Moore Industries THZ2, TDZ2 User Manual

THZ
2
& TDZ
2
THZ
2
& TDZ
2
Temperature Transmitter and Display
-ay 201 235-797-01'
TPRG
Programmable Smart HART
Temperature Transmitter and Display
Table of Contents
Introduction ............................................................................................................................................. 4
About this Manual .......................................................................................................... 4
The THZ2 and TDZ2 .......................................................................................... 4
Model and Serial Numbers ............................................................................................ 4
Specifications ................................................................................................. 5
Input Type and Accuracy Table .....................................................................................6
Stability, Ambient Temperature Effects and
Normal Mode Rejection Ratio Tables ..........................................................................7
Dimensions ..................................................................................................................... 7
Configuring the THZ2 and TDZ2 ................................................................... 11
Installing the Configuration Software ........................................................................ 11
Connecting the THZ2 or TDZ2 to the PC ...................................................................... 12
Necessary Equipment Table ........................................................................................ 12
PC Configuration Software Summary ........................................................ 15
Menu and Tool Bar Legend ..........................................................................................16
Configuration Screens ................................................................................................. 16
Searching for a Connected Unit ..................................................................................21
Using the HART Communicator .................................................................. 21
Programming when a Device Description is Available ............................................. 21
The HART Communicator Menu With a Device Description .................................... 23
The HART Communicator Menu Without a Device Description ............................... 28
HART Status Information ............................................................................. 29
Installation ..................................................................................................... 32
Mounting the THZ2 and TDZ
Making the Electrical Connections ................................................................................. 32
Recommended Ground Wiring Practices ....................................................................... 32
CE Conformity ................................................................................................................ 33
2 ......................................................................................................................................
32
Installation in Hazardous Locations ........................................................... 34
Operation ....................................................................................................... 35
HART Protocol .....................................................................................................................35
Maintenance ................................................................................................................... 35
Customer Support ........................................................................................ 35
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Introduction
This is the user’s manual for Moore Industries’ THZ2 and TDZ2 (TPRG: RTD, T/C, Ohms, mV and Potentiometer inputs) Programmable Smart HART Temperature Transmitter and Display. It contains all of the information needed to configure, install, operate and maintain the instruments.
About this Manual
Pay particular attention wherever you see a “Note”, Caution” or “WARNING ”.
Note– Information that is helpful for a procedure, condition or operation of the unit.
Caution– Hazardous procedure or condition that could damage or destroy the unit.
WARNING– Hazardous procedure or condition that could injure the operator.
The THZ2 and TDZ
The THZ2 and TDZ2 are 2-wire (loop-powered), user­configurable, HART®-based temperature transmitters. Their size, accuracy and compatibility make them the ideal solution when measurements must be made in remote or otherwise difficult-to-access locations.
The THZ2 and TDZ2 allow for configuration through two methods. You may use your PC’s RS-232 serial port or USB port and Moore Industries’ PC Configuration Software (once installed onto your PC). All configuration parameters are available through the PC Configuration Software.
The second method is to connect a HART Communicator and HART modem into your process loop. You must ensure that your communicator is configured with the THZ2 and TDZ2 Device Description (DD). You may then configure most parameters through the Communicator. Custom Curve variables cannot be entered using the Communicator. They must be configured using the PC Configuration Software.
2
Default/Factory Configurations
The following are the default factory settings for your unit.
2
THZ
Input: 4W RTD Pt3850-100Ohms, 0-100degC Broken Wire: Enabled Filter: 60Hz Running Average: Disabled PV Damping: Disabled AO: 4-20mA Under Range Minimum Value: 3.8 Over Range Maximum Value: 21.6 Fail Mode: Low, 3.6mA
2
TDZ
Input: 4Wire RTD Pt3850-100Ohms, 0-100deg C Broken Wire: Enabled Filter: 60Hz Running Average Filter: DISABLED, 1 PV Damping: DISABLED, 0s Display Source: PV Decimal Places: 3 Output: 4-20mA Under Range Min Value: 3.8 Over Range Max Value: 21.6 Sensor Fail Mode: Low, 3.6mA
Model and Serial Numbers
Moore Industries uses the model and serial numbers of our instruments to track information regarding each unit that we sell and service. If a problem occurs with your instrument, check for a tag affixed to the unit listing these numbers. Supply the Customer Support representative with this information when calling.
4 The Interface Solution Experts
Specifications
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
Specifications
HART
Performance
Address Range: 0-15
(1-15 are for multidrop loops) Transmission Speed: 1200 bps Character Format: 1 Start Bit - 8 Data Bits - 1 Odd Parity Bit - 1 Stop Bit
Input Accuracy: Refer to Table 1
Output Range: 4-20mA Analog Output Accuracy:
3µA (0.01875% of 4-20mA span) Overall Accuracy: The overall accuracy of the unit is the combined input and out­put accuracy. It includes the combined effects of linearity, hysteresis, repeatability and adjustment resolution. It does not include ambient temperature effect. For T/C input only, add the Reference Junction Compensation error
Reference (Cold) Junction Compensation: ±0.25°C
(±0.45°F)
Stability: Refer to Table 2 Isolation: THZ2: HPP,
1500Vrms between input and output continuous; DIN, 500Vrms between input and output continuous; TDZ2: 500Vrms input-to­output continuous, and will withstand a 500Vac dielectric strength test for one minute with no breakdown Response (Rise) Time: 100msec maximum for the output to change from 10% to 90% for an input step change of 0% to 100% Step Response Time: 500msec maximum, 256msec typical from the time an input is applied until the output reaches 90% of its final value Ripple: 10mVp-p measured across a 250 ohm load resistor at frequencies up to 120Hz Over-voltage Protection: ±5Vdc peak, maximum Digital Input Filter: User­programmable; 50/60Hz Power Supply Effect: ±0.002% of span per 1V change
Performance
(Continued)
Display
(TDZ2 only)
Load Effect: Negligible
within specified power limits
Load Capability:
(500 ohms@24V) Supply Voltage - 12V
0.024A Burnout Protection: User­programmable, Upscale 20 to 23.6mA; Downscale 3.6 to
4.0mA Output Current Limiting: User-programmable, 3.6 to
4.0mA and 20 to 23.6mA for input under/over range; 25mA, maximum (hardware limit) T/C Input Impedance: 40Mohms, nominal RTD & Ohms Excitation: 250 microamps, ±10%
RTD Lead Wire Resistance Maximum: RTD resistance
+ 2X lead wire resistance < 4000 ohms; Recommend­ed lead wire resistance for three wire connections: <35 ohms/wire; 10 ohms copper sensor <5 ohms
Sensor Lead Resistance Effect: 2-wire sensors: Error
= 1.0 ohm in reading/ohm of lead resistance; 3-wire sensors: Error = 1.0 ohm in reading/ ohm of unbalanced resis­tance; 4-wire sensors: No effect Damping: User set; 0-30 seconds Resolution: Input, 20-bit; Output, 16-bit
Power Supply Requirement: 12-30Vdc
for I.S. version; 12-42Vdc for standard version
Type: TDZ2; Top Row, 10mm (0.4 in) high black digits on a reflective background; Bottom Row, 6mm (0.225 in) high digits on a reflective background; Two-digit HART address indicator Format: Two rows of five alphanumeric characters
= Ohms
Display (TDZ2 only, continued)
Ambient Tem-
perature
Weight
Decimal Points:
Can be user-set to enable automatic adjustment of decimal point to 2 decimal places; Allowed decimal places: Auto, 1, 2 or 3
Range: -99999 to 99999 Minimum Display Span:
1.00
Operating Range:
-40°C to +85°C (-40°F to +185°F) Storage Range:
-40°C to +85°C (-40°F to +185°F) Relative Humidity: 0-95%, non-condensing
Ambient Temperature Ef­fect: See Table 3 Effect on Reference (Cold) Junction Compensation:
±0.005°C per °C change of ambient temperature Startup Time: <0.5sec, maximum Noise Rejection: Common mode, 100dB@50/60Hz; Normal Mode: Refer to Table 4 RFI/EMI Immunity: THZ2: HPP and DIN 10V/m@80-1000MHz, 1kHz AM, when tested according to IEC 61326; With -RF DIN Option: 20V/m@80-1000MHz, 1kHz AM, when tested according to IEC 61326; TDZ2: 20V/m when tested according to IEC 61326
THZ2 DIN: 221g (7.9 oz) THZ2 HPP: 91g (3.2 oz) THZ2 HPP in LH1: 423g (15.1 oz) THZ2 HPP in LH2:
644g (22.9 oz) TDZ2 HP: 182g (6.4 oz) TDZ2 HP in BH:
1.4kg (50.2 oz)
TDZ2 HP in D-Box:
672g (23.4 oz)
Specifications and information subject to change without notice.
The Interface Solution Experts 5
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Table 1. THZ2 and TDZ2 Input and Accuracy Table
Input Type α Ohms
RTD
Ohms
T/C
Millivolts
Platinum
Nickel
Copper
Direct Resistance
Potentiometer
J
K
E
T
R
S
B
N
C
DC
0.003850
0.003902
0.003916
0.00672
0.00427
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
0-4000 ohms
125, 250, 500, 1k,
2k, 4k ohms
100
200
300
400
500
1000
100
200
400
500
1000
100
120
9.035
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Conformance
Range
-200 to 850°C
-328 to 1562°F
-100 to 650°C
-148 to 1202°F
-200 to 510°C
-328 to 950°F
-80 to 320°C
-112 to 608°F
-50 to 250°C
-58 to 482°F
0-4000 ohms
0-100%
-180 to 760°C
-292 to 1400°F
-150 to 1370°C
-238 to 2498°F
-170 to 1000°C
-274 to 1832°F
-170 to 400°C
-274 to 752°F
0 to 1760°C
32 to 3200°F
0 to 1760°C
32 to 3200°F
400 to 1820°C 752 to 3308°F
-130 to 1300°C
-202 to 2372°F
0 to 2300°C
32 to 4172°F
-50 to 1000mV
Minimum
Span
10°C
(18°F)
10 ohms
10%
35°C 63°F
40°C 72°F
35°C 63°F
35°C 63°F
50°C 90°F
50°C 90°F
75°C
135°F
45°C 81°F
100°C 180°F
4mV
Input
Accuracy
±0.1°C
(±0.18°F)
±0.85°C
(±1.53°F)
±0.4 ohms
±0.1%
±0.25°C
(±0.45°F)
±0.3°C
(±0.54°F)
±0.2°C
(±0.36°F)
±0.25°C
(±0.45°F)
±0.55°C
(±0.99°F)
±0.55°C
(±0.99°F)
±0.75°C
(±1.35°F)
±0.4°C
(±0.72°F)
±0.8°C
(±1.44°F)
15 microvolts
Maximum
Range
-240 to 960°C
-400 to 1760°F
-150 to 720°C
-238 to 1328°F
-240 to 580°C
-400 to 1076°F
-100 to 360°C
-148 to 680°F
-65 to 280°C
-85 to 536°F
0-4095 ohms
0-100%
-210 to 770°C
-346 to 1418°F
-270 to 1390°C
-454 to 2534°F
-270 to 1013°C
-454 to 1855.4°F
-270 to 407°C
-454 to 764.6°F
-50 to 1786°C
-58 to 3246.8°F
-50 to 1786°C
-58 to 3246.8°F
200 to 1836°C
392 to 3336.8°F
-270 to 1316°C
-454 to 2400.8°F
0 to 2338°C
32 to 4240.4°F
-50 to 1000mV
Sensor-to-
Transmitter
Matching
Up to ±0.014°C (±0.025°F) system accuracy*.
