSTRUCTIONS
3mm
Straight edge
Spark Gap
3.5mm
7.8
BURNER REMOVAL
1. Refer to Frame 7.3.
2. Undo the two screws and remove the sump cover.
3. Lift the manifold to clear the bottom sealing gasket and remove
manifold.
4. Remove the 2 front xing screws and loosen the 2 rear
extended nuts.
4. Lift off the burner from the combustion chamber. To facilitate
the removal angle the burner as shown.
5. Fit the new burner, replacing any damaged or deteriorating
sealing gasket.
6. Reassemble in reverse order.
Check the operation of the boiler.
7.
5
3
2
4
4
2
7.9
IGNITION ELECTRODE
1. Remove the burner. Refer to Frame 7.8.
2. Check dimensions are correct as in
diagram below..
3. Reassemble in reverse order.
FOR REMOVAL:
1. Unplug the ignition lead and remove the
earth lead.
2. Remove the 2 retaining screws and
remove the electrode.
3. Reassemble in reverse order replacing the
gasket if necessary.
Ignition Electrode
31
SECTION 7 - ROUTINE SERVICING INSTRUCTIONS
12.5mm
Straight edge
7.10
FLAME DETECTION ELECTRODE
1. Remove the burner. Refer to Frame 7.8.
2. Check dimensions are correct as in diagram
below.
3. Reassemble in reverse order.
FOR REMOVAL:
1. Unplug the ignition lead and remove the earth
lead.
2. Remove the 2 retaining screws and remove the
electrode.
3. Reassemble in reverse order replacing the
gasket if necessary.
Flame Detection Electrode
7.11
FINAL CHECKS
Turn all controls to “ON” position and check their correct functions in both DHW & CH modes.
Additional replacement of parts information can be found on our website. www.morcoproducts.co.uk
32
SECTION 8 - FACT SHEETS
8 FACT SHEETS
There are a number of detailed fact sheets available for users to download from Morco’s website.
Please visit www.morcoproducts.co.uk
The fact sheets can be located in the troubleshooting section and include:
- Winterisation of Holiday Homes
- Poor Hot Water Delivery - Causes and Solutions
- Low Central Heating Pressure - Fault 1
- Thermostats, Programmers and Thermostatic Radiator Valves
- Combi boiler “cycling”
- Noisy boilers
33
9 FAULT CODES
SECTION 9 - FAULT CODES
DISPLAY CODE ON BOILER
DESCRIPTION
BCC Activation Fault
BCC Fault
Low Water Pressure
Flame Loss
Return Thermistor
Fan Fault
ACTION
Restart the appliance - if the boiler fails to operate then please contact Morco (if under warranty)
or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In all other
countries contact a Registered Gas Installer.
Check system water pressure is between 1 & 1.5bar on the system pressure
pressurise the system see Section 3. If the boiler still fails to operate then please contact Morco (if
under
warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period.
In all other countries contact a Registered Gas Installer.
1. Check other gas appliances in the home are working to conrm a supply is present in the property.
2. If other appliances do not work or there are no other appliances, check the gas supply is on at the
meter/Gas Cylinder and/or pre payment meter has credit. If the boiler fails to operate then please
contact Morco (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the
warranty period. In all other countries contact a Registered Gas Installer.
Return temperature greater than ow temperature. Please contact Morco.
Restart the appliance - if the boiler fails to operate then please contact
or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In all other
countries contact a Registered Gas Installer.
gauge (G). To re-
Morco
(if under warranty)
Flow Thermistor
Return Thermistor
Outside Sensor Failure
Low Mains Voltage
Uncongured PCB
Flow Temperature
Overheat or No Water
Flow
Ignition Lockout
Restart the appliance - if the boiler fails to operate then please contact
or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In all other
countries contact a Registered Gas Installer.
Restart the appliance - if the boiler fails to operate then please contact
or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In all other
countries contact a Registered Gas Installer.
