Moore Industries CPA, TPRG User Manual

-AY 201225-701-01%
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
CPA
All product names are registered trademarks of their respective companies.

Table of Contents

Introduction ............................................................................................................................................. 4
About this Manual ............................................................................................................4
The CPA .......................................................................................................................... 4
Model and Serial Numbers............................................................................................... 4
Options ............................................................................................................................. 4
Specifi cations ................................................................................................. 5
Dimensions ...................................................................................................................... 7
Confi guring the CPA....................................................................................... 8
Installing the Confi guration Software ............................................................................... 9
Connecting the CPA to the PC ......................................................................................... 9
PC Confi guration Software Summary ........................................................ 10
Confi guration ................................................................................................ 11
Output Level if Failure ....................................................................................................11
Broken Wire Test Override ............................................................................................. 11
Alarms ............................................................................................................................ 12
Trimming/Damping ....................................................................................... 13
Sensor Trim ....................................................................................................................13
Output Trim ..................................................................................................................... 15
Loop Test ........................................................................................................................ 15
Output Damping ............................................................................................................. 16
Output If Measurement OFF .......................................................................................... 16
Custom Table ................................................................................................ 17
Installation ..................................................................................................... 18
Mounting the CPA ..........................................................................................................18
Making the Electrical Connections ................................................................................. 18
Recommended Ground Wiring Practices ....................................................................... 18
CE Conformity ................................................................................................................ 18
Operation ....................................................................................................... 18
Maintenance ...................................................................................................................18
CPA
READY
INPUT
ALARM 1
ALARM 2
COMPUTER PROGRAMMABLE ALARM
COM
PC-Programmable RTD, T/C, Ohms, mV and Potentiometer Limit Alarm Trips

Introduction

This is the users’ manual for the Moore Industries CPA PC-Programmable Alarm (TPRG: RTD, T/C, mV, Ohms and Potentiometer Limit Alarm Trips). It contains all of the information needed to confi gure, install, operate, and maintain this instrument.

About this Manual

Wherever you see a “ Note”, “ Caution”, or “ WARNING ” pay particular attention.
WARNING - Hazardous procedure or condition that could injure the operator.
Caution - Hazardous procedure or condition that could damage or destroy the unit.
Note - Information that is helpful for a procedure, condition, or operation of the unit.

The CPA

The CPA (TPRG) is a PC-Programmable, user­confi gurable alarm. The instrument includes two alarm (relay) outputs and an optional analog output. The alarms can be confi gured as trip or fault alarms.
Figure 1. The CPA (TPRG)
The CPA has a READY LED to indicate the health of the unit, an INPUT LED to indicate the status of the input and a dual color LED, per relay, to indicate alarm status.

Model and Serial Numbers

Moore Industries uses a system of model and serial numbers to keep track of all of the information on every unit it sells and services. If a problem occurs with your CPA, check for a tag affi xed to the unit listing these numbers. Supply the Customer Support representative with this information when calling.

Inputs

Refer to Table 3 of this manual for input ranges and accuracies of the CPA (TPRG).

Outputs

1PRG
This is a one relay output with a 5A@250Vac or 5A@24Vdc, 50/60Hz non-inductive contact rating. It is available in a DPDT arrangement. All relay contacts (NO, NC and COM) are available for use. No jumpers are required.
2PRG
This is a two relay ouptut with a 5A@250Vac or 5A@24Vdc, 50/60Hz non-inductive contact rating. The contact arrangement is SPDT. All relay contacts (NO, NC and COM) are available for use. No jumpers are required.
4 The Interface Solution Experts