*High-accuracy measurements are achieved by using a 4-wire, 1000 ohm platinum RTD with a span of 100°F (50°F minimum) calibrated in our sensor-matching calibration bath.
6 The Interface Solution Experts
30mm
TOPBOTTOM
SIDE
C
L
C
L
C
L
C
L
(1.1 in)
25mm
(1.0 in)
52mm
(2.0 in)
49mm
(1.9 in)
27mm
(1.0 in)
4 X 40
0.125 in depth 2 Places
33mm
(1.3 in)
L
C
33mm
(1.3 in)
+PS
2
3
4
1
–PS
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
Table 2. Long-Term Stability Table
Stability (%
of maximum
span)
T/C, mV
RTD, Ohm,
Potentiometer
Table 3. Ambient Temperature Effects Table
Sensor
Type
RTD
T/C
Millivolt
Ohm
Digital Accuracy per 1°C (1.8°F)
0.002 ohms + 0.005% of reading
Input to Output Input to HART
1 yr
3 yrs
0.08
0.14
0.09
0.16
change in Ambient
0.003°C
0.003°C + 0.005% of reading
0.005mV + 0.005% of reading
5 yrs
0.18
0.21
1 yr
0.008
0.047
Table 4. Normal Mode Rejection Ratio Table
Sensor Type
T/C: J, K, N, C, E
3 yrs
0.015
0.081
Analog Accuracy per 1°C (1.8°F)
5 yrs
0.019
0.104
change in Ambient
0.004% of span (16mA)
0.004% of span (16mA)
0.004% of span (16mA)
0.004% of span (16mA)
T/C: T, R, S, B
Pt RTD: 100, 200, 300 ohms
Pt RTD: 400, 500, 1000 ohms
Cu: 9.03 ohms
Resistance
1-4kohms
0.25-1kohms
0.125-0.25kohms
Ni: 120 ohms
31.25-62.5
mV
250-1000
62.5-250
Max. p-p Voltage Injection for
70dB at 50/60Hz
150mV
80mV
250mV
1V 500mV 100mV
1V 250mV
100mV
Figure 1. THZ2 Hockey-Puck (HPP Housing) Dimensions
The Interface Solution Experts 7
FRONT VIEW
SIDE VIEW
61mm
(2.4 in)
+PS
-PS
1234 5 COM
TDZ
83mm
(3.2 in)
62mm
(2.4 in)
64mm
(2.5 in)
66mm
(2.5 in)
76mm
(3.0 in)
43mm
(1.7 in)
18mm
(0.70 in)
2
138mm (5.4 in)
When Installed
133mm
(5.2 in)
When Installed
80mm
(3.1 in)
43mm
(1.6 in)
113mm
(4.4 in)
110mm
(4.3 in)
25mm
(1.0 in)
1234
+PS –PS
C
L
THZ
COM
2
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Figure 2. TDZ2 Hockey-Puck (HP Housing) Dimensions
Figure 3. THZ2 DIN Dimensions
8 The Interface Solution Experts
Figure 4. BH Housing Dimensions (For use with the TDZ2)
+PS COM-PS 12345
TDZ
ADDR
0
602.78
D EG C
68mm
(2.6 in )
GND
1/2 NPT
102mm
(4.0 in )
84mm
(3.3 in )
68mm
(2.6 in )
64mm
(2.5 in )
10mm
(0.3 in )
124mm
(4.8 in )
25mm
(1.0 in)
102mm
(4.0 in )
119mm
(4.6 in )
76mm
(2.9 in )
57mm
(2.2 in )
22mm
(0.8 in )
SIDE VIEW
TOP VIEW
2
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
The Interface Solution Experts 9
92mm
(3.62 in)
9mm
(0.3 in)
87mm
(3.4 in)
Conduit
Entry Port
89mm
(3.5 in)
84mm
(3.3 in)
C
L
61mm
(2.4 in)
2-in Pipe Bracket
Mounting Holes (4)
61mm
(2.4 in)
Process Connection
1/2-in NPT (N and M models) or
G½ (BSP) (C models)
61mm
(2.4 in)
10-32
Mounting
Holes (2)
51mm
(2.0 in)
Safety Lock
(LH2 only)
Metal Tag
BOTTOM
INSIDE
2-INCH PIPE MOUNTING HARDWARE
30mm
(1.1 in)
DIA. 72mm
(DIA. 2.8 in)
Instrument Mounting Holes 40mm (1.5 in)
Instrument Mounting Holes 33mm (1.3 in)
I.D. 62mm x 19mm Deep
(2.4 in x 0.75 in Deep)
Ground
M4.0 x 0.7
(4 places)
FRONT
SIDE
84mm
(3.3 in)
118mm
(4.6 in)
130mm (5.1 in)
112mm
(4.4 in)
83mm
(3.2 in)
64mm
(2.5 in)
C
L
Interior Diameter
81mm (3.2 in)
Instrument
Tag
116mm (4.5 in)
27mm
(1.0 in)
Conduit
Fitting
Cover
Body
Bezel
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Figure 5. LH Housing Dimensions (For use with the THZ2 HPP)
Figure 6. D-BOX Housing Dimensions (For use with the TDZ2)
10 The Interface Solution Experts
2
THZ
Programmable Smart HART
Temperature Transmitter and Display
&
TDZ
2
Configuring the THZ2 and TDZ
One of the benefits of these transmitters is that there are no internal or external controls to adjust or settings to change. All operating parameters are set using either a HART Communicator or a PC and Moore Industries’ Intelligent PC Configuration software.
The software settings are downloaded to the transmitter in the form of a Configuration File and stored in the instrument’s memory. You can save a backup copy of the file on your PC hard drive or external media. The transmitter communicates with the PC through an RS-232 port or USB port. A HART modem connection to the PC’s serial port may also be used.
You can configure the THZ2 or TDZ2 with either a standard HART Communicator or our PC software. Figures 7 and 8 (depending upon your instrument’s housing) and Table 5 provide the information you need to configure your unit.
Using a PC If you are going to use a PC to configure your unit, first install the software as described on the next page, then setup the hardware as shown in Figures 7 or 8 (depending upon your instrument’s housing).
2
Installing the Configuration Software
Refer to Table 5 for the equipment needed.
1. Insert the Moore Industries Interface Solution PC Configuration Software CD into the CD drive of the PC. Access the CD and open the THZ2_TDZ2 PC Configuration Software folder.
2. Double-click the installation program located in the folder. Follow the prompts to correctly install the program.
Once the Configuration Program is installed on the PC, the THZ2 or TDZ2 can be connected to equipment to simulate input and monitor output. You can then change the transmitter’s operating parameters.
The Interface Solution Experts 11
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
No Transmitter Needed
It is not necessary to connect the transmitter to a PC to create configuration files using the software. The Configuration Program can be run without connecting a transmitter, and most parameters can be set without benefit of input from a sensor or transmitter.
This makes it easy to create a set of operating parameters, save them to external media, and download them to one or more transmitters at a later time.
The THZ2 or TDZ2 must be connected to the PC in order to: trim input, trim output, assign a tag, perform a loop test, receive (via download) a configuration file and save the configuration file from the transmitter’s memory.
Connecting the THZ2 or TDZ2 to the PC
To set any of the options, you must first connect the unit to the PC. The THZ2 and TDZ2 all have the same terminal designations regardless of housing style, and all can be setup using the connections shown in Figures 7 and 8 (depending upon your instrument’s housing).
Establish a simple current loop for the transmitter by connecting a 24 Volt power supply, a 250 ohm resistor and the transmitter in series. See Table 5 for information on the necessary equipment.
Connect your instrument to the PC via the RS-232 serial port using Moore Industries Interface cable or USB cables listed in Table 5.
A HART modem may also be used to connect your unit to the PC. Connect the RS-232 end of the modem to the PC’s COM port, then connect the HART output end of the modem (two hook-up wires) across the transmitter or the load resistor. For hook­up diagrams, refer to Figures 7 or 8 (depending upon your instrument’s housing).
Table 5. Necessary Equipment Table
Device Specifications
Variable Input Simulator for Thermocouple,
RTD, Millivolt, Potentiometer, or Decade
Resistance Box
Power Supply
Precision Load Resistor
Multimeter (optional)
Personal Computer
(Required only if
using a PC for setup)
Moore Industries Interface Cables
HART Modem Cable
(Required only if using a PC)
Moore Industries PC
Configuration Software
(Required only if using a PC)
HART Communicator
(Required only if NOT using a PC)
Variable; Accurate to ±0.05% of unit span
24Vdc, ±10%
250 ohms, ±0.01% HART specifies that total loop resistance is to be maintained between 250 ohms and 1100 ohms.
Accurate to ±0.025% of span; e.g., Fluke Model 87
Microsoft Windows based PC; 16Mb free RAM; 20MB free disk space on hard drive Microsoft Windows XP, Vista or 7 1 (one) serial port or one available USB port
803-040-26, Isolated Interface Cable 803-039-26, USB cable 208-236-00 or Fuse Protected USB cable 804-030-26
Moore Industries part number 803-048-26, or equivalent
Version 1.0 or greater, successfully installed to the hard drive
Fisher-Rosemount Model 375/475 or equivalent (with THZ2/TDZ2 Device Description loaded)
12 The Interface Solution Experts
Figure 7. THZ2 (HPP) and TDZ2 (HP) Hook-Up Diagrams
+
12-24Vdc
Power
Supply
THE HART Communicator or the PC can be connected at any point on the output side of the loop. Total loop resistance must equal between 250 and 1100 ohms for proper HARTcommunications.
