PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Introduction
This is the users’ manual for the Moore Industries
CPA PC-Programmable Alarm (TPRG: RTD, T/C,
mV, Ohms and Potentiometer Limit Alarm Trips). It
contains all of the information needed to confi gure,
install, operate, and maintain this instrument.
About this Manual
Wherever you see a “ Note”, “ Caution”, or “ WARNING
” pay particular attention.
WARNING - Hazardous procedure or condition that
could injure the operator.
Caution - Hazardous procedure or condition that could
damage or destroy the unit.
Note - Information that is helpful for a procedure,
condition, or operation of the unit.
The CPA
The CPA (TPRG) is a PC-Programmable, userconfi gurable alarm. The instrument includes two
alarm (relay) outputs and an optional analog output.
The alarms can be confi gured as trip or fault alarms.
Figure 1. The CPA (TPRG)
The CPA has a READY LED to indicate the health of
the unit, an INPUT LED to indicate the status of the
input and a dual color LED, per relay, to indicate alarm
status.
Model and Serial Numbers
Moore Industries uses a system of model and serial
numbers to keep track of all of the information on
every unit it sells and services. If a problem occurs
with your CPA, check for a tag affi xed to the unit
listing these numbers. Supply the Customer Support
representative with this information when calling.
Inputs
Refer to Table 3 of this manual for input ranges and
accuracies of the CPA (TPRG).
Outputs
1PRG
This is a one relay output with a 5A@250Vac or
5A@24Vdc, 50/60Hz non-inductive contact rating. It
is available in a DPDT arrangement. All relay contacts
(NO, NC and COM) are available for use. No jumpers
are required.
2PRG
This is a two relay ouptut with a 5A@250Vac or
5A@24Vdc, 50/60Hz non-inductive contact rating.
The contact arrangement is SPDT. All relay contacts
(NO, NC and COM) are available for use. No jumpers
are required.
4 The Interface Solution Experts
Options
Analog Output (-AO)
The analog output range of the CPA (TPRG) can
be voltage or current. The current output is a
confi gurable source or sink output. Four terminals
are provided to allow voltage/current and current sink/
source selection without the need for jumpers. The
output can be confi gured to narrower spans from the
PC Confi guration program. The range of the current
output is 0–24mA. The range of the voltage output is
-0.5–11V.
RF Option (-RF)
An RF option is also available. This version provides
30V/m RFI/EMI immunity compared to our standard
model which offers 10V/m RFI/EMI immunity.
Specifi cations
Performance
Alarm Trip Repeatability:
See Table 3
Input Accuracy:
See Table 3
Overall Accuracy: The
overall accuracy of the unit
is the combined input and
output (if any) accuracies.
It includes the combined
effects of linearity,
hysteresis, repeatability,
and adjustment resolution.
It does not include ambient
temperature effect
300msec (Defi ned as time
from step change on input
to alarm state change when
alarm is set to trip midpoint)
Alarm Deadband:
Programmable from
0-100% of input range
Alarm Trip Delay:
0-120 seconds
Line Voltage Effect:
±0.002% of span per 1%
change in line voltage
(ac or dc)
Isolation: Standard unit,
1000Vrms between case,
input and output. 1500Vrms
between power and input
and between power and
output; Unit with -RF option,
500Vrms between case,
input, output and power
Power Consumption:
3W typical, 4W max.
Performance
(continued)
Performance
with Analog
Output (-AO
Option)
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Power Supply Effect:
±0.002% of span per 1%
of line change
Input Impedance: T/C
inputs, 40Mohms, nominal
Input Over-Range
Protection: ±5Vdc
Excitation Current (RTD
and Ohm Inputs Only):
250microamps, ±10%
WITH ANALOG
OUTPUT:
Output Accuracy:
Current, ±0.01% of max.
span (±2 microamps)
Voltage, ±0.01% of max.
span (±1mV)
Response Time:
256msec maximum
(128msec typical) for the
output to change from
10% to 90% of its scale
for an input step change
of 0 to 100%
Ripple: 50mVp-p
maximum on voltage
output; 10mVp-p
measured across a
250 ohm load resistor
for current output.
(Frequencies up to
120Hz)
Output Limiting:
Input over range,
-0.2V/0mA and
10.5V/21.4mA; Input
failure, -0.5V/0mA and
11V/24mA
Output Current Limiting:
25mA max.