Restart the appliance - if the boiler fails to operate then please contact
or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In all other
countries contact a Registered Gas Installer.
Contact a qualied electrician or your electricity provider.
Uncongured PCB. Please contact
Registered Engineer if outside of the warranty period. In all other countries contact a Registered
Gas Installer.
Check system water pressure is between 1 & 1.5bar on the system pressure
re-pressurise the system see Section 3. If the boiler fails to operate then please contact
(if under
warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty
period. In all other countries contact a Registered Gas Installer.
1. Check other gas appliances in the home are working to conrm a supply is present in the property.
2. If other appliances do not work or there are no other appliances, check the gas supply is on at the
meter/Gas Cylinder and/or pre-payment meter has credit. If the boiler fails to operate then please
contact Morco (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the
warranty period. In all other countries contact a Registered Gas Installer.
3. Check condensate sump, internal pipe work and siphon, ensuring this is not frozen or blocked through
to external pipe work. If frozen defrost using a non-direct heat method. If the boiler fails to operate then
please contact Morco (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of
the warranty period. In all other countries contact a Registered Gas Installer.
Morco
(if under warranty) or alternatively a Gas Safe
Morco
(if under warranty)
Morco
(if under warranty)
Morco
(if under warranty)
gauge (G). To
Morco
34
5 Boiler Resets in
15 minutes
False Flame Lockout
1. Turn electrical supply to boiler off and on.
2. If the boiler fails to operate please contact
Safe Registered Engineer if outside of the warranty period. In all other countries contact a
Registered Gas Installer.
Restart the appliance - if the boiler fails to operate then please contact
or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In all other
countries contact a Registered Gas Installer.
Morco
(if under warranty) or alternatively a Gas
Morco
(if under warranty)
35
SECTION 10 - COMBUSTION CHECK
FLOWCHART FOR CO LEVEL AND COMBUSTION RATIO
CHECK ON COMMISSIONING A CONDENSING BOILER
Important Preliminary Information on Checks
The air gas ratio valve is factory-set and must not be adjusted DURING COMMISSIONING.
PRIOR TO CO LEVEL AND COMBUSTION RATIO CHECK
The installation instructions must have been followed, gas type verified and gas supply pressure / gas rate checked as
required prior to commissioning.
As part of the installation process, ESPECIALLY WHERE A FLUE HAS BEEN FITTED BY PERSONS OTHER THAN
THE BOILER INSTALLER, visually check the integrity of the whole flue system to confirm that all components are
correctly assembled, fixed and supported. Check that maximum flue lengths have not been exceeded and all guidance
has been followed (e.g. Gas Safe Register Technical Bulletin (TB) 008 where chimney/flues are in voids).
The ECGA should be of the correct type, as specified by BS 7967.
Prior to its use, the ECGA should have been maintained and calibrated as specified by the manufacturer. The installer
must have the relevant competence for use of the analyser.
Check and zero the analyser IN FRESH AIR in accordance with the analyser manufacturer’s instructions.
KEY:
CO = carbon monoxide
2
= carbon dioxide
CO
O2 = oxygen
2
Combustion Ratio = The CO reading measured in ppm divided by the CO
ppm = parts per million
GS(I&U)R = Gas Safety (Installation and Use) Regulations
reading first converted to ppm
*Setting to Minimum Rate:
1. Turn the CH temperature control knob to the 11 O’clock position.
2. Create a CH demand by ensuring that the system controls are requesting heat and the boiler Mode
Knob is in the Winter Position.
3. Within an overall time of 3 seconds, turn the CH temperature control knob fully clockwise, back to
11 O’clock and then fully clockwise again.
4. “S” will be shown on the display and the boiler output will be reduced to minimum
5. The boiler will remain at minimum rate for 5 minutes before reverting to normal operation
36
SECTION 10 - COMBUSTION CHECK
Start
Set Boiler to Maximum Gas Rate
In accordance with boiler instructions,
(by fully turning on hot tap) set boiler to
operate at maximum rate (full load
condition). Allow sufficient time for
combustion to stabilise.