Current Meter
Load=250 ohms
+
+PS
2
3
4
1
–PS
PC
OR
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
+
2-Wire RTD
or Decade
Resistance Box
Thermocouple
and Millivolt Input
3-Wire RTD
or Decade
Resistance Box
4-Wire RTD
or Decade
Resistance Box
Potentiometer
Input
2
3
4
1
Input Hook-Up Connections
HART Modem connects to serial (COM) port of PC
+
12-24Vdc
Power
Supply
THE HART Communicator or the PC can be connected at any point on the output side of the loop. Total loop resistance must equal between 250 and 1100 ohms for proper HARTcommunications.
Current Meter
Load=250 ohms
+
PC
OR
HART Modem connects to serial (COM) port of PC
+PS
-PS12
34
TDZ
2
THZ (HPP) Hook-Up
2
TDZ (HP) Hook-Up
2
NOTE:
1. Te rminal blocks can accommodate 14-22 AWG (2.0-0.3mm ) solid wiring.
2. HP Housing terminals utilize M2.6 screws. Tighten terminals to 2.8 in lb (0.31Nm) (maximum).
3. HPP Housing terminals utilize #4 screws. Tighten terminals to 4.7 in lb (0.53Nm) (maximum).
2
To serial
(COM) port
of PC
To USB
(COM)
Port of PC
OR
To serial
(COM) port
of PC
To USB
(COM)
Port of PC
OR
2
THZ
&
TDZ
Programmable Smart HART
Temperature Transmitter and Display
2
The Interface Solution Experts 13
1234
+PS –PS
THZ
COM
2
PC
To serial
(COM) port
of PC
Input Hook-Up Connections
+
143214321432
Thermocouple
and Millivolt
Input
2-Wire RTD
or Decade
Resistance Box
143
2
3-Wire RTD
or Decade
Resistance Box
4-Wire RTD
or Decade
Resistance Box
1432
Potentiometer
Input
+
12-24Vdc
Power
Supply
THE HART Communicator or the PC can be connected at any point on the output side of the loop. Total loop resistance must equal between 250 and 1100 ohms for proper HARTcommunications.
Current Meter
Load =250 ohms
OR
HART Modem connects to serial (COM) port of PC
+
NOTE:
1. Te rminal blocks can accommodate 14-22 AWG (2.0-0.3mm ) solid wiring.
2. DIN Housing terminals on TPRG input instruments utilize #6 screws. Tighten terminals to 7.9 in lb (0.89Nm) (maximum).
2
To USB
(COM)
Port of PC
OR
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Figure 8. THZ2 DIN Hook-Up Diagram
14 The Interface Solution Experts
PC Configuration Software Summary
1
2
6
4
3
5
7
Figure 9-A. THZ2/TDZ2 PC Configuration Software Main Screen
2
THZ
Programmable Smart HART
Temperature Transmitter and Display
&
TDZ
2
Once the default configuration has been saved to your PC or external media, it is safe to program other parameters. The PC Software is made up of these sections:
1. Menu Bar/Tool Bar– Dropdown menus and corresponding icons allow you to perform various functions throughout the PC Configuration Program. Refer to the Menu and Tool Bar Legend for a complete description.
2. Program Status– This portion of the program displays the activity of the connected unit. It will display such messages as: Idle, Monitoring, Uploading and Downloading.
3. Devive Status– Indicates if there are problems or faults with the instrument.
4. Identification Parameters– Use this parameter to place an identifying Ta g (8 alphanumeric characters, maximum), Descriptor (16 alphanumeric characters, maximum) or Message (32 alphanumeric characters, maximum). Use the Address box to change the unit’s address (0-15).
To utilize a longer Tag identifier (up to 32 characters, maximum) you may access the Long Tag feature located in the View dropdown menu. Enter the desired information and click Set. To view the Long Tag, click Read.
5. THZ2/TDZ2 Device Info– This “read-only” display indicates instrument configuration and device identification.
6. Communications– Notifies user of current PC connection/communications status. The address displayed in the Address box must match the address of the unit if HART Communciations are being used.
7. Input/Display/Scaling/Custom Curve/Analog Output Tabs–These tabs change the right side of
the screen to allow you to set the appropriate part of the THZ2’s and the TDZ2’s configuration. See corresponding sections of this manual for additional information regarding these tabs.
The Interface Solution Experts 15
Allows such functions as New, Open, Save and Print functions
Allows you to Upload and Download configurations and perform an Address Search
Allows selection of PC COM ports as well as Communcation Method (Auto, RS232 or HART)
Allows you to Monitor and Stop monitoring processes
Provides functions specific to your Custom Curve table
Controls whether Tool and Status Bars are viewed on the screen as well as Additional Status Information, Long Tag and Device Information
Displays the version of the PC Configuration Program
Allows you to enable Burst Mode
2
THZ
Programmable Smart HART Temperature Transmitter and Display
&
TDZ
2
Figure 9-B. THZ2/TDZ2 PC Configuration Software Main Screen
When Monitoring is selected the Process Variable window will appear and display the present Process Variable readings along with Device Status and Output Current.
Note:
When Monitoring user is unable to make any
changes to configuration.
Configuration Screens
Note:
Unless otherwise noted, ensure that the PC
Configuration Program is idle before making any
selections or configuration changes to the program.
Also, when attempting to download or upload,
monitoring must be stopped. To do this, click Stop
in the Monitoring dropdown menu, or click the Stop
Monitoring icon on the Tool Bar.
Input
Figure 10. Input Tab
Menu and Tool Bar Legend
Input Type– Select your input type and the
respective range of your input.
Temperature / SV Temperature– Use this section to select the temperature unit you wish to view.
If the selected Input Type is an RTD or T/C, this sec- tion is displayed as Temperature.
If a mV, Resistance or Potentiometer input is selected, this section is displayed as SV Temperature.
Filter– This setting is used to configure the input filter. The filter is designed to reduce the effects of mains­induced noise. The input filter frequency value should be set to the frequency of the local AC supply–either 50Hz or 60Hz.
Input Type section.
16 The Interface Solution Experts
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
Broken Wire Detection– During operation, the THZ2 and TDZ2 send random microamp pulses through input wiring to check for broken wiring or a burned out sen­sor.
To utilize Broken Wire Detection, check the Enabled box. If a failure is detected, a message will appear in the THZ2/TDZ2 Status box.
Running Average Filter Settings– This function is for filtering the input signal. The THZ2 and TDZ2 provide this filter with a user-selected range between 1 and 16. Factory default is 1.
Note:
A higher Running Average Filter setting provides
smoother output transitions; however, reduces
response time. Conversely, a lower setting provides
a faster response time, but may seem more unstable.
PV Damping–PV Damping allows you to introduce a delay into the response of your unit in order to stop short-lived spikes from initiating faults and generating fault messages.
The configured damping period will determine the time response that the analog output will take to achieve a 66% change in output in response to a stepped input.
To enable PV Damping, select the Enabled button. Use the arrows to select a value between 1sec and 30sec.
Sensor Trimming– Sensor Trimming increases the measurement accuracy of your instrument by match­ing the reading of its actual input, to either a calibrated source or the device to which it is connected. This veri­fies that the input to the transmitter is being interpreted correctly.
You may trim any point between 0% and 100% along the scale. Note that one-point trimming applies an offset to the sensor reading, while two-point trimming applies both an offset and a gain.
Follow the steps below in order to perform sensor trimming.
1. Select either 1 Point (one-point trimming) or 2 Points (two-point trimming) by clicking the appropriate button. Each pair consists of Set Value and Tr i m fields.
2. Enter the values that require trimming into the Set Value field and click Set.
3. Apply the targeted signal to the input, wait until it settles, and click Tri m to capture the measured value. If you chose 2 Points, repeat the step above for the second point.
Note:
Once you have configured all parameters, download
to the unit by selecting Download in the Transfer
dropdown menu located in the Menu Bar. Or, click
the button in the Tool Bar.
Sensor Range– Allows you to set your upper and lower range values within the range chosen in the Input Type section.
The desired Upper and Lower Range settings can be entered via your PC keyboard or captured. To capture an input, follow the steps below.
1. Apply the desired Upper Range input and press the corresponding Capture button.
2. Next, apply the desired Lower Range input and press the corresponding Capture button.
The Interface Solution Experts 17
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Display (TDZ2 Only)
Figure 11. Display Tab Figure 12. Scaling Tab
Display Source– Select how your reading is displayed.
Primary Variable–The reading will be displayed as the Primary Variable value.
Output Current–Your reading will be displayed as the output current value.
Scaling
Using the Scaling feature will disable the Custom Curve capability. Since both are scaling features
used to manipulate the appearance of your process
variable, only one of these functions may be used at
Scaling– This allows you to customize your display for your application. By example, if your process is sending a -200°C to 850°C signal to the THZ2 or TDZ and you wish to view the input as 0-100% then this can be accomplished with the Scaling feature.
Note:
a time.
2
Toggle PV / mA– Every four seconds your display will toggle between the primary variable and mA (current) reading.
Percent of Range– Selecting this allows your instrument to display its output in the percent of the range at which the output current is transmitting ( 0-100%).
Custom Label– The Custom Label is used to display a calculated or scaled variable. Clicking the Use custom label box causes the instrument to always display the custom label as Engineering Units (EGU).
1. Check the Use custom label box.
2. Enter the label you wish viewed into the text box. This value is limited to five characters.
Precision– Select the number of decimal places (up to three) of your display.
Note:
Once you have configured all parameters, download
to the unit by selecting Download in the Transfer
dropdown menu located in the Menu Bar. Or, click
the button in the Tool Bar.
To scale your instrument, perform the following steps:
1. Check the Enabled box. The Sensor Range boxes will display the range selected in the Input Type section of the Input screen.
2. In the Scaled to text boxes, enter the values you wish displayed when your input is at its Zero Range and Full Range.
Once downloaded, your unit will display the scaled values on its LCD and through HART communication.
Scaling PV Units of Measure– Use this to select a preset HART EGU process variable display for your scaled values. These HART EGU codes are compatible with HART Revision 5, and earlier, communications.
To customize your display and set your own EGU, open the Display screen and use the Custom Label feature.
Note:
Once you have configured all parameters, download
to the unit by selecting “Download” in the Transfer
dropdown menu located in the Menu Bar. Or, click
the button in the Tool Bar.
18 The Interface Solution Experts
2
THZ
Programmable Smart HART
Temperature Transmitter and Display
&
TDZ
2
Custom Curve
Figure 13. Custom Curve Tab
Note:
Using the Custom Curve feature will disable the
Scaling capability. Since both are scaling features
used to manipulate the appearance of your process
variable, only one of these functions may be used at
a time.
Custom Curve–The Custom Curve feature allows you to set up your own custom curve table. This allows you to tell the transmitter what it should output when it receives a certain input. This feature also allows you the ability to write a table in Microsoft® Excel, save it in a .csv format, and import it into the Configuration Software. This makes it simple to save the custom table for downloading to multiple units or for backup purposes.