Load Effect (current
outputs):
from 0 to maximum load
resistance on current
output
Maximum Load
Resistance: Current
outputs, 1kohms; Voltage
outputs, 2kohms
0.01% of span
Indicators
Ambient
Conditions
Weight
CPA
LED Type: INPUT LED:
Dual color LED indicates
input failure
READY LED: Green LED
indicates unit is operating
properly
ALARM 1 & ALARM 2 LED:
Dual color LED per relay
indicates alarm status
Operating & Storage
Range: -40°C to +85°C
(-40°F to +185°F)
Relay Range: -25°C to
+70°C (-13°F to +158°F)
Effect of Ambient
Temperature on Cold
Junction Compensation
(T/C Inputs Only):
±0.005°C per °C change of
ambient temperature
Relative Humidity:
0-95%, non-condensing
Ambient Temperature
Effect: ±0.015% of
maximum span/°C
RFI/EMI Immunity
(Standard Unit):
10V/m@20-1000MHz, 1kHz
when tested according to
IEC1000-4-3-1995 with
0.5% of span or less error
RFI Immunity (with -RF
Option):
30V/m@20-1000MHz, 1kHz
AM when tested according
to
IEC1000-4-3-1995 with
0.5% of span or less error
Noise Rejection: Common
mode,
100dB@50/60Hz;
Normal Mode,
See Table 2
653 g (21 oz)
Specifi cations and information subject to change without notice.
Table 1. Long-Term Stability
Stability
(% of maximum
span)
RTD, Ohm, & Pot Inputs
T/C & mV Inputs
Input-to-Analog
Output (Years)
1
0.066
0.047
3
0.114
0.082
5
0.147
0.106
Input-to-Relay
Output (Years)
1
0.47
0.081
0.008
0.014
Table 2. Normal Mode Rejection Ratio Table
Sensor Type
T/C: J, K, N, C, E
5
3
0.104
0.019
T/C: T, R, S, B
Pt RTD: 100, 200, 300 ohms
Pt RTD: 400, 500, 1000 ohms
Ni: 120 ohms
Cu: 9.03 ohms
Resistance mV
1-4kohms 250-1000
0.25-1kohms 62.5-250
0.125-0.25kohms 31.25-62.5
The Interface Solution Experts 5
Max. p-p Voltage Injection for
100dB at 50/60Hz
150mV
80mV
250mV
1V
500mV
100mV
1V
250mV
100mV
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Table 3.Accuracy with RTD, Thermocouple, Ohms, Potentiometer and Millivolt Inputs
Input Type α Ohms
RTD
(2-, 3-,
4-Wire)
0.003850
Platinum
0.003902
0.003916
Nickel
Copper
Direct Resistance
Ohms
Potentiometer
0.00672
0.00427
n/a
4000 max.
100
200
300
400
500
1000
100
200
400
500
1000
100
120
9.035
0-4000
Conformance
Range
-200 to 850°C
-328 to 1562°F
-100 to 650°C
-148 to 1202°F
-200 to 510°C
-328 to 950°F
-80 to 320°C
-112 to 608°F
-50 to 250°C
-58 to 482°F
0-4000ohms
0-100%
Minimum
Span
10°C
(18°F)
10ohms
10%
Accuracy/Repeatability
Input
±0.1°C
(±0.18°F)
±0.85°C
(±1.53°F)
±0.4ohms
±0.1%
Maximum
Range
-240 to 960°C
-400 to 1760°F
-150 to 720°C
-238 to 1328°F
-240 to 580°C
-400 to 1076°F
-100 to 360°C
-148 to 680°F
-65 to 280°C
-85 to 536°F
0-4000ohms
0-100%
T/C
mV
J
K
E
T
R
S
B
N
C
DC
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
-180 to 760°C
-292 to 1400°F
-150 to 1370°C
-238 to 2498°F
-170 to 1000°C
-274 to 1832°F
-170 to 400°C
-274 to 752°F
0 to 1760°C
32 to 3200°F
0 to 1760°C
