This is the users’ manual for the Moore Industries
TMZ PC-Programmable MODBUS Temperature
Transmitter (TPRG: RTD, T/C, Ohms, mV and
Potentiometer inputs). It contains all of the
information needed to configure, install, operate and
maintain this instrument.
About this Manual
Wherever you see a “Note”, “Caution” or “WARNING ”
pay particular attention.
WARNING - Hazardous procedure or condition that
could injure the operator.
Caution - Hazardous procedure or condition that could
damage or destroy the unit.
Note - Information that is helpful for a procedure,
condition or operation of the unit.
Figure 1. The TMZ (TPRG)
The TMZ
The TMZ is a PC-Programmable, user-configurable,
signal converter. It has a digital output and retains the
high accuracy of an Analog to Digital converter without
the limitation of low resolution which is associated with
analog outputs. The multi-drop nature of the RS-485
port allows the connection of up to 32 units on a single
drop of cable that consists of two pairs of wires. The
TMZ has a READY LED to indicate the health of the
unit and an INPUT LED to indicate status.
Model and Serial Numbers
Moore Industries uses the model and serial numbers
of our instruments to track all information on each
unit that we sell and service. If a problem occurs
with your TMZ, check for a tag affixed to the unit
listing these numbers. Supply the Customer Support
representative with this information when calling.
Inputs
Refer to Table 4 for input ranges and accuracies of the
TMZ (TPRG).
Outputs
The TMZ has a standard RS-485 port that supports
the MODBUS RTU protocol.
4 The Interface Solution Experts
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Specifications
Performance
Specifications and information subject to change without notice.
Table 1. Long-Term Stability
Stability
(% of maximum
span)
RTD, Ohm & Pot Inputs
Table 2. Normal Mode Rejection Ratio
T/C: J, K, N, C, E
Pt RTD: 100, 200, 300ohms
Pt RTD: 400, 500, 1000ohms
Resistance
1-4kohms
0.25-1kohms
0.125-0.25kohms
Input Accuracy:
See Table 4
Overall Accuracy: The
overall accuracy of the
unit is the input accuracy.
It includes the combined
effects of linearity,
hysteresis, repeatability and
adjustment resolution. It
does not include ambient
temperature effect. For
T/C input, add the RJC
error.
UPDATE TIME: 128msec;
MODBUS POLLING TIME:
Dependent upon how fast
and how often a MODBUS
master requests data
Isolation: Standard unit,
1000Vrms between case,
input. 1500Vrms between
power and input; WITH
-RF OPTION, 500Vrms
between case, input and
power.
Power Consumption:
1W max.
Input Impedance:
T/C and mV inputs,
40Mohms, nominal
Input Over-Range
Input-to-Output (Years)
0.09
0.08
Sensor Type
T/C: T, R, S, B
Ni: 120ohms
Cu: 9.03ohms
mV
250-1000
62.5-250
31.25-62.5
1
3
0.16
0.14
Max. p-p Voltage Injection for
100dB at 50/60Hz
Performance
(continued)
Communications
Indicators
5
0.21
0.18T/C & mV Inputs
150mV
80mV
250mV
1V
500mV
100mV
1V
250mV
100mV
Protection: ±5Vdc
Excitation Current (RTD
and Ohm Inputs Only):
250µA, ±10%
Type: Standard
MODBUS RTU protocol
interface over RS-485
(parameters as specified
in U.S. Standard EIARS485)
Address Range:
Configurable from 1 to
247. Unit will assume a
MODBUS address of 01
by default.
Baud Rates: Interface
supports the following:
300, 600, 1200, 2400,
4800, 9600, 19.2k and
38.4k
Character Format: One
start bit, 8 data bits and
one stop bit
LED Type: INPUT LED:
Dual color LED indicates
input failure
READY LED: Green LED
indicates unit is operating
properly
Table 3.
