Operating The System.......................................................................................................................................4
1.2 Powering Up With The Control Station ..................................................................................................................4
1.3 Control Station Overview........................................................................................................................................5
1.4 Control Station Function Keys ................................................................................................................................6
1.5 Secondary Function Keys........................................................................................................................................7
1.6 Installer Arming and Disarming..............................................................................................................................7
Programming the Control.................................................................................................................................8
2.2 Local Programming.................................................................................................................................................8
2.4 Area Partitioning .....................................................................................................................................................8
2.5 LED Control Station Programming.........................................................................................................................9
3.1 Menu Options ........................................................................................................................................................10
3.1.2 Set Clock ................................................................................................................................................................ 10
3.1.3 Edit Function Map .................................................................................................................................................. 11
3.1.3.1 Entering a New Value at a Location ............................................................................................................ 11
3.1.3.2 Programming Account Code and Telephone Number Digits ...................................................................... 11
3.1.3.3 Programming Report Codes and Attribute Fields ....................................................................................... 12
3.1.7 Days Until Next Comm Test .................................................................................................................................. 14
3.1.9 Program RF Data .................................................................................................................................................... 14
3.2 Function Map ........................................................................................................................................................14
3.2.1 Area Data Descriptions........................................................................................................................................... 15
3.2.4 User Data Description ............................................................................................................................................ 21
3.2.5.1 Bell Output Activation................................................................................................................................. 24
3.2.6 Global System Options Description ....................................................................................................................... 26
3.2.7 Communicator Data Description ............................................................................................................................ 28
3.2.8 Communication Telephone Numbers Description ................................................................................................. 29
3.2.9 Area Event Reporting Description.......................................................................................................................... 30
3.2.10 Zone Report Codes Description ............................................................................................................................ 32
3.2.11 User Report Codes Description ............................................................................................................................. 33
3.2.12 System Report Codes Description ........................................................................................................................ 34
3.2.13 Area Schedules Description................................................................................................................................... 35
Digital Communicator Table For Contact ID Formats................................................................................ 44
UL Programming Requirements.................................................................................................................... 46
Index .................................................................................................................................................................48
3
1
Operating The System
1.1Introduction
The Moose ZX400/ZX410 Security System incorporates the most desired operational features available today. The ZX400/
ZX410 features ease of installation and programming with an easy-to-operate keypad. Features such as cross-zoning, delay
before dialing, and an audibles “mute” function on the keypad help reduce false alarms. The ZX400/ZX410 also provides
two truly independent partitions which allow the system to be divided into two distinct fully functional areas.
The ZX400/ZX410 is pre-programmed at the factory with one 2-wire smoke detector zone and twelve burglar zones (one
delay, two interior, and nine instant) through Moose’s unique “2 in 1” Zoning™. A Zone Expander Module (ZXEXP) may
be added to provide an additional 2-wire smoke detector zone and up to 16 additional zones.
The ZX400/ZX410 Security Control is easily programmed with any one of four ZX400/ZX410 Controls Stations (LCD,
LED, SSD, or VFD). The Control’ s on-board RAM maintains its data even with the power disconnected. The Control may
also be programmed remotely with the aid of a personal computer (PC) and a modem using Moose’s remote programming
software (RPM2PRO) and a panel support module (PRO400).
The ZX400/ZX410 Security Control allows the division of a single system into two distinct areas. To the customer, each
area appears to be a fully functional system. Each zone and Control Station must be assigned to one of the two areas. The
Control Stations may also be extended to operate in the other area as a secondary area. A user passcode may be assigned to
access and control one or both of the areas. The Control may have up to 50 user codes programmed with 15 different levels
of authority.
1.2Powering Up With The Control Station
The control comes from the manufacturer with a factory set (default) program. The factory default code for user passcode
No. 1 is “1234”. This passcode is authorized to perform all user level functions. The default setting for the installer
passcode is “9632”. The installer passcode can perform the installer level functions. (See section 3.2.4 for the listed
functions.) All zones and Control Stations are assigned to Area 1 at default. The default setting for user passcode No. 50 is
“1245” and it is authorized to perform all user level functions. It is assigned to both Area 1 and 2.
When a Control Station is powered-up, it briefly displays a test pattern followed by its data bus address. The Control
Station will then begin displaying information from the control panel. During the first fifteen seconds after power-up, the
control panel will instruct the Control Station to display the panel’s software revision and flash the AWAY, STAY, NIGHT,
READY, and TROUBLE LEDs.
PANEL REV 1.04
Once the zones are in a secure state, the Control Station displays:
A1 READY TO ARM
READY
TROUBLE
(NOTE: Rev number may change as software is upgraded)
READY
TROUBLE
JAN 21 05:27:52
Nearly every option on the control requires the use of a valid user passcode. The user passcode may be used for functions
in a specific area or system-wide. Most of the options may be performed at any time, even while the control is fully or
partially armed. To perform a function, a user must press the key corresponding to that function and then enter a passcode
with the appropriate authority level. For purposes of discussion, the installer and the end user are both considered system
users, but have different levels of authorization.
4
CANCEL
AWAY
NIGHT
1
234
READY
TROUBLE
5678
11 12109
FIRE
EVENT LOG
OFF
D
STAY
VIEW INFO ALM MEM
1
23
BYPASSCHIME
DELAY ARM
4
56
RST SMOKE TEST PROGRAM
7
89
QUIT ACCESS INSTANT
CLEAR
ENTER
0
HOMENEXT
A
B
C
PREV
CANCEL
AWAY
NIGHT
OFF
STAY
READY
TROUBLE
EVENT LOG
D
VIEW INFO ALM MEM
1
23
BYPASS DELAY ARM CHIME
4
56
RST SMOKE TEST PROGRAM
7
89
QUIT ACCESS INSTANT
CLEAR
ENTER
0
HOMENEXT
LED Control Station
(ZXLED)
D
CANCEL
AWAY
STAY
NIGHT
1
23
BYPASS DELAY ARM CHIME
4
56
RST SMOKE TEST PROGRAM
7
89
QUIT ACCESS INSTANT
CLEAR
ENTER
0
HOMENEXT
EVENT LOG
VIEW INFO ALM MEM
OFF
LCD Control Station
(ZXLCD)
SSD Control Station
(ZXSSD)
VIEW INFO ALM MEM
OFF
D
CANCEL
AWAY
STAY
NIGHT
1
23
BYPASS DELAY ARM CHIME
4
56
RST SMOKE TEST PROGRAM
7
89
QUIT ACCESS INSTANT
CLEAR
0
HOMENEXT
VFD Control Station
(ZXVFD)
EVENT LOG
ENTER
FIGURE 1-1 System Control Stations
1.3Control Station Overview
For SSD, LED, LCD, and VFD Control Stations:
Away, Stay, and Night KeysThese keys, followed by a passcode, arm one or both areas to the AWAY, STAY, or
NIGHT level.
A way, Stay, and Night LED’sThese LEDs backlight the AW AY, ST AY, and NIGHT keys to indicate the armed level
of the Control Station’s primary area. These will flash during Exit Time or during a
Burglar Alarm after Dialer Delay has expired.
Off / Cancel KeyThis key, followed by a valid user code, disarms an area(s), silences and cancels alarms,
and silences trouble conditions.
Instant/Enter KeyThis key is used in programming to store entered data. Also, when pressed during an
exit time from a STAY or NIGHT arming, this key disables both the entry and exit
times for the primary area of the Control Station.
Keypad AudiblesThe piezo resonator activates for conditions including entry and exit notification, alarm,
trouble, chime, etc.
Auxiliary KeysWhen enabled, these keys activate the auxiliary alarms (Fire, Police, Medical Emer-
gency).
Clear/Quit KeyThis key is used to reset any entry error and to allow you to escape out of an operation.
To clear a “Missing Keypad”, “Memory Error”, or “Smoke Trouble” system trouble
condition or to turn off the Duress output, press and hold the CLEAR key for three
seconds.
Keyboard BacklightingThe Control Station contains recessed LEDs to provide a light in dark or dimly lit
environments.
5
For SSD and LED Control Stations only:
Ready LEDThis LED indicates the status of the Burglar zones assigned to the Control Station’s
primary area. It illuminates when the Burglar zones are all secure.
Trouble LEDThis LED will illuminate for system troubles (AC failure, low battery , communication
failure), zone troubles, and Burglar T amper conditions. (See Section 3.2.5.2 for a complete list of trouble conditions.)
For LED Control Stations only:
Zone Status LED’sThese LEDs generally indicate the condition of zones 1 through 12. See the ZXLED
User Guide for how the LEDs indicate the Normal, Faulted, Bypassed, Trouble, and
Alarm conditions.
These LEDs may also display system trouble conditions and programming information.
Fire Zone LEDThis LED indicates the status of the two-wire smoke zone on the main control board
(Zone 30).
For SSD Control Stations only:
Seven Segment DisplayThe three Seven Segment Display (SSD) characters enunciate system status, zone sta-
tus and user information. See the ZXSSD User Guide for details.
1.4Control Station Function Keys
All Control Station function keys (except the View Info Key) require that the function key be pressed followed by a valid
passcode. The passcode’s authority level will determine if the selected function can be performed. While entering the
passcode, there will be a four second time-out for no activity . After the passcode has been entered, there will be a three
minute time-out for no activity. The time-out will return the Control Station to idle. The operator may press the CLEAR
key at any time to return the Control Station to idle.
Below are the functions associated with keys 0 - 9 and a brief description of the functions. For details on the operation of
these functions, as well as on the three arming keys, see the appropriate User Guide.
KEY #1VIEW INFO KEY
This key is used to view information and scroll through alarm and trouble conditions. A passcode is not
required to perform this function.
KEY #2ALM MEM KEY
This key allows you to view the most recent alarm event(s) on the Control Station.
KEY #3EVENT LOG KEY
From an LED or SSD Control Station, this key will initiate printing of the Event Log. From an LCD or
VFD Control Station, this key will allow you to view the Event Log on the Control Station or initiate
printing the log.
KEY #4BYPASS KEY
This key allows you to select zones to be bypassed (removed from the system) and unbypassed (restored
to the system).
KEY #5DELA Y ARM KEY
This key extends or postpones an automatic arming by one hour.
6
KEY #6CHIME KEY
This key turns the chime function on or off for a particular area.
KEY #7RST SMOKE KEY
This key resets all latched smoked detectors and clears “Smoke Troubles”.
KEY #8TEST KEY
This key allows you to perform one of the six following tests: Walk, Battery, Bell, Communications,
Keypad, and RF Signal Strength. After a valid passcode is entered, you may select the test to perform.
KEY #9PROGRAM KEY
This key is used to enter installer or user level programming. User level programming is described in the
appropriate User Guide. Installer level programming is described in Chapter 3.
KEY #0ACCESS KEY
This key is used to activate a door strike or other similar function.
1.5Secondary Function Keys
The Control Station secondary function keys may be activated by pressing the ENTER key followed by Key #1 through
Key #6. A passcode is not required to activate these functions. These functions are activated by pressing the following:
ENTER + KEY #1Turns Lamp Trigger Output ON or OFF
ENTER + KEY #2Turns Universal Output ON or OFF
ENTER + KEY #3Quick Access from Keypad
ENTER + KEY #4Turns Key 4 Output ON or OFF
ENTER + KEY #5Turns Key 5 Output ON or OFF
ENTER + KEY #6Turns Key 6 Output ON or OFF
Please see section 3.2.5 for more details on the operation of these functions. The above outputs are only available to the
user if you program them as Programmable Outputs. If any of these features are made available to the user, please instruct
the user on their operation as it is not detailed in the appropriate User Guide.
1.6Installer Arming and Disarming
The installer passcode may be used to arm one or both areas. It may be used to disarm one or both areas, but only if the area
was armed by the installer passcode. It may be used to silence alarms and to silence trouble conditions. When it is used to
silence a Burglar alarm, it will not disarm the area or cancel the alarm unless the area was armed by the installer passcode.
For a detailed description of arming and disarming procedures, see the appropriate User Guide.
7
Programming the Control2
2.1Introduction
The control may be programmed locally from any LED, SSD, LCD, or VFD Control Station. It may also be programmed
using the remote programming software, RPM/2 Pro.
2.2Local Programming
There are two levels of Control Station programming : User level and Installer level.
User level programming provides the ability to add, change, or delete user passcodes. It also allows Scheduled Arming and
Latchkey operation to be changed. A user passcode with authority level 9, 10, or 15 is required to access the user level
programming (see Section 3.2.4). See the appropriate User Guide for more information regarding user level programming.
Installer level programming allows total customization of the control’s operating features. Only the installer code may
access this level. Anyone attempting installer level programming should be familiar with the contents of this publication
prior to programming the control panel.
NOTE
If the installer code is lost or forgotten, it may be impossible to program the control locally.
If remote programming is used, it is possible to “lockout” or prevent takeover of a control by another installation company
by selecting “Lockout Local Prog.” This prevents the installer passcode from gaining access through local Control Station
programming. The installer passcode may still be used for the non-programming functions described in Section 3.2.4.
,does not affect remote programming.
2.3Remote Programming (RPM/2 Pro)
The entire control database can be programmed remotely through a computer and modem using a remote program called
RPM/2 Pro. To use RPM/2 Pro with the ZX400, you will need RPM2PRO and a panel support module for the ZX400
family (PRO400). Remote programming utilizes extensive error checking and security safeguards, including data encryption, password log-on, panel IDs and agency codes.
Panel IDs are used by RPM/2 Pro to identify a control during a remote programming session. The agency code is used by
the control to identify the remote programmer during initialization of a remote programming session. These codes are
loaded into the control by RPM/2 Pro during the first RPM/2 Pro session. They cannot be viewed by local programming.
The panel ID and agency code work together to prevent illegal takeover by another computer with RPM/2 Pro. Once the
agency code is programmed, the control also prevents local changing of account codes and telephone numbers and disables
the RESTORE DEFAULTS function.
2.4Area Partitioning
The control may be divided (partitioned) into two independent areas. To the customer, each area appears to be a fullfeatured system. This allows one control to be shared by two independent departments within a common structure. Note
that LED Control Stations cannot have a Secondary Area.
When reporting to the Central Station, events such as AC Power Failure, Low Battery, automatic tests, etc., are considered
system reports and are transmitted as an Area 1 account although they are displayed on all Control Stations regardless of
area. All fire related events (i.e.: fire alarms, troubles, etc.) are also considered system events and are reported using an Area
1 account.