Options

Analog Output (-AO)
The analog output range of the CPA (TPRG) can be voltage or current. The current output is a confi gurable source or sink output. Four terminals are provided to allow voltage/current and current sink/ source selection without the need for jumpers. The output can be confi gured to narrower spans from the PC Confi guration program. The range of the current output is 0–24mA. The range of the voltage output is
-0.5–11V.
RF Option (-RF)
An RF option is also available. This version provides 30V/m RFI/EMI immunity compared to our standard model which offers 10V/m RFI/EMI immunity.
Specifi cations
Performance
Alarm Trip Repeatability:
See Table 3 Input Accuracy: See Table 3 Overall Accuracy: The overall accuracy of the unit is the combined input and output (if any) accuracies. It includes the combined effects of linearity, hysteresis, repeatability, and adjustment resolution. It does not include ambient temperature effect
Mimimum Span at Specifi ed Accuracy:
See Table 3
Cold Junction Compensation Accuracy (T/C Inputs Only): ±0.45°C Stability: See Table 1 Response Time:
300msec (Defi ned as time from step change on input to alarm state change when alarm is set to trip midpoint)
Alarm Deadband:
Programmable from 0-100% of input range
Alarm Trip Delay:
0-120 seconds Line Voltage Effect: ±0.002% of span per 1% change in line voltage (ac or dc) Isolation: Standard unit, 1000Vrms between case, input and output. 1500Vrms between power and input and between power and output; Unit with -RF option, 500Vrms between case, input, output and power
Power Consumption:
3W typical, 4W max.
Performance
(continued)
Performance
with Analog Output (-AO
Option)
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Power Supply Effect:
±0.002% of span per 1% of line change Input Impedance: T/C inputs, 40Mohms, nominal
Input Over-Range Protection: ±5Vdc Excitation Current (RTD and Ohm Inputs Only):
250microamps, ±10%
WITH ANALOG OUTPUT: Output Accuracy:
Current, ±0.01% of max. span (±2 microamps) Voltage, ±0.01% of max. span (±1mV)
Response Time:
256msec maximum (128msec typical) for the output to change from 10% to 90% of its scale for an input step change of 0 to 100% Ripple: 50mVp-p maximum on voltage output; 10mVp-p measured across a 250 ohm load resistor for current output. (Frequencies up to 120Hz) Output Limiting: Input over range,
-0.2V/0mA and
10.5V/21.4mA; Input failure, -0.5V/0mA and 11V/24mA
Output Current Limiting:
25mA max.
Load Effect (current outputs):
from 0 to maximum load resistance on current output
Maximum Load Resistance: Current
outputs, 1kohms; Voltage outputs, 2kohms
0.01% of span
Indicators
Ambient
Conditions
Weight
CPA
LED Type: INPUT LED:
Dual color LED indicates input failure READY LED: Green LED indicates unit is operating properly ALARM 1 & ALARM 2 LED: Dual color LED per relay indicates alarm status
Operating & Storage Range: -40°C to +85°C
(-40°F to +185°F) Relay Range: -25°C to +70°C (-13°F to +158°F)
Effect of Ambient Temperature on Cold Junction Compensation (T/C Inputs Only):
±0.005°C per °C change of ambient temperature Relative Humidity: 0-95%, non-condensing
Ambient Temperature Effect: ±0.015% of
maximum span/°C
RFI/EMI Immunity (Standard Unit):
10V/m@20-1000MHz, 1kHz when tested according to IEC1000-4-3-1995 with
0.5% of span or less error
RFI Immunity (with -RF Option):
30V/m@20-1000MHz, 1kHz AM when tested according to IEC1000-4-3-1995 with
0.5% of span or less error Noise Rejection: Common mode, 100dB@50/60Hz; Normal Mode,
See Table 2
653 g (21 oz)
Specifi cations and information subject to change without notice.
Table 1. Long-Term Stability
Stability
(% of maximum
span)
RTD, Ohm, & Pot Inputs
T/C & mV Inputs
Input-to-Analog
Output (Years)
1
0.066
0.047
3
0.114
0.082
5
0.147
0.106
Input-to-Relay
Output (Years)
1
0.47
0.081
0.008
0.014
Table 2. Normal Mode Rejection Ratio Table
Sensor Type
T/C: J, K, N, C, E
5
3
0.104
0.019
T/C: T, R, S, B
Pt RTD: 100, 200, 300 ohms
Pt RTD: 400, 500, 1000 ohms
Ni: 120 ohms
Cu: 9.03 ohms
Resistance mV
1-4kohms 250-1000
0.25-1kohms 62.5-250
0.125-0.25kohms 31.25-62.5
The Interface Solution Experts 5
Max. p-p Voltage Injection for
100dB at 50/60Hz
150mV
80mV
250mV
1V
500mV
100mV
1V
250mV
100mV
CPA
PC-Programmable RTD, T/C, Ohms, mV and Potentiometer Limit Alarm Trips

Table 3. Accuracy with RTD, Thermocouple, Ohms, Potentiometer and Millivolt Inputs

