Moore Industries DCA S, DCA H2, DCA H1, DCA D, DCA L2 User Manual

...
May 2016
DCA
Direct Current Alarm
USER’S MANUAL
No. 192-701-00 K
© 2012 by Moore Industries-International, Inc.

Table of Contents

Introduction 1
Description 1
Calibration 4
Installation 19
Maintenance 22
HR.
DELIVERY
48
United States/Canada
TOLL FREE
1-800-999-2900
United Kingdom
FREE PHONE
0800 525107
Australia
TOLL FREE
008 251928
Ask for the STAR Center
16650 Schoenborn Street Sepulveda, California 91343, U.S.A. Tel: (818) 894-7111 • Tlx: 65-1322 FAX: (818) 891-2816 CONNECT (MacNet): MIISEPULVEDA
1 Lloyds Court, Manor Royal, Crawley W. Sussex RH10-2QU, United Kingdom Tel: 0293 514488 • Tlx: 87667 FAX: 0293 536852
3/18 Resolution Drive, Caringbah New South Wales 2229, Australia Tel: (02) 525-9177 • Tlx: 790-75914 FAX: (02) 525-7296
Moore Industries’ STAR Center has a wide variety of quality instrumentation in stock and ready to ship.
• Signal Transmitters
• Temperature Transmitters
• P/I and I/P Converters
• Isolators and Converters
• Indicators and Displays
• Alarm Trips
• Integrators and Totalizers
• Power Transducers
• Instrument Power Supplies
• Racks, Rails and Enclosures
Most instruments can be customized to meet your needs. Even then, you’ll never have to wait more than a few days.
Moore Industries
CENTER
* Support, Technical Assistance, and Repair (our Quick-Ship Facility)
*
Page 1
DCA

Introduction

Moore Industries’ Direct Current Alarm (DCA) is a highly versatile, fully adjustable device that is factory­configured to accept either current or voltage input. The unit’s internal relays are tripped when input deviates from a customer-set “safe” range defined by adjustable trip points. The DCA is ideal for use in an alarm system, where it may be used to activate a warning device, or to drive an analog indicator.
This manual provides a brief description of the DCA, including its physical characteristics and options; a table of performance and operating specifications; a set of procedures for calibrating the unit; instructions for installation, including physical mounting and electrical connections; and finally, information on basic maintenance and troubleshooting.
Notes, Cautions, and Warnings are included as a means of identifying those practices that may present unnecessary inconveniences (notes), result in dam­age to the unit (cautions), or cause injury (warnings).
bination of single, dual, high, low, fail-safe, or non-fail­safe alarm relays. The following paragraphs describe each of these configurations.
High Alarm/Low Alarm. A DCA configured as a high alarm is tripped when the input increases, and reaches a customer-set trip point. A low alarm unit is tripped by a decreasing input that drops below a customer-set trip point.
Figure 1 illustrates the concept.
Fail-safe/Non-fail-safe. A fail-safe unit’s relay is energized when input is within a “safe” range, i.e. is normal, or not in an alarm condition. When the input goes into an alarm condition, reaching a trip point or losing power, the relay of a fail-safe DCA is de­energized.
Conversely, a non-fail-safe unit’s relay is de-energized when input is within the customer-specified “safe” range, and is energized when the input reaches the trip point setting.
Figure 1 also depicts the action of fail-safe relays.