8
Each area can be programmed to control separate outputs with a dedicated audible or annunciator. It is also possible to
combine the outputs of both areas so that a central siren, bell or audible can be used. The audible should be positioned so
that it can be heard by all partitions. When partitioning is not desired, simply designate all zones to a single area (Area 1).
An example of a partitioning application is a business that is divided into two departments with both departments occupied
by a different manager. The control communicator would be installed in a secure area (common utility closet) with dedicated and uninterrupted AC power and telephone service. This must be considered when planning the control panel position as the power and phone service to a tenant may be terminated if that tenant leaves.
Each tenant’s compartment is assigned an area with a number of zones, codes, and Control Stations. When an area experiences an alarm or other event, the adjacent system area is not alerted to the event since the Control Station would be
programmed to respond only to events in the assigned area.
Another programming feature is the ability to allow crossover between areas. This allows the user(s) from one area to
operate the other area from a designated Control Station. Programming is discussed in detail later in this manual. By
factory default, users are only allowed to see and operate their primary assigned area. Multi-area operation may be useful
for applications where the security system is installed in a facility that is divided into departments. Each department has a
set of users who are responsible for arming and disarming only the security system to which they are assigned. If desired,
the system may be set up to allow one or more users to have control over both areas.
User 1 assigned to A1
CONTROL
PANEL
AREA 1
ACCT 1
AREA 2
ACCT 2
User 2 assigned to A1
User 3 assigned to A1
User 4 assigned to A2
User 5 assigned to A2
User 6 assigned to A2
1. Maximum Zones = 30
Zn 1
Zn 2
Zn 3
Zn 4
Zn 5
Zn 6
Up to 28 zones may be assigned to any area
in any sequence, except fire (always Area 1).
2. Maximum Users = 50
Any number of users may be assigned to
operate on any combination of areas.
3. Maximum Addressable = 6
SSD, LCD, and VFD Control Stations can be
assigned to operate in both areas if desired.
LED Control Stations can only be assigned
to operate in either Area 1 or Area 2.
= Control Station
Each area has a separate account number at the Central Station and may
report to one or two receivers or one with the second as backup. The type of
activity within a specific area/account may be divided among the two receivers
as well. For example, Open/Close reports may transmit to receiver A and alarm
activity may transmit to receiver B.
Figure 2-1 Area Partitioning
2.5LED Control Station Programming
When in programming mode, an LED Control Station will mimic what is displayed on an SSD Control Station. The top row
of LEDs will correspond to the first SSD character, the second row to the second SSD character and the third row to the
third SSD character. If an SSD character is 1 - 9 or A - F, then that hexadecimal digit will be displayed in binary on the
appropriate row of LEDs. See Chapter 3 for programming with the Control Station. Chapter 3 will also show examples of
SSD, LCD, or VFD Control Station displays. There are no examples for LED Control Stations (see Figure 2-2).
READY and
TROUBLE LEDs
Flash indicating that the
control is in programming
mode
READY
TROUBLE
FIRE
ZONE LEDs (1 - 4)
Display hexadecimal value
1
2
56
910
3
7
11
12
corrresponding to left digit on SSD
4
Control Station (shown is '5')
8
ZONE LEDs (5 - 8)
Display hexadecimal value of
center digit (shown is '6')
ZONE LEDs (9 - 12)
Display hexadecimal value of
right digit (shown is '3')
This section will describe Installer Level Programming as performed locally from a Control Station.
To enter Installer Level Programming, press the PROGRAM (9) key and enter the installer passcode (default = 9632). The
Control Station will then prompt you to select a programming option from 1 to 9 where:
1 = REMOTE CONNECT6 = RESTORE FACTORY DEFAULTS
2 = SET CLOCK7 = SET DAYS UNTIL NEXT COMM TEST
3 = EDIT FUNCTION MAP8 = CALL RPM
4 = EDIT ZONE NAMES9 = PROGRAM RF DAT A
5 = DEFAULT USER CODE 1
3.1.1Remote Connect
After entering programming mode, press the ‘1’ key to perform a Remote Connect. The control will seize the telephone line
and the control station will return to idle. This feature is used to manually connect the control to a remote programming
computer.
REMOTE CONNECT
3.1.2Set Clock
After entering programming mode, press the ‘2’ key for Set Clock programming. The Control Station will go into clock set
mode.
The SSD Control Station will have a Set Clock prompt display . The LCD and VFD Control Station will display the current
hour, minute, month, day, and year (HH:MM MM/DD/YY). The zone LEDs on an LED Control Station will remain off.
The hour must be entered in 24-hour format.
14:58 02/11/96
ENTER = COMPLETE
The operator may start entering numbers from the first hour digit. As a number is entered, it is displayed and the cursor
automatically moves to the next position on the LCD and VFD Control Station. When a digit is entered, the Control Station
will display:
24:58 02/11/96
ENTER = COMPLETE
If the CLEAR key is pressed, the cursor will move back to the first hour digit and any changes that were entered will be
erased, i.e.: the current time and date will be re-displayed. If the CLEAR key is pressed and no changes have been entered,
the Control Station will return to idle with no changes to the time or date.
14:58 02/11/96
ENTER = COMPLETE
10
If the ENTER key is pressed, all changes that were entered will be range checked. The entire time and date need not be
entered. Any fields that are not entered will remain unchanged. If the data entered is within range parameters, the clock will
be updated and the Control Station will return to idle. A “Begin Set Clock” event will indicate the time before the change
and an “End Set Clock” event will indicate the time after the change. If the entered data is out of range, the Control Station
will indicate an error, erase the previous entries and re-display the current time and date.
INVALID SETTING
3.1.3Edit Function Map
After entering programming mode, press the ‘3’ key to enter Edit Function Map mode. The Control Station will prompt you
for a location to be programmed. The location numbers, definitions, and valid entries for the locations are described in
Section 3.2. From this mode, you may edit the entire Function Map except for User Codes and Zone Names. Editing Zone
Names is described in Section 3.1.4. Editing User Codes is described in the appropriate User Guide, but is not accessible
with the installer passcode.
From the LOCATION prompt, enter digits for the desired location number. The digits entered will be displayed. If more
than three digits are entered, the first digit entered will be discarded. If you make a mistake, you may press the CLEAR key
to clear out the location and start over. When the desired location number is displayed, press the ENTER key. The Control
Station will then display the current value programmed at that location.
3.1.3.1 Entering a New Value at a Location
While the Control Station is displaying the value at a location, you can enter digits to change the value at that location. The
new value is displayed as you enter the digits. Other keys work as follows:
ENTER - if pressed after new digits are entered, the displayed value is stored at the current location.
- if pressed with no new digits entered, then it will go to the next location.
‘C’ Key - if pressed, it will go back one location and ignore any digits entered.
CLEAR - if pressed after new digits are entered, erase those digits and re-display the original value at the location.
- if pressed with no new digits entered, then it will return to the LOCATION prompt.
OFF CANCEL- on an LED or SSD Control Station, it will momentarily display the present location number.
NOTE
When you press the ENTER key to store the new value, the system will store the value as entered.
It is the responsibility of the programmer to enter a value within the specified range. If the value
entered is out of the range, then undesirable operation may occur. In some cases, if the value
entered is too large, it will be truncated before it is stor ed causing a different value to be stored than
was entered.
3.1.3.2 Programming Account Code and Telephone Number Digits
When the location being programmed is an account code or telephone number digit (see Sections 3.2.8 and 3.2.9), the value
will be displayed as an “H” followed by a single digit. The “H” indicates that this location is a Hexadecimal field. The valid
entries for these locations are “0” through “F”, where A - F correspond to 10 - 15 respectively.
To program a digit, enter digits as normal. To enter an A - F, enter a ‘1’ followed by a ‘0’ through ‘5’.
As in programming normal fields, if too many digits are entered, the first digit entered will be discarded. The ENTER, OFF
CANCEL, ‘C’, and CLEAR keys will work the same as described above.
11
3.1.3.3 Programming Report Codes and Attribute Fields
When the location being programmed is a report code (see sections 3.2.10 - 3.2.12) or an attribute field (see sections 3.2.1
- 3.2.3 and 3.2.12 - 3.2.13), the value will be displayed as an “H” followed by two digits. The “H” indicates that this
location is a Hexadecimal field. The valid entries for these locations are “00” through “FF”, where A - F correspond with
10 - 15 respectively. The Control Station display will automatically display the hexadecimal value.
To program one of these locations, enter digits as normal. To display a ‘1’ in the first digit location, you must enter a ‘0’
before the ‘1’, i.e. ‘01’ displays a ‘1’. To enter an A - F, enter a ‘1’ followed by a ‘0’ through ‘5’. For example:
EnterTo Get
1-2-3C3
0-1-212
1-818
0-1-1-01A
1-20C
2-121
As in programming normal fields, if too many digits are entered, the first digit entered will be discarded. The ENTER, OFF
CANCEL, ‘C’, and CLEAR keys will work the same as described above.
3.1.3.4 Additional Programming Notes
To exit out of Edit Function Map mode and return the Control Station to the idle state, press the CLEAR key from the
LOCATION prompt. (You may need to press the CLEAR key several times to get to the LOCATION prompt.) An “End
Local Programming” event will not be logged until 255 seconds after you exit programming mode. This is to allow you to
exit and re-enter programming mode repeatedly without logging each one. T o force an “End Local Programming” event to
be logged, immediately (i.e.: to have it reported to the Central Station), press and hold the CLEAR key for three seconds.
When programming the value at the last programming location, the Control Station will return to the LOCATION prompt
if the ENTER key is pressed.
If the panel has been programmed from RPM/2 Pro and the Agency Code has been loaded into the panel, then the locations
corresponding to the telephone numbers and account codes will not be editable.
3.1.4Edit Zone Names
Only the LCD and VFD Control Station may be used to edit zone names. From the Installer Programming Menu, press the ‘4’ key to edit
the zone names. The Control Station will prompt you for a Zone ID to be programmed. The valid Zone IDs are 1 to 30.
Enter a number corresponding to the Zone ID and press ENTER. Once a valid Zone ID is selected, the control will display the Zone ID
and the current Zone Name with the cursor on the first character. Press the key associated with each character . Each keypress will change
the display to the next character listed for that key. The characters available for editing the Zone Name are as follows:
Key #10123456789: ; <=>?@
Key #2ABC
Key #3DEF
Key #4GHI
Key #5JKL
Key #6M NO
Key #7PQRS
Key #8TUV
Key #9W XYZ[ù]^_
Key #0space!“#$% &‘*+,-./
‘A’ KeyUsed to move the cursor back one position
‘C’ KeyUsed to move the cursor forward one position
12
If the ENTER or CLEAR key is pressed and no changes have been made, the Control Station will return to the Zone ID
prompt. If the CLEAR key is pressed and changes have been made, all changes will be cleared and the control station will
return to displaying the original Zone Name. To save any changes made to the Zone Name, press the ENTER key. The
control station will return to the Zone ID prompt. Press the CLEAR key to return to idle.
3.1.5Default User Code 1
The installer passcode does not have the authority to edit user passcodes locally and only high level user passcodes (User
Code 1 at default) have the authority to edit user passcodes. If you need to edit user passcodes or if the User Code 1
passcode is forgotten, this function may be used to reset the User Code 1 passcode back to the default value of “1234”.
After entering programming mode, press the ‘5’ key to default the User Code 1 passcode. The Control Station will prompt
you to re-enter the installer passcode for verification.
TO DEFAULT USER1
ENTER PASSCODE
If the passcode is entered correctly, the Control Station will display an acknowledgment and return back to the idle mode.
USER1 DEFAULTED
3.1.6Restore Factory Defaults
This function provides a means to completely wipe out the panel’s memory and restore it to a factory default state. If
successfully completed, the panel will:
•default the entire Function Map (including Zone Names and User Passcodes)
•clear the Event Log and log a “System Startup” event
•clear all alarm, trouble and armed conditions
•not affect the System Clock (time and date).
•not affect data programmed in the RF Gateway(s)
If the panel has been programmed from RPM/2 Pro and the Agency Code has been loaded into the panel, then this function
will be disabled.
After entering programming mode, press the ‘6’ key to enter Restore Factory Defaults mode. The Control Station will
prompt you to re-enter the installer passcode for verification.
TO DEFAULT PANEL
ENTER PASSCODE
If it is entered correctly, the Control Station will go back to the system powering up display.
13
3.1.7Days Until Next Comm Test
The scheduling of Automatic Communications Tests requires programming a “Comm Test Time-of-Day” and the number
of “Days Between Comm Tests” as described in Section 3.2.7. If “Days Between Comm Tests” is zero, then no automatic
comm tests will occur. Otherwise, a comm test will occur when a Days Until the Next Comm Test counter ticks down to
zero. This function allows you to view that Days counter . If the value displayed is zero or one, then the next comm test will
occur at the next “Comm Test Time-of-Day”. This function also allows you to change the number of Days Until the NextComm Test.
After entering programming mode, press the ‘7’ key to enter Days Until Next Comm test programming. The Control
Station will display the number of days until the next scheduled comm test.
To change this value, enter a number between 0 and 255. If a mistake is make, press the CLEAR key to start over. If a
number greater than 255 is entered, the first digit entered will be discarded. When the desired number of days is displayed,
press the ENTER key. The Control Station will return to idle. To exit out of this function without adjusting the number of
days, press the CLEAR key.
3.1.8Call RPM
This option is not available at this time.
3.1.9Program RF Data
This option is not available at this time.
3.2Function Map
To edit the Function Map, press the PROGRAM (9) key, enter the installer passcode, and press the ‘3’ key to select the Edit
Function Map programming option. The Control Station will prompt for a location to be programmed. All function map
locations can be programmed except for user codes and zone names.
NOTE
When entering values into the programming locations, it is possible to enter values which exceed
the valid range of the programmed options. It is the responsibility of the installer to ensure the
correct value of any entry programmed into the control. The valid entries for each location are
detailed in the following sections.