Input Type α Ohms
RTD
(2-, 3-,
4-Wire)
0.003850
Platinum
0.003902
0.003916
Nickel
Copper
Direct Resistance
Ohms
Potentiometer
0.00672
0.00427
n/a
4000 max.
100
200
300
400
500
1000
100
200
400
500
1000
100
120
9.035
0-4000
Conformance
Range
-200 to 850°C
-328 to 1562°F
-100 to 650°C
-148 to 1202°F
-200 to 510°C
-328 to 950°F
-80 to 320°C
-112 to 608°F
-50 to 250°C
-58 to 482°F
0-4000ohms
0-100%
Minimum
Span
10°C
(18°F)
10ohms
10%
Accuracy/Repeatability
Input
±0.1°C
(±0.18°F)
±0.85°C
(±1.53°F)
±0.4ohms
±0.1%
Maximum
Range
-240 to 960°C
-400 to 1760°F
-150 to 720°C
-238 to 1328°F
-240 to 580°C
-400 to 1076°F
-100 to 360°C
-148 to 680°F
-65 to 280°C
-85 to 536°F
0-4000ohms
0-100%
T/C
mV
J
K
E
T
R
S
B
N
C
DC
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
-180 to 760°C
-292 to 1400°F
-150 to 1370°C
-238 to 2498°F
-170 to 1000°C
-274 to 1832°F
-170 to 400°C
-274 to 752°F
0 to 1760°C
32 to 3200°F
0 to 1760°C
32 to 3200°F
400 to 1820°C 752 to 3308°F
-130 to 1300°C
-202 to 2372°F
0 to 2300°C
32 to 4172°F
-50 to 1000mV
35°C 63°F
40°C 72°F
35°C 63°F
35°C 63°F
50°C 90°F
50°C 90°F
75°C
135°F
45°C 81°F
100°C 180°F
4mV
±0.25°C
(±0.45°F)
±0.3°C
(±0.54°F)
±0.2°C
(±0.36°F)
±0.25°C
(±0.45°F)
±0.55°C
(±0.99°F)
±0.55°C
(±0.99°F)
±0.75°C
(±1.35°F)
±0.4°C
(±0.72°F)
±0.8°C
(±1.44°F)
±15 microvolts
-210 to 770°C
-346 to 1418°F
-270 to 1390°C
-454 to 2534°F
-270 to 1013°C
-454 to 1855.4°F
-270 to 407°C
-454 to 764.6°F
-50 to 1786°C
-58 to 3246.8°F
-50 to 1786°C
-58 to 3246.8°F
200 to 1836°C
392 to 3336.8°F
-270 to 1316°C
-454 to 2400.8°F
0 to 2338°C
32 to 4240.4°F
-50 to 1000mV
6 The Interface Solution Experts
Figure 2. CPA (TPRG) Dimensions
50mm
(1.97 in)
126mm
(4.97 in)
52mm
(2.05 in)
48mm
(1.89 in)
C
L
133mm
(5.24 in)
138mm
(5.43 in)
100mm
(3.94 in)
WHEN INSTALLED
WHEN INSTALLED
READY
INPUT
ALARM 1
ALARM 2
COMPUTER PROGRAMMABLE ALARM
COM
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips

Table 4. Terminal Designations

Input Type
T1 T2 T3 T4 T5 T6 T7 T8 T9
RTD, Ohm, Potentiometer,
T/C & mV Inputs
Output Type/Power
B1 B2 B3 B4 B5 B6 B7 B8 B9
Single Alarm (DPDT Relay)
Dual Alarms (SPDT Relays)
NOTES:
1. Terminal blocks can accomodate 14-22 AWG solid wiring.
2. ±IO/±VO labeling is present only when the unit is equipped with the Analog Output (-AO) option.
NO1
Relay 1
NO1

