MOOSE ZX400, ZX410 Programming Manual

ZX400/ZX410
SECURITY SYSTEM CONTROL
PROGRAMMING GUIDE
1
2
Table of Contents
Operating The System.......................................................................................................................................4
1.1 Introduction .............................................................................................................................................................4
1.2 Powering Up With The Control Station ..................................................................................................................4
1.3 Control Station Overview........................................................................................................................................5
1.4 Control Station Function Keys ................................................................................................................................6
1.6 Installer Arming and Disarming..............................................................................................................................7
Programming the Control.................................................................................................................................8
2.1 Introduction .............................................................................................................................................................8
2.2 Local Programming.................................................................................................................................................8
2.3 Remote Programming (RPM/2 Pro)........................................................................................................................8
2.4 Area Partitioning .....................................................................................................................................................8
2.5 LED Control Station Programming.........................................................................................................................9
Installer Level Programming.......................................................................................................................... 10
3.1 Menu Options ........................................................................................................................................................10
3.1.1 Remote Connect ..................................................................................................................................................... 10
3.1.2 Set Clock ................................................................................................................................................................ 10
3.1.3 Edit Function Map .................................................................................................................................................. 11
3.1.3.1 Entering a New Value at a Location ............................................................................................................ 11
3.1.3.2 Programming Account Code and Telephone Number Digits ...................................................................... 11
3.1.3.3 Programming Report Codes and Attribute Fields ....................................................................................... 12
3.1.3.4 Additional Programming Notes................................................................................................................... 12
3.1.4 Edit Zone Names .................................................................................................................................................... 12
3.1.5 Default User Code 1 ............................................................................................................................................... 13
3.1.6 Restore Factory Defaults ........................................................................................................................................ 13
3.1.7 Days Until Next Comm Test .................................................................................................................................. 14
3.1.8 Call RPM ................................................................................................................................................................ 14
3.1.9 Program RF Data .................................................................................................................................................... 14
3.2 Function Map ........................................................................................................................................................14
3.2.1 Area Data Descriptions........................................................................................................................................... 15
3.2.4 User Data Description ............................................................................................................................................ 21
3.2.5 Output Definitions Description .............................................................................................................................. 23
3.2.5.1 Bell Output Activation................................................................................................................................. 24
3.2.5.2 Programmable Output Activation................................................................................................................ 25
3.2.6 Global System Options Description ....................................................................................................................... 26
3.2.7 Communicator Data Description ............................................................................................................................ 28
3.2.8 Communication Telephone Numbers Description ................................................................................................. 29
3.2.9 Area Event Reporting Description.......................................................................................................................... 30
3.2.10 Zone Report Codes Description ............................................................................................................................ 32
3.2.11 User Report Codes Description ............................................................................................................................. 33
3.2.12 System Report Codes Description ........................................................................................................................ 34
3.2.13 Area Schedules Description................................................................................................................................... 35
3.2.14 Programming Options ........................................................................................................................................... 38
3.3 Programming Notes...............................................................................................................................................39
Digital Communicator Table For Contact ID Formats................................................................................ 44
UL Programming Requirements.................................................................................................................... 46
Index .................................................................................................................................................................48
3
1
Operating The System
1.1 Introduction
The Moose ZX400/ZX410 Security System incorporates the most desired operational features available today. The ZX400/ ZX410 features ease of installation and programming with an easy-to-operate keypad. Features such as cross-zoning, delay before dialing, and an audibles “mute” function on the keypad help reduce false alarms. The ZX400/ZX410 also provides two truly independent partitions which allow the system to be divided into two distinct fully functional areas.
The ZX400/ZX410 is pre-programmed at the factory with one 2-wire smoke detector zone and twelve burglar zones (one delay, two interior, and nine instant) through Moose’s unique “2 in 1” Zoning™. A Zone Expander Module (ZXEXP) may be added to provide an additional 2-wire smoke detector zone and up to 16 additional zones.
The ZX400/ZX410 Security Control is easily programmed with any one of four ZX400/ZX410 Controls Stations (LCD, LED, SSD, or VFD). The Control’ s on-board RAM maintains its data even with the power disconnected. The Control may also be programmed remotely with the aid of a personal computer (PC) and a modem using Moose’s remote programming software (RPM2PRO) and a panel support module (PRO400).
The ZX400/ZX410 Security Control allows the division of a single system into two distinct areas. To the customer, each area appears to be a fully functional system. Each zone and Control Station must be assigned to one of the two areas. The Control Stations may also be extended to operate in the other area as a secondary area. A user passcode may be assigned to access and control one or both of the areas. The Control may have up to 50 user codes programmed with 15 different levels of authority.