Ambient Temperature Effect
Accuracy per 1°C (1.8°F) change in AmbientInput Type
*RTD
Millivolt
Ohm
Input Type
J
K
E
T
R, S
B
N
C
mV
*Accuracy of Ni672 is 0.002°C
Accuracy per 1°C (1.8°F) change in Ambient
Ambient
Conditions
Weight
0.5µV + 0.005% of reading
0.002ohms + 0.005% of reading
Thermocouples
0.00016°C + 0.005% of reading
0.0002°C + 0.005% of reading
0.00026°C + 0.005% of reading
0.0001°C + 0.005% of reading
0.00075°C + 0.005% of reading
0.0038°C + 0.005% of reading
0.0003°C + 0.005% of reading
0.00043°C + 0.005% of reading
0.5µV + 0.005% of reading
Operating & Storage
Range: -40°C to +85°C
(-40°F to +185°F)
Effect of Ambient
Temperature on Cold
Junction Compensation
(T/C Inputs Only):
±0.005°C per °C change
of ambient temperature
Relative Humidity:
0-95%, non-condensing
Ambient Temperature
Effect: See Table 3
RFI/EMI Immunity
(Standard Unit):
10V/m@20-1000MHz,
1kHz when tested
according to
IEC1000-4-3-1995
WITH -RF OPTION,
30V/m@20-1000MHz,
1kHz AM when tested
according to
IEC1000-4-3-1995
Noise Rejection:
Common mode,
100dB@50/60Hz; Normal
mode, Refer to Table 2
290 g (10.2 oz)
0.0035°C
The Interface Solution Experts 5
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Table 4. Accuracy with RTD, Thermocouple, Ohms, Potentiometer and Millivolt Inputs
Input Type α Ohms
RTD
(2-, 3-,
4-Wire)
Ohms
T/C
mV
Platinum
Nickel
Copper
Direct Resistance
Potentiometer
J
K
E
T
R
S
B
N
C
mV
0.003850
0.003902
0.003916
0.00672
0.00427
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
0-4000
4000 max.
100
200
300
400
500
1000
100
200
400
500
1000
100
120
9.035
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Conformance
Range
-200 to 850°C
(-328 to 1562°F)
-100 to 650°C
(-148 to 1202°F)
-200 to 510°C
(-328 to 950°F)
-80 to 320°C
(-112 to 608°F)
-50 to 250°C
(-58 to 482°F)
0-4000ohms
0-100%
-180 to 760°C
(-292 to 1400°F)
-150 to 1370°C
(-238 to 2498°F)
-170 to 1000°C
(-274 to 1832°F)
-170 to 400°C
(-274 to 752°F)
0 to 1760°C
(32 to 3200°F)
0 to 1760°C
(32 to 3200°F)
400 to 1820°C
(752 to 3308°F)
-130 to 1300°C
(-202 to 2372°F)
0 to 2300°C
(32 to 4172°F)
n/a
Accuracy/Repeatability
±0.1°C
(±0.18°F)
±0.85°C
(±1.53°F)
±0.4ohms
±0.25°C
(±0.45°F)
±0.30°C
(±0.54°F)
±0.20°C
(±0.36°F)
±0.25°C
(±0.45°F)
±0.55°C
(±0.99°F)
±0.55°C
(±0.99°F)
±0.75°C
(±1.35°F)
±0.40°C
(±0.72°F)
±0.80°C
(±1.44°F)
Input
±0.1%
±15µV
Maximum
Range
-240 to 960°C
(-400 to 1760°F)
-150 to 720°C
(-238 to 1328°F)
-240 to 580°C
(-400 to 1076°F)
-100 to 360°C
(-148 to 680°F)
-65 to 280°C
(-85 to 536°F)
0-4095ohms
0-100%
-210 to 770°C
(-346 to 1418°F)
-270 to 1390°C
(-454 to 2534°F)
-270 to 1013°C
(-454 to 1855.4°F)
(-454 to 2400.8°F)
-270 to 407°C
(-454 to 764.6°F)
-50 to 1786°C
(-58 to 3246.8°F)
-50 to 1786°C
(-58 to 3246.8°F)
200 to 1836°C
(392 to 3336.8°F)
-270 to 1316°C
0 to 2338°C
(32 to 4240.4°F)
-50 to 1000mV
6 The Interface Solution Experts
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Figure 2. TMZ (TPRG) Dimensions
100mm
(3.94 in)
52mm
(2.05 in)
48mm
(1.89 in)
C
L
WHEN INSTALLED
WHEN INSTALLED
12
34
COM
TMZ
PROGAMMABLE
MODBUS
TRANSMITTER
READY
INPUT
25mm
(1.00 in)
138mm
(5.43 in)
133mm
(5.24 in)
(4.97 in)
126mm
Table 5. Terminal Designations
INPUT
1234
A
B
S
Figure 3. Temperature Sensor Hook-Up Guide
MODBUS
NOT
USED
NOT
USED
+
Thermocouple
and Millivolt
Input
-
See Figure 3 for Input options
Top ViewBottom View
2-Wire RTD
or Decade
Resistance Box
INPUT
3-Wire RTD
or Decade
Resistance Box
MODBUS
4-Wire RTD
or Decade
Resistance Box
Potentiometer
Input
+
143
2
–
143 2 143 2 143 2
The Interface Solution Experts 7
143 2
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Figure 4. Hooking-Up the TMZ (TPRG)
1 2
34
COM
TMZ
PROGAMMABLE
MODBUS
TRANSMITTER
READY
INPUT
MILLIVOLT
SOURCE
OR T/C
SIMULATOR
_
+
OHMS OR
2-WIRE
RTD
SIMULATOR
24Vdc
POWER
SUPPLY
–
+
A
B
S
MODBUS OUTPUT
TO SERIAL
(COM) PORT
OF PC
MODBUS Host
RS-485/RS-232
Converter
3-Wire RTD or
Decade Resistance Input
4-Wire RTD or
Decade Resistance Input
Potentiometer Input
INPUT HOOKUP CONNECTIONS
OHMS
OR RTD
SIMULATOR
OHMS
OR RTD
SIMULATOR
PC
TO SERIAL
(COM) PORT
OF PC
OR
To USB
(COM)
Port of PC
Configuring the TMZ
One of the benefits of the TMZ is that there are no
internal or external controls to adjust or settings to
change. All operating parameters are set using a
PC and Moore Industries’ Intelligent PC Configuration
Software.