Figure 3. Temperature Sensor Hook-Up Guide

Thermocouple
and Millivolt
Input
+
143
2
2-Wire RTD
or Decade
Resistance Box
See Figure 3
CM1
Relay 1
CM1
KEY:
AC/DC = Power Input ACC/DCC = Power Input COM = Common DPDT = Double-Pole/Double­Throw GND = Ground
NC1 NO2
Relay 1
NC1
3-Wire RTD
or Decade
Resistance Box
Top Terminals (Left to Right)
Not
Present
+IO
Source
Bottom Terminals (Left to Right)
CM2
Relay 2
NO2
Relay 2
CM2
IO = Current Output NO = Normally Open NC = Normally Closed Sink = Current Sink
4-Wire RTD
or Decade
NC2 AC/DC ACC/DCC
Relay 2
NC2
Source = Current Source SPDT = Single-Pole/Double­VO = Voltage Output
Potentiometer
Input
Resistance Box
143 2 143 2 143 2
143 2
–IO Source
+IO Sink
AC/DC
+VO
ACC/DCC
–VO
–IO Sink
GND
GND
The Interface Solution Experts 7
CPA
PC-Programmable RTD, T/C, Ohms, mV and Potentiometer Limit Alarm Trips
Figure 4. Use the PC Confi guration Software to program the CPA (TPRG)
MILLIVOLT
SOURCE
OR T/C
SIMULATOR
OHMS
OR RTD
SIMULATOR
AC OR DC
POWER SUPPLY
GND
_
+
To Serial
(COM)
Port of PC
PC
COMPUTER PROGRAMMABLE ALARM
INPUT
READY
ALARM 1
ALARM 2
COM
To USB
(COM)
Port of PC
(optional)
INPUT HOOKUP CONNECTIONS
3-Wire RTD or
Decade Resistance Input
OHMS
OR RTD
SIMULATOR
OHMS
OR RTD
SIMULATOR
Confi guring the CPA
One of the benefi ts of this alarm is that there are no internal or external controls to adjust or settings to change. All operating parameters are set using a PC and Moore Industries’ Intelligent PC Confi guration software.
4-Wire RTD or
Decade Resistance Input
Potentiometer Input
The software settings are downloaded to the instrument in the form of a Confi guration File and stored in the instruments’ memory. You can save a backup copy of the fi le on your PC hard drive or disk. The alarm communicates with the PC through an RS­232 connection to the PC’s serial port.
8 The Interface Solution Experts
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Installing the Confi guration Software
Refer to Table 5 for the equipment needed.
1. I
nsert the Moore Industries Interface Solution PC Confi guration Software CD into the CD drive of the PC. Access the CD and open the “CPA CPT PC Confi guration Software” folder.
2.
Double-click the installation program located in the folder. Follow the prompts to correctly install the program
Once the Confi guration Program is installed on the PC, the CPA can be connected to equipment to simulate input and monitor output. You can then change the operating parameters of the alarm.
No Alarm Needed
It is not necessary to connect the CPA to a PC to create confi guration fi les using the software. The Confi guration Program can be run without connecting an alarm, and most parameters can be set without benefi t of input from a sensor or CPA.
.
This makes it easy to create a set of operating parameters, save them to disk, and download them to one or more instruments at a later time.
The CPA must be connected to the PC in order to: trim input, trim output, assign a tag, perform a loop test, receive (via download) a confi guration fi le, and save the confi guration fi le from the alarm’s memory.