To create a custom curve:
1. Click the Enabled box.
2. Select the number of points for your curve (128 points maximum) and enter it into the No Of Points text box.
3. In the Custom Curve (Y) Range text boxes, enter the values you wish displayed, and represented as your 4-20mA span, when your input is at its upper and lower ranges.
4. Type your individual values in the X data and Ydata columns. Source variables are inserted into the X Column, while the corresponding data is inserted into the Y Column.
5. After all of your data has been entered, you must use the Custom Curve dropdown menu to save your newly created custom table (Save Custom Curve) and to download it to your instrument (Download Custom Curve).
Custom Curve PV Units of Measure– Use this to select a preset HART EGU process variable display for your custom curve values. These HART EGU codes are compatible with HART Revision 5, and earlier, communications.
To customize your display and set your own EGU, open the Display screen and use the Custom Label feature.
Note:
Once you have configured all parameters, download
to the unit by selecting “Download” in the Transfer
dropdown menu located in the Status Bar. Or, click
the button in the Tool Bar.
The Interface Solution Experts 19
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Analog Output
Figure 14. Analog Output Tab
Process Variable Range– Displays the selected process variable range.
Output Range– Sets your output limits. Default value is 4-20mA.
1. Enter your low and high limit values into the text boxes.
2. In the Under Range Min. Value box, enter the lowest limit your output can reach before indicating a failure. The allowed limits are
3.6mA to 4.0mA. Default is 3.8mA.
3. In the Over Range Max. Value box, enter the highest limit your output can reach before indicating a failure. The allowed limits are
20.0mA to 23.6mA. Default is 21.8mA.
Fail Mode– In the case of an input failure, you have the ability to set an indicator to alert of the failure.
High– Selecting High will send the output to a user­selected high value between 20.0mA and 23.6mA. Default is 23.6mA.
Hold Last– This will maintain the last value present before the failure.
Note:
Once you have configured all parameters, download
to the unit by selecting Download in the Transfer
dropdown menu located in the Menu Bar. Or, click
the button in the Tool Bar.
Output Current– While in monitoring mode, this dis­plays the present output value.
Trimming– Output Trimming increases the accuracy of your instrument by calibrating its analog output to the device that is receiving the output. This ensures that the instruments are matched to each other.
1. Click the Lower button to fix the lower output range.
2. To “fine tune” trimmed values, place the value read on the external ammeter in the
Measured Loop Current text box and click Tr i m .
3. Click the Upper button and repeat Step 2 to trim the upper output range.
4. Once you have perfomed your output trimming, click Unfix.
Note:
Do not click the Reset button in the Trimming menu
unless you want to disregard your trimmed values
and return to the manufacturer’s trim values.
Output Test– This test may be performed in order to check output performance and accuracy and to trim other instruments in your setup. Your output will be a current value, in mA, equal to the value you enter into the text box. You can check the other devices on the system and calibrate them to this signal.
This feature is independent of the input. If you find that the output requires adjustment, you may perform the Trimming function.
Low– By selecting Low, the failure indication value will be driven to a user-selectable value between 3.6mA and 4.0mA. Default is 3.6mA.
Note:
When setting Fail Mode to Low on the THZ2 while
it is operating at temperatures below -30 Degree C,
set the Output Fail Current to 3.8mA, or higher, to
ensure full HART communication functionality.
To select a value other than the default setting for High and Low fail mode, enter the value into the Sensor
Error Value text box.
20 The Interface Solution Experts
1. Ensure that THZ2/TDZ2 monitoring is stopped. In the Fix current text box, enter a value between 3.6mA and 23.6mA and click the Fix button.
2. Return to monitoring the THZ2/TDZ2. You will see the “fixed” value in the Output Current display and on the external ammeter connected to the output.
3. Once you have finished, stop monitoring your instrument and click Unfix.
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
Note:
While performing Analog Output Trimming functions,
you may notice a message in the THZ2/TDZ2 Status
display reading **OUTPUT FIXED**” Clicking the
Unfix button will clear this message.
Searching for a Connected Unit
If using HART Communications and you need to search for a connected THZ2 or TDZ2 unit with an unknown address, you can perfom an address search. An address search sequentially polls short frame addresses 0 through 15 with HART Command 0–read unique ID. The first device to respond stops the address search and the device’s configuration is uploaded to the PC Configuration Program.
To begin an address search, you may either click the button on the tool bar or select Address Search from the View dropdown menu. You can view search progress in the Address box located in the Communications section of the PC Configuration Program.
HART Communication Foundation 9390 Research Blvd., Suite I-350 Austin, TX 78759-6540 USA Phone: (512) 794-0369 Fax: (512) 794-3904 www.hartcomm.org
Ensure that you contact the HART Foundation to determine their requirements in sending the instrument to their facility.
If you are using a Fisher-Rosemount Model 275 HART Communicator, perform the following steps to determine if your communicator has the appropriate Device Description. With the communicator turned on, press 1 to select Offline then press 1 again to select New Configuration. A list of companies will appear which, if you have the appropriate Device Description, will include Moore Industries THZ2/TDZ2.
If you find that you require the latest version of the DD, you must send the Communicator to Moore Industries. To do this, contact our Customer Service department for a Returned Material Authorization (RMA).
Using the HART Communicator
The THZ2 and TDZ2 can be programmed using a HART Communicator. If your communicator is equipped with the Device Description (DD) for your transmitter, The HART Communicator Menu with a Device Description section gives an overview of the menus and instructions for programming.
If your communicator is not equipped with the required Device Description, go to The HART Communicator Menu without a Device Description section of this manual. Even if your communicator is not up to date, most of the important programming features can be accessed without the THZ2 and TDZ2 DD by using the Generic HART DD available on HART Communicators.
If you are using a Fisher-Rosemount Model 375 HART Communicator, or other host, you may download the latest Moore Industries DD at www.hartcomm.org. The THZ2 and TDZ2 DDs are available on the HART Foundation’s Device Driver Library Release December 2005 and later.
For installation of the latest device description through the HART Foundation, send the Communicator to the the following address:
Include Moore Industries’ configuration sheet indicating the Device Descriptions that you require. We will load the Device Descriptions of your choice for a nominal charge.
Programming When a Device Description is Available
Note:
All parameters, except the Custom Curve feature,
can be configured using the HART Communicator.
The Custom Curve table can only be configured
using the PC Configuration Software Program.
With the transmitter connected as illustrated in Figures 7 or 8 (depending upon your instrument’s housing) apply power and turn on the communicator. After a brief self-test, the communicator will show the main menu and identify the unit as a THZ2 or TDZ2.
This section contains the instructions for programming the transmitter using a HART Communicator that has been programmed with a HART Device Description. If your communicator does not have the appropriate Device Description, skip to The HART Communicator Menu without a Device Description section of this manual. Figure 15 shows an overview of the programming menus for the configuration process.
The Interface Solution Experts 21
Online Menu
1 Model 2 Device Setup 3 PV 4 AO 4 LRV 6 URV
1 Process Variable
2 Setup
3 Diagnostic & Services
4 Review
1 PV 2 % Range 3 AO 4 Term. Temp
Setup
1 Configure Sensor
2 Configure Options
3 Configure Range
4 Configure Output
5 Configure Dev Info
6 *Configure Display
Configure Sensor
Sensor Type
1 RTD2W 2 RTD3W 3 RTD4W 4 mV 5 OHMS2W 6 OHMS3W 7 OHMS4W 8 T/C 9 T/C w/RJC 10 Potentiometer
RTD
Thermocouple
1 T/C J 2 T/C K 3 T/C E 4 T/C T 5 T/C R 6 T/C S 7 T/C B 8 T/C N 9 T/C C
Sensor Information
1 LSL 2 USL 3 Min Span
Configure Options
1 EGU Selecton 2 EGU 3 Filter 4 Running Average 5 Broken Wire 6 AO URV 7 AO ORV 8 Fail Mode
9 Fail Mode AO Smart Range Selection
Configure Range
1 Smart Ranging 2 Input Capture
Smart Ranging
Set the:
1 4mA 2 20mA 3 Exit
Configure Output
1 Analog output 2 HART output
Analog Output
1 Output Zero 2 Output Full 3 Output Trim 4 Output Trim Reset
HART Output
1 Poll addr 2 Burst mode 3 Burst option
Configure Dev Info
1 Tag 2 Descriptor 3 Message 4 Date 5 Final asmbly num 6 Device id 7 Hardware rev
Configure Display
1 Mode (PV, mA, Toggle, %) 2 Decimal Places (1, 2, 3, Auto) 3 Custom Label (Disabled/Enabled) 4 Label Displayed
Diagnostic & Services
Review
1 Device Parameters
2 Device Information
Sensor Trim
1 Sensor Trim Mode 2 Sensor Trim 3 Sensor Trim Reset
Loop Test
1 4mA 2 20mA 3 Other 4 End
Device Parameters
Model Measure Mode Input Type Sensor Serial Number Filter Running Average Broken Wire Broken Wire Level EGU LRV URV LSL USL Min Span PV Damping Sensor Trim Mode AO URV AO ORV Fail Mode Fail Mode AO Smart Range Selection
Device Information
Tag Descriptor Message Date Dev id Universal rev Fld dev rev Software rev Hardware rev Physicl signl code Poll addr Burst mode Num req preams
Key
*If unit is TDZ
2
1 LSL 2 USL 3 Min Span 4 Sensor LRV 5 Sensor LRV Scaled to 6 Sensor URV 7 Sensor URV Scaled to 8 Scaling EGU
Smart Ranging
(If Scaling Enabled)
Smart Ranging (If Custom Curve
Enabled)
Process Variable
1 Sensor Type 2 Sensor Serial Number 3 PV Damping 4 Sensor Information
If Scaling Enabled
If Custom Curve Enabled
1 PT3850 100 2 PT3850 200 3 PT3850 300...
13 NI 672 120 14 CU 427 9.035
1 LSL 2 USL 3 Min Span 4 CC Points 5 Custom Curve LRV 6 Custom Curve URV 7 CC EGU
1 LSL 2 USL 3 Min Span 4 LRV 5 URV
1 Test device (Status) 2 Sensor Trimming 3 Loop Test
% RANGE = Output Current in % of Span # PREAMBLES = Number of Preamble Characters AO = Output Current AO ORV = Analog Output Over Range Value AO URV = Analog Output Under Range Value DAMP = Damping Value DEV ID = Device Identification DIAG = Diagnostic LRV = Lower Range Value MAX VALUE = Maximum Process Value MIN VALUE = Minimum Process Value OFFS = Offset POLL ADDR = Polling Address URV = Upper Range Value
1
2
3
4
A
B
C
D
E
F
5
6
Device Setup
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Figure 15. THZ2 and TDZ2 HART Communicator Configuration Menu Summary
22 The Interface Solution Experts
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
The HART Communicator Menu With a Device Description
To program your THZ2 or TDZ2, if your communicator is equipped with the Device Description for your instrument, follow the steps below. For all steps outlined below, refer to Figure 15 for menu parameters.