14
3.2.1Area Data Descriptions
Area Data Default Table
AREA 1AREA 2
LocationDefaultLocationDefault
AWAY Exit Time (sec)[1]60[12]60
STAY/NIGHT Exit Time (sec)[2]60[13]60
Entry Time 1 (sec)[3]20[14]20
Entry Time 2 (sec)[4]40[15]40
Pre-Alarm Time (sec)[5]0[16]0
‘B’ Key Alarms[6]2[17]2
‘C’ Key Alarms[7]1[18]1
Closing Ringback[8]0[19]0
Burglar Audible Lockout[9]0[20]0
Swinger Shunt[10]0[21]0
Area Attributes[11]H-09[22]H-09
The following table refers to programming locations 1 through 22.
ItemValid RangeDescription
AWAY Exit Delay Time0 to 255 seconds
STAY & NIGHT Exit0 to 255 seconds
Time
Entry Delay Time 10 to 255 seconds
Entry Delay Time 20 to 255 seconds
Pre-Alarm Warning Time0 to 255 seconds
‘B’ Key Alarms0 = No Keypad Sounder or Bell
Output (invisible)
1 = Keypad Sounder Only
2 = Keypad Sounder and Bell Output
‘C’ Key Alarms0 = No Keypad Sounder or Bell
Output (visible)
1 = Keypad Sounder Only
2 = Keypad Sounder and Bell Output
Closing Ringback0 = Ringback Output
1 = Ringback Output and Keypads
2 = Ringback Output, Bell Output and
Keypads
Burglar Audible Lockout0 = No Lockout
1 to 15 = Alarms for an Area
Swinger Shunt0 = No Shunt
1 to 15 = Violations for a Zone
Time in seconds for all Burglar zones, may be audibly
annunciated. (See Section 3.3, Programming Note 1.)
Time in seconds for all Burglar zones, always silent.
Time in seconds to enter Burglar zones defined as Delay #1,
may be audibly annunciated.
Time in seconds to enter Burglar zones defined as Delay #2,
may be audibly annunciated.
Time in seconds to correct a false alarm, always audible. (See
Section 3.3, Programming Note 2.)
Defines the annunciation of an alarm activated by the Police
key.
Defines the annunciation of an alarm activated by the Medical/
Emergency key.
Determines how the system annunciates the successful
transmission of an AWAY closing report to the Central Station.
Determines the number of times that a Bell Output may be
activated during an armed cycle, resets with disarm.
Determines the number of violations that may occur from an
armed burglar zone before that zone is automatically bypassed.
15
Area Attributes00 to FF
(see the Area Attribute Table)
Bypassing - enables selective bypassing of any zone that is defined
as bypassable in this area.
Force-Arming - permits arming of the area with zones faulted.
Faulted zones are temporarily bypassed and return to operation if the
fault is corrected. Only zones that are defined as bypassable may be
force-armed. See Section 3.3, Programming Note 4.
Exit Arm - see Section 3.3, Programming Note 3.
3 Second Panic Keys - requires all panic keys to be pressed and held
for approximately 3 seconds in order to activate alarm condition.
Only pertains to Control Stations that are Primary to this area.
Double Press Panic Keys - requires all panic keys to be pressed
twice within one second to activate. Only pertains to control stations
that are Primary to this area.
Two Button Arm - enables quick arming by pressing AWAY, STAY,
or NIGHT followed by the ENTER key. Cannot be used with forcearming
Double Press Arm - enables quick arming by pressing AWAY, STAY,
or NIGHT twice. Cannot be used with force-arming.
Open After Alarm - enables opening reports to be reported only if
they occur after an alarm. All “opening” events will be logged in the
Event Log regardless of setting.
Display Bypass Armed - when armed in STAY or NIGHT mode with
bypassed or force-armed zones, Control Stations with the area as the
Primary area will indicate that there are zones that are bypassed.
Area Attribute T able
Enter For:0123456789ABCDEF
First Digit
All Features Below Disabled*
Two Button Arm********
Double Button Press Arm********
Open After Alarm********
Display Bypassed Armed********
Keypad TypeLEDLEDSSDSSDLCD/VFDLCD/VFD
Keypad Attribute[23]H-1C[25]H-1C[27] H-1C[29]H-1C[31]H-1C[33]H-1E
Access Time (sec)[24]5[26]5[28] 5[30]5[32] 5[34]5
The following table refers to programming locations 23 through 34.
ItemValid RangeDescription
Keypad Attributes00 to FF
(see the Keypad
Attribute table.)
Access Time *0 = Toggle ,
1 - 255 seconds
Primary Area 1 or 2 - determines which area the Control Station’s status indicator will
reflect and which area the Control Station will display area status for when it is idle.
Secondary Area Enabled - see the Programming Note 5 in Section 3.3.
‘A’ Key Enabled - defines if the Fire key is to be enabled at this Control Station
‘B’ Key Enabled - defines if the Police key is to be enabled at this Control Station.
‘C’ Key Enabled - defines if the Medical/Emergency key is to be enabled at this Control
Station.
Silent Exit Time - silences the exit alert at the Control Station.
Silent Entry Time - silences the entry alert at the Control Station. This does not affect
Pre-Alarm Warning Time.
Silent Trouble - silences the trouble conditions at the Control Station.
Time in seconds for an access output activated from this Control Station. Toggle access
feature allows the output to latch ON/OFF.
All access outputs assigned to this Control Station are affected when the access function
and a valid code is entered for this Control Station (see Section 3.2.5). It is not area
dependent. Typically used to activate electrically operated door strikes.
* This control is not a UL Listed Access Control System. The access feature should not be used in UL Listed installations.
Keypad Attribute Table
Enter For:0123456789ABCDEF
First Digit
All Features Below Disabled*
‘C’ Key Enabled********
Silent Exit Time********
Silent Entry Time********
Silent Troubles********
Second Digit
Primary Area 1****
Primary Area 2****
Primary Area 1, Secondary Area 2****
Primary Area 2, Secondary Area 1****
‘A’ Key Enabled********
‘B’ Key Enabled********
NOTE: If the First Digit entered is ‘1’, it must be entered as ‘01’. A = 10; B = 11; C = 12; D = 13; E = 14; F = 15
17
3.2.3 Zone Data Descriptions
Zone Data Default Table
Zone T ypeAreaExpansion ZoneBurglar Zone Attribute Zone Attribute
Zone 01[35]1[36]1[37]H-0D[38]H-37
Zone 02[39]1[40]1[41]H-03[42]H-37
Zone 03[43]1[44]1[45]H-03[46]H-37
Zone 04[47]1[48]1[49]H-0C[50]H-37
Zone 05[51]1[52]1[53]H-0C[54]H-37
Zone 06[55]1[56]1[57]H-0C[58]H-37
Zone 07[59]1[60]1[61]H-0C[62]H-37
Zone 08[63]1[64]1[65]H-0C[66]H-37
Zone 09[67]1[68]1[69]H-0C[70]H-37
Zone 10[71]1[72]1[73]H-0C[74]H-37
Zone 11[75]1[76]1[77]H-0C[78]H-37
Zone 12[79]1[80]1[81]H-0C[82]H-37
Zone 13[83]1[84]0[85]0[86]H-0C[87]H-37
Zone 14[88]1[89]0[90]0[91]H-0C[92]H-37
Zone 15[93]1[94]0[95]0[96]H-0C[97]H-37
Zone 16[98]1[99]0[100]0[101]H-0C[102]H-37
Zone 17[103]1[104]0[105]0[106]H-0C[107]H-37
Zone 18[108]1[109]0[110]0[111]H-0C[112]H-37
Zone 19[113]1[114]0[115]0[116]H-0C[117]H-37
Zone 20[118]1[119]0[120]0[121]H-0C[122]H-37
Zone 21[123]1[124]0[125]0[126]H-0C[127]H-37
Zone 22[128]1[129]0[130]0[131]H-0C[132]H-37
Zone 23[133]1[134]0[135]0[136]H-0C[137]H-37
Zone 24[138]1[139]0[140]0[141]H-0C[142]H-37
Zone 25[143]1[144]0[145]0[146]H-0C[147]H-37
Zone 26[148]1[149]0[150]0[151]H-0C[152]H-37
Zone 27[153]1[154]0[155]0[156]H-0C[157]H-37
Zone 28[158]1[159]0[160]0[161]H-0C[162]H-37
Zone 29*[163]0[164]H-63
Zone 30**[165]2[166]H-63
* Zone 29 is the Two-Wire Smoke Zone on the Expander Module
** Zone 30 is the Two-Wire Smoke Zone on the Control Board
18
The following table refers to programming locations 35 - 166.
ItemValid Range
Zone Type0 = Not Used
1 = Burglar
2 = 24 Hour Fire
3 = 24 Hour Holdup
Note: Zone 29 & 30
may only be programmed as 24 Hour
Fire, Verified Fire or
Not Used; any other
will be interpreted as
Not Used. All other
zones may be
programmed as any
10 = Verified Fire
zone type.
11 = Fire Supervisory
12 = Listen-In Module Input
Area Number0 = Disable
1 = Area 1
2 = Area 2
Expansion Zone0 = ZXEXP Zone
1 = RF Gateway 1 Zone
2 = RF Gateway 2 Zone
3 = ZEM Zone
Burglar Zone Attributes00 to FF
(see the Burglar Zone
Attribute Table.)
Zone Attributes00 to FF
(see the Zone Attribute Table.)
Description
Critical Condition Monitor (CCM), no local display
May be used to activate an output that is programmed as
Universal. Only the Universal Logged is posted in the Event
Log when activated. No events are reported to the Central
Station.
Upon activation, control resets switched smoke power. The
loop is ignored for 30 seconds. Subsequent activation within
the next 60 seconds causes an alarm.
See Section 3.3, Programming Note 11.
Determines which area the zone belongs to. Fire zones are
visible to both areas regardless of settings.
Determines which data bus device the system will poll to get
the zone’s status data.
Reserved for future use.
Reserved for future use.
Reserved for future use.
See Section 3.3, Programming Notes 2, 6, and 7 for a
complete description of the Burglar Zone Attributes.
Bell Output on Alarm - determines if Bell Output activates
due to an alarm from the zone. See Section 3.3, Programming
Note 8.
Keypad Sounder on Alarm - determines if control station
sounder activates due to an alarm from the zone. See Section
3.3, Programming Note 8.
Bypassable - determines if a zone may be bypassed or forcearmed. See Section 3.3, Programming Note 9.
Senior Watch - see Section 3.3, Programming Note 10.
Zone Supervision - determines how opens and shorts are
handled.
Fast Zones - only applies to zones 1 - 12. A Fast Zone on
zones 1 - 6 has a loop response time of 80 msec. A Fast Zone
on zones 7 - 12 has a loop response time of 20 msec.
19
Burglar Zone Attribute Table
Enter For:0123456789ABCDEF
First Digit
Standard (all below disabled)*
Chime Always********
Verifying********
Self-Verifying********
Sentry Test********
Armed AWAY,
Second Digit Armed AW AYArmed A WAYArmed AW AYST A Y & NIGHT
only (interior) & STAY & NIGHT (perimeter)
Instant****
Delay 1****
Delay 2****
Follower****
Arm STAY********
Arm NIGHT********
Zone Attribute Table
Enter For:0123456789ABCDEF
First Digit
Invalid**
Alarm on Open - No Trouble (EOL optional)**
Alarm on Short - No Trouble (EOL optional)**
Alarm on Open or Short - No Trouble**
(with EOL)
Trouble on Open or Short**
Alarm on Open - Trouble on Short**
Alarm on Short - Trouble on Open**
Alarm on Open or Short - Trouble on
Open when Disarmed (Burg only)**
Fast Zones*******
Second Digit
All Features Below Disabled*
Bell Output on Alarm********
Keypad Sounder on Alarm********
Bypassable********
Senior Watch********
NOTE: If the First Digit entered is ‘1’, it must be entered as ‘01’. A = 10; B = 11; C = 12; D = 13; E = 14; F = 15
20
3.2.4User Data Description
The user data block is used to set the level of authority that determines the level of activity the user can perform on the
control and the areas that a particular user can perform operations on. The passcodes associated with each user may only be
programmed through user level programming as described in the appropriate User Guide.
User Data Code Default Table
CodeAuthority LevelOperation Area CodeAuthority LevelOperation Area
User 011234[167]10[168]1User 260000[217]6[218]1
User 020000[169]6[170]1User 270000[219]6[220]1
User 030000[171]6[172]1User 280000[221]6[222]1
User 040000[173]6[174]1User 290000[223]6[224]1
User 050000[175]6[176]1User 300000[225]6[226]1
User 060000[177]6[178]1User 310000[227]6[228]1
User 070000[179]6[180]1User 320000[229]6[230]1
User 080000[181]6[182]1User 330000[231]6[232]1
User 090000[183]6[184]1User 340000[233]6[234]1
User 100000[185]6[186]1User 350000[235]6[236]1
User 110000[187]6[188]1User 360000[237]6[238]1
User 120000[189]6[190]1User 370000[239]6[240]1
User 130000[191]6[192]1User 380000[241]6[242]1
User 140000[193]6[194]1User 390000[243]6[244]1
User 150000[195]6[196]1User 400000[245]6[246]1
User 160000[197]6[198]1User 410000[247]6[248]1
User 170000[199]6[200]1User 420000[249]6[250]1
User 180000[201]6[202]1User 430000[251]6[252]1
User 190000[203]6[204]1User 440000[253]6[254]1
User 200000[205]6[206]1User 450000[255]6[256]1
User 210000[207]6[208]1User 460000[257]6[258]1
User 220000[209]6[210]1User 470000[259]6[260]1
User 230000[211]6[212]1User 480000[261]6[262]1
User 240000[213]6[214]1User 490000[263]6[264]1
User 250000[215]6[216]1User 501245[265]10[266]3
The following table refers to programming locations 167 - 266
ItemValid RangeDescription
Authority Level0 to 15See the Authority Level table on following page for options available .
(Enter 0 to disable)
Areas of Operation0 = DisabledDetermines which areas the passcode can be used to perform operations on.
1 = Area 1If a 3 is selected, the control station it is used on must be programmed for
2 = Area 2both areas in order to access both areas.
3 = Both
21
Authority Levels
Authorities levels 1 through 10 are the general purpose levels with level 10 having the highest capabilities. Level 11 is for
limited disarm capabilities (ie: Maid’s passcode). Level 12 is for User on Premise reporting. Level 13 is for Duress reporting.
For High Level Security applications, only levels 14 and 15 should be used. If levels 14 and 15 are used, all other users should
be set to Level 0 (zero).