8 The Interface Solution Experts
The software settings are downloaded to the
transmitter in the form of a Configuration File and
stored in the instrument’s memory. You can save a
backup copy of the file on your PC hard drive or disk.
The transmitter communicates with the PC through an
RS-232 connection to the PC’s serial port or through
the MODBUS output with a fixed baud rate at 19.2k.
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Installing the Configuration
Software
Refer to Table 6 for the equipment needed.
1. Insert the Moore Industries Interface Solution PC Configuration Software CD into the CD
drive of the PC. Access the CD and open the
“TMZ PC Configuration Software” folder.
2. Double-click the installation program located
in the folder. Follow the prompts to correctly
install the program.
Once the Configuration Program is installed on the
PC, the TMZ can be connected to equipment to
simulate input and monitor output. You can then
change the transmitter’s operating parameters.
No Transmitter Needed
It is not necessary to connect the transmitter to a PC
to create configuration files using the software. The
Configuration Program can be run without connecting
a transmitter, and most parameters can be set
without the benefit of input from a sensor or TMZ.
This makes it easy to create a set of operating
parameters, save them to disk, and download them to
one or more transmitters at a later time.
The TMZ must be connected to the PC in order to:
perform sensor trimming; assign a tag, descriptor or
message; receive (via download) a configuration file;
and save the configuration file from the transmitter’s
memory.
The latest version of our Configuration Software for
your TMZ unit is also available for download on our
website www.miinet.com.
Table 6. Assembling the equipment needed to configure the TMZ (TPRG)
Device Specifications
Variable Input Simulator for Thermocouple,
RTD, Millivolt, Potentiometer, or Decade Re-
sistance Box
Power Supply
Personal Computer
Moore Industries PC
Configuration Software
Variable; Accurate to ±0.05% of unit span
24Vdc, ±10%
Microsoft Windows based PC;
16Mb free RAM; 20MB free disk space on hard drive
Microsoft Windows XP, Vista or 7
1 (one) serial port or one available USB port (with optional USB cable)
Version 1.0 or greater, successfully installed to the hard drive
Connecting the TMZ to the PC
Connect the RS-232 end of the cable to the PC’s COM
port.
See Table 6 for information on the necessary
equipment.
Communication Cable
Part# 803-053-26, or optional USB cable 208-236-00
The Interface Solution Experts 9
TMZ
PC-Programmable MODBUS
Temperature Transmitter
PC Configuration Software Summary
1
2
3
4
5
6
7
8
9
10
11
12
13
Figure 5. TMZ (TPRG) PC Configuration Software Screen
Once the default configuration has been saved to disk,
it is safe to program other parameters. The PC
Software is made up of these sections:
1. Tool Bar/Status Bar– Dropdown menus and
corresponding icons allow you to perform various
functions throughout the PC Configuration Program.
Refer to the Status and Tool Bar Legend section for a
complete description.
2. Program Status– This portion of the program
displays the activity (idle, monitoring, downloading,
uploading) of the connected unit.
3. Device ID– Displays your unit configuration
(HLPRG/TPRG), ID, Hardware revision and Software
revision.
10 The Interface Solution Experts
4. Identification Parameters– Use this parameter to
place an identifying “Tag” (8 alphanumeric characters
max.), “Descriptor” (16 alphanumeric characters max.)
or “Message” (32 alphanumeric characters max.). You
may also use the Quick Set feature to set your Ta g
and download it.
5. Device Configuration– Displays the Input and
MODBUS parameters you have chosen as settings for
your TMZ.
6. Input Type– Select your input type (RTD, T/C,
Ohms, mV and Potentiometer) and characteristics.
7.Variables– Displays the value of the Process
Variable that is being monitored, the Reference
Junction temperature, the scaled output and the
Custom Curve output.
8. Device Status– Notifies of any errors or conditions
which are outside of tolerance range.
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Allows such functions as New,
Open, Save and Print
Allows you to Upload and
Download configurations
Select the PC Port
(Comm Port) that you will use
Allows you to Monitor and
Stop monitoring processes
Provides functions specific to
your Custom Curve table
Controls whether Tool and Status
Bars are viewed on the screen
Displays the version of the TMZ
Configuration Program
9. Communications– Indicates current PC
connection/communications status.