32 to 3200°F
400 to 1820°C
752 to 3308°F
-130 to 1300°C
-202 to 2372°F
0 to 2300°C
32 to 4172°F
-50 to 1000mV
35°C
63°F
40°C
72°F
35°C
63°F
35°C
63°F
50°C
90°F
50°C
90°F
75°C
135°F
45°C
81°F
100°C
180°F
4mV
±0.25°C
(±0.45°F)
±0.3°C
(±0.54°F)
±0.2°C
(±0.36°F)
±0.25°C
(±0.45°F)
±0.55°C
(±0.99°F)
±0.55°C
(±0.99°F)
±0.75°C
(±1.35°F)
±0.4°C
(±0.72°F)
±0.8°C
(±1.44°F)
±15 microvolts
-210 to 770°C
-346 to 1418°F
-270 to 1390°C
-454 to 2534°F
-270 to 1013°C
-454 to 1855.4°F
-270 to 407°C
-454 to 764.6°F
-50 to 1786°C
-58 to 3246.8°F
-50 to 1786°C
-58 to 3246.8°F
200 to 1836°C
392 to 3336.8°F
-270 to 1316°C
-454 to 2400.8°F
0 to 2338°C
32 to 4240.4°F
-50 to 1000mV
6 The Interface Solution Experts
Figure 2. CPA (TPRG) Dimensions
50mm
(1.97 in)
126mm
(4.97 in)
52mm
(2.05 in)
48mm
(1.89 in)
C
L
133mm
(5.24 in)
138mm
(5.43 in)
100mm
(3.94 in)
WHEN INSTALLED
WHEN INSTALLED
READY
INPUT
ALARM 1
ALARM 2
COMPUTER
PROGRAMMABLE
ALARM
COM
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Table 4. Terminal Designations
Input Type
T1 T2 T3 T4 T5 T6 T7 T8 T9
RTD, Ohm, Potentiometer,
T/C & mV Inputs
Output Type/Power
B1 B2 B3 B4 B5 B6 B7 B8 B9
Single Alarm (DPDT Relay)
Dual Alarms (SPDT Relays)
NOTES:
1. Terminal blocks can accomodate 14-22 AWG solid wiring.
2. ±IO/±VO labeling is present only when the unit is equipped
with the Analog Output (-AO) option.
NO1
Relay 1
NO1
Figure 3. Temperature Sensor Hook-Up Guide
Thermocouple
and Millivolt
Input
+
143
2
–
2-Wire RTD
or Decade
Resistance Box
See Figure 3
CM1
Relay 1
CM1
KEY:
AC/DC = Power Input
ACC/DCC = Power Input
COM = Common
DPDT = Double-Pole/DoubleThrow
GND = Ground
NC1NO2
Relay 1
NC1
3-Wire RTD
or Decade
Resistance Box
Top Terminals (Left to Right)
Not
Present
+IO
Source
Bottom Terminals (Left to Right)
CM2
Relay 2
NO2
Relay 2
CM2
IO = Current Output
NO = Normally Open
NC = Normally Closed
Sink = Current Sink
4-Wire RTD
or Decade
NC2AC/DCACC/DCC
Relay 2
NC2
Source = Current Source
SPDT = Single-Pole/DoubleVO = Voltage Output
Potentiometer
Input
Resistance Box
143 2 143 2 143 2
143 2
–IO Source
+IO Sink
AC/DC
+VO
ACC/DCC
–VO
–IO Sink
GND
GND
The Interface Solution Experts 7
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Figure 4. Use the PC Confi guration Software to program the CPA (TPRG)
MILLIVOLT
SOURCE
OR T/C
SIMULATOR
OHMS
OR RTD
SIMULATOR
AC OR DC
POWER
SUPPLY
GND
_
+
To Serial
(COM)
Port of PC
PC
COMPUTER
PROGRAMMABLE
ALARM
INPUT
READY
ALARM 1
ALARM 2
COM
To USB
(COM)
Port of PC
(optional)
INPUT HOOKUP CONNECTIONS
3-Wire RTD or
Decade Resistance Input
OHMS
OR RTD
SIMULATOR
OHMS
OR RTD
SIMULATOR
Confi guring the CPA
One of the benefi ts of this alarm is that there are no
internal or external controls to adjust or settings to
change. All operating parameters are set using a PC
and Moore Industries’ Intelligent PC Confi guration
software.