1.2 Powering Up With The Control Station

The control comes from the manufacturer with a factory set (default) program. The factory default code for user passcode No. 1 is “1234”. This passcode is authorized to perform all user level functions. The default setting for the installer passcode is “9632”. The installer passcode can perform the installer level functions. (See section 3.2.4 for the listed functions.) All zones and Control Stations are assigned to Area 1 at default. The default setting for user passcode No. 50 is “1245” and it is authorized to perform all user level functions. It is assigned to both Area 1 and 2.
When a Control Station is powered-up, it briefly displays a test pattern followed by its data bus address. The Control Station will then begin displaying information from the control panel. During the first fifteen seconds after power-up, the control panel will instruct the Control Station to display the panel’s software revision and flash the AWAY, STAY, NIGHT, READY, and TROUBLE LEDs.
PANEL REV 1.04
Once the zones are in a secure state, the Control Station displays:
A1 READY TO ARM
READY
TROUBLE
(NOTE: Rev number may change as software is upgraded)
READY
TROUBLE
JAN 21 05:27:52
Nearly every option on the control requires the use of a valid user passcode. The user passcode may be used for functions in a specific area or system-wide. Most of the options may be performed at any time, even while the control is fully or partially armed. To perform a function, a user must press the key corresponding to that function and then enter a passcode with the appropriate authority level. For purposes of discussion, the installer and the end user are both considered system users, but have different levels of authorization.
4
CANCEL
AWAY
NIGHT
1
234
READY
TROUBLE
5678
11 12109
FIRE
EVENT LOG
OFF
D
STAY
VIEW INFO ALM MEM
1
23
BYPASS CHIME
DELAY ARM
4
56
RST SMOKE TEST PROGRAM
7
89
QUIT ACCESS INSTANT
CLEAR
ENTER
0
HOME NEXT
A
B
C
PREV
CANCEL
AWAY
NIGHT
OFF
STAY
READY
TROUBLE
EVENT LOG
D
VIEW INFO ALM MEM
1
23
BYPASS DELAY ARM CHIME
4
56
RST SMOKE TEST PROGRAM
7
89
QUIT ACCESS INSTANT
CLEAR
ENTER
0
HOME NEXT
LED Control Station
(ZXLED)
D
CANCEL
AWAY
STAY
NIGHT
1
23
BYPASS DELAY ARM CHIME
4
56
RST SMOKE TEST PROGRAM
7
89
QUIT ACCESS INSTANT
CLEAR
ENTER
0
HOME NEXT
EVENT LOG
VIEW INFO ALM MEM
OFF
LCD Control Station
(ZXLCD)
SSD Control Station
(ZXSSD)
VIEW INFO ALM MEM
OFF
D
CANCEL
AWAY
STAY
NIGHT
1
23
BYPASS DELAY ARM CHIME
4
56
RST SMOKE TEST PROGRAM
7
89
QUIT ACCESS INSTANT
CLEAR
0
HOME NEXT
VFD Control Station
(ZXVFD)
EVENT LOG
ENTER
FIGURE 1-1 System Control Stations