10. Input– Use this tab to set your input parameters.
Refer to the Input section for a complete description.
11. Trimming– This parameter allows you to
configure and perform sensor trimming. Refer to the
Trimming section for a complete description.
12.Scaling & Custom Curve– Use this portion of
the screen to set up your custom curve table. Refer to
the Scaling & Custom Curve section for a complete
description.
13. MODBUS– Allows you to configure your
MODBUS parameters. Refer to the MODBUS section
for a complete description.
Status and Tool Bar Legend
Default/Factory Configurations
The following are the default factory settings for your
unit.
Input:
RTD 4W Pt3850 100Ohms
-240 to 960°C
Filter: 60Hz
Broken Wire: ON
Running Average Filter: ENABLED, 4
MODBUS:
Address: 1
Baud Rate: 9600
Parity: None LSW
No. of DP’s in integer: 0
The Interface Solution Experts 11
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Configuration Screens
Input
Figure 6. Input Tab
Running Average Filter– This function is for
filtering the input signal. The TMZ provides this filter
with a user-selected range between 1 and 16. Factory
default is 4.
Note:
A higher Running Average Filter setting provides
smoother output transitions however, reduces
response time. Conversely, a lower setting provides
a faster response time, but may seem more
unstable.
Input Filter– This setting is used to configure the
input filter. This filter is designed to reduce the effects
of mains-induced noise. The input filter frequency
value should be set to the frequency of the local AC
supply-either 50Hz or 60Hz.
Note:
Once you have configured all parameters, download
to the unit by selecting “Download” in the Transfer
dropdown menu located in the Status Bar. You may
also download by clicking the button in the
Tool Bar.
Input Range– Allows you to set your “Upper
Range Value” (URV) and “Lower Range Value” (LRV)
depending upon the input configuration and range
chosen in the Input Type section.
Note:
The upper and lower range values will, by default, be
set to the maximum range determined by input type
with the exception of thermocouple and RTD inputs,
which have fixed range values user cannot change.
Temperature Measurements– Select the unit in
which you wish your Input Range displayed. Choose
from Deg C, Deg F, Kelvin or Deg R.
Broken Wire– Allows the TMZ to continuously
test the integrity of your sensor wiring by sending
out random microamp pulses during operation. If a
problem is detected, a message is displayed in the
Device Status box.
You may also use the Quick Set feature to configure
your Input parameters and download the settings.
12 The Interface Solution Experts
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Trimming
Figure 7. Trimming Tab
Sensor Trimming– Sensor Trimming increases
the measurement accuracy of your instrument by
matching the reading of its actual input to either
a calibrated source or the device to which it is
connected. This verifies that the input from the sensor
to the transmitter is being interpreted correctly.
You may trim any point between 0% and 100% along
the scale. Note that one-point trimming applies an
offset to the sensor reading, while two-point trimming
applies both an offset and a gain.
Follow the steps below in order to perform sensor
trimming.
1. Select either “1 Point” (one-point trimming) or “2
Points” (two-point trimming) by clicking the appropriate
button. Each pair consists of “Set” and “Trim” values.
2. Enter the values that need to be trimmed into the
“Set Value” field and click “Set”.
3. Apply the targeted signal to the input, wait until it
settles and click “Trim” to capture the measured value.
If you chose “2 Points”, repeat the step above for the
second point.
Note:
Once you have configured all parameters, download
to the unit by selecting “Download” in the Transfer
dropdown menu located in the Status Bar. You may
also download by clicking the button in the
Tool Bar.
Scaling & Custom Curve
Figure 8. Scaling & Custom Curve Tab
Scaling– Scaling allows you to take your PV
(Process Variable) reading and manipulate it to a more
customized display range (Scaled PV). PV is the unit
read after selecting your input type. For example,
choosing a mV input would then produce a PV
displayed in mV.
Should you require a Scaled PV, follow the instructions
below.
1. In the “PV” parameter, enter the actual range of
your input type. Place the minimum value in the “LRV”
text box and the maximum value in the “URV” box.
2. In the “Scaled PV” parameter, enter the scale, or
range you require. In the “LRV” text box, enter the
value that you wish displayed when your reading is at
its minimum. In the “URV” text box, place the value to
be displayed when the process variable has reached
maximum.
The Interface Solution Experts 13
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Custom Curve– The Custom Curve feature
allows you to setup your own custom curve table.
This allows you to tell the transmitter what it should
output when it receives a certain input. This feature
also allows you the ability to write a table in Microsoft®
Excel, save it in a .csv format, and import it into the
Configuration Software. This makes it simple to save
the custom table for downloading to multiple units or
for backup purposes.
To create a custom curve:
1. Click the “Enabled” box .
2. Select the number of points for your curve (32
points maximum).