Connecting the CPA to the PC

Connect the RS-232 end of the cable to the PC’s
COM port.
See Table 5 for information on the necessary equipment.
Table 5. Assembling the equipment needed to confi gure the CPA (TPRG)
Device Specifi cations
Variable Input Simulator for Thermocouple,
RTD, Millivolt, Potentiometer, or Decade
Resistance Box
Power Supply
Multimeter (optional)
Personal Computer
Moore Industries PC
Confi guration Software
Communication Cable
Variable; Accurate to ±0.05% of unit span
24Vdc, ±10% or 117/230Vac (depending on confi guration)
Accurate to ±0.009% of span; e.g., HP Model 3478A
80386-based(or faster) IBM PC, or 100% compatible; 4Mb free RAM; 8Mb recommended; 20Mb free disk space on hard drive (More RAM & hard disk space is required for Windows NT, 2000, XP, Vista, or 7) Microsoft Windows Internet Explorer 3.0+ 1 (one) serial port (COM 1, 2, 3, or 4) set to 9600 baud, no parity, 8 data bits, and 1 stop bit or one available USB port (with optional USB cable)
Version 1.0 or greater, successfully installed to the hard drive
Part# 803-053-26 or optional USB cable, Part# 208-236-00A
®
)
NT, 2000, XP, Vista, or 7
The Interface Solution Experts 9
CPA
1
2
3
4
5
6
7
8
9
11
12
10
PC-Programmable RTD, T/C, Ohms, mV and Potentiometer Limit Alarm Trips
PC Confi guration Software Summary
Figure 5. Most of the CPA (TPRG) Operating Parameters can be set from the Main Screen of the Confi guration Program
Once the default confi guration has been saved to disk, it is safe to program other parameters. The PC Software is made up of these sections:
1. Status– This portion of the program displays the activity of the connected unit. It will show the COM Port being used and the Measurement Mode.
2. Measurements– Displays current software processes and indications. Allows you to select the decimal place of your process variable (Decimal Places (PV)) indication and monitor up to two confi guration variables (Monitored Vars).
3. Device Information– This “read-only” display indicates fi rmware version, hardware revision, serial number, calibration date, software version, confi guration date and the last confi guration source.
4. Communication– From here you may enable Start Measurements and Stop Measurements, upload your
confi guration to PC or download your confi guration to the unit, save your confi guration to a fi le, and print out your confi guration settings.
5. Input Confi guration– Set 50/60Hz Rejection Selection and selection of °C or °F. Allows you to choose input type. You may also enable Input Trim, Output Trim, Custom Table and Broken Wire Test functions.
6. Device Confi guration– Use this parameter to place an identifying “Message” (32 alphanumeric characters max.), select an “I.D. Tag” (8 alphanumeric characters max.) and a “Descriptor” (16 alphanumeric characters max.).
7. Output Confi guration– Use this section to select your output confi guration and output limits.
8. Output Level if Failure– Used to select confi guration of Upscale/Downscale Drive failure detection of sensor or sensor wiring. Refer to Output
Level if Failure section for a complete description.
10 The Interface Solution Experts
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
9. Broken Wire Test Override- Allows you to enable or disable the Broken Wire Test by clicking the “BW ON” or “BW OFF” buttons. Refer to the Broken Wire Test Override section for a complete description.
10. Alarm Parameters– Use this to choose an alarm mode and confi gure as either a Trip, Fault or Band alarm. Select whether to use as a Fail Safe or NON Fail Safe Alarm. You may also choose a Delay (0-120sec) and a Deadband (0-100%). Refer to the Alarms section for a complete description.
11. Trimming/Damping Tab– Selecting this parameter allows you to perform Sensor Trim, Output Trim and Output Damping functions. Refer to the Trimming/Damping section for a complete description.
12. Custom Table Tab– The CPA has two modes of operation: linear mode and custom mode. In linear mode, the scaled output is proportional to the scaled input. In custom mode, reached by selecting the Cus- tom Table Tab, you defi ne a special linearization func­tion. Refer to the Custom Table section for a complete description.
Confi guration

Output Level if Failure

In the Output Level if Failure section you will notice Down Scale and Up Scale selection. Using its output, the CPA can be confi gured to provide a special warning of a breakdown or failure. Use this setting to confi gure the instrument to drive its output either up or down when a failure is detected. For current outputs, limits are 3.6mA (downscale) and 23.6mA (upscale); for voltage outputs, limits are -0.5V (downscale) and
11.0V (upscale).
When a failure is detected, the “Fail Last” feature, if enabled, holds the last measured value before the failure occurred.
If the “User Selected” feature is enabled, you may enter any value, within the range, to view at the output when a failure is detected.

Broken Wire Test Override

During operation, the CPA sends random microamp pulses through input wiring to check for broken wiring or a burned out sensor.
Upon power-up Broken Wire Test is enabled. If a problem is detected, “Broken Wire Failure” in the Process Information section of the confi guration program will light to indicate a problem. The Broken Wire Test may be temporarily disabled by clicking the “BW OFF” button in the Broken Wire Test Override section.
Note:
Once you have confi gured all parameters,
download to the unit by either selecting “Download
Confi guration” in the Confi guration dropdown menu
located in the Communications bar or by clicking the
button.
The Interface Solution Experts 11
CPA
PC-Programmable RTD, T/C, Ohms, mV and Potentiometer Limit Alarm Trips