1. Online Menu– The Online menu displays the current process value of your application, the lower and upper range values and the actual output current. Use the Device Setup menu to configure the THZ2 and TDZ2.
2. Device Setup Menu– The Device Setup menu allows you to access the following menus: Process Variable, Setup, Diagnostic & Services and Review.
3. Process Variable Menu– The Process Variable menu displays the present values of parameters listed on the Communicator display which include the selected EGU, output current in percent of span (% range), analog output and terminal temperature.
4. Setup Menu– Scroll through the Setup menu to access configuration menus for the following parameters: Configure Sensor, Configure Options,
Configure Range, Configure Output, Configure Dev Info and Configure Display (for TDZ2 units only).
A. Configure Sensor
This menu allows access to sensor configuration.
1 Sensor Type– Select the sensor type you will use (RTD, Ohms, T/C or Potentiometer). You will navigate through sub-menus depending upon parameters that are being set.
2 Sensor Serial Number– Assign a unique serial number to your sensor.
3 PV Damping– Allows you to introduce a delay into the response of your unit in order to stop short-lived spikes from appearing as faults and generating fault messages. The allowable PV Damping range is 0sec to 30sec.
4 Sensor Information– Displays the Upper Sensor Limit (USL), Lower Sensor Limit (LSL) and minimum span of the selected sensor type.
B. Configure Options
You may configure the THZ2 and TDZ2 options listed below from the this menu.
1 EGU Selection– Choose the EGU you wish displayed.
2 EGU– View the existing EGU setting.
3 Filter– This is used to configure the input filter
which helps reduce mains-induced noise. The value selected should match the frequency of the local AC supply (50Hz or 60Hz).
4 Running Average– This feature filters the input signal. The THZ2 and TDZ2 provide this feature with a user-selected value between 1 and 16. Factory default is 4.
Note:
A higher Running Average setting provides smoother
output transitions, however, will reduce response
time. Conversely, a lower setting provides a faster
response time, but may seem more unstable.
5 Broken Wire– If enabled (by selecting On) the THZ2
and TDZ2 send random microamp pulses through input wiring to check for broken wiring or a burned out sensor.
6 AO URV– Select a value between 3.6mA and
22.6mA as your analog output under range value (AO URV). If the analog output drops below the set value, a fault will be declared.
7 AO ORV– Select a value between 4.6mA and
23.6mA as your analog output over range value (AO ORV). If the analog output exceeds the set value, a fault will be declared.
8 Fail Mode– In the case of a sensor failue, this determines how the analog output will respond. You may select a Fail Mode of High (proceed to Step
9), Low (proceed to Step 9) or Hold Last (last value present will be held upon a failure).
Note:
When setting Fail Mode to Low on the TDZ2 while
it is operating at temperatures below -30 Degree C,
set the Output Fail Current to 3.8mA, or higher, to
ensure full HART communication functionality.
9 Fail Mode AO– Enter a value to correspond to your selection in Step 8. If selecting High Fail Mode, enter a value between 20mA to 23.6mA. For Low Fail Mode, select a value between 3.6mA to 4.0mA.
The Interface Solution Experts 23
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Smart Range Selection– Select whether you choose to view the process variable, use a custom curve table or scale the input. Custom curve and input scaling configuration are performed in the Configure Range menu.
C. Configure Range Within the Configure Range menu are the capabilities to configure Smart Ranging and capture the input.
1 Smart Ranging– Configuration steps will vary depending on whether PV, Custom Curve or Input Scaling was selected in the Configure Options menu.
PV 1 LSL– Displays the lower sensor limit (LSL) of the
attached sensor.
2 USL– Displays the upper sensor limit (USL) of the attached sensor.
3 Min Span– Indicates the allowable minimum difference between the upper range value (URV) and lower range value (LRV).
4 LRV– Enter the value you wish displayed as your low range value when your process variable is output at its lower end (0%).
5 Custom Curve LRV– Enter your Custom Curve lower range value (LRV) for the lower end output value (0%).
6 Custom Curve URV– Enter your Custom Curve upper range value (URV) for the upper end output value (100%).
7 CC EGU– Select the EGU you wish displayed for your Custom Curve values.
If Scaling is Enabled 1 LSL– Displays the lower sensor limit (LSL) of the
attached sensor.
2 USL– Displays the upper sensor limit (USL) of the attached sensor.
3 Min Span– Indicates the allowable minimum difference between the upper range value (URV) and lower range value (LRV).
4 Sensor LRV– Enter the sensor’s lower range value (LRV).
5 Sensor LRV Scaled– Select the value you wish as your scaled LRV (for 0% value). Allowed span is from
-99999 to 99998.
5 URV– Enter the value you wish displayed as your upper range value when your process variable is output at its upper end (100%).
Input Capture– To match your input (zero) and output (full scale) to a known value, use the Input Capture feature.
Apply your 0% value to your THZ2 or TDZ2 and press Enter at the prompt. This will set your 4mA value. Repeat this step with a 100% value in order to set your output to a known 20mA. Press Exit when you have finished.
If Custom Curve is Enabled 1 LSL– Displays the lower sensor limit (LSL) of the
attached sensor.
2 USL– Displays the upper sensor limit (USL) of the attached sensor.
3 Min Span– Indicates the allowable minimum difference between the upper range value (URV) and lower range value (LRV).
6 Sensor URV– Enter the sensor’s upper range value (URV).
7 Sensor URV Scaled– Select the value you wish as your scaled URV (for 100% value). Allowed span is from -99998 to 99999.
8 Scaling EGU– Select the EGU you wish displayed for your scaled input values.
D. Configure Output
This menu allows you to configure your instrument’s analog and HART outputs.
Analog Output
Use this portion of the menu to set the Output Zero and Output Full values, to trim the output and to reset
the trimmed output.
1 Output Zero– Enter your lower range output current value. Allowed values range from 3.6mA to 23.6mA.
2 Output Full– Enter your upper range output current value. Allowed values range from 3.6mA to 23.6mA.
4 CC Points– Displays the number of Custom Curve points you have enabled (2 to 128 points).
24 The Interface Solution Experts
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
3 Output Trim– Output trimming increases the accuracy of your instrument by calibrating its analog output to the device that is receiving the output. This ensures that the instrument is being correctly interpreted.
Connect a multimeter to your THZ2 or TDZ2 output to indicate present output reading.
Setting fld device to Output Zero will be displayed on your communicator. Select OK if ready to proceed. When prompted, enter the value displayed on the multimeter into your communciator. Press Enter. If your output matches the value on the multimeter, select Ye s .
Next, Setting fld dev to Out Full is displayed on your communicator. Select OK if ready to proceed. When prompted, enter the value displayed on the multimeter into your communciator. Press Enter. If your output matches the value on the multimeter, select Ye s .
Note:
Do not perform the Output Trim Reset function
unless you want to disregard your trim values and
return to the manufacturer’s values.
HART Output
Use this portion of the menu to configure the Poll Address, Burst mode and Burst Option.
1 Poll addr– The HART polling address is represented by a number between 0 and 15. This identifies the transmitter on the loop. In a loop with only one HART slave on it, this address should be 0. In a multidrop loop, any of these numbers can be used.
Note:
For Fisher-Rosemount HART Communicator, Model
275, you must enable the Burst Mode and send the
configuration to the unit before selecting the Burst
Option.
3 Burst option– Once Burst Mode is enabled, choose which value is transmitted–PV, % range/current or Process vars/crnt (Process variables/current).
E. Configure Dev Info
This menu allows you to configure identification parameters for your THZ2 or TDZ2.
1 Tag– Place a unique label that corresponds to your instruments location or specific usage (8 characters maximum).
2 Descriptor– Place text that is used as a description of how the instrument is being used (16 characters, maximum).
3 Message– Place additional information that may be helpful in describing the instrument or its use (32 characters, maximum).
4 Date– Store a date that corresponds to specific system function, i.e. instrument configuration date, calibration due date, preventive maintenence schedule, etc.
5 Final asmbly num– You may enter a number that is used for identification purposes, and is associated with the field device (8 characters, maximum).
6 Dev id– This is a read-only value that uniquely identifies the field device when combined with the manufacturer identification and device type.
Note:
If the polling address is set to 0, the transmitter is
automatically set to analog mode. Multiple units on
the same bus must have different addresses.
2 Burst mode– This function allows you to achieve a
higher data rate. When enabled (On), your instrument repeatedly transmits a data message as if it were being commanded to do so. The Master device receives the data more frequently than if it were only polling the transmitter, achieving a higher data trasnfer rate.
7 Hardware rev– This value corresponds to the revision of the electronics hardware of the field device.
F. Configure Display
This menu only applies to the TDZ2 as it is used to configure the manner in which the display is viewed.
1 Mode– Select whether your variable is displayed as a PV, current value or a percent.
2 Decimal Places– Choose the resolution of your value. Select one, two or three decimal places. You may also choose Auto to allow the instrument to automatically select the decimal placement.
3 Custom Label– Enable or disable custom label for use on the display.
The Interface Solution Experts 25
2
THZ
Programmable Smart HART Temperature Transmitter and Display
4 Label Displayed– Select your custom label. Enter all capitalized characters or an accepted numeric value.
5. Diagnostic & Service Menu– Allows you to perform diagnostic functions (device test and loop tests) and sensor trimming.
1 Test device– Directs you to a Status sub-menu. When accessed, it causes the THZ2 or TDZ2 to per­form a self test of its electronics. Any errors that occur are reported on the communicator.
2 Sensor Trimming– This menu allows you to view previously configured Sensor Trim Mode settings.
3 Loop Test– A loop test may be performed in order to check output performance and accuracy and to trim other instruments in the loop. Your output will be a current value, in mA, equal to the value you input. You can check the other current devices on the loop and calibrate them to this signal.
&
TDZ
2
From the menu, select whether to perform the test at 4mA (low end value), 20mA (upper end value) or at another specified value. Once you have competed your test, select End.
It will also allow you to introduce Device Variable Trim (Step 4) which allows for calibration measurement of a device variable to be adjusted linearly. You may also enable Device Variable Trim Reset (Step 5) which al- lows for the device variable to be reset to the factory trim default settings.