Level 14 needs 2 different level 14 passcodes in order to activate any of the options available. The Control Station will beep 4
times after the 1st passcode is entered signifying that it has been accepted. The 2nd passcode may then be entered. Level 15 is
for maintenance activities only. Level 15 does not allow the user to arm or disarm the system, only to maintain it.
See the table below for the options available for each authority level. T o disable all capabilities, set the authority level to zero (0).
Authority Level
Capabilities123456789101112131415
Access from Keypad*************
Chime Enable/Disable***********
Silence Bell without Disarm***
Arm (AWAY, STAY, NIGHT)************
Change Arming Level************
Remote Connect************
Silence/Cancel Alarm********
Silence Trouble*********
Disarm********
V iew Alarm Memory*********
Reset Smoke Power*********
Bypass Zones******
Force-Arm*********
Abort Exit Arm*****
Walk Test******
Comm Test******
Bell Test******
Battery Test******
Keypad Test******
Delay Scheduled Arming*****
View & Print Event Log*****
Edit Scheduled Arming****
Edit Latch Key Operation**
Set Clock**
Abort Auto-Arming****
Edit Zone Names**
Edit User Codes***
Disarm if Armed by a Level 11 User Passcode*
Silence/Cancel Alarm if not Armed or if Armed*
by a Level 11 Passcode
Silence Bell without Disarm if Armed by other*
than a Level 11 Passcode
Access from Keypad with User on Premises Report*
Silence/Cancel Alarm with User on Premises Report*
Disarm with User on Premises Report*
Access from Keypad with Duress*
Arm (AWAY, STAY, NIGHT) with Duress*
Change Arming Level with Duress*
Force-Arm with Duress*
Silence/Cancel Alarm with Duress*
Disarm with Duress*
** For High Level Security applications only
22
The Installer passcode has the authority level to perform the following operations:
•Access from KeypadInitiate Call to RPM/2 Pro
•Arm (AWAY, STAY, NIGHT)Remote Connect
•Disarm if Armed by an InstallerReset Smoke Power
•Change Arming LevelProgram RF Data
•Default User Code 1RF Signal Strength
•Edit Zone NamesSet Clock
•Force-ArmSilence Trouble
•View & Print Event LogView Alarm Memory
•Bypass ZonesBattery Test
•Chime Enable/DisableBell Test
•Default Function MapComm Test
•Edit Function Map (except Zone Names & User Codes)Keypad Test
•Silence/Cancel Alarm if not Armed or if Armed by InstallerWalk Test
Silence Bell without Disarm if Armed by other than InstallerAdjust Days Until Next Auto Comm Test
• Disabled if Lockout Local Programming is enabled (See table in Section 3.2.14.)
3.2.5Output Definitions Description
This data block is used to assign the programmable outputs. The control is equipped with one programmable on-board
output (PGO1) and one bell output (BELL). Additional outputs can be obtained in groups of ten by the addition of output
driver modules (ZXODM) or a zone expander (ZXEXP). The 10 outputs on ODM2 are identical to the 10 outputs on the
zone expander.
Each output is assigned a condition (i.e.: Burglar, Fire, Status, Alarm) and areas to which it should respond when the
condition is active in those areas. For access conditions, the output is assigned to a control station(s). Output conditions 1
- 8 ignore the area setting.
Output Definitions Default Table
ConditionArea or KeypadConditionArea or Keypad
Loc DefaultLocDefaultLocDefaultLocDefault
Control - BellZone Expander or ODM 2
Output 00[267]1Output 01[290]9[291]1
ControlOutput 02[292]1[293]1
Output 01[268]13[269]1Output 03[294]10[295]1
ODM 1Output 04[296]11[297]1
Output 01[270]9[271]1Output 05[298]15[299]1
Output 02[272]1[273]1Output 06[300]26[301]1
Output 03[274]10[275]1Output 07[302]14[303]1
Output 04[276]11[277]1Output 08[304]21[305]1
Output 05[278]15[279]1Output 09[306]29[307]1
Output 06[280]26[281]1Output 10[308]34[309]1
Output 07[282]14[283]1
Output 08[284]21[285]1
Output 09[286]29[287]1* Output conditions 34 and 35 add combinations of keypads 1 - 6.
Output 10[288]34[289]1 Conditions 9 - 33 are specified as a combination of Areas 1 & 2.
23
The following table refers to programming locations 267 through 309.
ItemValid Range
Output ConditionSee Section 3.2.5.2 for complete descriptions
0 = Not Used19 = Exit Time
1 = Fire Alarm20 = Entry Time
2 = Fire Supervisory21 = Pre-Alarm Warning Time
3 = Duress22 = Annunciation
4 = Low Battery23 = Auto-Arm Warning
5 = Failed to Comm24 = Closing Ringback
6 = Telco Line Fault25 = Trouble
7 = Telco Line Seized26 = Chime
8 = Ground Start27 = Universal
9 = Burglar Alarm28 = Listen-In Module Output
10 = Hold-up Alarm29 = Lamp Trigger
11 = Auxiliary Alarm 30 = Key 4 Output
12 = Bell Output Trigger31 = Key 5 Output
13 = Violation32 = Key 6 Output
14 = Ready33 = RF Annunciator
15 = Armed AWAY34 = Access by Keypad
16 = Armed STAY35= Quick Access by Keypad
17 = Armed NIGHT101 - 130 = Zone (1 to 30) Violated
18 = Armed and Exit Time Expired201 - 230 = Zone (1 to 30) In Alarm or Senior Watch
Areas of Operation(for Output Conditions 9 - 33)[add up selections]
1 = Area 1(for Output Conditions 34 & 35)
2 = Area 21 = Control Station 1
3 = Both2 = Control Station 2
4 = Control Station 3
8 = Control Station 4
16 = Control Station 5
32 = Control Station 6
If the Output Condition is “Ready”, “Armed AWAY”, “Armed STAY”, “Armed NIGHT”, “Armed & Exit Time Expired”,
“Exit Time”, “Entry Time”, “Annunciation”, “Key 4 Output”, “Key 5 Output”, or “Key 6 Output”, then the Areas of
Operation should be limited to a single area.
3.2.5.1 Bell Output Activation
The Bell Output is assignable to a combination of areas and may activate due to an alarm condition in any of the areas. A
Fire Alarm from a Fire or Verified Fire zone or the ‘A ’ Key will always activate the Bell Output. A Bur glar Alarm, a Burglar
Tamper, a Holdup Alarm, the ‘B’ Key, an Auxiliary Alarm, or the ‘C’ Key may activate the Bell Output.
Each alarm type is programmable for its Bell Output operation. (See Section 3.2.6.) If more than one alarm type is active
at the same time, the Bell Output will annunciate the highest priority alarm. The priority order is Fire, Auxiliary, Burglar,
and Holdup.
If any of the Bell Output’ s areas have Closing Ringback Annunciation set to “Ringback Output, Keypads, and Bell Output”,
the Bell Output will emit a two (2) second ringback tone. (See Section 3.2.1.)
24
3.2.5.2 Programmable Output Activation
The programmable outputs will be activated according to their Output Condition listed in the following table. The output
will go ON STEADY for the following conditions unless otherwise specified in the table.
ConditionOutput Becomes Active When:
Fire AlarmA Fire or Verified Fire zone or an ‘A ’ Key is in alarm.
Fire SupervisoryA zone defined as Fire Supervisory is in alarm.
DuressA Duress code has been used. To turn off, press the CLEAR key for 3 seconds.
Panel Low BatteryA Panel Low Battery trouble condition occurs.
Failed to CommA Failed to Comm trouble condition occurs.
Telco Line FaultA T elco Line Fault trouble condition occurs.
Telco Line SeizedThe system seizes the telephone line for an RPM connection or prior to making a call to the Central Station.
Ground StartA Telco ground start circuit is triggered for one second.
Burglar AlarmA Burglar or a Bur glar Tamper defined zone is in alarm.
Holdup AlarmA Holdup zone or an ‘B’ Key is in alarm.
Auxiliary AlarmAn Auxiliary zone or an ‘C’ Key is in alarm.
Bell Output TriggerIn the same manner as the Bell Output (see Section 3.2.5.1).
ViolationA Fire, Fire Supervisory, Burglar , Auxiliary, Visible Holdup or Burglar Tamper is in alarm.
ReadyThe area is ready to arm.
Armed A WA YThe area has been armed in the AW AY mode.
Armed STAYThe area has been armed in the ST A Y mode.
Armed NIGHTThe area has been armed in the NIGHT mode.
Armed & Exit Time ExpiredThe area has been armed in any way and the exit time has expired.
Exit TimeThe exit time starts in its area due to an A WA Y, ST AY , or NIGHT arm. The output will go ON STEADY
until the last ten seconds, then it will PULSE for the last ten seconds. When the Exit Time expires, it will go
ON STEADY for two seconds.
Entry TimeThe entry time starts in its area. The output will stay ON STEADY until the last ten seconds of entry time.
During the last ten seconds of entry time, it will PULSE.
Pre-Alarm W arning TimeAny of its areas are in Pre-Alarm Warning T ime. The output will PULSE when any of its areas are in Pre-
Alarm Warning Time.
AnnunciationThe Annunciation output operates like a combination of the Exit T ime, Entry Time, and Pre-Alarm Warning
Time outputs. When the exit time starts in its area due to an AW AY, STA Y, or NIGHT arm, the output will go
ON STEADY until the last ten seconds. During the last ten seconds, it will PULSE and when the exit time
expires, it will go ON STEADY for two seconds. When the entry time starts in its area, the output will go ON
STEADY until the last ten seconds of entry time. During the last ten seconds, it will PULSE. When in PreAlarm W arning Time, the output will PULSE.
Auto Arm WarningThe timer activates for 3 seconds for each minute of the ten minutes left before Auto-Arming occurs. It will
also activate at one minute and two minutes until before an Exit Arm occurs.
Closing RingbackA Closing Report due to an AW AY arm from a Control Station or keyswitch has been successfully transmit-
ted to the Central Station.
TroubleA System Trouble condition is present. (Following this table is a list of T rouble Conditions.)
ChimeA Disarmed Chime Always Burglar zone in any of its areas is violated, a Disarmed Perimeter (Arm on STAY
& Arm on NIGHT) Burglar zone in any of its areas is violated and that area has Chime Enabled.
UniversalA Universal or Universal Logged zone is violated. (See Section 3.3, Programming Note 16.)
Listen-InAn alarm event is reported to the Central Station from one of the output’ s areas. (See Section 3.3, Program-
ming Note 11.)
Lamp TriggerAny of its areas are in exit time, entry time and five minutes after entry time. The Output will go ON
STEADY when its areas are in entry time and will stay ON STEADY until five minutes after entry time
expires or five minutes after disarm (whichever is shorter). (See Section 3.3, Programming Note 17.)
Key 4 OutputENTER + Key #4 is pressed on a keypad primary to its area. May be used to toggle an output ON/OFF.
Key 5 OutputENTER + Key #5 is pressed on a keypad primary to its area. May be used to toggle an output ON/OFF.
25
Key 6 OutputENTER + Key #6 is pressed on a keypad primary to its area. May be used to toggle an output ON/OFF.
RF AnnunciatorReserved for future use.
Access by KeypadAny of its Control Stations have an Access timer that is running or ON. (See Section 3.3, Programming Note
18.)
Quick Access By KeypadAny of its Control Stations have a Quick Access timer that is running or ON. (See Section 3.3, Programming
Note 18.)
Zone ViolatedThe zone is violated
Zone in Alarm or Senior W atchThe zone goes into alarm. For a Burglar zone, it will deactivate when the alarm is silenced. For Fire, Holdup,
Auxiliary, Bur glar Tamper, Verified Fire, and Fire Supervisory zones, it will deactivate when the zone restores
after the alarm has been silenced. The zone goes into Senior W atch Trouble until the condition restores (See
Section 3.3, Programming Note 10.)
The list of Trouble conditions are as follows:
AC Power FailureLow BatteryMemory Error
Communication FailureSilenced Fire AlarmFire Supervisory
Smoke TroubleCall RPM FailedSilenced Burglar Tamper
Missing KeypadZone TroubleZone Missing
Fire TroubleTelco Line FaultBell Fault
RF JammingRF Point Not ReportingRF Point Tampering
RF Point Low Battery
3.2.6Global System Options Description
Global System Options Default Table
TimeTime
LocDefaultLocDefault
Fire Cutoff Time (min)[310]0AC Failure Delay (min)*[317]30
Burglar Cutoff Time (min)[311]10Senior Watch Time (hrs)[318]24
Holdup Cutoff Time (min)[312]10System Attributes[319]H-31
Aux Cutoff Time (min)[313]10Passcode Attempts[320]8
Universal Output Time (sec)[314]0AC Cycles **[321]0
Delay Before Dial (sec)[315]0
Fire Delay Before Dial (sec)[316]0 * ODD = Silent, EVEN = Audible
** 0 = 60 Hz, 1 = 50 Hz
The following table refers to programming locations 310 through 321:
ItemValid RangeDescription
Fire Cutoff Time0 = No Cutoff,
1 to 255 minutes
Burglar Cutoff Time0 = No Cutoff,
1 to 255 minutes
Holdup Cutoff Time0 = No Cutoff,
1 to 255 minutes
Auxiliary Cutoff Time0 = No Cutoff,
1 to 255 minutes
Universal Output Time0 = Toggle ON,
1 to 255 seconds
Determines the time in minutes for Bell Output and Fire Alarm signaling device.
Determines the time in minutes for Bell Output and Burglar Alarm signaling
device.
Determines the time in minutes for Bell Output and Holdup Alarm signaling
device.
Determines the time in minutes for Bell Output and Auxiliary Alarm signaling
device.
Controls the timer for output programmed as Universal. Activated from Universal
or Universal Logged zones. (See Section 3.3, Programming Note 16.)
26
Delay Before Dial0 to 255 seconds
Fire Delay Before Dial0 to 255 seconds
AC Trouble Delay0 to 255 minutes
Senior Watch Time0 - 42 hours
System Attributes00 to FF
(see the System
Attribute Table.)
Passcode Entry Lockout0 = No Lock,
1 to 15 attempts
AC Cycles0 = 60 Hz
1 = 50 Hz
Time in seconds that a user has after a Burglar, Holdup or Auxiliary Alarm from a zone
has occurred to silence the alarm with a disarm and abort the alarm event. (See
Section 3.3, Programming Note 12.)