3. Type your individual values in the X and Y columns.
Source variables are inserted into the X column while
the corresponding data is inserted into the Y column.
4. After all of your data has been entered, you must
use the Custom Curve dropdown menu to save your
newly created custom (“Save Custom Curve”) and to
download it to your TMZ (“Download Custom Curve”).
Note:
Once you have configured all parameters, download
to the unit by selecting “Download” in the Transfer
dropdown menu located in the Status Bar. You may
also download by clicking the button in the Tool
Bar. However, this does not download your custom
table. To do so, you must use the Custom Curve
dropdown menu.
14 The Interface Solution Experts
TMZ
PC-Programmable MODBUS
Temperature Transmitter
MODBUS
PV = 123.456789
"No of DPs in integer" Value Displayed Integer
1
2
3
1234
12345
123456
Figure 9. MODBUS Tab
Communications– Used to set MODBUS
Address, Baud Rate and Parity parameters.
No of DPs in integer- This is a calculation that stores
a more accurate value in the MODBUS register and
offers better resolution. Select your value using the
up and down arrows to the right of the display. See
below for an example of this process.
Note:
Once you have configured all parameters, download
to the unit by selecting “Download” in the Transfer
dropdown menu located in the Status Bar. You may
also download by clicking the button in the
Tool Bar.
Address- The number that the TMZ uses to identify
itself on the MODBUS network. It is configurable from
1 to 247. By default, the assigned MODBUS address
is 01.
Baud Rate- The speed of data transmission. It
should be set to match the baud rate of the attached
controller. Supported Baud Rates include: 300, 600,
1200, 2400, 4800, 9600, 19.2k and 38.4k. Factory
default is 9600.
Parity- A method in serial asynchronous
communications of “checking” that characters have
been sent correctly. Even, Odd and no Parity (None)
are supported. Factory default is None.
Data Format– Allows you to select the word order
and number of decimal places you choose.
Selecting LSW (Normal), Least Significant Word,
stores the most signifcant bits in the second register
and the least significant bits in the first register (factory
default).
MSW (Reversed), Most Significant Word, reverses the
above order. The most significant bits will be stored in
the first register with the least significant bits stored in
the second register.
The Interface Solution Experts 15
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Installation
Installation consists of physically mounting the unit
and completing the electrical connections.
Mounting the TMZ
The TMZ can be mounted on standard DIN mounting
rails.
Making the Electrical
Connections
Please refer to Figure 4 for electrical connections.
CE Conformity
Installation of any Moore Industries’ products that
carry the CE marking must adhere to the guidelines in
the Recommended Ground Wiring Practices section in
order to meet the EN 61326 requirements set forth in
the applicable EMC directive.
Operation
Once programmed, calibrated, installed, and supplied
with the correct power, the TMZ transmitter begins to
operate immediately. Depending upon environmental
conditions, it can be expected to operate unattended
for extended periods of time.
Recommended Ground Wiring
Practices
Moore Industries recommends the following ground
wiring practices:
all the way from the signal source to the receiving
device. (see Note below)
• Themaximumlengthofunshieldedinputand
output signal wiring should be 2 inches.
Note:
Some of Moore Industries’ instruments can be
classified as receivers (IPT 2, IPX 2, etc.) and some
can be classified as transmitters (TRX, TRY, etc.)
while some are both a receiver and a transmitter
(SPA 2, HIM, etc). Hence, your shield ground
connections should be appropriate for the type
of signal line being shielded. The shield should
be grounded at the receiver and not at the signal
source.
Maintenance
Moore Industries suggests a check for terminal tightness and general unit condition every 6-8 months.
Always adhere to any site requirements for programmed maintenance.
Customer Support
Moore Industries is recognized as the industry leader
in delivering top quality to its customers in products
and services. We perform a battery of stringent quality assurance checks on every unit we ship. If any
Moore Industries product fails to perform up to rated
specifications, call us for help. Our highly skilled staff
of trained technicians and engineers pride themselves
on their ability to provide timely, accurate and practical
answers to your process instrumentation questions.
Factory phone numbers are listed on the back cover of
this manual.
If problems involve a particular TMZ (TPRG), there
are several pieces of information that can be gathered
before you call the factory that will help our staff get
the answers you need in the shortest time possible.
For the fastest service, gather the complete model
and serial number(s) of the problem unit(s) and the job
number of the original sale.
16 The Interface Solution Experts
TMZ
PC-Programmable MODBUS
Temperature Transmitter
Appendix A: TMZ MODBUS
)
Register Set
Table A-1 contains all of the MODBUS integer
registers supported by the TMZ. These registers
constitute both the 30000 and 40000 register set.