6. Review Menu–This is a read-only menu that pro­vides information on both Device Parameters and De- vice Information. Refer to the Review menu portion of Figure 15 for a description of the parameters included in this menu.
26 The Interface Solution Experts
Figure 16. Generic HART Communicator Menu Overview
Online Generic
1 Device Setup
2 PV
3 PV AO
4 PV LRV
5 URV
Device Setup
1 Process Variables
2 Diag/Service
3 Basic Setup
4 Detailed Setup
5 Review
Process Variable
1 Snsr
2 AI %
3 A01 Display
Diag/Service
1 Test Device
2 Loop Test
3 Calibration
4 D/A Trim
Basic Setup
1 Tag
2 PV Unit
3 Range Values
4 Device Information
5 PVXFER FNCTN
6 PV Damp
Detailed Setup
1 Sensors
2 Signal Condition
3 Output Condition
4 Device Information
Calibration
1 Apply Values
2 Enter Values
Range Values
1 PVLRV
2 URV
3 PVLSL
4 USL
Device Information
1 Distributor
2 Model
3 Dev ID
4 Tag
5 Date
Sensors
1 PV
2 PV SNSR
3 Sensor Information
Signal Condition
1 SNSR DAMP
2 URV
3 AI LRV
4 AI XFER FNCTN
5 AI % Range
Output Condition
1 Analog Output
2 HART Output
Analog Output
1 AO1
2 AO Alrm Trip
3 Loop Test
4 D/A Trim
5 Scaled D/A Trim
HART Output
1 Poll addr
2 Num req preams
3 Burst mode
4 Burst option
Key
AI % = % of Analog Input AO = Analog Output Damp = Damping Value Dev ID = Device Identification Diag = Diagnostic D/A Trim = Trim Digital/Analog LRV = Lower Range Value LSL = Lower Sensor Level Num req preams = Number of Preamble Characters Poll addr = Polling Address PV = Process Variable SNSR = Sensor URV = Upper Range Value USL = Upper Sensor Level XFER FNCTN = Transfer Function
Enter Values
1 PVLRV
2 URV
3 PVUSL
4 PVLSL
1
2
3
4
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
The Interface Solution Experts 27
+
+
+
HART-Based
DCS
(Primary Master)
HART Communicator (HART Secondary Master)
THZ
(HART
Slave)
THZ
(HART
Slave)
TDZ
(HART
Slave)
1234
+PS–PS
THZ
SMART HART TEMPERATURE TRANSMITTER
+PS
-PS12
34
TDZ
0
602.78
DE G C
2
2
2
2
2
ADDR
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
The HART Communicator Menu Without a Device Description
This section contains the instructions for program­ming a THZ2 and TDZ2 using a HART communicator without a Device Description. If your communicator has a Device Description, please see The HART Com- municator Menu with a Device Description section of this manual.
1. Online Generic– The initial screen, the Online Ge- neric menu, displays the process value, analog output
and the programmed upper and lower parameters of the process value. The generic HART Communicator overview menu (Figure 16) shows the screen. Use the Device Setup menu for configuring your THZ2 and TDZ2.
2. Basic Setup– The Basic Setup menu allows you to enter a name for an individual transmitter, the units of measurement, the upper and lower range and sensor values, and a damping time between 0sec and 30sec.
3. Analog Output– The Analog Output menu displays the analog output, changes the loop current to a fixed value so that it can be checked against the value be­ing received and displayed by your receiving device, and enters and trims the sensor.
4. HART Output– From the HART Output menu, you can enter the polling address and display the number of preamble characters sent by the master to the slave to ensure synchronization.
If the polling address is set to 0, the THZ2 and TDZ2 is automatically set to analog mode. Multiple units on the same bus must have different addresses.
Figure 17. Connecting the THZ2 or TDZ2 in Multidrop Configuration
28 The Interface Solution Experts
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
HART Status Information
Each time the THZ2 and TDZ2 generate a response, frame status information is included in the reply mes­sage. The first byte indicates communications errors, if any. Otherwise, if communication was good, this byte may indicate the status of the received command (such as transmitter busy or a command not support- ed). The second status byte indicates the operational state of the slave device. A properly operating slave device will have both status bytes set to logic zero.
The following tables include the common information
Table 6. Communications Errors
Bit 7 = 1
Bit
Undefined
0
Buffer Overflow
1
Reserved set to zero
2
Checksum Error
3
Framing Error
4
Overrun Error
5
Parity Error
6
This bit is always set when Communication errors occur
7
that is returned in every response message. However, they do not detail the transmitter-specific Additional Status Information that is returned in the data portion of the response to HART Command 48. You may ac- cess the Additional Status Information window via the View dropdown menu in the tool bar.
Description
Table 7. Command Errors
Bit 7 = 0
Value
0
1
2
3
4
5
6
18
32
64
Hex
0x00
0x01
0x02
0x03
0x04
0x05
0x06
0x12
0x20
0x40
Description
No command Errors
Undefined Error
Invalid selection
Passed Parameter too large
Passed Parameter too small
Too Few bytes received
Transmitter Specific Command Error
Invalid UOM Code
Transmitter Busy
Command not supported
The Interface Solution Experts 29
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Table 8. Device Status Bytes Table
Bit
0
1
2
3
4
5
6
7
Type
Error
Error
Error
Error
Error
Error
Error
Error
Primary Variable Out of Limits. The process applied to the sensor for the Primary Variable is beyond the operating limits of the device.
Non-Primary Variable Out of Limits. The process applied to a sensor, other than that of the Primary Variable, is beyond the operating limits of the device. Command #48, Additional Status Information, may be requried to identify the variable.
Analog Output Saturated. The analog and digital outputs for the Primary Variable are beyond their limits and no longer represent the true applied process.
Analog Output Current Fixed. The analog and digital outputs for the Primary Variable are held at the requested value. They will not respond to the applied process.
Additional Status Available. More status information is available than can be returned in the Field Device Status. Command #48, Additional Status Information may be required to identify the variable.
Cold Start. Power has been removed and reapplied resulting in the reinstallation of the setup information. The first command to recognize this condition will automatically reset this flag. This flag may also be set following a Master Reset or a Self Test.
Configuration Changed. A write or set command has been executed.
Device Malfunction. A hardware error or failure has been detected by the device. Further information may be available through Command #48, Additional Status Information.
TDZ2 Displayed Error
Description
Messages
The TDZ2 will need to be sent back to Factory for repair is any of the messages shown in Table 9. are displayed.
Table 9. Process Variable Error Displayed Messages
Error Condition
Hardware failure
EEPROM failure
Calibration data bad
Configuration or calibration data checksum mismatch
EEPROM blank
Process variable out of range (< -99999 or > +99999)
Maths division by zero error
Configuration information bad
Software watchdog failure
RJC Broken
Input saturation condition
Front-end comms error condition
Other or combination of errors
ERROR HWARE
ERROR EEROM
ERROR CALIB
ERROR CKSUM
ERROR BLANK
ERROR RANGE
ERROR DZERO
ERROR CONFG
ERROR SWARE
RJC BROKE
ERROR INSAT
ERROR F END
ERROR
Displayed Message
30 The Interface Solution Experts
HART Command 48
The Additional Status Information section in the View dropdown menu returns five additional HARTstatus information bytes in response to HART Command 48–
Read Additional HART Status Information.
The five data bytes are described in Table 10.
Table 10. HART Command 48 Data Bytes
Status Byte
0
1
2
3 4 5
Status
Word Bit
0 1 2
3 4
5 6
7
0
1
2 3
4 5
6
7
0 1 2
3 4-7
0-7 0-7 0-7
Type
Error Error Error
Error Error
Error Error
Error
Error
Error
Error
Status
Status Status
Status
Error
Error Error Error
Error Not used Not used
Not used Not used
Configuration data error Calibration data error
EEPROM blank
EEPROM failure Division by zero error
RJC Broken Software watchdog failure
COP watchdog failure
Sensor wire 1 broken
Sensor wire 2 broken
Sensor wire 3 broken Sensor wires broken
Table Out of Range A-D Saturation
Busy / Calibration, trimming active Configuration data area checksum error
Calibration data area checksum error ADC Error Bad custom curve Front-end / Back-end communications failure Set to zero
Set to zero Set to zero Set to zero
Description
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
The Interface Solution Experts 31
THZ
2
&
TDZ
2
Programmable Smart HART Temperature Transmitter and Display
Installation
Installation consists of physically mounting the unit and completing the electrical connections.
Mounting the THZ2 or TDZ
The THZ2 HPP fits inside a 30-35mm connection head (such as the LH1) using captive mounting screws. The THZ DIN2 can be mounted on standard DIN mounting rails. The TDZ2 HP can be mounted with rails, flanges, or in one of our larger housings, such as the D-BOX or BH.
Making the Electrical Connections
The connections for the various inputs are shown in Figures 7 and 8. The figure shows a single transmitter. If you are using multiple units, connect them using the connections shown in Figure 17.
In multi-drop networks, the unit’s receiving device is normally a HART-communicating control system acting as the HART Primary Master. The control system uses each transmitter’s individual address to access real-time process data, sensor diagnostics and THZ2 or TDZ2 diagnostic data. The address is also used to locate the appropriate unit, to initiate configuration and to calibrate. A HART communicator, acting as the HART Secondary Master, can be used to simultaneously access information from, or transmit configuration information to the transmitter from anywhere along the HART digital link.
Make sure that the total loop resistance is at least 250 ohms so that the 4-20mA signal containing the HART protocol is not shorted. If loop resistance is less than 250 ohms, add a resistor.
2
Recommended Ground Wiring Practices
Moore Industries recommends the following ground wiring practices:
• AnyMooreIndustriesproductinametalcaseor
housing should be grounded.
• Theprotectiveearthconductormustbeconnected
to a system safety earth ground before making other connections.
• Allinputsignalsto,andoutputsignalsfrom,
Moore Industries’ products should be wired using a shielded, twisted pair wiring technique. Shields should be connected to an earth or safety ground.
• Forthebestshielding,theshieldshouldberun
all the way from the signal source to the receiving device. (see Note below)
• Themaximumlengthofunshieldedinputand
output signal wiring should be 2 inches.
Note:
Some of Moore Industries’ instruments can be
classified as receivers (IPT 2, IPX 2, etc.) and some
can be classified as transmitters (TRX, TRY, etc.)
while some are both a receiver and a transmitter
(SPA 2, HIM, etc). Hence, your shield ground
connections should be appropriate for the type
of signal line being shielded. The shield should
be grounded at the receiver and not at the signal
source.
Switches and Circuit Breakers
A switch or circuit breaker must be wired in series with the AC power conductors. The switch or circuit breaker used must be located within three meters of the unit.