Time in seconds that a user has after a Fire Alarm from a zone has occurred to silence
the alarm and abort the alarm event. (See Section 3.3, Programming Note 13.)
Time in minutes that AC power must be down until the condition is reported to the
Central Station. If time set is an odd number, it will be silent, if time set is an even
number, it will be audible at the keypad.
Time in hours during which there is no activity before a Senior Watch event is logged to
be reported. (See Section 3.3, Programming Note 10.)
Fire Bell (Steady/Temporal) - determines the operation of the Bell Output during a Fire
alarm.
Burglar Bell (Steady/Pulsed) - determines the operation of the Bell Output during a
Burglar alarm.
Holdup Bell (Steady/Pulsed) - determines the operation of the Bell Output during a
Holdup alarm.
Auxiliary Bell (Steady/Pulsed) - determines the operation of the Bell Output during an
Auxiliary alarm.
Log Alarm Abort Events - if enabled, Abort Alarm events are posted in the Event Log.
(See Section 3.3, Programming Notes 12 & 13.)
Log Access Events - if enabled, the “Keypad Access Activated” events will be posted in
the Event Log. These events are not reportable to the Central Station.
Print Access Only R/T - if enabled with a printer connected, then only Keypad Access
Activated” events will be printed. This does not affect the Event Log print command.
Bell Test on Arm - if enabled, then the Bell Output(s) for an area will be activated for
two seconds when that area is armed in the AW AY mode.
Sets the number of failed passcode entry attempts allowed before a 50 second lockout
for a particular Control Station.
Synchronizes the internal clock with the local power company’s 50 or 60 Hz for
accurate time keeping.
NOTE
Alarm Bell operations only affect the Bell Output. They do not affect the associated Alarm Indicator outputs.
System Attribute Table
Enter For:0123456789ABCDEF
First Digit
All Features Below Disabled*
Log Alarm Abort Events********
Log Access Events********
Print Access Only R/T********
Bell Test on Arm********
Second Digit
Burglar Bell Steady********
Burglar Bell Pulsed********
Holdup Bell Steady********
Holdup Bell Pulsed********
Aux Bell Steady********
Aux Bell Pulsed********
Fire Bell Steady********
Fire Bell Temporal********
NOTE: If the First Digit entered is ‘1’, it must be entered as ‘01’. A = 10; B = 11; C = 12; D = 13; E = 14; F = 15
27
3.2.7Communicator Data Description
Communicator Data Default Table
LocDefaultLocDefault
Enable Communicator[322]1T1 Trans Format[330]3
Enable Skip Test[323]0T2 Trans Format[331]3
Power-up Comm Test[324]0Dialer Type[332]1
Disable Call Waiting[325]0T1 Dial Attempts[333]5
Comm Test Time of Day (hr:min)[326: 327]00:00T2 Dial Attempts[334]5
Days Between Comm Tests[328]0On-Hook Time (sec)[335]5
Time Between Calls (sec)[329]5Off-Hook Time (sec)[336]3
The following table refers to programming locations 322 through 336:
Used to enable the control digital communicator for event
reporting. Must be set to 0 if phone line is disconnected. If line is
disconnected and a trouble condition occurs, the control station
will display ‘Failed to Communicate’ and/or ‘Phone Line Fault’
trouble until it is disabled.
Allows the auto comm test to be skipped if any signal has been
transmitted to the Central Station since the last auto comm test.
Causes a communicator test to be initiated immediately upon
system power up. Does not affect days between tests counter.
If enabled, the system will automatically dial “*70D” (or “1170D”
if pulse dialing) prior to dialing a telephone number . This will
temporarily disable the Call W aiting beeps during a phone call.
Sets the hour and minute in military format for the auto communicator test.
Sets the time intervals in days for the auto communicator test. A
setting of 0 disables Automatic Comm Test Reporting. Days until
next comm test may be manually adjusted by control station. See
Section 3.1.7.
Time in seconds between a failed dial attempt to a Central Station
and the next dial attempt.
Transmission format to be used when the communicator dials
telephone #1. See Section 3.3, Programming Note 14.
Transmission format to be used when the communicator dials
telephone #2. See Section 3.3, Programming Note 14.
Sets the type of dialing.
“US Rotary” uses North American Standard (60/40) make/ break
ratio pulses.
TT (Touchtone®) uses industry standard DTMF tones.
Touchtone® is a trademark of A T&T .
“Foreign Rotary” uses 67/33 make/break ratio pulses, typical of
foreign countries.
28
T1 Dial Attempts1 to 15 attempts
T2 Dial Attempts1 to 15 attempts
On-Hook Time1 to 15 seconds
&
Off-Hook Time
Maximum number of dial attempts when the communicator dials telephone #1.
Maximum number of dial attempts when the communicator dials telephone #2.
Before the communicator dials a phone number, it seizes the phone line and goes
off-hook for two seconds. It will then go back on-hook for the On-Hook Time to
disconnect an existing phone connection. The communicator will then go back
off-hook for the Off-Hook Time to acquire dial tone before dialing.
All receivers listed functioned with the listed formats at time of testing. Modifications or programming changes may affect
receiver operation. Consult manufacturer of specific receiver for setup and operation.
3.2.8Communication Telephone Numbers Description
Event reporting assignments for each telephone number are programmed under the Area Event Reporting section. (See
Section 3.2.9.) The assignment of telephone dialing options and reporting formats are programmed under the Communicator Options section. (See Section 3.2.7.)
The following table refers to programming locations 337 through 392:
ItemDescription
T1 Telephone Number16 hex digits
T2 Telephone Number24 hex digits
RPM/2 Pro Telephone Number16 hex digits (Available for future use.)
T2 telephone number has extra digits to allow for pager reporting. All six digits of the account code and both digits of the
report code will be added on to the end of Telephone number 2. The digits in the telephone number will consist of the
pager’s phone number , a significant delay, and possibly the beginning of the pager message. The telephone number will be
dialed for the number of dial attempts programmed and the pager message will be blindly sent each time. There will be no
feedback and, therefore, no failed to communicate.
29
NOTE
2
2
2
2
2
2
2
The paging network setup for your area determines if your pager will work with the T2 telephone
number.
Dialed Digits Allowed
See Section 3.1.3.2 for information on programming account codes and telephone number digits.
0 - 9Numbers from 0 to 9 dial the appropriate Touchtone® or pulse digit.
ATo be determined.
BProgramming a B into any digit position causes the communicator to produce a Touchtone® * tone. Useful for
unique applications such as voice mail, cellular, or paging applications.
CProgramming a C into any digit position causes the communicator to produce a Touchtone® # tone.
DProgramming a D into any digit position causes a three second pause during dialing.
ETo be determined.
FAn F may be programmed after the last digit of a telephone number to signify end of dialing. An ‘F’ entered as
the first digit of a phone number disables that phone number.
3.2.9Area Event Reporting Description
Area Event Reporting Default Table
Area 1Area 2
LocationDefaultLocationDefault
Tel 1 Account No (6 Hex Digits)[393 - 398]000000[405 - 410]000000
Tel 2 Account No (6 Hex digits)[399 - 404]000000[411 - 416]000000
Fire Phone No. *[417]3
System Events Phone No. **[418]0
Burglar Phone No.[419]3[427]3
Hold-up Phone No.[420]3[428]3
Auxiliary Phone No.[421]3[429]3
CCM Phone No.[422]3[430]3
Zone Trouble/Restore Phone No.[423]0[431]0
Zone Bypass/Restore Phone No.[424]0[432]0
Open/Close Phone No.[425]0[433]0
Supervision Phone No.[426]0[434]0
* Note: Fire Events communicate as Area 1 only.
** Note: System Events communicate as Area 1 only.
The following table refers to programming locations 393 through 434:
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
ItemValid RangeDescription
Telephone 1 Account No.
Telephone 2 Account No.
6 Hex Digits
6 Hex Digits
Account number used when dialing telephone #1. See Section
3.3, Programming Note 14.
Account number used when dialing telephone #2. See Section
3.3, Programming Note 14.
30
Fire Phone No.
Note: These events are reported
using Area 1 account codes only.
Systems Events Phone No.
Note: These events are reported
using Area 1 account codes only.
Burglar Phone No.
Hold-up Phone No.
Auxiliary Phone No.
Critical Condition Monitor (CCM)
Phone No.
Zone Trouble/Restore Phone No.
Zone Bypass/Restore Phone No.
Open/Close Phone No.
Supervision Phone No.
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
0 = Do Not Report
1 = Phone 1 Only
2 = Phone 2 Only
3 = Phone 1 (2 on Failure)
4 = Phone 2 (1 on Failure)
5 = Phone 1 and 2
Directs which telephone number(s) to report Fire Alarms, Fire
Supervisories, and Restorals.
Directs which phone #’ s report system events. Includes Keypad
Lockout, Keypad Missing & Restoral, Auto Comm Test, AC Failure &
Restoral, Panel Low Battery & Restoral, Bell Fault & Restoral, Comm
Restoral, Memory Error, Begin & End Installer Local Programming,
End Remote Programming, Remote Programming Denied & Aborted,
RF Jamming, RF Channel Clear , and RF Keyfob low battery.
Directs which telephone number(s) to report Burglar Alarms,
Burglar Tamper, Exit Alarm, Recent Closing, Burglar Alarm
Canceled, and Restorals.
Directs which telephone number(s) to report Holdup Alarms,
Duress, and Restorals.
Directs which telephone number(s) to report Auxiliary Alarms
and Restorals.
Directs which telephone number(s) to report Critical Condition
Monitoring events and Restorals.
Directs which telephone number(s) to report Zone Troubles and
Restorals.
Directs which telephone number(s) to report Zone Bypasses and
Restorals.
Directs which telephone number(s) to report Openings, Closings,
Auto Arm Fail, Auto Arm Aborted, and Closing Extended.
Directs which telephone number(s) to report Latchkey Supervision, User on Premises, Senior Watch, and Senior Watch
Restore.
31
3.2.10 Zone Report Codes Description
The Zone Report Codes utilize programming locations 435 through 554. Each Zone has an alarm, restore, bypass and
trouble code. The restore may be an alarm, trouble, or bypass restoral. A Zone Trouble may result from one of the
following conditions:
Wiring problemSmoke Trouble
Senior Watch TroubleRF Point Not Reporting
No Response from Zone ExpanderRF Sensor Tamper
Fire Trouble (Fire zone bypassed or Fire zone in Walk Test)RF Point Low Battery
These events will be posted and displayed differently in the Event Log. If one of these events is reported using a Pulsed
format, then the standard Zone Trouble report code will be used. If one of these events is reported using Contact ID then a
more descriptive report code will be used.
Each report code requires a two digit entry . The first digit sets the primary event code and the second digit sets the extended
code. (See Section 3.1.3.3 for Programming Report Codes). If a transmission format other than a Pulsed format is used,
it is only necessary to program a value other than zero into either digit to enable that event to be reported, the correct
transmitted data is automatically sent.
Zone Report Codes Default Table
AlarmRestoreBypassTrouble
LocDefaultLocDefaultLocDefaultLocDefault
Zone 01[435]H-31[436]H-E3[437]H-AB[438]H-F3
Zone 02[439]H-32[440]H-E3[441]H-AB[442]H-F3
Zone 03[443]H-33[444]H-E3[445]H-AB[446]H-F3
Zone 04[447]H-34[448]H-E3[449]H-AB[450]H-F3
Zone 05[451]H-35[452]H-E3[453]H-AB[454]H-F3
Zone 06[455]H-36[456]H-E3[457]H-AB[458]H-F3
Zone 07[459]H-37[460]H-E3[461]H-AB[462]H-F3
Zone 08[463]H-38[464]H-E3[465]H-AB[466]H-F3
Zone 09[467]H-39[468]H-E3[469]H-AB[470]H-F3
Zone 10[471]H-3A[472]H-E3[473]H-AB[474]H-F3
Zone 11[475]H-3B[476]H-E3[477]H-AB[478]H-F3
Zone 12[479]H-3C[480]H-E3[481]H-AB[482]H-F3
Zone 13[483]H-3D[484]H-E3[485]H-AB[486]H-F3
Zone 14[487]H-3E[488]H-E3[489]H-AB[490]H-F3
Zone 15[491]H-3F[492]H-E3[493]H-AB[494]H-F3
Zone 16[495]H-61[496]H-E6[497]H-AB[498]H-F6
Zone 17[499]H-62[500]H-E6[501]H-AB[502]H-F6
Zone 18[503]H-63[504]H-E6[505]H-AB[506]H-F6
Zone 19[507]H-64[508]H-E6[509]H-AB[510]H-F6
Zone 20[511]H-65[512]H-E6[513]H-AB[514]H-F6
Zone 21[515]H-66[516]H-E6[517]H-AB[518]H-F6
Zone 22[519]H-67[520]H-E6[521]H-AB[522]H-F6
Zone 23[523]H-68[524]H-E6[525]H-AB[526]H-F6
Zone 24[527]H-69[528]H-E6[529]H-AB[530]H-F6
Zone 25[531]H-6A[532]H-E6[533]H-AB[534]H-F6
Zone 26[535]H-6B[536]H-E6[537]H-AB[538]H-F6
Zone 27[539]H-6C[540]H-E6[541]H-AB[542]H-F6
Zone 28[543]H-6D[544]H-E6[545]H-AB[546]H-F6
Zone 29[547]H-11[548]H-E1[549]H-AB[550]H-F1
Zone 30[551]H-12[552]H-E1[553]H-AB[554]H-F1
32
3.2.11 User Report Codes Description
The User Report Codes utilize programming locations 555 through 654. This data block is used to program the opening and
closing reports for each user code.
Each report code requires a two digit entry . The first digit sets the primary event code and the second digit sets the extended
code. (See Section 3.1.3.3 for Programming Report Codes). If a transmission format other than a Pulsed format is used,
it is only necessary to program a value other than zero into either digit to enable that event to be reported, the correct
transmitted data is automatically sent.
The open and close report code is assigned to the user, not the area. Some users may be assigned to arm and disarm multiple
areas. Any user with the authority to arm and disarm multiple areas has the same opening and closing report codes.
However, the Central Station can differentiate between areas by the account code transmitted.