Table A-1. MODBUS Register Table
Register Variable Read Description
0 PV R PV (integer
1
2 PercentOfRange R
3 ScaledPV R Scaled PV (integer)
4
5
256-257 PV R PV (floating point)
258-259 SV R
260-261 PercentOfRange R Percent of Range (floating point)
262-263
264-265
266 ErrorStatus R
Table A-2. Status Word Table
SV
LinearedPV
ErrorStatus
ScaledPV
LinearedPV
R
R
R
R
R
SV (integer)
Percent of range (integer)
Linearised PV (integer)
TMZ Error / Status Word
SV (floating point)
Scaled PV (floatpoint)
Linearised PV (floating point)
TMZ Error / Status Word
Status Bit Description
0 Configuration data checksum bad
1 Calibration data checksum bad
2 The configuration data is bad / illegal
3 The calibration data is bad
4 A division by zero error condition
5 RJC is broken
6 Microcontroller watchdog reset has occurred
7 A software watchdog error has occurred
8 Sensor wire 1 is broken (If broken wire is enabled)
9 Sensor wire 2 is broken (If broken wire is enabled)
10 Sensor wire 3 is broken (If broken wire is enabled)
11 Sensor wire 4 is broken (If broken wire is enabled)
12 Input is saturated
13 Hardware error has occurred (one of the ADCs is not working)
14 The calibration process is active
15 TMZ is off line
The Interface Solution Experts 17
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair –
If you are unsure if your unit is still under warranty, we can use the unit’s serial number
to verify the warranty status for you over the phone. Be sure to include the RMA
number on all documentation.
Non-Warranty Repair –
If your unit is out of warranty, be prepared to give us a Purchase Order number when
you call. In most cases, we will be able to quote you the repair costs at that time.
The repair price you are quoted will be a “Not To Exceed” price, which means that the
actual repair costs may be less than the quote. Be sure to include the RMA number on
all documentation.
2. Provide us with the following documentation:
a) A note listing the symptoms that indicate the unit needs repair
b) Complete shipping information for return of the equipment after repair
c) The name and phone number of the person to contact if questions arise at the factory
3. Use sufficient packing material and carefully pack the equipment in a sturdy shipping container.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries representative will contact the person designated on your documentation if more information is
needed. The repaired equipment, or its replacement, will be returned to you in accordance
with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WARRANTIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR
OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY
GOODS OR SERVICES SOLD BY THE COMPANY. THE COMPANY DISCLAIMS ALL WARRANTIES ARISING FROM ANY COURSE OF DEALING
OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM
THE COMPANY ACKNOWLEDGES THAT THERE ARE NO WARRANTIES
IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND
OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER
WITH THE COMPANY DO NOT IMPLY THAT THE COMPANY WARRANTS
THE GOODS OR SERVICES IN ANY WAY.
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY
AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REMEDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR
SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR
OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE
PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS
IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES
, BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE
THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER
FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY
THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RECEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED
DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE
ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED
THE ALLEGED DEFECT OR BREACH, AND NO ACTION FOR THE
BREACH OF ANY WARRANTY SHALL BE COMMENCED BY THE
BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST
DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under
normal conditions of use and service, Moore Industries (“The Company”)
will at its option replace, repair or refund the purchase price for any of its
manufactured products found, upon return to the Company (transportation
charges prepaid and otherwise in accordance with the return procedures
established by The Company), to be defective in material or workmanship.
This policy extends to the original Buyer only and not to Buyer’s customers
or the users of Buyer’s products, unless Buyer is an engineering contractor
in which case the policy shall extend to Buyer’s immediate customer only.
This policy shall not apply if the product has been subject to alteration,
misuse, accident, neglect or improper application, installation, or operation.
THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL
OR CONSEQUENTIAL DAMAGES.
Information contained within this supplement accompanies data in the TMZ (TPRG) User’s Manual, 225720-02. This document addresses the TMZ (2TPRG)
dual input model of the TMZ. The TMZ (2TPRG) has
two individually configurable sensor inputs and a
single isolated MODBUS output. The inputs are not
isolated from each other.
Specifications and information subject to change without notice.*For detailed sensor accuracy specifications, please refer to Tables 1-4 in the TMZ TPRG User Manual.
Input Accuracy:See Table 4*
Overall Accuracy: The
overall accuracy of the
unit is the input accuracy.
It includes the combined
effects of linearity,
hysteresis, repeatability and
adjustment resolution. It
does not include ambient
temperature effect. For
T/C input, add the RJC
error.
UPDATE TIME: 128msec;
MODBUS POLLING TIME:
Dependent upon how fast
and how often a MODBUS
master requests data
Isolation: Standard unit,
1000Vrms between case,
input. 1500Vrms between
power and input; WITH
-RF OPTION, 500Vrms
between case, input and
power.
Power Supply: 9-30Vdc
Power Consumption:
1W max.