Description

The DCA comes in either Moore Industries’ standard (STD) or plug-in card (PC) housing.
The STD unit can be used with a variety of mounting options, including those suitable for use with explo­sion-proof and NEMA enclosures.
PC-style DCA’s are designed for use with Moore Industries’ multi-position card racks; the surface mounted SMR, or the rack mounted RMR.
Both STD and PC DCA’s are available with either single or dual alarm configurations. The relays used are single-pole/double-throw, form C. There are a number of input ranges and alternate relay ratings available.
Operationally, the unit can be ordered with any com-
Controls and Indicators
Every type and configuration of DCA comes with potentiometers (pots) to set the alarm trip points of each installed relay. Additional pots for controlling unit dead band are available as an option, and preci­sion ten-turn vernier scales can be used instead of the standard pots.
Trip point pots afford full 0- to 100-percent adjustabil­ity over the unit’s specified span.
Each installed relay is wired to a front panel LED, which lights when the relay is energized. Depending upon the type of relay ordered, i.e. fail-safe/non-fail­safe, a lit LED can indicate either an “alarm” or a “non­alarm” input condition.
Table 1 summarizes the alarm type/LED status options for the available types of DCA.
Page 2
DCA
100 %
ANALOG
INPUT VALUE
0 %
Model Number
Designator
HIGH-ALA RM DCA
TIME
100 %
TRIP POINT DEAD BAND
RESET
FAIL-SAFE R ELAY ENERGIZED , LED ON FAIL-SAFE R ELAY DE-ENERGIZED, LED OFF
ANALOG
INPUT VALUE
0 %
LOW-ALARM DCA
RESET
DEAD BAND
TRIP POINT
TIME
Figure 1. High - and Low-alarm Relay Configurations
Table 1. DCA Alarm Types
This Unit is...
S Single Alarm - - Only one relay installed
This Unit signals an
“Alarm” condition when...
Its LED will be...
Relay(s)
D Dual Alarm - - Two relays are installed
H1 High Fail-Safe
H2 High NON-Fail-Safe
L1 Low Fail-Safe
L2 Low NON-Fail-Safe
Input increases, and exceeds
Trip Point. (See Note 2).
Input increases, and exceeds
Trip Point. (See Note 2).
Input decreases, and drops
below Trip Point
(See Note 2)
Input decreases, and drops
below Trip Point
(See Note 2)
OFF in alarm
ON in Non-alarm
ON in Alarm,
OFF in Non-alarm
OFF in alarm
ON in Non-alarm
ON in Alarm,
OFF in Non-alarm
DE-energized in alarm
Energized in Non-alarm
Energized in Alarm,
DE-energized in Non-alarm
DE-energized in alarm
Energized in Non-alarm
Energized in Alarm,
DE-energized in Non-alarm
NOTES: 1. Older DCA’s may use X1 for H1, X2 for H2, X3 for L1, and X4 for L2.
2. The “UPPER” and “LOWER” labeling on the DCA front panel is for reference only. Configurations where “LOWER” terminals and pots pertain to the unit’s high alarm, for example, are quite possible.
3. Relays in fail-safe alarms are DE-energized in the event of power loss to the unit.
Page 3
DCA
Table 2 lists the performance and operational specifi­cations for the unit.