User Report Code Default Table
CloseOpenCloseOpen
LocDefaultLocDefaultLocDefaultLocDefault
User 01[555]H-C1[556]H-B1User 26[605]H-CF[606]H-BF
User 02[557]H-C2[558]H-B2User 27[607]H-CF[608]H-BF
User 03[559]H-C3[560]H-B3User 28[609]H-CF[610]H-BF
User 04[561]H-C4[562]H-B4User 29[611]H-CF[612]H-BF
User 05[563]H-C5[564]H-B5User 30[613]H-CF[614]H-BF
User 06[565]H-C6[566]H-B6User 31[615]H-CF[616]H-BF
User 07[567]H-C7[568]H-B7User 32[617]H-CF[618]H-BF
User 08[569]H-C8[570]H-B8User 33[619]H-CF[620]H-BF
User 09[571]H-C9[572]H-B9User 34[621]H-CF[622]H-BF
User 10[573]H-CA[574]H-BAUser 35[623]H-CF[624]H-BF
User 11[575]H-CB[576]H-BBUser 36[625]H-CF[626]H-BF
User 12[577]H-CC[578]H-BCUser 37[627]H-CF[628]H-BF
User 13[579]H-CD[580]H-BDUser 38[629]H-CF[630]H-BF
User 14[581]H-CE[582]H-BEUser 39[631]H-CF[632]H-BF
User 15[583]H-CF[584]H-BFUser 40[633]H-CF[634]H-BF
User 16[585]H-CF[586]H-BFUser 41[635]H-CF[636]H-BF
User 17[587]H-CF[588]H-BFUser 42[637]H-CF[638]H-BF
User 18[589]H-CF[590]H-BFUser 43[639]H-CF[640]H-BF
User 19[591]H-CF[592]H-BFUser 44[641]H-CF[642]H-BF
User 20[593]H-CF[594]H-BFUser 45[643]H-CF[644]H-BF
User 21[595]H-CF[596]H-BFUser 46[645]H-CF[646]H-BF
User 22[597]H-CF[598]H-BFUser 47[647]H-CF[648]H-BF
User 23[599]H-CF[600]H-BFUser 48[649]H-CF[650]H-BF
User 24[601]H-CF[602]H-BFUser 49[651]H-CF[652]H-BF
User 25[603]H-CF[604]H-BFUser 50[653]H-CF[654]H-BF
33
3.2.12 System Report Codes Description
Each report code requires a two digit entry . The first digit sets the primary event code and the second digit sets the extended
code. (See Section 3.1.3.3 for Programming Report Codes). If the transmission format is anything other than a Pulsed
format, it is only necessary to program a value other than zero into either digit to enable that event to be reported, the correct
transmitted data is automatically sent.
System Event Report Codes Default Table
LocDefaultLocDefault
‘A’ Key Report Code[655]H-19Comm Test Report Code[674]H-00
‘B’ Key Report Code[656]H-29AC Fail Report Code[675]H-FA
‘C’ Key Report Code[657]H-49AC Restore Report Code[676]H-EA
Duress Code[658]H-99Low Battery Report Code[677]H-F9
Keypad Lockout Code[659]H-00Battery Restore Code[678]H-E9
Burg Cancel Report Code[660]H-00Bell Fault Report Code[679]H-00
Quick Arm Report Code[661]H-00Bell Restore Report[680]H-00
Auto-Arm Code[662]H-00Comm Restore Report Code[681]H-00
Auto-Arm Failed Code[663]H-00Memory Error Report Code[682]H-00
Keyswitch Closing Code[664]H-00Local Program Begin Code[683]H-00
Keyswitch Opening Code[665]H-00Local Program End Code[684]H-00
Installer/RPM Closing Code[666]H-00RPM End Report Code[685]H-00
Installer/RPM Opening Code[667]H-00RPM Denied Report Code[686]H-00
Closing Extended Code[668]H-00RPM Abort Report Code[687]H-00
Exit Alarm Code[669]H-00Missing Keypad Code[688]H-00
Recent Closing Code[670]H-00Restore Keypad Code[689]H-00
Latch Key Supervision Code[671]H-00RF Jamming Code[690]H-00
User on Premises Code[672]H-00RF Channel Clear Code[691]H-00
Comm Test Not Norm Code[673]H-00RF Keyfob Low Battery Code[692]H-00
The following table refers to programming locations 655 through 692:
ItemValid RangeDescription
‘A’ Key Report Code00 to FFCode sent for alarms activated by pressing the Fire panic key.
‘B’ Key Report Code00 to FFCode sent for alarms activated by pressing the Police panic key.
‘C’ Key Report Code00 to FFCode sent for alarms activated by pressing the Medical panic key.
Duress Code00 to FFCode sent for a duress (Authority Level 13) code arm or disarm.
Keypad Lockout Code00 to FFCode sent when a control station is locked out due to failed passcode attempts.
Burg Cancel Report Code00 to FFCode sent when an authorized user resets a burglar alarm after reporting and
before the Burglar Bell Cutoff timer expires.
Quick Arm Report Code00 to FFCode sent when an area is armed using Two-Button or Double Press Arming.
Auto-Arming Code00 to FFCode sent when armed by scheduled program or Exit Arm.
Auto-Arm Failed Code00 to FFCode sent when a scheduled arming is aborted or could not be completed.
Keyswitch Closing Code00 to FFCode sent when an area is armed by keyswitch zone
Keyswitch Opening Code00 to FFCode sent when an area is disarmed by keyswitch zone.
Installer/RPM Closing Code00 to FFCode sent when an area is armed by RPM or the installer at a Control Station.
Installer/RPM Opening Code00 to FFCode sent when an area is disarmed by RPM or the installer at a Control Station.
Closing Extended Code00 to FFCode sent when the scheduled closing time is extended.
Exit Alarm Code00 to FFCode sent in addition to a burglar alarm event if the alarm occurs when the exit
time expires.
34
Recent Closing Code00 to FFCode sent in addition to a burglar alarm event if the alarm occurs within two
minutes after exit time expires.
Latchkey Supervision Code00 to FFCode sent when the latchkey code is not entered during the programmed time
window.
User on Premises Code00 to FFCode sent when the User on Premises (Authority Level 12) passcode is entered
to disarm the system or perform the access operation.
Comm Test Not Norm Code00 to FFCode sent at the comm test time-of-day in place of the comm test report when a
trouble condition is present. If this report code is set to 00, a normal comm test
event is transmitted.
Comm Test Report Code00 to FFCode sent at the comm test time-of-day when no trouble conditions are present.
Transmitted at power-up, if Test On Power-Up is enabled (see Section 3.2.7).
Implies proper operation of the communicator and the telephone line.
AC Fail Report Code00 to FFCode sent when the control has lost the primary AC input. The delay time
before this report is transmitted is located in Section 3.2.6.
AC Restore Report Code00 to FFCode sent when the AC primary power has been restored.
Low Battery Report Code00 to FFCode sent when the control detects a low battery voltage reading of 11.3 VDC
or less.
Battery Restore Code00 to FFCode sent when the low battery condition has been restored.
Bell Fault Report Code00 to FFCode sent when the control panel detects a Bell Fault.
Bell Restore Report Code00 to FFCode sent when the Bell Fault trouble is restored.
Comm Restore Report Code00 to FFWhen the control is unsuccessful in reporting an event, the fail to communicate
(local trouble) displays. If a subsequent report of any type is successful, the
control also reports this code.
Memory Error Report Code00 to FFCode sent when the internal memory check finds an unauthorized change in the
value of one or more of the programming options.
Local Prog Begin Code00 to FFCode sent when a program function map is initiated at the control site.
Local Prog End Code00 to FFCode sent after programming mode is terminated at the installation site. This
occurs 255 seconds after exiting programming mode or by holding the CLEAR
key for three seconds.
RPM End Report Code00 to FFCode sent when an RPM session has been completed normally.
RPM Denied Report Code00 to FFCode sent when an unauthorized RPM session is attempted (i.e.: improper ID
code or access device).
RPM Abort Report Code00 to FFCode sent when an RPM session is aborted. If an alarm event requiring a
report to the Central Station occurs during an RPM session, the control may
abort the session to report the event.
Missing Keypad Code00 to FFCode sent when a supervised Control Station is removed or fails to respond to
system polling.
Restore Keypad Code00 to FFCode sent when a missing Control Station is restored to the data bus.
RF Jamming Report Code00 to FFReserved for future use.
RF Channel Clear Code00 to FFReserved for future use.
RF Keyfob Low Battery Code00 to FFReserved for future use.
3.2.13 Area Schedules Description
Automatic Arming
If automatic arming is enabled, the control produces a warning signal at the appropriate Control Station(s) once every minute
beginning ten minutes prior to the event. During this warning, the same control station(s) may display a visual indication of the
impending action and the amount of time remaining. This allows the user ample warning to exit or override the impending
action. Auto Arming time may be extended by one hour during each ten minute warning period (but not past midnight) using the
Delay Auto Arming function. The user can also abort the scheduled arming for that day through User Level programming. (See
the appropriate User Guide). Auto Arming arms the control in the AWAY, ST AY, or NIGHT mode with normal exit time.
35
Latch Key Schedules
A Latch Key User ID is used to determine which user passcode must be entered on selected Latch Key Days. The user
passcode must be entered within a time window. If the user passcode is not entered during the Time Window, a Latch key
Supervision event will be posted in the Event Log to be reported.
For example, if Monday is a Latch Key Day and the Latch Key Time for Monday is 14:30 with a thirty minute Time
Window and the Latch Key User ID is not entered between 14:00 and 15:00 hours, then a Latch Key Supervision event will
be posted at 15:00 hours.
NOTE
The Latchkey Time W indow cannot cr oss over the Midnight boundary. During the Time Window ,
the Control Station will chime once a minute until the user passcode is entered or the T ime Window
has expired, whichever comes first.
Area Schedules Default Table
Area 1Area 2
LocationDefaultLocationDefault
Scheduled Arm Mode[693] 0[726] 0
Scheduled Arm Days[694]H-00[727]H-00
Arm Time Sun (hr:min)[695:696]00:00[728:729]00:00
Arm Time Mon (hr:min)[697:698]00:00[730:731]00:00
Arm Time Tues (hr:min)[699:700]00:00[732:733]00:00
Arm Time Wed (hr:min)[701:702]00:00[734:735]00:00
Arm Time Thurs (hr:min)[703:704]00:00[736:737]00:00
Arm Time Fri (hr:min)[705:706]00:00[738:739]00:00
Arm Time Sat (hr:min)[707:708]00:00[740:741]00:00
Latch Key User ID[709] 0[742] 0
Latch Key Days[710]H-00[743]H-00
Latch Key Window (min)[711] 0[744] 0
Latch Time Sun (hr:min)[712:713]00:00[745:746]00:00
Latch Time Mon (hr:min)[714:715]00:00[747:748]00:00
Latch Time Tues (hr:min)[716:717]00:00[749:750]00:00
Latch Time Wed (hr:min)[718:719]00:00[751:752]00:00
Latch Time Thurs (hr:min)[720:721]00:00[753:754]00:00
Latch Time Fri (hr:min)[722:723]00:00[755:756]00:00
Latch Time Sat (hr:min)[724:725]00:00[757:758]00:00
36
The following table refers to programming locations 693 through 758:
ItemValid RangeDescription
Scheduled Arming Mode0 = AWAY 1 = STAY 2 = NIGHTDetermines the Auto Arm mode.
Scheduled Arming Days00 to FFSelects the days of the week the system automatically arms.
(see the table below for acomplete
description of each value’ s activation)
Sunday Arming Time00:00 to 23:59The time for Auto Arming on Sunday.
Monday Arming Time00:00 to 23:59The time for Auto Arming on Monday.
Tuesday Arming Time00:00 to 23:59The time for Auto Arming on Tuesday.
Wednesday Arming Time00:00 to 23:59The time for Auto Arming on Wednesday.
Thursday Arming Time00:00 to 23:59The time for Auto Arming on Thursday.
Friday Arming Time00:00 to 23:59The time for Auto Arming on Friday.
Saturday Arming Time00:00 to 23:59The time for Auto Arming on Saturday.
Latch Key User ID0 = disable, User 1 to 50Determines the user passcode that has Latch Key Supervision.
Latch Key Days00 to FF (see Scheduled ArmingSelects the days of the week that Latch Key Supervision is
and Latch Key Days Table.)performed.
Latch Key Time Window0 to 255 minutesT ime in minutes (+/-) the Latch Key User Code may be
entered.
Sunday Latch Key Time00:00 to 23:59The time, (+/-) the Time Window, the Latch Key user
passcode must be entered on Sunday .
Monday Latch Key Time00:00 to 23:59The time, (+/-) the Time Window, the Latch Key user
passcode must be entered on Monday .
Tuesday Latch Key Time00:00 to 23:59The time, (+/-) the Time Window, the Latch Key user
passcode must be entered on Tuesday.
Wednesday Latch Key Time00:00 to 23:59The time, (+/-) the Time Window, the Latch Key user
passcode must be entered on Wednesday.Thursday Latch Key
Time00:00 to 23:59The time, (+/-) the Time Window, the Latch Key user
passcode must be entered on Thursday.
Friday Latch Key Time00:00 to 23:59The time, (+/-) the Time Window, the Latch Key user
passcode must be entered on Friday .
Saturday Latch Key Time00:00 to 23:59The time, (+/-) the Time Window, the Latch Key user
passcode must be entered on Saturday.
Scheduled Arming and Latch Key Days Table
Enter For:0123456789ABCDEF
First Digit
All Days Below Disabled**
Thursday********
Friday********
Saturday********
Second Digit
All Days Below Disabled*
Sunday********
Monday********
Tuesday********
Wednesday********
NOTE: If the First Digit entered is ‘1’, it must be entered as ‘01’. A = 10; B = 11; C = 12; D = 13; E = 14; F = 15
37
3.2.14 Programming Options
This section deals with the attributes of the Remote Programming Manager Software. Before programming the specific
functions, it is important to understand the following:
ABORT: During a remote programming session, the control is fully functional and can detect and annunciate alarms
locally. The control aborts a session with RPM/2 Pro to report alarm events.
DATALOCK: As a provision of anti-takeover, the control does not permit local programming of the account numbers
and telephone numbers, or the Restore Factory Defaults option to operate when an agency code has been established
and programmed by the RPM/2 Pro software. Other installer programming changes are still allowed. When the
Datalock (agency code) is set, the Control Station emits an error tone if any attempt is made to change an account
number or a phone number or to default the control.