WARNING:
Terminals on this unit may be connected to
hazardous voltages. Before making ANY
connections to this unit, ALL hazardous voltages
must be de-energized.
32 The Interface Solution Experts
The circuit breaker or switch will only remove power to the unit, hazardous voltages may still be connected to other terminals on the unit.
Installation Category
All of Moore Industries’ terminals are rated CAT II, except those with the -RF option. These terminals are rated CAT I.
Equipment Ratings
The THZ2 and TDZ2 do not generate hazardous volt­ages, rather, they accommodate a temperature input, and generate a low voltage current output. Products connected to the THZ2 or TDZ2 should be designed to receive these inputs.
Supply Wiring
All power connections should be made with the proper wire.
The end of each conductor should be stripped no more than 8mm (0.31 in). The end of the stripped wire should be tinned with solder, or inserted into a ferrule and crimped before being placed into a terminal block.
Conductors connected to screw-type connections should have a ring-lug or spade-lug crimped onto the wire end.
2
THZ
Programmable Smart HART
Temperature Transmitter and Display
&
TDZ
2
CE Conformity
Installation of any Moore Industries’ products that carry the CE marking must adhere to the guidelines in the Recommended Ground Wiring Practices section in order to meet the EN 61326 requirements set forth in the applicable EMC directive.
The Interface Solution Experts 33
2
THZ
Programmable Smart HART Temperature Transmitter and Display
&
TDZ
2
Installation in Hazardous Locations’
This page contains information for the THZ2 and TDZ2 instruments when used within an intrinsically-safe system.
The diagram on the following page must be used for units that are to operate in areas requiring intrinsically­safe instrumentation.
Refer to the Special Conditions outlined below before proceeding with installation.
Special Conditions of Use
The following instructions must be adhered to when the THZ2 and TDZ2 are used in hazardous ‘Classified’ locations and potentially explosive atmospheres.
I. Intrinsically Safe (Ex ia) Applications (Zones 0 and 1)
1. The Models THZ2 and TDZ2 Temperature Transmitters shall be installed in a final enclosure rated for a minimum of IP20.
Safety Concerns
For your safety, read the following information carefully before proceeding with installation.
WARNING: EXPLOSION HAZARD – FOR
DIVISION 2 HAZARDOUS LOCATIONS. DO
NOT DISCONNECT EQUIPMENT WHEN A
FLAMMABLE ATMOSPHERE IS PRESENT.
WARNING: SUBSTITUTION OF COMPONENTS
IS NOT ALLOWED AS IT MAY IMPAIR THE
INTRINSIC SAFETY (ZONES 0 & 1, DIVISION 1)
OF THE UNIT AND/OR THE NON-INCENDIVE/
TYPE N (DIVISION 2, ZONE 2) CIRCUIT. DO NOT
OPEN THE UNIT WHEN EITHER ENERGIZED OR
WHEN AN EXPLOSIVE GAS/DUST ATMOSPHERE
IS PRESENT. DISCONNECT POWER BEFORE
SERVICING. READ AND UNDERSTAND THE
MANUFACTURER’S INSTALLATION AND
OPERATING PROCEDURES, AND ADHERE TO
ALL APPLICABLE ELECTRICAL CODES, SAFETY
INSTRUCTIONS AND REGULATIONS.
AVERTISSEMENT – RISQUE D’EXPLOSION. NE PAS DEBRANCHER TANT QUE LE CIRCUIT EST
SOUS TENSION, A MOINS QU’IL NE S’ AGISSE
D’UN EMPLACEMENT NON DANGEREUX.
2. For Zone 0 installations, the final enclosure shall not contain more than 10% in total of aluminum, magnesium, titanium and zirconium, or 7.5% in total of magnesium, titanium and zirconium.
3. For Zone 1 installations, the final enclosure shall not contain 7.5% in total of magnesium.
4. Wiring must be rated for 85°C.
II. Type N (Ex n) Applications (Zone 2)
1. As Category 3 equipment, the Models THZ2 and TDZ2 Temperature Transmitters shall be installed in an enclosure which maintains an ingress protection of IP54 and meets the enclosure requirements of EN60079-0 and EN60079-15.
2. The Models THZ2 & TDZ2 Temperature Transmitters shall contain external transient protection to prevent the supply voltage from exceeding 46.2V including tolerance.
3. Wiring must be rated for 85°C.
WARNING: END-USER MUST MARK EITHER
CHECKER BOX ON THE INSTRUMENT ID
LABEL WITH THE INTENDED APPLICATION
– INTRINSICALLY SAFE OR TYPE N / NON-
INCENDIVE.
34 The Interface Solution Experts
THZ
2
&
TDZ
2
Programmable Smart HART
Temperature Transmitter and Display
Operation
Once programmed, calibrated, installed and supplied with the correct power, THZ2 and TDZ2 transmitters begin to operate immediately. Depending upon envi­ronmental conditions, they can be expected to operate unattended for extended periods of time.
HART Protocol
This section of the manual gives an overview of the HART format used by THZ2 and TDZ2 modules dur­ing operation. Use the information in this section to process the data provided by the module(s) during op­eration. For more information on the HART protocol, contact the HART Foundation at:
HART Communication Foundation 9390 Research Blvd., Suite I-350 Austin, TX 78759-6540 USA Phone: (512) 794-0369 Fax: (512) 794-3904 www.hartcomm.org
Device Types
To implement two-way communication between the THZ2 and the device being used to configure it or re­ceive its information, the THZ2 and TDZ2 operate in a HART Master/Slave structure. The THZ2 or TDZ2 is the Slave (or slaves in a multidrop network).
There can be two Masters per system: a Primary Master and a Secondary Master. Masters are typically either a HART Hand-Held Communicator or a HART­based control system.
Communication Speed and Format
The speed of the HART transmission is 1200 bps. The time delay between a master initiating a request for data from a slave and the slave receiving and ac­knowledging the request depends upon which com­mand is issued. Generally, a master can poll a slave 2-3 times per second.
The byte structure of the HART signal is:
1 Start Bit, 8 Data Bits, 1 Odd Parity Bit, 1 Stop Bit.
Maintenance
Moore Industries suggests a quick check for termi­nal tightness and general unit condition every 6-8 months. Always adhere to any site requirements for programmed maintenance.
Customer Support
If service assistance is ever required for an device in your application, refer to the back cover of this manual for the telephone numbers to Moore Industries’ cus­tomer service department.
If possible, make a note of the model number of the unit before calling. For fastest assistance, have the following information available: serial number, the job number and purchase order number under which it was shipped
In many applications, the Primary Master is a HART Hand-Held Communicator. The communicator is used solely as a configuration tool to set up the transmitter, periodically view its real-time process measurement, or view its operating and diagnostic information from a loop termination point.
Digital Signal
One of the advantages of the HART protocol is that the digital information is conveyed by the same wires used to output the 4-20mA signal. After being polled by the master, the THZ2 or TDZ2 responds to the in­quiry by modulating the 4-20mA current 0.5mA above or below the output signal. 1200 Hz represents 1 and 2200 Hz represents 0.
The Interface Solution Experts 35
Field Installation Diagram:
TDZ2 [HP] & THZ2 [HPP]
Intrinsically Safe System
For Hazardous 'Classified' Locations
100-100-71 A
CONTROL DRAWING
INITIAL RELEASE
CATEGORY
TITLE
DRAWING NUMBER
REVISED BY DATE BY APPROVAL
REVISION
DECIMALS.X.XX
.XXX
HOLES:
=+.003-.002/+.08-.05
ANGLES:
NOTICE RE PROPRIETARY INFORMATION: This drawing and the inform-
ation contained herein are the proprietary property of Moore Industries-
International, Inc. (MII) and should not be reproduced or disclosed to any
third party without the written consent of an authorized officer of MII.
DRAWN
CHECKED
ENGINEER
SCALE
DO NOT SCALE DRAWING
TOLERANCES
(UNLESS NOTED)
= ±inch
= ±.1
= ±.03
= ±.010
= ± 30'
/mm
/2.54
/0.76
/0.25
NONE
06/07
Gus H. Elias
S.K.
CB
06/07
06/07
06/07 G.E.
Gus H. Elias
CERTIFIED PRODUCT
This is a controlled 'Related' or 'Schedule'
drawing. No modifications are permitted
without the notification and final approval
of the Certification Engineer (related dwgs.)
or the Certifying Agency (schedule dwgs.).
(1)- Apparatus which is unspecified except that it must not be supplied from, or contain under normal or abnormal conditions a source of potential with respect to earth in excess of 250 VRMS or 250 VDC
which is considered to be the Safe Area's maximum voltage.
(2)- The Barrier or other Associated Apparatus must be agency-approved (CSA/FM/SAA/SIRA/UL, etc..) per the "specific" installation area for Intrinsically Safe connections (Zones 0/1, Class I / Div. 1).
US barriers for USA, Canadian barriers for Canada, ATEX bariers for Europe, IECEx barriers where applicable. The output voltage (Voc, Vt or Vo) must not
exceed 30 VDC & the output
current (Isc, It or Io) must not
exceed 110 mA. Also, it must be installed per the manufacturer's guidelines. A Shunt Zener Barrier is NOT required for Non-Incendive / Type N installations.
(3)- The combined Capacitance and Inductance of the inter-connecting cables of the device (hazardous area) must not
exceed the values indicated on the Associated Apparatus (safe area).
4- For US applications, installation must
be in accordance to 'ANSI-P12.6' (Installation of I.S. Systems for Hazardous 'Classified' Locations) and the National Electric Code 'ANSI/NFPA 70'. Also, a
dust-tight conduit seal must
be used when installed in Class II and Class III environments. For applications in Canada, adhere to the 'Canadian Electric Code C22.1' most current publication on I.S.
installationguidelines. For CENELEC/ATEX and IECEx applications, adhere to 'EN 60079-14:1997' or any equivalent IEC-based, most current and pertaining publication on I.S. installation guidelines.
5- Warning:
Substitution of components is NOT allowed as it may impair the Intrinsic Safety of the unit and/or the Non-Incendive circuit. DO NOT open the unit when either energized or if an explosive
gas/dust atmosphere is present. Disconnect power before servicing. Also read, understand and adhere to the manufacturer's installation and operating procedures.
6- The maximum power parameters of the COM port (to be used only in safe/non-hazardous areas) are: V
max
= 3.0 VDC, I
max
= 300 µA, P
max
= 240 µW.