1.3 Control Station Overview

For SSD, LED, LCD, and VFD Control Stations:
Away, Stay, and Night Keys These keys, followed by a passcode, arm one or both areas to the AWAY, STAY, or
NIGHT level.
A way, Stay, and Night LED’s These LEDs backlight the AW AY, ST AY, and NIGHT keys to indicate the armed level
of the Control Station’s primary area. These will flash during Exit Time or during a Burglar Alarm after Dialer Delay has expired.
Off / Cancel Key This key, followed by a valid user code, disarms an area(s), silences and cancels alarms,
and silences trouble conditions.
Instant/Enter Key This key is used in programming to store entered data. Also, when pressed during an
exit time from a STAY or NIGHT arming, this key disables both the entry and exit times for the primary area of the Control Station.
Keypad Audibles The piezo resonator activates for conditions including entry and exit notification, alarm,
trouble, chime, etc.
Auxiliary Keys When enabled, these keys activate the auxiliary alarms (Fire, Police, Medical Emer-
gency).
Clear/Quit Key This key is used to reset any entry error and to allow you to escape out of an operation.
To clear a “Missing Keypad”, “Memory Error”, or “Smoke Trouble” system trouble condition or to turn off the Duress output, press and hold the CLEAR key for three seconds.
Keyboard Backlighting The Control Station contains recessed LEDs to provide a light in dark or dimly lit
environments.
5
For SSD and LED Control Stations only:
Ready LED This LED indicates the status of the Burglar zones assigned to the Control Station’s
primary area. It illuminates when the Burglar zones are all secure.
Trouble LED This LED will illuminate for system troubles (AC failure, low battery , communication
failure), zone troubles, and Burglar T amper conditions. (See Section 3.2.5.2 for a com­plete list of trouble conditions.)
For LED Control Stations only:
Zone Status LED’s These LEDs generally indicate the condition of zones 1 through 12. See the ZXLED
User Guide for how the LEDs indicate the Normal, Faulted, Bypassed, Trouble, and Alarm conditions.
These LEDs may also display system trouble conditions and programming informa­tion.
Fire Zone LED This LED indicates the status of the two-wire smoke zone on the main control board
(Zone 30).
For SSD Control Stations only:
Seven Segment Display The three Seven Segment Display (SSD) characters enunciate system status, zone sta-
tus and user information. See the ZXSSD User Guide for details.

1.4 Control Station Function Keys

All Control Station function keys (except the View Info Key) require that the function key be pressed followed by a valid passcode. The passcode’s authority level will determine if the selected function can be performed. While entering the passcode, there will be a four second time-out for no activity . After the passcode has been entered, there will be a three minute time-out for no activity. The time-out will return the Control Station to idle. The operator may press the CLEAR key at any time to return the Control Station to idle.
Below are the functions associated with keys 0 - 9 and a brief description of the functions. For details on the operation of these functions, as well as on the three arming keys, see the appropriate User Guide.
KEY #1 VIEW INFO KEY
This key is used to view information and scroll through alarm and trouble conditions. A passcode is not required to perform this function.
KEY #2 ALM MEM KEY
This key allows you to view the most recent alarm event(s) on the Control Station.
KEY #3 EVENT LOG KEY
From an LED or SSD Control Station, this key will initiate printing of the Event Log. From an LCD or VFD Control Station, this key will allow you to view the Event Log on the Control Station or initiate printing the log.
KEY #4 BYPASS KEY
This key allows you to select zones to be bypassed (removed from the system) and unbypassed (restored to the system).
KEY #5 DELA Y ARM KEY
This key extends or postpones an automatic arming by one hour.
6
KEY #6 CHIME KEY
This key turns the chime function on or off for a particular area.
KEY #7 RST SMOKE KEY
This key resets all latched smoked detectors and clears “Smoke Troubles”.
KEY #8 TEST KEY
This key allows you to perform one of the six following tests: Walk, Battery, Bell, Communications, Keypad, and RF Signal Strength. After a valid passcode is entered, you may select the test to perform.
KEY #9 PROGRAM KEY
This key is used to enter installer or user level programming. User level programming is described in the appropriate User Guide. Installer level programming is described in Chapter 3.
KEY #0 ACCESS KEY
This key is used to activate a door strike or other similar function.

1.5 Secondary Function Keys

The Control Station secondary function keys may be activated by pressing the ENTER key followed by Key #1 through Key #6. A passcode is not required to activate these functions. These functions are activated by pressing the following:
ENTER + KEY #1 Turns Lamp Trigger Output ON or OFF ENTER + KEY #2 Turns Universal Output ON or OFF ENTER + KEY #3 Quick Access from Keypad ENTER + KEY #4 Turns Key 4 Output ON or OFF ENTER + KEY #5 Turns Key 5 Output ON or OFF ENTER + KEY #6 Turns Key 6 Output ON or OFF
Please see section 3.2.5 for more details on the operation of these functions. The above outputs are only available to the user if you program them as Programmable Outputs. If any of these features are made available to the user, please instruct the user on their operation as it is not detailed in the appropriate User Guide.