4-Wire RTD or
Decade Resistance Input
Potentiometer Input
The software settings are downloaded to the
instrument in the form of a Confi guration File and
stored in the instruments’ memory. You can save a
backup copy of the fi le on your PC hard drive or disk.
The alarm communicates with the PC through an RS232 connection to the PC’s serial port.
8 The Interface Solution Experts
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Installing the Confi guration Software
Refer to Table 5 for the equipment needed.
1. I
nsert the Moore Industries Interface Solution PC Confi guration Software CD into the CD
drive of the PC. Access the CD and open the
“CPA CPT PC Confi guration Software” folder.
2.
Double-click the installation program located
in the folder. Follow the prompts to correctly
install the program
Once the Confi guration Program is installed on the
PC, the CPA can be connected to equipment to
simulate input and monitor output. You can then
change the operating parameters of the alarm.
No Alarm Needed
It is not necessary to connect the CPA to a PC to
create confi guration fi les using the software. The
Confi guration Program can be run without connecting
an alarm, and most parameters can be set without
benefi t of input from a sensor or CPA.
.
This makes it easy to create a set of operating
parameters, save them to disk, and download them to
one or more instruments at a later time.
The CPA must be connected to the PC in order to:
trim input, trim output, assign a tag, perform a loop
test, receive (via download) a confi guration fi le, and
save the confi guration fi le from the alarm’s memory.
Connecting the CPA to the PC
Connect the RS-232 end of the cable to the PC’s
COM port.
See Table 5 for information on the necessary
equipment.
Table 5. Assembling the equipment needed to confi gure the CPA (TPRG)
Device Specifi cations
Variable Input Simulator for Thermocouple,
RTD, Millivolt, Potentiometer, or Decade
Resistance Box
Power Supply
Multimeter (optional)
Personal Computer
Moore Industries PC
Confi guration Software
Communication Cable
Variable; Accurate to ±0.05% of unit span
24Vdc, ±10% or 117/230Vac (depending on confi guration)
Accurate to ±0.009% of span; e.g., HP Model 3478A
80386-based(or faster) IBM PC, or 100% compatible;
4Mb free RAM; 8Mb recommended; 20Mb free disk space on hard drive
(More RAM & hard disk space is required for Windows NT, 2000, XP, Vista, or 7)
Microsoft Windows
Internet Explorer 3.0+
1 (one) serial port (COM 1, 2, 3, or 4) set to 9600 baud, no parity, 8 data bits,
and 1 stop bit or one available USB port (with optional USB cable)
Version 1.0 or greater, successfully installed to the hard drive
Part# 803-053-26 or optional USB cable, Part# 208-236-00A
®
)
NT, 2000, XP, Vista, or 7
The Interface Solution Experts 9
CPA
1
2
3
4
5
6
7
8
9
11
12
10
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
PC Confi guration Software Summary
Figure 5. Most of the CPA (TPRG) Operating Parameters can be set from the Main Screen of the Confi guration Program
Once the default confi guration has been saved to
disk, it is safe to program other parameters. The PC
Software is made up of these sections:
1. Status– This portion of the program displays the
activity of the connected unit. It will show the COM
Port being used and the Measurement Mode.
2. Measurements– Displays current software
processes and indications. Allows you to select
the decimal place of your process variable (Decimal Places (PV)) indication and monitor up to two
confi guration variables (Monitored Vars).
3.Device Information– This “read-only” display
indicates fi rmware version, hardware revision,
serial number, calibration date, software version,
confi guration date and the last confi guration source.
4.Communication– From here you may enable Start
Measurements and Stop Measurements, upload your
confi guration to PC or download your confi guration to
the unit, save your confi guration to a fi le, and print out
your confi guration settings.
5. Input Confi guration– Set 50/60Hz Rejection
Selection and selection of °C or °F. Allows you to
choose input type. You may also enable Input Trim, Output Trim, Custom Table and Broken Wire Test
functions.
6.Device Confi guration– Use this parameter to
place an identifying “Message” (32 alphanumeric
characters max.), select an “I.D. Tag” (8 alphanumeric
characters max.) and a “Descriptor” (16 alphanumeric
characters max.).
7. Output Confi guration– Use this section to select
your output confi guration and output limits.
8. Output Level if Failure– Used to select
confi guration of Upscale/Downscale Drive failure
detection of sensor or sensor wiring. Refer to Output
Level if
Failure section for a complete description.