Alarms

Trip Low and Trip High Alarms
In the Alarm Parameters portion of the Confi guration Program you may choose a “Trip Low” and “Trip High” limit. In choosing your limits you are setting the parameters for your unit to notify you if your process input drops below (Trip Low) or exceeds (Trip High) your trip point setting.
Deadband
Deadband (0-100%) is a type of buffer zone. It allows an alarm to remain tripped even after the process input has returned to, or passed, the trip point. If no deadband is set, the alarm will reset itself once reaching the trip point.
Fail Safe/NON Fail Safe Alarms
A Fail Safe alarm, if in the alarm condition, will remain in the alarm condition even if power to the unit is removed.
The Band Alarm is activated when the Process Variable is outside of the Low/High Trip point ranges. The Trip Low is always lower than the Trip High and their deadbands are inside the range of Low/High Trip. The span between the Low and High Trip is not limited which allows control of measurements in a very narrow range.
The two alarms can be set in any combination. For example, Alarm 1 can be set as the Band Alarm and Alarm 2 as the Fault Alarm. Conversely, both alarms can also be set as Band Alarms.
The HI/LO Alarm can be used when the input signal reaches a critical level. The HI/HI / LO/LO Alarm is used to provide early warning that an action is required before a dangerous level is reached. See Figure 7 for details.
Figure 7. Two Alarm Functionality Graph
Fail Safe alarm trip relays are energized whenever the process input is in a non-alarm condition (including any deadband setting). These relays de-energize when the process input trips the alarm.
NON Fail Safe alarm trip relays are energized whenever the process input is in an alarm condition. These relays de-energize when the process input returns to the reset point (including any deadband).
Band Alarm
The Band Alarm incorporates Low and High Trip points, Deadband and Delay (0-120sec).
The Band Alarm combines two Trip Alarm settings. The fi rst alarm is always confi gured as Low Trip (Trip Point Low) and the second as High Trip (Trip Point High). See Figure 6 for information on alarm parameters.
Figure 6. Band Alarm Parameter Graph
Fault Alarm
To simply be alerted in the case of any fault that may arise, select the “Fault Alarm” button. This requires no parameters to be set and will notify you anytime a fault is sensed.
Note:
Once you have confi gured all parameters,
download to the unit by either selecting “Download
Confi guration” in the Confi guration dropdown menu
located in the Communications bar or by clicking the
button.
12 The Interface Solution Experts

Trimming/Damping

Figure 8. PC Confi guration Software Trimming/Damping Tab
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
To access the Trim feature, click the Trimming/ Damping tab . Trimming increases the measurement
accuracy of the parameter you are trimming by either matching the reading of its actual input to its scaling (Sensor Trimming) or calibrating the output to the device receiving the output (Output Trimming). Damping allows you to introduce a delay into the response of your transmitter in order to stop short­lived spikes from setting off alarms. Refer to Figure 9 for hookup.

Sensor Trim

Sensor Trimming increases the measurement accuracy of your CPA by matching the reading of its actual input to either a calibrated source or the device to which it is connected. This verifi es that the input from the sensor to the alarm is being interpreted correctly.
The CPA can trim any point along the scale. Note that one-point trimming applies an offset to the sensor reading, while two-point trimming applies both an offset and a gain.
Before you attempt to perform the Sensor Trim function ensure that the Status section of the screen indicates “Measurements On”. Sensor Trim can be done only when the measurements are on. To do this click the Mode dropdown box, from the menu bar, and select “Measurements On”.
1. Select either one trim point or two trim points by clicking the appropriate button. Each pair consists of “trim” and “captured” values.
2. Enter the values that need to be trimmed into the corresponding fi elds.
3. Apply the targeted signal to the input, wait until it settles and click “Point 1 Trim” to capture the measured value. If you chose “Two-point Trim” repeat the step above for the second point and click “Point 2 Trim”.
4. To enable input trim and the values stored, click the “Input Trim ON”.
The Interface Solution Experts 13
CPA
PC-Programmable RTD, T/C, Ohms, mV and Potentiometer Limit Alarm Trips
Figure 9. Trimming the CPA (TPRG)
MILLIVOLT
SOURCE
OR T/C
SIMULATOR
OHMS
OR RTD
SIMULATOR
AC OR DC
POWER SUPPLY
GND
_
+
COMPUTER PROGRAMMABLE ALARM
INPUT
READY
ALARM 1
ALARM 2
COM
MULTIMETER
OR
DCS
-
+
CURRENT OUTPUT SOURCE
14 The Interface Solution Experts
TRIM CONFIGURATION
EXTERNAL
POWER SUPPLY +
-
OR
DCS
+
-
MULTIMETER
CURRENT OUTPUT SINK
MULTIMETER
OR
DCS
+
VOLTAGE OUTPUT
-
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips

Output Trim

Output Trimming increases the measurement accuracy of your CPA by calibrating its analog output to the device that is receiving the output. This ensures that the instrument is being correctly interpreted.
Before you attempt to perform the Output Trim function ensure that the Status section of the screen indicates “Measurements Off”. To do this click the Mode dropdown box from the Menu bar and select “Measurements Off”.
1. Select either “Output: mA” or “Output: V”, whichever is appropriate for your application.
2. Attach a multimeter to the analog output and select the “4mA” or “0V” button. Use the scroll bar to trim the measured output to your desired value.
3. With the multimeter still connected select the “20mA” or “10V” button. Use the scroll bar to trim the measured output to your desired value.
4. To enable Output Trim and the values stored, click the “Output Trim ON”.
5. Set Status back to “Measurements On”.
If selected, the user trim values will be used and the manufacturer settings will be nullifi ed.