Table 2. DCA Performance and Operational Specifications

Characteristic
Input
Output
Specifications
Current: 1-5 mA @ 200 nominal input impedance
4-20 mA @ 50 nominal input impedance 10-50 mA @ 20 nominal input impedance Selectable Current (SC) comes with three load resistors for selecting1-5, 4-20, or 10-50 mA (See Note 1)
Voltage: 0.25-1.25 V @ 1MΩ, minimum (See Note 2)
1-5 V @ 1M, minimum
Consult factory for dual input and special range options.
Factory-configured with one (Single DCA) or two (Dual DCA) single pole/double throw (SPDT), form C, mechanical relays rated for 5 A @ 117 Vac non-inductive, or 28 Vdc.
User selects Normally Open (NO), Normally Closed (NC), or any combination of NO/NC configurations during installation. Fail-safe/Non-fail-safe configuration factory-set. Refer to table 1 for available combinations.
Options
Each DCA is configured according to customer requirements. The paragraphs on the following pages highlight some of the options available.
Power
Performance
Environmental
Ratings
NOTES: 1. One of the available resistors MUST be installed.
2. Requires extra engineering when used with some option combinations.
3. DPDT not available with some enclosures and option combinations.
Double pole/double throw (DPDT), form 2C and 7.5 A relays available as options. (See Note 3)
24 or 45 Vdc ±10%, 5 watts nominal 100, 117, 200, 220, or 240 Vac ±10%, 50/60 Hz AC power inputs not available with PC-style housing
Repeatability: Trip point settings repeat within ±0.1% of span. Dead Band: 1% of span, standard. Adjustable Dead Band Option available. Alarm Response: 50 milliseconds for step change of 1% of span. Line Voltage Effect: ±0.005% per 1% line voltage change (ac or dc). Isolation: No galvanic path between input, output, and power. Accuracy: Front panel potentiometers capable of setting trip points from 0 to 100% of
span. Lockable, scaled vernier dials optional. Effect of Ambient Temperature on Performance: Less than ±0.018% per °C through the specified range (Less than ±0.01% per °F)
Ambient Operating Temperature: –18 to 65 °C (0 to 150 °F)
Page 4
DCA
For a complete list of available options, and for information on other housings, mounting hardware, and enclosures, contact your Moore Industries Sales Representative.
AD Option —
Front panel potentiometers vary dead band 1- to 20­percent of span (nominal), 1- to 50-percent of span (AD50), or 1- to 100-percent (AD100) of span. (AD Option not available with some option combinations).
AR Option —
factory for output delays of 1 to 5, 10, 15, 20, 25, or 30 seconds, according to customer specification.
DA Option —
condition when the difference between two inputs exceeds adjustable percent of full span. Requires DI Option or 2X input. (Not available with some option combinations.)
DI Option —
to operate as two, single-alarm units. Standard DI unit provides a high alarm for one input and a low alarm for the other. (DI Option not available with some option combinations).
DPDT Option —
Relays. Contact 5 amps at 28 Vdc, or 117 Vac non­inductive. (DPDT Option not available with some option combinations).
Externally-adjustable Dead Band.
Response Time Delay. Set by the
Deviation Input. Unit signals alarm
Dual Input. Configures dual-alarm DCA
Double Pole, Double Throw/Form 2C
TX Option
at 30 Vdc @ 25 mA.
7.5A Option —
UL at 7.5 amps, 28 Vdc or 120 Vac.
Model/Serial Number. Moore Industries uses a system of unit model and serial numbers to keep track of factory configuration and options for each DCA shipped and serviced.
The example outlines the significance of each field of information in a typical DCA model number. Refer to table 1 for an explanation of the relay configuration codes used.
If service information or assistance for a DCA is needed, make a note of the unit’s model and serial number before contacting Moore Industries’ Customer Service Department. Our highly skilled technicians will be happy to assist you.
STD units’ serial and model numbers are located on an L-shaped metal tag at the top of the connection terminal strips. On PC DCA’s, the numbers are located on an adhesive label affixed to the side of the front panel.
— Two-wire Transmitter Excitation. Rated
7.5 amp Relay(s). Rated by CSA and