10 The Interface Solution Experts
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
9.Broken Wire Test Override- Allows you to enable
or disable the Broken Wire Test by clicking the “BW
ON” or “BW OFF” buttons. Refer to the Broken Wire Test Override section for a complete description.
10.Alarm Parameters– Use this to choose an
alarm mode and confi gure as either a Trip, Fault or
Band alarm. Select whether to use as a Fail Safe or
NON Fail Safe Alarm. You may also choose a Delay
(0-120sec) and a Deadband (0-100%). Refer to the
Alarms section for a complete description.
11. Trimming/Damping Tab– Selecting this
parameter allows you to perform Sensor Trim, Output
Trim and Output Damping functions. Refer to the
Trimming/Damping section for a complete description.
12.Custom Table Tab– The CPA has two modes of
operation: linear mode and custom mode. In linear
mode, the scaled output is proportional to the scaled
input. In custom mode, reached by selecting the Cus-tom Table Tab, you defi ne a special linearization function. Refer to the Custom Table section for a complete
description.
Confi guration
Output Level if Failure
In the Output Level if Failure section you will notice
Down Scale and Up Scale selection. Using its output,
the CPA can be confi gured to provide a special
warning of a breakdown or failure. Use this setting to
confi gure the instrument to drive its output either up or
down when a failure is detected. For current outputs,
limits are 3.6mA (downscale) and 23.6mA (upscale);
for voltage outputs, limits are -0.5V (downscale) and
11.0V (upscale).
When a failure is detected, the “Fail Last” feature, if
enabled, holds the last measured value before the
failure occurred.
If the “User Selected” feature is enabled, you may
enter any value, within the range, to view at the output
when a failure is detected.
Broken Wire Test Override
During operation, the CPA sends random microamp
pulses through input wiring to check for broken wiring
or a burned out sensor.
Upon power-up Broken Wire Test is enabled. If a
problem is detected, “Broken Wire Failure” in the
Process Information section of the confi guration
program will light to indicate a problem. The Broken
Wire Test may be temporarily disabled by clicking the
“BW OFF” button in the Broken Wire Test Override
section.
Note:
Once you have confi gured all parameters,
download to the unit by either selecting “Download
Confi guration” in the Confi guration dropdown menu
located in the Communications bar or by clicking the
button.
The Interface Solution Experts 11
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Alarms
Trip Low and Trip High Alarms
In the Alarm Parameters portion of the Confi guration
Program you may choose a “Trip Low” and “Trip High”
limit. In choosing your limits you are setting the
parameters for your unit to notify you if your process
input drops below (Trip Low) or exceeds (Trip High)
your trip point setting.
Deadband
Deadband (0-100%) is a type of buffer zone. It allows
an alarm to remain tripped even after the process
input has returned to, or passed, the trip point. If
no deadband is set, the alarm will reset itself once
reaching the trip point.
Fail Safe/NON Fail Safe Alarms
A Fail Safe alarm, if in the alarm condition, will remain
in the alarm condition even if power to the unit is
removed.
The Band Alarm is activated when the Process
Variable is outside of the Low/High Trip point ranges.
The Trip Low is always lower than the Trip High and
their deadbands are inside the range of Low/High Trip.
The span between the Low and High Trip is not limited
which allows control of measurements in a very narrow
range.
The two alarms can be set in any combination. For
example, Alarm 1 can be set as the Band Alarm and
Alarm 2 as the Fault Alarm. Conversely, both alarms
can also be set as Band Alarms.
The HI/LO Alarm can be used when the input signal
reaches a critical level. The HI/HI / LO/LO Alarm is
used to provide early warning that an action is required
before a dangerous level is reached. See Figure 7 for
details.
Figure 7. Two Alarm Functionality Graph
Fail Safe alarm trip relays are energized whenever the
process input is in a non-alarm condition (including
any deadband setting). These relays de-energize
when the process input trips the alarm.
NON Fail Safe alarm trip relays are energized
whenever the process input is in an alarm condition.
These relays de-energize when the process input
returns to the reset point (including any deadband).
Band Alarm
The Band Alarm incorporates Low and High Trip
points, Deadband and Delay (0-120sec).
The Band Alarm combines two Trip Alarm settings.