Loop Test

A Loop Test may be performed in order to check output performance and accuracy and to trim other instruments in the loop. Your output will be a current value, in mA, or a voltage equal to the value you input. You can check the other current devices on the loop and calibrate them to this signal.
This feature is independent of the input. If you fi nd that the output requires adjustment you may perform the Output Trim function.
1. To use the Loop Test function select the Mode dropdown box in the Communications bar and select “Measurements Off”.
2. Next, in the “Output Value %” box, type the percentage of the output value you wish to test. You may also use your mouse, left click and adjust the scroll bar to adjust to your desired value. Hit “Enter”.
3. In the “Output Value” box enter the value, within your confi guration range, that you wish to signify as your output value. Hit “Enter”.
4. Perform your test and calibration.
5. When you are fi nished, return to Mode in the Communications bar and reset your status to “Measurements On”.
The Interface Solution Experts 15
CPA
PC-Programmable RTD, T/C, Ohms, mV and Potentiometer Limit Alarm Trips

Output Damping

Output Damping allows you to introduce a delay into the response of your unit in order to stop short-lived spikes from setting off alarms. Output Damping is activated when the value set in the “Output Step Threshold” fi eld is exceeded.
1. To enable output damping, select the “Enabled” button. If you do not wish to use the damping feature, then select “Disabled”.
2. Insert a value between 1 and 16mA in the “Output Step Threshold” fi eld. This is how much of an output step change is allowed in a specifi ed time frame before fl agging the software.
3. Insert a value between .5 and 120sec in the “Damping Sec” fi eld. This is the amount of time it will take for the output to reach 63% of the step output change once the input exceeds the value in the “Output Step Threshold” fi eld.
By checking the appropriate box in the Other Damping Options section, you may also choose to select Output Damping to occur upon power up or start up from a PC, upon broken wire failure detection or upon resolution of broken wire failure.
A possible source for this occurence is a rapid change on the input. Another possiblity would be an existing output level of 5.6mA upon Start Measurements from a PC.
Figure 11 gives another damping example where the output has been driven upscale to 23.6mA. After fi ve seconds the 63% output change is reached at
16.98mA.
Figure 11. Damping When Output Driven Upscale to 23.6mA
In this instance, detection of an open sensor or broken wire could be a cause. An instrument malfunction or Adc/EEPROM failure may also be suspect.
A typical damping situation would be described as a step change in output which causes the output to go from 5.6mA to 20mA. After fi ve seconds the output reaches 14.58mA which equals 63% of the output step change. This is graphed in Figure 10.
Figure 10. Typical Damping Scenario

Output if Measurement OFF

Choose “Zero Range” to read zero volts or mA at output if measurement was off.
Choose “Stay Last” to read the last value held before the measurement was off.
Note:
Once you have confi gured all parameters,
download to the unit by either selecting “Download
Confi guration” in the Confi guration dropdown menu
located in the Communications bar or by clicking the
button.
16 The Interface Solution Experts

Custom Table

Figure 12. PC Confi guration Software Custom Table Tab
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
The Custom Table feature allows you to setup your own custom curve table (Figure 12). This allows you to tell the CPA what it should output when it receives a certain input. This feature also allows you the ability to write a table in Microsoft format. The fi les are saved to/read to/read from the “Moore Industries\Custom Curves” folder. This makes it simple to save the custom table for downloading to multiple units or for backup purposes.
The linearization will be in the form of X, Y coordi­nates. You may choose up to 128 points.
To access this function click the Custom Table tab.
1. Select the number of points you are to set and insert this value into the “Number Of Points” line, hit “Enter”. This will highlight the number of points you have selected.
To clear the table and start over at any time, click
®
Excel and save it in a .csv
Note:
“Clear Table”.
2. Type your individual values in the X and Y columns. Source variables are inserted into the X Column while the corresponding data is inserted into the Y Column.
3. To save the displayed custom table to your hard drive click the “Save Table” button.
To open or use this saved table at a later time, click the “Open Table” button and select the folder in which it has been saved.
Use the “Table EGU” box to enter any alphanumeric engineering unit (up to 6 digits).
To use the Custom Table feature in your operation, check the “Custom Table ON” box.
Note:
Once you have confi gured all parameters,
download to the unit by either selecting “Download
Confi guration” in the Confi guration dropdown menu
located in the Communications bar or by clicking the
button.
The Interface Solution Experts 17
CPA
PC-Programmable RTD, T/C, Ohms, mV and Potentiometer Limit Alarm Trips

Installation

Installation consists of physically mounting the unit and completing the electrical connections.