1.6 Installer Arming and Disarming

The installer passcode may be used to arm one or both areas. It may be used to disarm one or both areas, but only if the area was armed by the installer passcode. It may be used to silence alarms and to silence trouble conditions. When it is used to silence a Burglar alarm, it will not disarm the area or cancel the alarm unless the area was armed by the installer passcode. For a detailed description of arming and disarming procedures, see the appropriate User Guide.
7
Programming the Control2

2.1 Introduction

The control may be programmed locally from any LED, SSD, LCD, or VFD Control Station. It may also be programmed using the remote programming software, RPM/2 Pro.

2.2 Local Programming

There are two levels of Control Station programming : User level and Installer level.
User level programming provides the ability to add, change, or delete user passcodes. It also allows Scheduled Arming and Latchkey operation to be changed. A user passcode with authority level 9, 10, or 15 is required to access the user level programming (see Section 3.2.4). See the appropriate User Guide for more information regarding user level programming.
Installer level programming allows total customization of the control’s operating features. Only the installer code may access this level. Anyone attempting installer level programming should be familiar with the contents of this publication prior to programming the control panel.
NOTE
If the installer code is lost or forgotten, it may be impossible to program the control locally.
If remote programming is used, it is possible to “lockout” or prevent takeover of a control by another installation company by selecting “Lockout Local Prog.” This prevents the installer passcode from gaining access through local Control Station programming. The installer passcode may still be used for the non-programming functions described in Section 3.2.4.
,does not affect remote programming.

2.3 Remote Programming (RPM/2 Pro)

The entire control database can be programmed remotely through a computer and modem using a remote program called RPM/2 Pro. To use RPM/2 Pro with the ZX400, you will need RPM2PRO and a panel support module for the ZX400 family (PRO400). Remote programming utilizes extensive error checking and security safeguards, including data encryp­tion, password log-on, panel IDs and agency codes.
Panel IDs are used by RPM/2 Pro to identify a control during a remote programming session. The agency code is used by the control to identify the remote programmer during initialization of a remote programming session. These codes are loaded into the control by RPM/2 Pro during the first RPM/2 Pro session. They cannot be viewed by local programming.
The panel ID and agency code work together to prevent illegal takeover by another computer with RPM/2 Pro. Once the agency code is programmed, the control also prevents local changing of account codes and telephone numbers and disables the RESTORE DEFAULTS function.

2.4 Area Partitioning

The control may be divided (partitioned) into two independent areas. To the customer, each area appears to be a full­featured system. This allows one control to be shared by two independent departments within a common structure. Note
that LED Control Stations cannot have a Secondary Area.
When reporting to the Central Station, events such as AC Power Failure, Low Battery, automatic tests, etc., are considered system reports and are transmitted as an Area 1 account although they are displayed on all Control Stations regardless of area. All fire related events (i.e.: fire alarms, troubles, etc.) are also considered system events and are reported using an Area 1 account.
8
Each area can be programmed to control separate outputs with a dedicated audible or annunciator. It is also possible to combine the outputs of both areas so that a central siren, bell or audible can be used. The audible should be positioned so that it can be heard by all partitions. When partitioning is not desired, simply designate all zones to a single area (Area 1).
An example of a partitioning application is a business that is divided into two departments with both departments occupied by a different manager. The control communicator would be installed in a secure area (common utility closet) with dedi­cated and uninterrupted AC power and telephone service. This must be considered when planning the control panel posi­tion as the power and phone service to a tenant may be terminated if that tenant leaves.
Each tenant’s compartment is assigned an area with a number of zones, codes, and Control Stations. When an area experi­ences an alarm or other event, the adjacent system area is not alerted to the event since the Control Station would be programmed to respond only to events in the assigned area.
Another programming feature is the ability to allow crossover between areas. This allows the user(s) from one area to operate the other area from a designated Control Station. Programming is discussed in detail later in this manual. By factory default, users are only allowed to see and operate their primary assigned area. Multi-area operation may be useful for applications where the security system is installed in a facility that is divided into departments. Each department has a set of users who are responsible for arming and disarming only the security system to which they are assigned. If desired, the system may be set up to allow one or more users to have control over both areas.
User 1 assigned to A1
CONTROL
PANEL
AREA 1 ACCT 1
AREA 2 ACCT 2
User 2 assigned to A1 User 3 assigned to A1
User 4 assigned to A2 User 5 assigned to A2 User 6 assigned to A2
1. Maximum Zones = 30
Zn 1
Zn 2
Zn 3
Zn 4
Zn 5
Zn 6
Up to 28 zones may be assigned to any area in any sequence, except fire (always Area 1).
2. Maximum Users = 50 Any number of users may be assigned to operate on any combination of areas.
3. Maximum Addressable = 6 SSD, LCD, and VFD Control Stations can be assigned to operate in both areas if desired. LED Control Stations can only be assigned to operate in either Area 1 or Area 2.
= Control Station
Each area has a separate account number at the Central Station and may report to one or two receivers or one with the second as backup. The type of activity within a specific area/account may be divided among the two receivers as well. For example, Open/Close reports may transmit to receiver A and alarm activity may transmit to receiver B.
Figure 2-1 Area Partitioning