The fi rst alarm is always confi gured as Low Trip
(Trip Point Low) and the second as High Trip (Trip
Point High). See Figure 6 for information on alarm
parameters.
Figure 6. Band Alarm Parameter Graph
Fault Alarm
To simply be alerted in the case of any fault that may
arise, select the “Fault Alarm” button. This requires no
parameters to be set and will notify you anytime a fault
is sensed.
Note:
Once you have confi gured all parameters,
download to the unit by either selecting “Download
Confi guration” in the Confi guration dropdown menu
located in the Communications bar or by clicking the
button.
12 The Interface Solution Experts
Trimming/Damping
Figure 8. PC Confi guration Software Trimming/Damping Tab
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
To access the Trim feature, click the Trimming/
Damping tab . Trimming increases the measurement
accuracy of the parameter you are trimming by
either matching the reading of its actual input to its
scaling (Sensor Trimming) or calibrating the output
to the device receiving the output (Output Trimming).
Damping allows you to introduce a delay into the
response of your transmitter in order to stop shortlived spikes from setting off alarms. Refer to Figure 9
for hookup.
Sensor Trim
Sensor Trimming increases the measurement
accuracy of your CPA by matching the reading of
its actual input to either a calibrated source or the
device to which it is connected. This verifi es that the
input from the sensor to the alarm is being interpreted
correctly.
The CPA can trim any point along the scale. Note
that one-point trimming applies an offset to the sensor
reading, while two-point trimming applies both an
offset and a gain.
Before you attempt to perform the Sensor Trim
function ensure that the Status section of the screen
indicates “Measurements On”. Sensor Trim can be
done only when the measurements are on. To do this
click the Mode dropdown box, from the menu bar, and
select “Measurements On”.
1. Select either one trim point or two trim points by
clicking the appropriate button. Each pair consists of
“trim” and “captured” values.
2. Enter the values that need to be trimmed into the
corresponding fi elds.
3. Apply the targeted signal to the input, wait until
it settles and click “Point 1 Trim” to capture the
measured value. If you chose “Two-point Trim” repeat
the step above for the second point and click “Point 2
Trim”.
4. To enable input trim and the values stored, click the
“Input Trim ON”.
The Interface Solution Experts 13
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Figure 9. Trimming the CPA (TPRG)
MILLIVOLT
SOURCE
OR T/C
SIMULATOR
OHMS
OR RTD
SIMULATOR
AC OR DC
POWER
SUPPLY
GND
_
+
COMPUTER
PROGRAMMABLE
ALARM
INPUT
READY
ALARM 1
ALARM 2
COM
MULTIMETER
OR
DCS
-
+
CURRENT OUTPUT SOURCE
14 The Interface Solution Experts
TRIM CONFIGURATION
EXTERNAL
POWER
SUPPLY
+
-
OR
DCS
+
-
MULTIMETER
CURRENT OUTPUT SINK
MULTIMETER
OR
DCS
+
VOLTAGE OUTPUT
-
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Output Trim
Output Trimming increases the measurement accuracy
of your CPA by calibrating its analog output to the
device that is receiving the output. This ensures that
the instrument is being correctly interpreted.
Before you attempt to perform the Output Trim
function ensure that the Status section of the screen
indicates “Measurements Off”. To do this click the
Mode dropdown box from the Menu bar and select
“Measurements Off”.
1. Select either “Output: mA” or “Output: V”, whichever
is appropriate for your application.
2. Attach a multimeter to the analog output and select
the “4mA” or “0V” button. Use the scroll bar to trim the
measured output to your desired value.
3. With the multimeter still connected select the
“20mA” or “10V” button. Use the scroll bar to trim the
measured output to your desired value.
4. To enable Output Trim and the values stored, click
the “Output Trim ON”.
5. Set Status back to “Measurements On”.
If selected, the user trim values will be used and the
manufacturer settings will be nullifi ed.
Loop Test
A Loop Test may be performed in order to check
output performance and accuracy and to trim other
instruments in the loop. Your output will be a current
value, in mA, or a voltage equal to the value you input.
You can check the other current devices on the loop
and calibrate them to this signal.
This feature is independent of the input. If you fi nd
that the output requires adjustment you may perform
the Output Trim function.
