Moore industries TDZ3, STZ User Manual

TDZ3 / STZ [HP]
Thermocouple Code Wire Color
ANSI
IEC
Code
Kit P/N
+-+
-
J
209-845J-00A
White
(Fe)
Red
(Cu-Ni)
Black
(Fe)
White
(Cu-Ni)
K
209-845K-00A
Yellow
(Ni-Cr)
Red
(Ni-Al)
Green
(Ni-Cr)
White
(Ni-Al)
T
209-845T-00A
Blue
(Cu)
Red
(Cu-Ni)
Brown
(Cu)
White
(Cu-Ni)
E
209-845E-00A
Purple
(Ni-Cr)
Red
(Cu-Ni)
Purple
(Ni-Cr)
White
(Cu-Ni)
N
209-845N-00A
Orange
(Ni-Cr-Si)
Red
(Ni-Si-Mg)
Pink
(Ni-Cr-Si)
White
(Ni-Si-Mg)
Thermocouple Rear Terminal Kit
CAUTION: Each kit is made for a specific thermocouple type (J,K, etc.) since the terminals and lugs are made from the same thermocouple metal. Using an unmatched kit could result in large measurement errors.
STEP 1
STEP 2
STEP 5
+3-4+1-
4
STEP 6
Attach thermocouple wires directly or using spade lugs provided. Please note that the spade lugs are made from the same material as the thermocouple wire and must be matched with the terminal (+ or -). Refer to table below for wire color and polarity.
Crimp wire to lug
STEP 3
STEP 4
Tighten
4 screws
Loosen 4 screws. Do not remove.
Slide on
STEP 7
Replace HP unit into enclosure
209-245-01A