2.5 LED Control Station Programming

When in programming mode, an LED Control Station will mimic what is displayed on an SSD Control Station. The top row of LEDs will correspond to the first SSD character, the second row to the second SSD character and the third row to the third SSD character. If an SSD character is 1 - 9 or A - F, then that hexadecimal digit will be displayed in binary on the appropriate row of LEDs. See Chapter 3 for programming with the Control Station. Chapter 3 will also show examples of SSD, LCD, or VFD Control Station displays. There are no examples for LED Control Stations (see Figure 2-2).
READY and TROUBLE LEDs
Flash indicating that the control is in programming mode
READY
TROUBLE
FIRE
ZONE LEDs (1 - 4)
Display hexadecimal value
1
2
56 910
3
7
11
12
corrresponding to left digit on SSD
4
Control Station (shown is '5')
8
ZONE LEDs (5 - 8)
Display hexadecimal value of center digit (shown is '6')
ZONE LEDs (9 - 12)
Display hexadecimal value of right digit (shown is '3')
Figure 2-2 LED Display
Value Display
1
0 1 2 3 4 5 6 7 8
9 10 (“A”) 11 (“B”) 12 (“C”) 13 (“D”) 14 (“E”) 15 (“F”)
8
2
4
9

Installer Level Programming3

3.1 Menu Options
This section will describe Installer Level Programming as performed locally from a Control Station.
To enter Installer Level Programming, press the PROGRAM (9) key and enter the installer passcode (default = 9632). The Control Station will then prompt you to select a programming option from 1 to 9 where:
1 = REMOTE CONNECT 6 = RESTORE FACTORY DEFAULTS 2 = SET CLOCK 7 = SET DAYS UNTIL NEXT COMM TEST 3 = EDIT FUNCTION MAP 8 = CALL RPM 4 = EDIT ZONE NAMES 9 = PROGRAM RF DAT A 5 = DEFAULT USER CODE 1
3.1.1 Remote Connect
After entering programming mode, press the ‘1’ key to perform a Remote Connect. The control will seize the telephone line and the control station will return to idle. This feature is used to manually connect the control to a remote programming computer.
REMOTE CONNECT
3.1.2 Set Clock
After entering programming mode, press the ‘2’ key for Set Clock programming. The Control Station will go into clock set mode.
The SSD Control Station will have a Set Clock prompt display . The LCD and VFD Control Station will display the current hour, minute, month, day, and year (HH:MM MM/DD/YY). The zone LEDs on an LED Control Station will remain off. The hour must be entered in 24-hour format.
14:58 02/11/96 ENTER = COMPLETE
The operator may start entering numbers from the first hour digit. As a number is entered, it is displayed and the cursor automatically moves to the next position on the LCD and VFD Control Station. When a digit is entered, the Control Station will display:
24:58 02/11/96 ENTER = COMPLETE
If the CLEAR key is pressed, the cursor will move back to the first hour digit and any changes that were entered will be erased, i.e.: the current time and date will be re-displayed. If the CLEAR key is pressed and no changes have been entered, the Control Station will return to idle with no changes to the time or date.
14:58 02/11/96 ENTER = COMPLETE
10
If the ENTER key is pressed, all changes that were entered will be range checked. The entire time and date need not be entered. Any fields that are not entered will remain unchanged. If the data entered is within range parameters, the clock will be updated and the Control Station will return to idle. A “Begin Set Clock” event will indicate the time before the change and an “End Set Clock” event will indicate the time after the change. If the entered data is out of range, the Control Station will indicate an error, erase the previous entries and re-display the current time and date.
INVALID SETTING