1. To use the Loop Test function select the Mode
dropdown box in the Communications bar and select
“Measurements Off”.
2. Next, in the “Output Value %” box, type the
percentage of the output value you wish to test. You
may also use your mouse, left click and adjust the
scroll bar to adjust to your desired value. Hit “Enter”.
3. In the “Output Value” box enter the value, within
your confi guration range, that you wish to signify as
your output value. Hit “Enter”.
4. Perform your test and calibration.
5. When you are fi nished, return to Mode in the
Communications bar and reset your status to
“Measurements On”.
The Interface Solution Experts 15
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Output Damping
Output Damping allows you to introduce a delay into
the response of your unit in order to stop short-lived
spikes from setting off alarms. Output Damping is
activated when the value set in the “Output Step
Threshold” fi eld is exceeded.
1. To enable output damping, select the “Enabled”
button. If you do not wish to use the damping feature,
then select “Disabled”.
2. Insert a value between 1 and 16mA in the “Output
Step Threshold” fi eld. This is how much of an output
step change is allowed in a specifi ed time frame
before fl agging the software.
3. Insert a value between .5 and 120sec in the
“Damping Sec” fi eld. This is the amount of time it will
take for the output to reach 63% of the step output
change once the input exceeds the value in the
“Output Step Threshold” fi eld.
By checking the appropriate box in the Other Damping Options section, you may also choose to select Output
Damping to occur upon power up or start up from
a PC, upon broken wire failure detection or upon
resolution of broken wire failure.
A possible source for this occurence is a rapid change
on the input. Another possiblity would be an existing
output level of 5.6mA upon Start Measurements from
a PC.
Figure 11 gives another damping example where the
output has been driven upscale to 23.6mA. After
fi ve seconds the 63% output change is reached at
16.98mA.
Figure 11. Damping When Output Driven Upscale to 23.6mA
In this instance, detection of an open sensor or broken
wire could be a cause. An instrument malfunction or
Adc/EEPROM failure may also be suspect.
A typical damping situation would be described as a
step change in output which causes the output to go
from 5.6mA to 20mA. After fi ve seconds the output
reaches 14.58mA which equals 63% of the output
step change. This is graphed in Figure 10.
Figure 10. Typical Damping Scenario
Output if Measurement OFF
Choose “Zero Range” to read zero volts or mA at
output if measurement was off.
Choose “Stay Last” to read the last value held before
the measurement was off.
Note:
Once you have confi gured all parameters,
download to the unit by either selecting “Download
Confi guration” in the Confi guration dropdown menu
located in the Communications bar or by clicking the
button.
16 The Interface Solution Experts
Custom Table
Figure 12. PC Confi guration Software Custom Table Tab
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
The Custom Table feature allows you to setup your
own custom curve table (Figure 12). This allows you
to tell the CPA what it should output when it receives
a certain input. This feature also allows you the ability
to write a table in Microsoft
format. The fi les are saved to/read to/read from the
“Moore Industries\Custom Curves” folder. This makes
it simple to save the custom table for downloading to
multiple units or for backup purposes.
The linearization will be in the form of X, Y coordinates. You may choose up to 128 points.
To access this function click the Custom Table tab.
1. Select the number of points you are to set and
insert this value into the “Number Of Points” line, hit
“Enter”. This will highlight the number of points you
have selected.
To clear the table and start over at any time, click
®
Excel and save it in a .csv
Note:
“Clear Table”.
2. Type your individual values in the X and Y columns.
Source variables are inserted into the X Column while
the corresponding data is inserted into the Y Column.
3. To save the displayed custom table to your hard
drive click the “Save Table” button.
To open or use this saved table at a later time, click
the “Open Table” button and select the folder in which
it has been saved.
Use the “Table EGU” box to enter any alphanumeric
engineering unit (up to 6 digits).
To use the Custom Table feature in your operation,
check the “Custom Table ON” box.
Note:
Once you have confi gured all parameters,
download to the unit by either selecting “Download
Confi guration” in the Confi guration dropdown menu
located in the Communications bar or by clicking the
button.
The Interface Solution Experts 17
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Installation
Installation consists of physically mounting the unit
and completing the electrical connections.
Mounting the CPA
The CPA can be mounted on standard DIN mounting
rails.
Making the Electrical Connections
Please refer to Figure 4 for electrical connections.