Programming Options Default Table
LocationDefault
Installer Passcode[759 - 762]9632
Call 2 Timer (sec)[763]0
Auto Answer Ring Count[764]5
Enable RPM[765]1
Enable Power Up Program[766]0
Lockout Local Program[767]0
The following table refers to programming locations 759 through 767:
ItemValid RangeDescription
Installer Passcode0000 to 9999The installer passcode is the only passcode that may program the
entire Function Map. See Section 3.2.4 for a description of the
other functions that may be performed.
2nd Call Timer0 - 255 secondsTime in seconds for the answering machine bypass time window.
This allows the remote programmer to bypass an answering
machine by making two calls to the premises. The first call must
ring three times or less and not be answered. The answering
machine bypass time window starts ten seconds after the last ring
of the first call. If the first ring of the second call occurs within the
answering machine bypass time window, the panel answers the
second call on the first ring. Remote Programming must be
enabled and Auto-Answer Ring count must be non-zero.
Auto Answer Ring Count0 - 15 ringsSets the number of rings that must occur before the panel automati-
cally answers the telephone for operation with RPM/2 Pro. A ring
count of 0 disables automatic answering, but manual connection
may still be used. If Remote Programming is not enabled, then the
auto-answer ring count is ignored and the panel never answers.
Enable RPM0 = NoEnables operation of the control with the RPM/2 Pro package.
1 = Yes
Enable Power Up Program0 = NoA quick way to enter program mode upon power up. Pressing the
1 = Yes9 key and entering “9999” within the first 60 seconds after power
up enters the control into Installer Level Programming mode.
Consider disabling this feature for anti-takeover.
Lockout Local Program0 = NoThis is provided for anti-takeover protection. If it is enabled, the
1 = Yesinstaller passcode is limited as noted in Section 3.2.4. A user may
still be able to perform user level programming and RPM/2 Pro
will be fully operational. Do not enable this unless an RPM/2 Pro
account has been established for the control.
38
3.3Programming Notes
Note 1: Restarting Exit Time
If an exit time is counting down from an AWAY arming, the exit time may be automatically restarted once to reduce false alarms.
The exit time will be restarted if a Perimeter (arm in ST AY mode and arm in NIGHT mode) Burglar zone is violated anytime during the last
ten seconds of exit time.
If the exit time is not due to an Exit Arm or a Scheduled Arming, then the exit time will be restarted if it expires and a Perimeter (Arm in ST AY
mode and Arm in NIGHT mode) Burglar zone has not been violated during the exit time (i.e.: nobody went out the door).
Note 2: Entry Time versus Pre-Alarm Warning Time
Assuming Exit, Entry and Pre-Alarm Warning Times are inactive, a violation of an armed Burglar zone will cause the following actions
depending on the area’s arm level and the type of Bur glar zone:
AWAYSTAYSTAY INSTANTNIGHTNIGHT INSTANT
Instant BurglarInstant AlarmPre-Alarm W arning Pre-Alarm WarningPre-Alarm WarningPre-Alarm Warning
An Exit Arm is intended to automatically arm an area ten minutes after the premises are vacated. An Exit Arm will only be attempted when
it is enabled for an area and the area is disarmed and not in alarm. The end user can disable the Exit Arm feature on a day-to-day basis (see the
appropriate User Guide). If a Disable Exit Arming is performed, the Exit Arm will be disabled until midnight.
When a Delay Burglar zone restores from a violation, the area’s Exit Arm timer is started at ten minutes. During this time, the Control Station
may display a visual indication of the impending action and the amount of time remaining. An audible warning signal will occur at two
minutes until arming and at one minute until arming. When any Burglar zone is violated, the area’ s Exit Arm timer is halted. If a Delay zone
restores from a violation while the timer is running, the timer is restarted at ten minutes. If an Instant or Follower Burglar zone restores from
a violation, the timer is halted.
If the timer expires (i.e.: ten minutes of no Burglar zone activity following a Delay zone restoration), then the system attempts to arm the area
in the A WA Y mode. If Force-Arming is enabled, then a Force-Arm may occur if needed. If the arming is successful, then Exit time is started
and an Auto-Arm event is logged to be reported. If the arming cannot be completed, then nothing will happen.
Note 4: Force-Arming
If Force-Arming is enabled for an area, then an arming from a keyswitch zone, an Exit Arming or a Scheduled Arming will be Force-Armed
if necessary.
Note 5: LED Control Stations
The Secondary Area setting is ignored for LED Control Stations since they cannot provide area information and prompts. Therefore, LED
Control Stations cannot have a Secondary Area.
39
Note 6: Verifying or Self-Verifying Burglar Zones
If an armed Verifying Burglar zone is violated, then a forty second Verification Timer is started. If the timer expires and the zone that started
it is still in violation, then the zone’s violation is verified. If another armed Burglar zone is violated while the timer is still running, then that
violation verifies the first zone’s violation.
If an armed Self-V erifying Burglar zone is violated, then a forty second Verification T imer is started. If the Timer expires and the zone is still
in violation, then the zone’ s violation is verified. If another armed Burglar zone is violated while the T imer is still running, then that violation
verifies the first zone’s violation. If the same armed Burglar zone is violated a second time while the Timer is still running, then the zone’s
violation is verified.
If the area is armed such that a violation from the zone would normally cause an instant alarm:
•when the zone is first violated, nothing happens.
•when the violation is verified, an instant alarm occurs.
•If the Verification Timer expires without the violation being verified, then nothing happens.
If the area is armed such that a violation from the zone would normally cause an Entry Time or Pre-Alarm Warning Time Delay:
•when the zone is first violated, the Delay T imer is started.
•if the violation is verified while the Delay T imer is still running, then the Delay Timer continues as normal.
•if the Verification Timer expires while the Delay T imer is still running and the violation has not been verified, then the time continues. If
the Delay T imer expires and no zones are violated from the Delay Time, then nothing happens.
•if the Delay timer expires before the Verification timer expires and the violation has not been verified, then nothing will happen until
either the violation is verified or the Verification Timer expires.
•if the violation is verified after the Delay Timer has expired, then an instant alarm occurs.
•if the Verification Timer expires after the Delay Timer has expired without the violation being verified, then nothing happens.
Note 7: Sentry Test Burglar Zones
If a Burglar zone has Sentry Test enabled, then each time the zone is disarmed, it must be tested before it can be armed again. A test consists
of violating the zone from a restored state and then restoring it again.
If the zone has not been tested, then it appears as a faulted zone, making its area not ready to arm. An untested zone cannot be armed. If the
zone is bypassable, then it may be bypassed to get around the testing. Force-Arming should not be enabled on systems with Sentry Test
Burglar Zones.
Note 8: Zone Activation of Bell Output and Keypad Sounders
The Bell Output on Alarm attribute determines whether the Bell Outputs for the zone’ s area activate due to an alarm from the zone. It does not
affect the activation of any other programmable outputs, including an associated Alarm output. This attribute is only used if the Zone Type is
Burglar, Holdup, Auxiliary and 24 Hour Burglar Tamper, otherwise, it is ignored. The Bell Outputs activate on all alarms from Fire and
Verified Fire zones and from an ‘A’ key. They never activate from the other Zone Types.
The Keypad Sounder on Alarm attribute determines whether the Control Station sounders activate due to an alarm from the zone. It does not
affect the activation of any programmable outputs. This attribute is only used if the Zone Type is Burglar, Holdup and Auxiliary, otherwise,
it is ignored. Keypad sounders activate on all alarms from Fire and Verified Fire zones and from an ‘A’ key, as well as from 24-Hour Burglar
Tamper and Fire Supervisory zones. They never activate from the other Zone Types.
If a Holdup zone is programmed with neither Bell Output on Alarm nor Keypad Sounder on Alarm, then an alarm from the zone will be
invisible on the Control Stations.
Note 9: Bypassable Zones - Fire Trouble Condition
All zones may be programmed as Bypassable. If a Fire, Verified Fire or Fire Supervisory zone is bypassable and is bypassed, a Fire Trouble
condition occurs and is reported. The condition remains until the zone is unbypassed.
The Fire Trouble condition will also occur during a Walk T est.
40
Note 10: Senior Watch
The Senior W atch attribute may only be used with Bur glar, Critical Condition Monitor , Universal, and Universal Logged zones. It is ignored
for all other zone types.
If a Burglar zone has Senior Watch enabled, then the Senior Watch only applies when the zone is disarmed and not bypassed. Whenever the
zone is violated, disarmed or unbypassed, the zone’s Senior Watch timer is reset to the programmed time. If that timer expires and the zone
is disarmed and not bypassed, then a Senior W atch Trouble event is posted for the zone to be reported. The trouble condition is not displayed
on the keypad and it does not prevent the area from being armed. A Senior Watch Trouble Restore event is posted for the zone to be reported
if the zone is then either violated, armed, or bypassed.
If a Critical Condition Monitor, Universal, or Universal Logged zone has Senior W atch enabled, then the Senior W atch only applies when the
zone is not bypassed. When the zone is violated or unbypassed, the zone’ s Senior Watch timer is reset to the programmed time. If that timer
expires and the zone is not bypassed, then a Senior Watch Trouble event is posted for the zone to be reported. The trouble condition is not
displayed on the keypad. A Senior Watch T rouble restore event is posted for the zone to be reported if the zone is either violated or bypassed.
While a zone has a Senior Watch Trouble condition, its corresponding Senior Watch signaling device (programmable output) will stay ON
steady.
Note 11: The Listen-In Module
The Listen-In Module must be wired to the telephone lines in series with and behind the control panel. The Listen-In Module must be
connected to the panel as follows. A Line-Seized indicator line must be connected from the ACTIVE output on the Listen-In Module to an
assigned Listen-In Module zone on the panel. A Listen-In output line must be connected from an assigned output on the panel to the
ACTIVATE input on the Listen-In Module.
The zone programmed as the Listen-In Module zone is area independent and is used by the panel to determine whether or not the Listen-In
Module has seized the telephone line and has the microphone(s) active. The output programmed as the Listen-In Output may be assigned to
any combination of areas. It is used by the panel to signal the Listen-In Module for activation.
The Listen-In Module may be configured in one of two modes, Instant Seize mode or Answer mode.
If the Listen-In Module is configured in Instant Seize mode, then when it is first signaled from the panel, it instantly seizes the phone line and
signals the panel through the Listen-In Module zone but does not turn on the microphones. When the panel releases the connection to the
Central Station and deactivates the Listen-In Output, the Listen-In Module already has the line seized and assumes the connection.
If the Listen-In Module is configured in Answer mode, then after the panel has signaled it by activating and later deactivating the Listen-In
Output, the Listen-In Module starts its incoming call timer . The incoming call timer starts when the Listen-In Output is dactivated and runs
for five minutes. If a call comes in while the timer is running, then the Listen-In Module answers the call on the first ring. At that time, it
signals the panel through the Listen-In Module zone that it has seized the line.
When the control panel detects the Line-Seized signal from the Listen-In Module zone, it temporarily silences all alarm tones at the Control
Stations and the Bell Outputs, although the alarm output timers continue. When the Listen-In Module releases the phone line, it removes the
Line-Seized signal to the panel. When the control panel detects the Line-Seized signal has been removed, it no longer silences alarm tones at
the Control Stations and Bell Outputs. The Bell Outputs are reactivated if they have not timed-out.
Also, when the panel detects the Line-Seized signal from the Listen-In Module zone and gets an event (any event) to report to the Central
Station, the panel signals the Listen-In operator by momentarily seizing the phone line and producing a tone. This interrupts the Listen-In
Module connection for about one second but it does not hang-up the phone line. The panel also starts a two minute timer. It will not try to call
out to the Central Station until either the Line-Seized signal from the Listen-In zone is removed or the two minute timer expires, whichever
comes first. If the timer expires before the Line-Seized signal is removed, the panel seizes the line to dial out to the Central Station,
disconnecting and hanging up the Listen-In Module’s connection.
If an alarm is silenced through a Control Station during a Listen-In session, it has no impact on the Listen-In operation.
NOTE
If a Holdup Alarm event is reported to the Central Station, it is the Listen-In operator’s responsibility to NOT activate the speakers on the Listen-In Module.
41
Note 12: Delay Before Dial Time
The Delay Before Dial Time is used as the time that a user has after a Burglar , Holdup, or Auxiliary Alarm from a zone has occurred to silence
the alarm with a disarm and abort the Alarm event.
If the Delay Before Dial T ime is not zero and the alarm is silenced before the Delay Before Dial Time expires, then no Alarm events are posted
to be reported. If this occurs and Log Alarm Aborted Events is enabled, then Alarm Aborted events are posted for each zone that went into
alarm, but they are not reported.
If the Delay Before Dial Time is zero or if the Delay Before Dial Time expires before the alarm is silenced with a disarm, then the Alarm
events are posted to be reported. If the alarm is a Burglar Alarm and the alarm is silenced with a disarm before the Burglar Bell Cutof f Timer
expires, then a “Cancel Alarm” event is logged to be reported.
If an alarm in a Control Station’ s Primary or Secondary area is in Delay Before Dial Time, then when the OFF CANCEL key is pressed on the
Control Station, all alarms in the Control Station’ s Primary and Secondary areas are muted until the Delay Before Dial Time expires. While
an alarm is muted, the Control Stations do not produce the alarm tone for the alarm and the Bell Output(s) are silent. The muting of an alarm
does not affect the operation of programmed outputs. If the Delay Before Dial Time expires without the alarm being silenced, then the
Control Stations resume the alarm tone and the Bell Output(s) re-activate. The alarm cut-off timer(s) continue to count while the alarm is
muted.
Note 13: Fire Delay Before Dial
The Fire Delay Before Dial Time is used as the time that a user has after a Fire Alarm from a zone has occurred to silence the alarm and abort
the Alarm event.
If the Fire Delay Before Dial Time is not zero and the alarm is silenced before the Fire Delay Before Dial Time expires, then no Alarm
events are posted to be reported. If this occurs and Log Alarm Abort Events is enabled, the Alarm Aborted events are posted for each zone
that went into alarm, but they are not reported. If a Fire Alarm is silenced before the Fire Delay Before Dial Time expires, the user has 255
seconds to reset the smoke detectors, otherwise a smoke reset will automatically occur when 255 seconds elapses.