3.1.3 Edit Function Map

After entering programming mode, press the ‘3’ key to enter Edit Function Map mode. The Control Station will prompt you for a location to be programmed. The location numbers, definitions, and valid entries for the locations are described in Section 3.2. From this mode, you may edit the entire Function Map except for User Codes and Zone Names. Editing Zone Names is described in Section 3.1.4. Editing User Codes is described in the appropriate User Guide, but is not accessible with the installer passcode.
From the LOCATION prompt, enter digits for the desired location number. The digits entered will be displayed. If more than three digits are entered, the first digit entered will be discarded. If you make a mistake, you may press the CLEAR key to clear out the location and start over. When the desired location number is displayed, press the ENTER key. The Control Station will then display the current value programmed at that location.

3.1.3.1 Entering a New Value at a Location

While the Control Station is displaying the value at a location, you can enter digits to change the value at that location. The new value is displayed as you enter the digits. Other keys work as follows:
ENTER - if pressed after new digits are entered, the displayed value is stored at the current location.
- if pressed with no new digits entered, then it will go to the next location.
‘C’ Key - if pressed, it will go back one location and ignore any digits entered.
CLEAR - if pressed after new digits are entered, erase those digits and re-display the original value at the location.
- if pressed with no new digits entered, then it will return to the LOCATION prompt.
OFF CANCEL - on an LED or SSD Control Station, it will momentarily display the present location number.
NOTE
When you press the ENTER key to store the new value, the system will store the value as entered. It is the responsibility of the programmer to enter a value within the specified range. If the value entered is out of the range, then undesirable operation may occur. In some cases, if the value entered is too large, it will be truncated before it is stor ed causing a different value to be stored than was entered.

3.1.3.2 Programming Account Code and Telephone Number Digits

When the location being programmed is an account code or telephone number digit (see Sections 3.2.8 and 3.2.9), the value will be displayed as an “H” followed by a single digit. The “H” indicates that this location is a Hexadecimal field. The valid entries for these locations are “0” through “F”, where A - F correspond to 10 - 15 respectively.
To program a digit, enter digits as normal. To enter an A - F, enter a ‘1’ followed by a ‘0’ through ‘5’. As in programming normal fields, if too many digits are entered, the first digit entered will be discarded. The ENTER, OFF CANCEL, ‘C’, and CLEAR keys will work the same as described above.
11

3.1.3.3 Programming Report Codes and Attribute Fields

When the location being programmed is a report code (see sections 3.2.10 - 3.2.12) or an attribute field (see sections 3.2.1
- 3.2.3 and 3.2.12 - 3.2.13), the value will be displayed as an “H” followed by two digits. The “H” indicates that this location is a Hexadecimal field. The valid entries for these locations are “00” through “FF”, where A - F correspond with 10 - 15 respectively. The Control Station display will automatically display the hexadecimal value.
To program one of these locations, enter digits as normal. To display a ‘1’ in the first digit location, you must enter a ‘0’ before the ‘1’, i.e. ‘01’ displays a ‘1’. To enter an A - F, enter a ‘1’ followed by a ‘0’ through ‘5’. For example:
Enter To Get 1-2-3 C3 0-1-2 12 1-8 18 0-1-1-0 1A 1-2 0C 2-1 21
As in programming normal fields, if too many digits are entered, the first digit entered will be discarded. The ENTER, OFF CANCEL, ‘C’, and CLEAR keys will work the same as described above.

3.1.3.4 Additional Programming Notes

To exit out of Edit Function Map mode and return the Control Station to the idle state, press the CLEAR key from the LOCATION prompt. (You may need to press the CLEAR key several times to get to the LOCATION prompt.) An “End Local Programming” event will not be logged until 255 seconds after you exit programming mode. This is to allow you to exit and re-enter programming mode repeatedly without logging each one. T o force an “End Local Programming” event to be logged, immediately (i.e.: to have it reported to the Central Station), press and hold the CLEAR key for three seconds.
When programming the value at the last programming location, the Control Station will return to the LOCATION prompt if the ENTER key is pressed.
If the panel has been programmed from RPM/2 Pro and the Agency Code has been loaded into the panel, then the locations corresponding to the telephone numbers and account codes will not be editable.