Recommended Ground Wiring
Practices
Moore Industries recommends the following ground
wiring practices:
• Any Moore Industries product in a metal case or
housing should be grounded.
• The protective earth conductor must be connected
to a system safety earth ground before making any
other connections.
• All input signals to, and output signals from, Moore
Industries’ products should be wired using a
shielded, twisted pair technique. Shields are to be
connected to an earth or safety ground at the unit
itself.
• The maximum length of unshielded input
and/or output signal wiring should be
two inches.
Operation
Once programmed, calibrated, installed, and supplied
with the correct power, the CPA alarm begins to
operate immediately. Depending upon environmental
conditions, it can be expected to operate unattended
for extended periods of time.
Maintenance
Moore Industries suggests a quick check for terminal
tightness and general unit condition every 6-8
months. Always adhere to any site requirements for
programmed maintenance.
Customer Support
Moore Industries is recognized as the industry leader
in delivering top quality to its customers in products
and services. We perform a battery of stringent
quality assurance checks on every unit we ship. If
any Moore Industries product fails to perform up
to rated specifi cations, call us for help. Our highly
skilled staff of trained technicians and engineers pride
themselves on their ability to provide timely, accurate,
and practical answers to your process instrumentation
questions.
Factory phone numbers are listed on the back cover of
this manual.
If problems involve a particular CPA, there are several
pieces of information that can be gathered
before you call the factory that will help our staff get
the answers you need in the shortest time possible.
For fastest service, gather the complete model and
serial number(s) of the problem unit(s) and the job
number of the original sale.
CE Conformity
Installation of any Moore Industries’ products that
carry the CE certifi cation must adhere to the
guidelines above in order to meet the requirements set
forth in the European EMC and Low Voltage Directives
(EN 61326 and EN 61010). Consult the factory for the
most current information on products that have been
CE certifi ed.
18 The Interface Solution Experts
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair –
If you are unsure if your unit is still under warranty, we can use the unit’s serial number
to verify the warranty status for you over the phone. Be sure to include the RMA
number on all documentation.
Non-Warranty Repair –
If your unit is out of warranty, be prepared to give us a Purchase Order number when
you call. In most cases, we will be able to quote you the repair costs at that time.
The repair price you are quoted will be a “Not To Exceed” price, which means that the
actual repair costs may be less than the quote. Be sure to include the RMA number on
all documentation.
2. Provide us with the following documentation:
a) A note listing the symptoms that indicate the unit needs repair
b) Complete shipping information for return of the equipment after repair
c) The name and phone number of the person to contact if questions arise at the factory
3. Use suffi cient packing material and carefully pack the equipment in a sturdy shipping container.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries representative will contact the person designated on your documentation if more information is
needed. The repaired equipment, or its replacement, will be returned to you in accordance
with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WARRANTIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR
OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY
GOODS OR SERVICES SOLD BY THE COMPANY. THE COMPANY DISCLAIMS ALL WARRANTIES ARISING FROM ANY COURSE OF DEALING
OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM
THE COMPANY ACKNOWLEDGES THAT THERE ARE NO WARRANTIES
IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND
OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER
WITH THE COMPANY DO NOT IMPLY THAT THE COMPANY WARRANTS
THE GOODS OR SERVICES IN ANY WAY.
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY
AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REMEDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR
SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR
OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE
PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS
IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES
, BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE
THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER
FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY
THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RECEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED
DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE
ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED
THE ALLEGED DEFECT OR BREACH, AND NO ACTION FOR THE
BREACH OF ANY WARRANTY SHALL BE COMMENCED BY THE
BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST
DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under
normal conditions of use and service, Moore Industries (“The Company”)
will at its option replace, repair or refund the purchase price for any of its
manufactured products found, upon return to the Company (transportation
charges prepaid and otherwise in accordance with the return procedures
established by The Company), to be defective in material or workmanship.
This policy extends to the original Buyer only and not to Buyer’s customers
or the users of Buyer’s products, unless Buyer is an engineering contractor
in which case the policy shall extend to Buyer’s immediate customer only.
This policy shall not apply if the product has been subject to alteration,
misuse, accident, neglect or improper application, installation, or operation.
THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL
OR CONSEQUENTIAL DAMAGES.