Mounting the CPA

The CPA can be mounted on standard DIN mounting rails.

Making the Electrical Connections

Please refer to Figure 4 for electrical connections.

Recommended Ground Wiring Practices

Moore Industries recommends the following ground wiring practices:
• Any Moore Industries product in a metal case or housing should be grounded.
• The protective earth conductor must be connected to a system safety earth ground before making any other connections.
• All input signals to, and output signals from, Moore Industries’ products should be wired using a shielded, twisted pair technique. Shields are to be connected to an earth or safety ground at the unit itself.
• The maximum length of unshielded input and/or output signal wiring should be two inches.

Operation

Once programmed, calibrated, installed, and supplied with the correct power, the CPA alarm begins to operate immediately. Depending upon environmental conditions, it can be expected to operate unattended for extended periods of time.

Maintenance

Moore Industries suggests a quick check for terminal tightness and general unit condition every 6-8 months. Always adhere to any site requirements for programmed maintenance.

Customer Support

Moore Industries is recognized as the industry leader in delivering top quality to its customers in products and services. We perform a battery of stringent quality assurance checks on every unit we ship. If any Moore Industries product fails to perform up to rated specifi cations, call us for help. Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide timely, accurate, and practical answers to your process instrumentation questions.
Factory phone numbers are listed on the back cover of this manual.
If problems involve a particular CPA, there are several pieces of information that can be gathered before you call the factory that will help our staff get the answers you need in the shortest time possible. For fastest service, gather the complete model and serial number(s) of the problem unit(s) and the job number of the original sale.
CE Conformity
Installation of any Moore Industries’ products that carry the CE certifi cation must adhere to the guidelines above in order to meet the requirements set forth in the European EMC and Low Voltage Directives (EN 61326 and EN 61010). Consult the factory for the most current information on products that have been CE certifi ed.
18 The Interface Solution Experts
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair If you are unsure if your unit is still under warranty, we can use the unit’s serial number to verify the warranty status for you over the phone. Be sure to include the RMA number on all documentation.
Non-Warranty Repair If your unit is out of warranty, be prepared to give us a Purchase Order number when you call. In most cases, we will be able to quote you the repair costs at that time. The repair price you are quoted will be a “Not To Exceed” price, which means that the actual repair costs may be less than the quote. Be sure to include the RMA number on all documentation.
2. Provide us with the following documentation: a) A note listing the symptoms that indicate the unit needs repair b) Complete shipping information for return of the equipment after repair c) The name and phone number of the person to contact if questions arise at the factory
3. Use suffi cient packing material and carefully pack the equipment in a sturdy shipping con­tainer.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries rep­resentative will contact the person designated on your documentation if more information is needed. The repaired equipment, or its replacement, will be returned to you in accordance with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WAR­RANTIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SERVICES SOLD BY THE COMPANY. THE COMPANY DIS­CLAIMS ALL WARRANTIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWLEDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IMPLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANY WAY. ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REM­EDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CON­SEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RE­CEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WARRANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOV­ERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under normal conditions of use and service, Moore Industries (“The Company”) will at its option replace, repair or refund the purchase price for any of its manufactured products found, upon return to the Company (transportation charges prepaid and otherwise in accordance with the return procedures established by The Company), to be defective in material or workmanship. This policy extends to the original Buyer only and not to Buyer’s customers or the users of Buyer’s products, unless Buyer is an engineering contractor in which case the policy shall extend to Buyer’s immediate customer only. This policy shall not apply if the product has been subject to alteration, misuse, accident, neglect or improper application, installation, or operation. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Tel: (818) 894-7111 • FAX: (818) 891-2816
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
© 2004 Moore Industries-International, Inc.
United States • info@miinet.com
Australia • sales@mooreind.com.au
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
Specifi cations and Information subject to change without notice.
China • sales@mooreind.sh.cn
Tel: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
Loading...