If the Fire Delay Before Dial Time is zero or if Fire Delay Before Dial Time expires before Fire Alarm is silenced, then the Alarm events are
posted to be reported.
If a Fire Alarm is in Fir e Delay Before Dial T ime then when the Off Cancel key is pressed from a keypad, all alarms in the keypads Primary
and Secondary area are muted until the Fire Delay Before Dial T ime expires. While an alarm is muted, the Control Stations do not produce
the alarm tone for the alarm and the Bell Output(s) are silent. The muting of an alarm does not affect the operation of programmed outputs.
If the Fire Delay Before Dial Time expires without the alarm being silenced, then the Control Stations resume the alarm tone and the Bell
Output(s) re-activate. The alarm cut-off timer(s) continue to count while the alarm is muted.
Note 14: Transmission Formats
If the Data Format is “Pulsed 20 Baud - Non-Extended”, then the number of digits in the account code determines how events are reported. If
the fourth digit of the account code is 0, then events are reported in the 3/1 Non-Extended format. If the fourth digit of the account code is not
0, then events are reported in the 4/1 Non-Extended format. Only the first digit of the report code is sent. If an account code digit or the first
digit of the report code is 0, then that digit is transmitted as an ‘A’. Each event is reported in two rounds for verification.
For the 3/1 Non-Extended format, the first three digits of the account code and the first digit of the report code are transmitted in a round. For
the 4/1 Non-Extended format, the first four digits of the account code and the first digit of the report code are transmitted in a round.
If the Data Format is “Pulsed 20 Baud - Extended” or “Pulsed 40 Baud - Extended”, then the number of digits in the account code must be four
(4) digits. Both digits of the report code are sent. If an account code digit or one of the report code digits is 0, then that digit is transmitted as
an ‘A’. Each event is reported in two rounds for verification.
For the 4/2 Extended format, then the first four digits of the account code and both digits of the report code are transmitted in a round.
If the Data Format is “Contact ID”, then the first four digits of the account code are sent. The report code is only used to determine if the event
is sent or not. The reports are generated from a Contact ID report table. This is an Ademco developed format.
If the Data Format is “Non-T elco Contact ID”, then the first four digits of the account code are sent. The report code is only used to determine
if the event is sent or not. The reports are generated from a Contact ID report table. The report will be sent to an interface device over the data
42
bus. The interface device will send an acknowledgment to the system upon successful transmission of an event. The telephone number will
not be used, but the first digit of T elephone Number 1 must not be an ‘F’. If the interface device responds back with a transmission failure or
if the interface device “loses” the event, the system will view it as a failed dial attempt. If the interface device is not responding on the data
bus, a “T elco Failure” condition will be posted and the system will not try to report through the interface. This may cause a “Comm Failure”
condition to occur or the event may be reported using another phone number.
If the Data Format is “Pager”, all six digits of the account code and both digits of the report code will be added on to the end of Telephone
Number 2. The digits in the telephone number will consist of the pager’s phone number , a significant delay , and possibly the beginning of the
pager message. The telephone number will be dialed for the number of dial attempts programmed and the pager message will be blindly sent
each time. There will be no feedback and, therefore, no failed to communicate.
The Pager format is perfect for the parent who works late and wants to know if their child arrived home safely. When the child disarms the
system, the parent is paged. Since arming/disarming reports are programmed for each user, the system can be programmed to only page when
the child’s user passcode is used or when a passcode with the User on Premises authority level is used. The pager format can also be used with
the Latchkey Supervision report to page the parent when the child does not come home when expected.
Note 15: Powering Up While Armed
If either area is armed when the panel powers up, violations from all the burglar zones are ignored for three minutes. This allows all armed
PIRs to stabilize without causing false alarms.
Note 16: Universal Outputs
A Universal output may be assigned to any combination of areas and is controlled by the Universal timer or keypad in each of the areas. When
a Universal or Universal Logged zone in an area is violated, the area’s Universal timer will begin a countdown. If the Universal Output Time
is set to zero (0), then the area’s Universal timer will turn ON. To turn it OFF , use the ENTER + Key #2 secondary function.
If the Universal Output Time is not set to zero (0), then the ENTER + Key #2 secondary function will override the Universal Output timer . For
example, if the timer is running when the function is performed, then the output will be turned OFF and the timer will halt. A new zone
activation will turn the output ON and re-start the timer. If the timer is not running when the function is performed, then the function will turn
the output ON and subsequent zone violations will be ignored until after the output is turned OFF by performing the function again.
A Universal output will go ON STEADY when any of its areas have a Universal timer that is either running or ON. If the Universal Output
Time is 0, only one area should be used to control a Universal output. Otherwise, an area will not be able to turn the output OFF if another area
has turned it ON.
Note 17: Lamp Trigger Outputs
A Lamp Trigger output will change state (ON to OFF or OFF to ON) for the Control Station’s Primary area when the ENTER + Key #1
secondary function is performed. If the output is turned ON with the ENTER + Key #1 secondary function and then an arming occurs, the
output will turn OFF when the Exit Time expires.
Note 18: Access and Quick Access Outputs
An Access output will be controlled by the Access operations (0 + passcode) performed on any of its Control Stations or from RPM. A Quick
Access output will be controlled by pressing ENTER + Key #3.
If a Control Station is used to toggle an Access or Quick Access output between ON and OFF, then it should be the only Control Station
controlling that output. Otherwise, you may not be able to turn the output OFF if another Control Station has turned it ON.
43
4
Digital Communicator Table For Contact ID Formats
This section cross-references many of the reporting options and equivalent codes sent by Sentrol-manufactured controls
when transmitting in the Contact ID formats.
Simplified example of data sent in Contact ID format: SSSS 18 Q XYZ AA CCC
Where: SSSS = 4 decimal digit subscriber #
18 = Contact ID que for automation systems
Q = Event qualifier; 1 = new event or opening; 3 = new restore or closing; 6 = previously reported event
XYZ = Event code (3 decimal digits)
AA = Area number (00 for system events)
CCC = Zone, sensor, or user # (3 decimal digits)
Event TypeCID CodeEvent Source
‘A’ Key Fire Alarm1115500 + Keypad (1 - 6)
Zone Fire Alarm1110Zone (1 - 30)
Zone Fire Supervisory1200Zone (1 - 28)
Zone Burglar Alarm1130Zone (1 - 28)
Zone Burglar Tamper1137Zone (1 - 28)
‘B’ Key Holdup Alarm1120500 + Keypad (1 - 6)
Zone Holdup Alarm1120Zone (1 - 28)
Duress1121User (1 - 50)
‘C’ Key Auxiliary Alarm1100500 + Keypad (1 - 6)
Zone Auxiliary Alarm1100Zone (1 - 28)
Zone CCM Alarm1150Zone (1 - 28)
Zone Fire Trouble1373Zone (1 - 30)
Zone Fire Test Mode Begin1604Zone (1 - 30)
Zone Burglar Trouble1370Zone (1 - 28)
Zone Holdup Trouble1370Zone (1 - 28)
Zone Auxiliary Trouble1370Zone (1 - 28)
Zone Other Trouble1370Zone (1 - 28)
Senior Watch Trouble1641Zone (1 - 28)
Zone No Response on Bus1333Zone (13 - 29)
RF Point Not Reporting1381Zone (13 - 28)
Smoke Trouble1380Zone (13 - 30)
RF Sensor Tamper1383Zone (13 - 28)
RF Point Low Battery1384Zone (13 - 28)
Zone Fire Bypass1571Zone (1 - 30)
Zone Burglar Bypass1573Zone (1 - 28)
Zone Holdup Bypass1572Zone (1 - 28)
Zone Auxiliary Bypass1572Zone (1 - 28)
Zone Other Bypass1570Zone (1 - 28)
Zone Fire Alarm Restore3110Zone (1 - 30)
Zone Fire Supervisory Restore3200Zone (1 - 28)
Zone Burglar Alarm Restore3130Zone (1 - 28)
Zone Burglar Tamper Restore3137Zone (1 - 28)
Zone Holdup Alarm Restore3120Zone (1 - 28)
Zone Auxiliary Alarm Restore3100Zone (1 - 28)
Zone Critical Condition Monitor Alarm Restore3150Zone (1 - 28)
Zone Fire Trouble Restore3373Zone (1 - 30)
Zone Fire Test Mode End3604Zone (1 - 30)
Zone Burglar Trouble Restore3370Zone (1 - 28)
Zone Holdup Trouble Restore3370Zone (1 - 28)
44
Zone Auxiliary Trouble Restore3370Zone (1 - 28)
Zone Other Trouble Restore3370Zone (1 - 28)
Senior Watch Trouble Restore3641Zone (1 - 28)
Zone No Response Restore3333Zone (13 - 29)
RF Point Reporting3381Zone (13 - 28)
Smoke Trouble Restore3380Zone (13 - 30)
RF Sensor Tamper Restore3383Zone (13 - 28)
RF Point Low Battery Restore3384Zone (13 - 28)
Zone Fire Bypass Restore3571Zone (1 - 30)
Zone Burglar Bypass Restore3573Zone (1 - 28)
Zone Holdup Bypass Restore3572Zone (1 - 28)
Zone Auxiliary Bypass Restore3572Zone (1 - 28)
Zone Other Bypass Restore3570Zone (1 - 28)
User AWAY Arm from Keypad3401User (1 - 50)
User STAY or NIGHT Keypad Arm3456User (1 - 50)
Quick AWAY Arm from Keypad3408No Data
Quick STAY or NIGHT Keypad Arm3408No Data
Keyswitch Arm3409Zone (1 - 28)
Installer Arm3400No Data
RPM/2 Pro Arm3407No Data
Auto Arm3403No Data
Auto Arm Failed1455No Data
Auto Arm Aborted3455User (1 - 50)
Closing Extended3405User (1 - 50)
Exit Alarm1374 Zone (1 - 28)
Recent Closing3459User (1 - 50)
User Disarm from Keypad1401User (1 - 50)
Keyswitch Disarm1409Zone (1 - 28)
Installer Disarm1400No Data
RPM/2 Pro Disarm1407No Data
Latch Key Supervision1642User (1 - 50)
User on Premises1458User (1 - 50)
Keypad Locked-out1300500 + Keypad (1 - 6)
Keypad Missing1330500 + Keypad (1 - 6)
Keypad Missing Restore3330500 + Keypad (1 - 6)
Burglar Alarm Canceled3406User (1 - 50)
Auto-Comm Test (Not Normal)1608No Data
Auto-Communicator Test1602No Data
AC Failure Reported1301No Data
AC Restore3301No Data
Panel Low Battery1302No Data
Panel Battery Restore3302No Data
Bell Fault1321No Data
Bell Restore3321No Data
Communication Restore3354No Data
Memory Error1303No Data
Begin Installer Local Program1627No Data
End Installer Local Program1628No Data
End Remote Programming3412No Data
Remote Programming Denied1413No Data
Remote Programming Aborted1412No Data
RF Jamming1381No Data
RF Channel Clear3381No Data
RF Keyfob Low Battery1384No Data
45
5
UL Programming Requirements
Underwriters Laboratories (UL) Listing
This control is listed by Underwriters Laboratories (UL) as follows:
ApplicationListing
Household Burglary (Grade A)UL 1023
Household FireUL 985
Central Station Burglary (Grade C)UL 1610/1635
Central Station Burglary (Grade B)UL 1610/1635
Home Health Care Signaling EquipmentUL 1637
Local Burglary (Grade A)UL 609
Police Station Burglary Connection (Grade A)UL 365
UL has established certain requirements which pertain to the installation, use, and programming of this equipment. The local Authority
Having Jurisdiction (AHJ) and/or UL may have other requirements which apply to the installation of this system that are not detailed in
this manual. It is the responsibility of the installing dealer to check with the AHJ and/or UL before installing this system. The following
pages detail guidelines that must be followed in order to comply with the UL listings as stated above.
UL Notes In This Manual
• Key “0” (Access) - The control has not been investigated to UL 294 Access Control System requirements.
• Unsupervised Burglary Zones - UL does not permit the use of unsupervised zones.
UL Notes About Program Functions
• Entrance Delay Time (1 and 2) - Maximum of 45 seconds.
• AWAY Exit Delay Time - Maximum of 60 seconds.
• Burglar Alarm Cutoff Time - Four minutes minimum for household BA/FA and 15 minutes for commercial burglar alarm and police station
connected burglar alarm system.
• Fire Cutoff Time - No automatic cutoff permitted. Will be programmed to “0”, no cutoff.
• Holdup Cutoff Time - maximum of four (4) minutes.
• Communicator Enable - Local or police station connected burglar alarm installations: The communicator must be enabled.
• Days Between Comm. Tests - Commercial installations: automatic test performed every 24 hours.
• Time Between Dial Attempts - UL certified accounts: no more than 45 seconds between attempts.
• Dial Type - Will not be programmed for foreign pulse.
• Dial Attempts Before Shutdown - Five dial attempts minimum, ten dial attempts maximum.
• Arming/Disarming Reports - This function will be enabled by programming report codes.
• Low Battery Reporting - This function will be enabled by programming a report code for Grade A Local Burglar, Grade A Police Connected,
and Grade B and C Central Station Burglar installations.
• Two Button/Double Press Arming - These functions will be disabled. Four digit passcodes will be used.
• Enable Force Arming - This function will be disabled.
• Enable Bypassing - This function will be disabled.
• Burglar Alarm Output - Will be programmed to STEADY.
• Fire Alarm Output - Will be programmed to TEMPORAL.
• Burglar Loop Audible Lockout - This function will be disabled.
• Enable Bell Test Upon Arming - This function will be enabled for Grade A Local Central Station Connected installations.
• Enable Keypad Sounder for BA Zones - The system will have an audible alarm output upon alarm.
• Auto-Arming - This function will be disabled.
• Listen-In Modules must not be used.
• Burglar zones will not be programmed as Verifying or Self-Verifying.
• Output Type can NOT be programmed as Ground Start
UL Notes About Zone Planning
• Burglar Loops - Will be defined as Alarm on Open/Alarm on Short.
• Fire, Holdup, and Auxiliary Emergency Zones - Will not be defined as bypassable.
• Special Functions/Alarms - Burglar zones will have an audible output.
• Medical Emergency - At least one control station will be used as part of the system.