Input Impedance:
T/C and mV inputs,
40Mohms, nominal
Performance
(continued)
Communications
Indicators
Input Over-Range
Protection: ±5Vdc
Excitation Current (RTD
and Ohm Inputs Only):
250µA, ±10%
Type: Standard
MODBUS RTU protocol
interface over RS-485
(parameters as specified
in U.S. Standard EIARS485)
Address Range:
Configurable from 1 to
247. Unit will assume a
MODBUS address of 01
by default.
Baud Rates: Interface
supports the following:
300, 600, 1200, 2400,
4800, 9600, 19.2k and
38.4k
Character Format: One
start bit, 8 data bits and
one stop bit
LED Type: INPUT LED:
Dual color LED indicates
input failure
READY LED: Green LED
indicates unit is operating
properly
Ambient
Conditions
Weight
Operating & Storage
Range: -40°C to +85°C
(-40°F to +185°F)
Effect of Ambient
Temperature on Cold
Junction Compensation
(T/C Inputs Only):
±0.005°C per °C change
of ambient temperature
Relative Humidity:
0-95%, non-condensing
Ambient Temperature
Effect: See Table 3*
RFI/EMI Immunity
(Standard Unit):
10V/m @ 80-1000MHz,
1 K AM, when tested
according to IEC610004-3
WITH -RF OPTION,
20V/M @ 80-1000MHZ,
1 K AM, WHEN TESTED
ACCORDING TO
IEC61000-4-3
Noise Rejection:
Common mode,
100dB@50/60Hz; Normal
mode, Refer to Table 2*
440 g (15.6 oz)
2 Demand Moore Reliability
Figure S-2. Dimensions of the TMZ (2TPRG)
See Figure 3A for Input Options
45mm
(1.77 in)
PROGAMMABLE
MODBUS
TMZ
TRANSMITTER
DUAL INPUT
READY
INPUT 1
INPUT 2
TAG
100mm
(3.94 in)
-2528A-LB2
User’s Manual Supplement
TMZ (2TPRG) Dual Input Model
133mm
(5.25 in)
102mm
(4.03 in)
Table S1. Terminal Designations
INPUT 1
1234
A
B
S
MODBUS
INPUT 2
1234
NOT
USED
NOT
USED
NOT
USED
-
+
Top View
INPUT 1INPUT 2
Figure S-3A. Temperature Sensor Hook-Up Guide (Sensor 1 & 2)
Thermocouple
and Millivolt
Input
2-Wire RTD
or Decade
Resistance Box
Resistance Box
3-Wire RTD
or Decade
4-Wire RTD
or Decade
Resistance Box
Bottom View
B
A
MODBUS
Potentiometer
S
Input
DC(+)
Power
9-30Vdc
DCC(-)
+
143
2
–
143 2 143 2 143 2
143 2
Demand Moore Reliability
3
Figure S-3. Hooking-Up the TMZ (2TPRG)
User’s Manual Supplement
TMZ (2TPRG) Dual Input Model
MODBUS Host
MILLIVOLT
SOURCE
OR T/C
SIMULATOR
TO SERIAL
(COM)
PORT
OF PC
OHMS OR
2-WIRE
RTD
SIMULATOR
RS-485/RS-232
Converter
MODBUS OUTPUT
_
_
MILLIVOLT
SOURCE
+
OR T/C
+
SIMULATOR
OHMS OR
PC
TO SERIAL
(COM)
PORT
OF PC
2-WIRE
12341234
PROGAMMABLE
MODBUS
TMZ
TRANSMITTER
DUAL INPUT
READY
INPUT 1
INPUT 2
RTD
SIMULATOR
OR
To USB
(COM)
Port of PC
-2528A-LB2
A
B
S
–
+
24Vdc
POWER
SUPPLY
INPUT HOOKUP CONNECTIONS
3-Wire RTD or
Decade Resistance Input
OHMS
OR RTD
SIMULATOR
SENSOR 1 or SENSOR 2
4 Demand Moore Reliability
4-Wire RTD or
Decade Resistance Input
Potentiometer Input
OHMS
OR RTD
SIMULATOR
SENSOR 1 or SENSOR 2 SENSOR 1 or SENSOR 2
User’s Manual Supplement
1
2
3
5
6
7
8
9
10
4
TMZ (2TPRG) Dual Input Model
PC Configuration Software Summary of TMZ (2TPRG) Dual Input
Figure S-4. Main Screen of the TMZ (2TPRG) PC Configuration Software Program for Dual Input Units
Once the default configuration has been saved to disk,
it is safe to program other parameters. The PC
Software is made up of these sections:
1. Tool Bar/Status Bar– Dropdown menus and corre-
6. TMZ Device Info– Displays your unit configuration,
ID, Hardware revision and Software revision.
7. Communications– Indicates current PC connec-
tion/communications status.
sponding icons allow you to perform various functions
throughout the PC Configuration Program. Refer to the Status and Tool Bar Legend section of this document for a complete description.