Note. Do not insert analyser probe during this
period to avoid possible flooding of sensor.
Insert analyser probe into air inlet test point (where available) and allow
Note. Where no air inlet test point is provided then a flue integrity check with
the analyser is not possible. The installer should verify that flue integrity has
been visually checked in accordance with the “Prior to CO level and
combustion ratio check” (see opposite page) before proceeding to the
“check CO level and combustion ratio at maximum rate” stage below.
Carry Out Flue Integrity Check Using Analyser
Verify Flue Integrity
Analyser readings indicate that combustion products and inlet air
must be mixing. Further investigation of the flue is therefore required.
Check that flue components are assembled, fixed and supported as
per instructions. Check that flue and flue terminal are not obstructed.
Is
2 more than or
O
equal to 20.6% OR CO
2
Yes
less than or equal to
0.2%?
No
Turn off appliance and call Morco Technical Helpline for advice
The appliance must not be commissioned until problems are identified
and resolved. If commissioning cannot be fully completed, the appliance
must be disconnected from the gas supply in accordance with GSIUR.
readings to stabilise.
Is
No
O2 more than or
equal to 20.6% OR CO
2
less than or equal to
0.2%?
Yes
Check CO level and Combustion Ratio
at Maximum Gas Rate
With boiler still set at maximum gas rate,
insert analyser probe into flue gas
sampling point. Allow readings to stabilise
before recording.
Is
No
CO level less
than 350ppm AND CO/CO
2
ratio less than
0.0040?
Check that no seals, e.g. Those on flue extensions, have
been displaced during installation. Rectify if necessary.
Is
CO level less
than 350ppm AND CO/CO
Yes
2
ratio less than
0.0040?
No
Turn off Appliance and Call Morco Technical Helpline
The appliance must not be commissioned until problems
are identified and resolved. If commissioning cannot be
fully completed, the appliance must be disconnected from
the gas supply in accordance with GS(I&U)R. NOTE:
Check and record CO level and combustion ratio at both
maximum AND minimum rate before contacting Ideal.
Ensure test points are capped, boiler case is correctly replaced and all
other commissioning procedures are completed. Complete Benchmark
Yes
Set Boiler to Minimum Gas Rate
(*see opposite page)
In accordance with boiler instructions, set boiler to
operate at minimum rate (to minimum load condition).
Allow sufficient time for combustion to stabilise.
Check CO and Combustion Ratio at Minimum Gas Rate
With boiler set at minimum rate, insert analyser probe into flue
gas sampling point. Allow readings to stabilise before recording.
Is
No
CO level less
than 350ppm AND CO/CO
2
ratio less than
0.0040?
Yes
Boiler is Operating Satisfactorily
No further actions required.
Checklist, recording CO and combustion ratio readings as required.
37
SECTION 11 - WARRANTY
WARRANTY CONDITIONS
The boiler is guaranteed against manufacturing defects for a period of two years from the
date of rst commissioning. However the guarantee is subject to proof of commissioning
in accordance with the Gas Safety (Installation and Use) act 1998.
The guarantee does NOT cover the following issues:
1. Frost damage to any part of the boiler containing water during freezing conditions.
2. The removal of sludge or hard water scale due to lack of antifreeze/inhibitor
3. Damage to electronics caused by a defective electrical supply.
4. Damage or failure caused by insect contamination or blocked water lters.
5. Loss of pressure within the heating system not caused directly by the boiler.
6. Incorrect operation of the boiler caused by defective outlets such as thermostatic
mixers or mono block mixer taps.
7. Damage caused by unauthorised modications to the boiler from original
specications.
38
NOTES
39
For more detailed servicing information, workshop manuals, technical advice, spare parts,
product training, please phone us on 01482 325456 or contact us at the address below:
MORCO PRODUCTS LTD
Morco House, Riverview Road, Beverley, East Yorkshire HU17 0LD