3.1.4 Edit Zone Names

Only the LCD and VFD Control Station may be used to edit zone names. From the Installer Programming Menu, press the ‘4’ key to edit the zone names. The Control Station will prompt you for a Zone ID to be programmed. The valid Zone IDs are 1 to 30.
Enter a number corresponding to the Zone ID and press ENTER. Once a valid Zone ID is selected, the control will display the Zone ID and the current Zone Name with the cursor on the first character. Press the key associated with each character . Each keypress will change the display to the next character listed for that key. The characters available for editing the Zone Name are as follows:
Key #1 0123456789: ; <=>?@ Key #2 A B C Key #3 D E F Key #4 G H I Key #5 J K L Key #6 M N O Key #7 P Q R S Key #8 T U V Key #9 W X Y Z [ ù ] ^ _ Key #0 space ! # $ % & * + , - . / ‘A’ Key Used to move the cursor back one position ‘C’ Key Used to move the cursor forward one position
12
If the ENTER or CLEAR key is pressed and no changes have been made, the Control Station will return to the Zone ID prompt. If the CLEAR key is pressed and changes have been made, all changes will be cleared and the control station will return to displaying the original Zone Name. To save any changes made to the Zone Name, press the ENTER key. The control station will return to the Zone ID prompt. Press the CLEAR key to return to idle.

3.1.5 Default User Code 1

The installer passcode does not have the authority to edit user passcodes locally and only high level user passcodes (User Code 1 at default) have the authority to edit user passcodes. If you need to edit user passcodes or if the User Code 1 passcode is forgotten, this function may be used to reset the User Code 1 passcode back to the default value of “1234”.
After entering programming mode, press the ‘5’ key to default the User Code 1 passcode. The Control Station will prompt you to re-enter the installer passcode for verification.
TO DEFAULT USER1 ENTER PASSCODE
If the passcode is entered correctly, the Control Station will display an acknowledgment and return back to the idle mode.
USER1 DEFAULTED

3.1.6 Restore Factory Defaults

This function provides a means to completely wipe out the panel’s memory and restore it to a factory default state. If successfully completed, the panel will:
default the entire Function Map (including Zone Names and User Passcodes)
clear the Event Log and log a “System Startup” event
clear all alarm, trouble and armed conditions
not affect the System Clock (time and date).
not affect data programmed in the RF Gateway(s)
If the panel has been programmed from RPM/2 Pro and the Agency Code has been loaded into the panel, then this function will be disabled.
After entering programming mode, press the ‘6’ key to enter Restore Factory Defaults mode. The Control Station will prompt you to re-enter the installer passcode for verification.
TO DEFAULT PANEL ENTER PASSCODE
If it is entered correctly, the Control Station will go back to the system powering up display.
13

3.1.7 Days Until Next Comm Test

The scheduling of Automatic Communications Tests requires programming a “Comm Test Time-of-Day” and the number of “Days Between Comm Tests” as described in Section 3.2.7. If “Days Between Comm Tests” is zero, then no automatic comm tests will occur. Otherwise, a comm test will occur when a Days Until the Next Comm Test counter ticks down to zero. This function allows you to view that Days counter . If the value displayed is zero or one, then the next comm test will occur at the next “Comm Test Time-of-Day”. This function also allows you to change the number of Days Until the Next Comm Test.
After entering programming mode, press the ‘7’ key to enter Days Until Next Comm test programming. The Control Station will display the number of days until the next scheduled comm test.
To change this value, enter a number between 0 and 255. If a mistake is make, press the CLEAR key to start over. If a number greater than 255 is entered, the first digit entered will be discarded. When the desired number of days is displayed, press the ENTER key. The Control Station will return to idle. To exit out of this function without adjusting the number of days, press the CLEAR key.

3.1.8 Call RPM

This option is not available at this time.

3.1.9 Program RF Data

This option is not available at this time.