Notes:
Barrier or other
Associated
Apparatus
Unspecified
Apparatus
(1)
Non-Hazardous (Safe) Area
Ground Path
Resistance Must
Not Exceed 1
(2)
Sensor Type - mA, mV,
POT, RTD,
, T/C:
V
oc
or V
t
= 6.51 VDC
I
sc
or I
t
= 35.39 mA
P
o
= 57.6 mW
C
a
or C
o
= 20 µF, Gr. A/B
C
a
or C
o
= 498 µF, Gr. C/D
C
a
or C
o
= 998 µF, Gr. D
L
a
or L
o
= 25 mH, Gr. A/B
L
a
or L
o
= 100 mH, Gr. C/D
L
a
or L
o
= 200 mH, Gr. D
Barrier-to-Xmitter Cable:
3,575 ft, 214.5 nF, Gr. A/B
103,166 ft, 6.19 µF, Gr. C/D
423,166 ft, 25.39 µF, Gr. D
+PS –PS 1 3
TDZ2
COM
{ }
= 30 VDC
= 110 mA
= 0.825 W
= 5.83 nF
= 0 H
C
i
+ C
cable
L
i
+ L
cable
V
oc
or V
t
I
sc
or I
t
I.S. Entity Parameters
(Power/Loop, +PS & -PS):
V
max
or
U
i
I
max
or
I
i
P
max
or
P
i
C
i
L
i
C
a
or
C
o
L
a
or
L
o
V
max
or
U
i
I
max
or
I
i
Input device must be"Agency-Approved" per
application area (CSA, FM, ISSeP, KEMA,
LCIE, UL, TestSafe, SIRA, TUV, etc....).
+PS
-PS
(3)
TDZ2 [HP]: 4-20 mA PC-Programmable Smart
HART Temperature Transmitter w/ Display
+PS -PS
COM
THZ2 [HPP]: 4-20mA PC-Programmable
Smart HART Temperature Transmitter
4
3
2
1
1
2
3
4
Caution: The 'COM' Port Must Not Be Used In Hazardous 'Classified' Locations.
THZ2
0518
IECEx
Hazardous 'Classified' Locations/Areas
US (NEC 500/505) / Canada (C22.2-1010.1)
Intrinsically Safe & Non-Incendive
Class I, Zone 0, AEx ia IIC, (T4 / T5 / T6)*
Class I; Divisions 1 & 2; Groups A-D
ATEX: II 1G Ex ia IIC, II 3G Ex nA IIC, (T4 / T5 / T6)*
*T. Codes: T4@85°C (TDZ2
), T5@85°C/T6@60°C (THZ2)
Operating Temperature Range:-40°C Tamb. +85°C
For areas classified with "dust-hazard" (Class II/III, Division 1,
Groups E, F & G), these devices must be mounted in approved
protective enclosures that are rated and suitable for use in the
designated application areas. Use +85°C rated electrical wire.
IECEx: Ex ia IIC, Ex nA IIC, (T4 / T5/ T6)*
Refer to the Safety Concerns section on the previous page before continuing with installation.
CATEGORY
TITLE
DRAWING NUMBER
REVISED BY DATE BY APPROVAL
REVISION
DECIMALS.X.XX
.XXX
HOLES:
=+.003-.002/+.08-.05
ANGLES:
NOTICE RE PROPRIETARY INFORMATION: This drawing and the information
contained herein are the proprietary property of Moore Industries-International,
Inc. (MII) and should not be reproduced or disclosed to any third party without
the written consent of an authorized officer of MII.
DRAWN
CHECKED
ENGINEER
SCALE
DO NOT SCALE DRAWING
TOLERANCES
(UNLESS NOTED)
= ±inch
= ±.1
= ±.03
= ±.010
= ± 30'
/mm
/2.54
/0.76
/0.25
NOTES:
1. TO PRINT THIS LABEL: JOB SPECIFIC MODEL, SERIAL, YEAR AND TAG NUMBERS
WILL BE DOWNLOADED FROM THE MENTOR DATA FILE AND PRINTED ALONG
WITH THE FIXED TEXT AND GRAPHICS (SUPPLIED BY THE LEGI 93 DATA FILE)
TO CREATE THE FINISHED LABEL.
2. THE FIXED TEXT AND GRAPHIC FIELDS FOR THIS LABEL ARE STORED UNDER
NO. 200-251-2207 IN THE LEGI 93 LABEL MACHINE COMPUTER HARD DISK.
3. MATERIAL: .002 SILVER, IDENTIPLATE (MII P/N 200-301-00) DIE CUT AS SHOWN
ABOVE. REFER TO LABEL SPEC. DRAWING 200-301-00.
COMPUTERIZED LABEL
200-251-2207
A
1/1
Gus H. Elias
INITIAL RELEASE
REAR ID LABEL
TDZ2 [HP]: 4-20mA HART Temp. X-mitter
Intrinsically Safe: 12-30Vdc
Gen. Loc., N.I., Type N: 12-42Vdc
ATEX, cFMus, IECEx.
06/07
06/07
Gus H. Elias
S.K.
06/07
G.E.
CB
06/07
CERTIFIED PRODUCT
This is a controlled 'Related' or 'Schedule'
drawing. No modifications are permitted
without the notification and approval of
the Certification Engineer (related dwgs.)
or the Certifying Agency (schedule dwgs.).
1.712
REF
1.532
REF
0.052 R.
REF
MODEL:
SERIAL: YEAR:
FM06ATEX0011X,FM06ATEX0030X,FMG07.0002X:
4-20mA: I.S. (12-30dc)*, N.I./TypeN (12-42dc)
Class I, Zone 0, AEx ia IIC, T4@85°C.
Class I, Divisions 1 & 2, Groups A-D.
II 1G Ex ia IIC T4 / II 3G Ex nA IIC T4.
Ex ia IIC T4 / Ex nA IIC T4. Use 85°C rated wire.
*Explosion Hazard: install per IS Dwg. 100-100-71.
Do not disconnect in hazardous locations. -2207A
0518
CA 91343 U.S.A.
TAG:
End-user must mark the checker box
with the intended application:
Intrinsically Safe or
Type N / Non-Incendive.
CATEGORY
TITLE
DRAWING NUMBER
REVISED BY DATE BY APPROVAL
REVISION
DECIMALS.X.XX
.XXX
HOLES:
=+.003-.002/+.08-.05
ANGLES:
NOTICE RE PROPRIETARY INFORMATION: This drawing and the information
contained herein are the proprietary property of Moore Industries-International,
Inc. (MII) and should not be reproduced or disclosed to any third party without
the written consent of an authorized officer of MII.
DRAWN
CHECKED
ENGINEER
SCALE
DO NOT SCALE DRAWING
TOLERANCES
(UNLESS NOTED)
= ±inch
= ±.1
= ±.03
= ±.010
= ± 30'
/mm
/2.54
/0.76
/0.25
NOTES:
1. TO PRINT THIS LABEL: JOB SPECIFIC MODEL, SERIAL, AND TAG NUMBERS WILL BE DOWNLOADED FROM THE MENTOR
DATA FILE AND PRINTED ALONG WITH THE FIXED TEXT AND GRAPHICS (SUPPLIED BY THE LEGI 93 DATA FILE) TO
CREATE THE FINISHED LABEL.
2. THE FIXED TEXT AND GRAPHIC FIELDS FOR THIS LABEL ARE STORED UNDER NO. 200-251-2208 IN THE LEGI 93 LABEL
MACHINE COMPUTER HARD DISK.
3. MATERIAL: .002 SILVER, IDENTIPLATE (MII P/N 200-304-00) DIE CUT AS SHOWN ABOVE. REFER TO LABEL SPEC. DRAWING
200-304-00.
COMPUTERIZED LABEL
200-251-2208 A
1/1
Gus H. Elias
INITIAL RELEASE
06/07
06/07Gus H. Elias
S.K.
06/07
G.E.
CB
06/07
CERTIFIED PRODUCT
This is a controlled 'Related' or 'Schedule'
drawing. No modifications are permitted
without the notification and final approval
of the Certification Engineer (related dwgs.)
or the Certifying Agency (schedule dwgs.).
2.250
MODEL:
SERIAL:
TAG:
-2208A
*100-100-71,**FM06ATEX0030X.
II 1G Ex ia IIC / Ex ia IIC.
II 3G Ex nA IIC / Ex nA IIC.
T6@60C/T5@85C, 4-20mA.
Class I, Zone 0, AEx ia IIC.
Class I, Div. 1 & 2, Gr. A-D.
FM06ATEX0011X/FMG07.0002X.
'Cut Line'
I.S. (12-30dc)*,N.I. (12-42dc)**:
0518
.720
ID LABEL
THZ2 [HPP]: 4-20mA HART Temp. X-mitter
Intrinsically Safe: 12-30Vdc
Gen. Loc, N.I., Type N: 12-42Vdc
ATEX, cFMus, IECEx.
CA 91343 USA
End-user must mark the checker box
with the intended application:
Intrinsically Safe or
Type N / Non-Incendive.
RETURN PROCEDURES
United States • info@miinet.com
Tel: (818) 894-7111 • FAX: (818) 891-2816
Australia • sales@mooreind.com.au
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
China • sales@mooreind.sh.cn
Tel: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair – If you are unsure if your unit is still under warranty, we can use the unit’s serial number to verify the warranty status for you over the phone. Be sure to include the RMA number on all documentation.
Non-Warranty Repair – If your unit is out of warranty, be prepared to give us a Purchase Order number when you call. In most cases, we will be able to quote you the repair costs at that time. The repair price you are quoted will be a “Not To Exceed” price, which means that the actual repair costs may be less than the quote. Be sure to include the RMA number on all documentation.
2. Provide us with the following documentation: a) A note listing the symptoms that indicate the unit needs repair b) Complete shipping information for return of the equipment after repair c) The name and phone number of the person to contact if questions arise at the factory
3. Use sufficient packing material and carefully pack the equipment in a sturdy shipping con­tainer.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries rep­resentative will contact the person designated on your documentation if more information is needed. The repaired equipment, or its replacement, will be returned to you in accordance with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WAR­RANTIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SERVICES SOLD BY THE COMPANY. THE COMPANY DIS­CLAIMS ALL WARRANTIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWLEDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IMPLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANY WAY. ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REM­EDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CON­SEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RE­CEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WARRANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOV­ERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under normal conditions of use and service, Moore Industries (“The Company”) will at its option replace, repair or refund the purchase price for any of its manufactured products found, upon return to the Company (transportation charges prepaid and otherwise in accordance with the return procedures established by The Company), to be defective in material or workmanship. This policy extends to the original Buyer only and not to Buyer’s customers or the users of Buyer’s products, unless Buyer is an engineering contractor in which case the policy shall extend to Buyer’s immediate customer only. This policy shall not apply if the product has been subject to alteration, misuse, accident, neglect or improper application, installation, or operation. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
© 2012 Moore Industries-International, Inc.
Specifications and Information subject to change without notice.
Loading...