2. Program Status– This portion of the program displays the activity (idle, monitoring, downloading, uploading) of the connected unit.
3. TMZ Status– Notifies of any errors or conditions
which are outside of tolerance range.
4. Process Variable (PV)– Displays the values of the
8. Input 1 / Input 2 Tabs– Use these tabs to set your
input parameters. Refer to the Input 1 / Input 2 section
for a complete description.
9. Scaling Tab– Use this portion of the screen to
scale your instrument. Refer to the Scaling section for
a complete description.
10. MODBUS– Allows you to configure your MODBUS
parameters. Refer to the MODBUS section of TMZ
(TPRG) User’s Manual (Page 15) for a complete de-
scription.
process variables that are being monitored.
5. Identification Parameters– Use this parameter to
place an identifying TAG (8 alphanumeric characters
max.), DESCRIPTOR (16 alphanumeric characters
max.) or MESSAGE (32 alphanumeric characters
max).
Demand Moore Reliability
5
User’s Manual Supplement
Allows such functions as New,
Open, Save and Print
Allows you to Upload and
Download configurations
Select the PC Port
(Comm Port) that you will use
Allows you to Monitor and
Stop monitoring processes
Controls whether Tool and Status
Bars are viewed on the screen
Displays the version of the TMZ
Confi
g
uration Program
TMZ (2TPRG) Dual Input Model
Status and Tool Bar Legend
Default/Factory Configurations
The following are the default factory settings
for your unit.
Inputs 1 & 2:
RTD 4W Pt3850 100Ohms
-240 to 960°C
Filter: 60Hz
Broken Wire: ON
Running Average Filter: ENABLED, 4
MODBUS:
Address: 1
Baud Rate: 9600
Parity: None LSW
Configuration Screens
Input 1 / Input 2
Figure S-5. Input 1 / Input 2 Tab
Note:
Sensor Trimming for each input to be trimmed is now
performed at the respective Input tab (Input 1 or
Input 2). Configuration remains as described in the
TMZ (TPRG) User’s Manual (Page 13).
In appearance, windows for both Input 1 and Input 2 are
the same. They are configured similarly for the specific
input chosen. Configuration of the Input windows follows
the general parameters, with slight variation, as
described in the TMZ (TPRG) User’s Manual (Page 12).
Input Type– Select your input type (RTD 2-Wire,
RTD 3-Wire or RTD 4-Wire).
6 Demand Moore Reliability
The Sensor Range section will adjust according to the
parameters that have been set.
Temperature, Filter, Broken Wire Detection and Running
Average Filter Settings configuration remains as
described in the TMZ (TPRG) User’s Manual (Page 12).
User’s Manual Supplement
TMZ (2TPRG) Dual Input Model
Scaling
Note:
The Custom Curve feature is not available with the
TMZ (2TPRG).
Figure S-6. Scaling Tab
The following instructions apply to Channel 1 and
Channel 2 Scaling configuration.
1. Select the ENABLED checkbox of the channel you
are configuring.
MODBUS
MODBUS configuration remains unchanged as
described in the TMZ (TPRG) User’s Manual (Page15).
To scale the zero and full range span of your sensor,
perform the following steps in the SENSOR RANGE
parameter.
2. Place the value you want displayed as the low, or zero
end of your range in the ZERO textbox.
3. Place the upper, or full range value in the FULL textbox.
To scale the zero and full range span of your process
variable reading, perform the following steps in the
PROCESS VARIABLE parameter.
4. Place the value you want displayed as the low, or zero
end of your range in the ZERO textbox.
5. Place the upper, or full range value in the FULL textbox.
Demand Moore Reliability
7
TMZ MODBUS Register Set
Table S-2 contains all of the MODBUS integer registers
supported by the TMZ (2TPRG) dual input model. These
registers constitute both the 30000 and 40000 register set.
SV2 (integer)
Percent of range channel 1 (integer)
Percent of range channel 2 (integer)
TMZ dual input status information
Raw measurement from front-end channel 1
Raw measurement from front-end channel 2
PV1
PV2
SV1
SV2
PercentOfRange1
PercentOfRange2
ErrorStatus
ErrorStatus2
TMZ_OffLine
Model Type
Reserved
R
R
R
R
R
R
R
R
R
R
W
PV1 (float)
PV2 (float)
SV1 (float)
SV2 (float)
Percent of range channel 1 (float)
Percent of range channel 2 (float)
TMZ dual input status information
TMZ dual input additional status information
TMZ on line (0) off line (1) mode
Model Type
0 = low level (single input)
1 = high level (single input)
2 = special RTD (single input)
19 = low level dual input
20 = high level dual input
Do not use
United States • info@miinet.com
Tel: (818) 894-7111 • FAX: (818) 891-2816
Australia • sales@mooreind.com.au
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
Specifications and information subject to change without notice.
China • sales@mooreind.sh.cn
Tel: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.