3.2 Function Map

To edit the Function Map, press the PROGRAM (9) key, enter the installer passcode, and press the ‘3’ key to select the Edit Function Map programming option. The Control Station will prompt for a location to be programmed. All function map locations can be programmed except for user codes and zone names.
NOTE
When entering values into the programming locations, it is possible to enter values which exceed the valid range of the programmed options. It is the responsibility of the installer to ensure the correct value of any entry programmed into the control. The valid entries for each location are detailed in the following sections.
14

3.2.1 Area Data Descriptions

Area Data Default Table
AREA 1 AREA 2
Location Default Location Default
AWAY Exit Time (sec) [1] 60 [12] 60 STAY/NIGHT Exit Time (sec) [2] 60 [13] 60 Entry Time 1 (sec) [3] 20 [14] 20 Entry Time 2 (sec) [4] 40 [15] 40 Pre-Alarm Time (sec) [5] 0 [16] 0 ‘B’ Key Alarms [6] 2 [17] 2 ‘C’ Key Alarms [7] 1 [18] 1 Closing Ringback [8] 0 [19] 0 Burglar Audible Lockout [9] 0 [20] 0 Swinger Shunt [10] 0 [21] 0 Area Attributes [11] H-09 [22] H-09
The following table refers to programming locations 1 through 22.
Item Valid Range Description
AWAY Exit Delay Time 0 to 255 seconds
STAY & NIGHT Exit 0 to 255 seconds
Time
Entry Delay Time 1 0 to 255 seconds
Entry Delay Time 2 0 to 255 seconds
Pre-Alarm Warning Time 0 to 255 seconds
‘B’ Key Alarms 0 = No Keypad Sounder or Bell
Output (invisible) 1 = Keypad Sounder Only 2 = Keypad Sounder and Bell Output
‘C’ Key Alarms 0 = No Keypad Sounder or Bell
Output (visible) 1 = Keypad Sounder Only 2 = Keypad Sounder and Bell Output
Closing Ringback 0 = Ringback Output
1 = Ringback Output and Keypads 2 = Ringback Output, Bell Output and Keypads
Burglar Audible Lockout 0 = No Lockout
1 to 15 = Alarms for an Area
Swinger Shunt 0 = No Shunt
1 to 15 = Violations for a Zone
Time in seconds for all Burglar zones, may be audibly annunciated. (See Section 3.3, Programming Note 1.)
Time in seconds for all Burglar zones, always silent.
Time in seconds to enter Burglar zones defined as Delay #1, may be audibly annunciated.
Time in seconds to enter Burglar zones defined as Delay #2, may be audibly annunciated.
Time in seconds to correct a false alarm, always audible. (See Section 3.3, Programming Note 2.)
Defines the annunciation of an alarm activated by the Police key.
Defines the annunciation of an alarm activated by the Medical/ Emergency key.
Determines how the system annunciates the successful transmission of an AWAY closing report to the Central Station.
Determines the number of times that a Bell Output may be activated during an armed cycle, resets with disarm.
Determines the number of violations that may occur from an armed burglar zone before that zone is automatically bypassed.
15
Area Attributes 00 to FF
(see the Area Attribute Table)
Bypassing - enables selective bypassing of any zone that is defined as bypassable in this area. Force-Arming - permits arming of the area with zones faulted. Faulted zones are temporarily bypassed and return to operation if the fault is corrected. Only zones that are defined as bypassable may be force-armed. See Section 3.3, Programming Note 4. Exit Arm - see Section 3.3, Programming Note 3. 3 Second Panic Keys - requires all panic keys to be pressed and held for approximately 3 seconds in order to activate alarm condition. Only pertains to Control Stations that are Primary to this area. Double Press Panic Keys - requires all panic keys to be pressed twice within one second to activate. Only pertains to control stations that are Primary to this area. Two Button Arm - enables quick arming by pressing AWAY, STAY, or NIGHT followed by the ENTER key. Cannot be used with force­arming Double Press Arm - enables quick arming by pressing AWAY, STAY, or NIGHT twice. Cannot be used with force-arming. Open After Alarm - enables opening reports to be reported only if they occur after an alarm. All “opening” events will be logged in the Event Log regardless of setting. Display Bypass Armed - when armed in STAY or NIGHT mode with bypassed or force-armed zones, Control Stations with the area as the Primary area will indicate that there are zones that are bypassed.
Area Attribute T able
Enter For: 0123456789ABCDEF First Digit
All Features Below Disabled * Two Button Arm ******** Double Button Press Arm * * * * * * * * Open After Alarm **** **** Display Bypassed Armed ********
Second Digit
Double Press Panic Keys ******** Bypass ******** Force-Arm * * * * * * * * Exit Arm **** **** 3 Second Panic Keys ********
NOTE: If the First Digit entered is ‘1’, it must be entered as ‘01’. A = 10; B = 11; C = 12; D = 13; E = 14; F = 15
16
Loading...
+ 36 hidden pages