Calibration

FU Option
PC-style unit. Use of the FU Option with the STD housing requires special engineering.
HS Option
@ 117 Vac non-inductive, 2A @ 28 Vdc. Meets requirements for installation in Class I, Division 2 locations.
MR Option —
button for single- and dual-alarm units. In place of dead band, MR-equipped units return to normal only when the process input returns to non-alarm state the external reset push button is pressed.
TT Option —
multiturn potentiometers for setting and locking trip points. Includes front panel ZERO potentiometer for appropriate offsets.
— Power Fuse. 400 mA rated fuse on
— Hermetically Sealed Relays. Rated 1A
Manual Reset. External reset push
and
Lockable Vernier Dial. Front panel,
Every DCA shipped from the factory is manufactured and tested according to Moore Industries’ exacting standards for product quality. A bench check of basic unit operations is recommended, however, in order to identify any damage to the unit that may have oc­curred during shipping. This also allows the user to effect operational adjustments to trip point settings and unit dead band, if available.
It is recommended that the procedures in this section be carried out at a technician’s bench or in a similar lab environment. This is the safest means of making adjustments to trip point values; isolated from the intended DCA application.
The calibration of the DCA consists basically of setting trip points and dead bands based on the resistance across the unit contact-closure terminals as measured by an ohmmeter. With relay contacts closed, resistance is negligible. With relay contacts open, resistance is infinite.
EXAMPLE
Unit Type
Input
Relay Configuration
Power
Options(s)
Housing
Page 5
DCA
DCA / 4-20MA / DH1L1 / 117AC / -AD [STD]
Basic Calibration Setup
The equipment listed in table 3 is needed for calibrat­ing the DCA. These items are not supplied with the unit, but should be available in most testing labs.
Table 3. DCA Calibration Equipment
Equipment Specifications
Voltage
Voltage or
Current Source
Current Source
Power Source
Ohmmeter Accuracy of ±1%, minimum.
Screwdriver Slotted-tip with head width no greater than 2.54 mm (0.01 in).
Wire Jumpers
(required for
AR-equipped
DCA’s ONLY)
or
Calibrated, adjustable unit, capable of output at discrete levels in the appropriate range, with the rated impedance for the unit being calibrated. EDC Models MV105, MV155, or equivalent.
AC or dc power input appropriate for the type of DCA being calibrated. Refer to table 2, earlier in this manual.
Temporary jumper wiring suitable for shorting AR Option diodes so that the alarm delay may be defeated while adjusting the unit’s trip point settings.
Be sure to use calibrated test equipment when performing the bench check and calibration of the DCA. The use of inaccurate test equipment may result in unreliable settings for the unit’s trip point(s), etc.
Extender Card
(optional for use
with PC-style
DCA’s ONLY)
Moore Industries’ part number 350-513-00.
Page 6
DCA
Setup for the STD DCA. Figure 2 shows the labeling used on the front panel of the STD DCA. Figure 3 shows the terminals on a unit equipped with DPDT relays.
CDC URRENT
DCA
UPPER RELAY NORM ALLY
OPEN — UNO
COMMON — COM
UPPER RELAY NORM ALLY
CLOSED — UNC
ALARM
UPPER LOWER
ZERO
U PPER
D EADBAN D
LOWER
To access the connection terminals for a DCA in the basic extruded housing (STD, AB, etc.), use a screw driver to remove the securing screw from the protec­tive plastic cover on the unit front panel. With the screw removed, the cover can be removed by hand, revealing the terminals and the labels depicted in the illustrations in this manual.
LNO — LOW ER R ELAY N ORM ALLY OPEN
COM — COMMON
LNC — LOWER RELAY NORMALLY CLOSED
ACC — –DC
AC — +DC
GND
NOTES: 1. Each uni t i s factor y- configured for ac or dc pow er .
2. Each unit is factor y-c onfi gur ed for specifi c cur r ent or voltage input.
Figure 2. STD DCA Terminal Locations
OPTION — +TX FOR TRANSMITTER EXCITATION, +REF FOR D EVIATION ALARM
+IN — CURRENT OR VOLTAGE +INPUT
-IN — CURRENT OR VOLTAGE -INPUT
UPPER RELAY #1 NOR MALLY
OPEN — UNO1
COMMON — COM
UPPER RELAY #1 NOR MALLY
CLOSED — UNC1
ACC — –DC
AC — +DC
GND
DC CURRENT
DCA
ALARM
UPPER LOWER
ZERO
U PPER
D EADBAN D
LOWER
Page 7
DCA
UN O2 — UPPER RELAY #2 NORM ALLY OPEN
COM — COMMON
UNO2 — UPPER RELAY #2 NORMALLY CLOSED
LNO1 — LOWER RELAY #1 NORMALLY OPEN
COM — COMMON
LNC1 — LOWER RELAY #1 NORMALLY CLOSED
LNO2 — LOWER RELAY #2 NORMALLY OPEN
COM — COMMON
LNC2 — LOWER RELAY #2 NORMALLY CLOSED
OPTION — +TX FOR TRANSMITTER EXCITATION, +R EF FOR D EVIATION ALARM
Figure 3. STD DCA w/DPDT Option Terminal Locations
Figure 4 shows the labeling for a STD DCA equipped with the DI Option. Note that both inputs share the “– IN” terminal.
+IN — CURRENT OR VOLTAGE +INPUT
-IN — CURRENT OR VOLTAGE -INPUT
WARNING
To guard against accidental electric
shock, it is recommended that the protec-
tive plastic cover be re-installed over the
terminal strip of the STD DCA before
applying power to the calibration setup.
Loading...
+ 19 hidden pages