PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Introduction
This is the users’ manual for the Moore Industries
CPA PC-Programmable Alarm (TPRG: RTD, T/C,
mV, Ohms and Potentiometer Limit Alarm Trips). It
contains all of the information needed to confi gure,
install, operate, and maintain this instrument.
About this Manual
Wherever you see a “ Note”, “ Caution”, or “ WARNING
” pay particular attention.
WARNING - Hazardous procedure or condition that
could injure the operator.
Caution - Hazardous procedure or condition that could
damage or destroy the unit.
Note - Information that is helpful for a procedure,
condition, or operation of the unit.
The CPA
The CPA (TPRG) is a PC-Programmable, userconfi gurable alarm. The instrument includes two
alarm (relay) outputs and an optional analog output.
The alarms can be confi gured as trip or fault alarms.
Figure 1. The CPA (TPRG)
The CPA has a READY LED to indicate the health of
the unit, an INPUT LED to indicate the status of the
input and a dual color LED, per relay, to indicate alarm
status.
Model and Serial Numbers
Moore Industries uses a system of model and serial
numbers to keep track of all of the information on
every unit it sells and services. If a problem occurs
with your CPA, check for a tag affi xed to the unit
listing these numbers. Supply the Customer Support
representative with this information when calling.
Inputs
Refer to Table 3 of this manual for input ranges and
accuracies of the CPA (TPRG).
Outputs
1PRG
This is a one relay output with a 5A@250Vac or
5A@24Vdc, 50/60Hz non-inductive contact rating. It
is available in a DPDT arrangement. All relay contacts
(NO, NC and COM) are available for use. No jumpers
are required.
2PRG
This is a two relay ouptut with a 5A@250Vac or
5A@24Vdc, 50/60Hz non-inductive contact rating.
The contact arrangement is SPDT. All relay contacts
(NO, NC and COM) are available for use. No jumpers
are required.
4 The Interface Solution Experts
Options
Analog Output (-AO)
The analog output range of the CPA (TPRG) can
be voltage or current. The current output is a
confi gurable source or sink output. Four terminals
are provided to allow voltage/current and current sink/
source selection without the need for jumpers. The
output can be confi gured to narrower spans from the
PC Confi guration program. The range of the current
output is 0–24mA. The range of the voltage output is
-0.5–11V.
RF Option (-RF)
An RF option is also available. This version provides
30V/m RFI/EMI immunity compared to our standard
model which offers 10V/m RFI/EMI immunity.
Specifi cations
Performance
Alarm Trip Repeatability:
See Table 3
Input Accuracy:
See Table 3
Overall Accuracy: The
overall accuracy of the unit
is the combined input and
output (if any) accuracies.
It includes the combined
effects of linearity,
hysteresis, repeatability,
and adjustment resolution.
It does not include ambient
temperature effect
300msec (Defi ned as time
from step change on input
to alarm state change when
alarm is set to trip midpoint)
Alarm Deadband:
Programmable from
0-100% of input range
Alarm Trip Delay:
0-120 seconds
Line Voltage Effect:
±0.002% of span per 1%
change in line voltage
(ac or dc)
Isolation: Standard unit,
1000Vrms between case,
input and output. 1500Vrms
between power and input
and between power and
output; Unit with -RF option,
500Vrms between case,
input, output and power
Power Consumption:
3W typical, 4W max.
Performance
(continued)
Performance
with Analog
Output (-AO
Option)
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Power Supply Effect:
±0.002% of span per 1%
of line change
Input Impedance: T/C
inputs, 40Mohms, nominal
Input Over-Range
Protection: ±5Vdc
Excitation Current (RTD
and Ohm Inputs Only):
250microamps, ±10%
WITH ANALOG
OUTPUT:
Output Accuracy:
Current, ±0.01% of max.
span (±2 microamps)
Voltage, ±0.01% of max.
span (±1mV)
Response Time:
256msec maximum
(128msec typical) for the
output to change from
10% to 90% of its scale
for an input step change
of 0 to 100%
Ripple: 50mVp-p
maximum on voltage
output; 10mVp-p
measured across a
250 ohm load resistor
for current output.
(Frequencies up to
120Hz)
Output Limiting:
Input over range,
-0.2V/0mA and
10.5V/21.4mA; Input
failure, -0.5V/0mA and
11V/24mA
Output Current Limiting:
25mA max.
Load Effect (current
outputs):
from 0 to maximum load
resistance on current
output
Maximum Load
Resistance: Current
outputs, 1kohms; Voltage
outputs, 2kohms
0.01% of span
Indicators
Ambient
Conditions
Weight
CPA
LED Type: INPUT LED:
Dual color LED indicates
input failure
READY LED: Green LED
indicates unit is operating
properly
ALARM 1 & ALARM 2 LED:
Dual color LED per relay
indicates alarm status
Operating & Storage
Range: -40°C to +85°C
(-40°F to +185°F)
Relay Range: -25°C to
+70°C (-13°F to +158°F)
Effect of Ambient
Temperature on Cold
Junction Compensation
(T/C Inputs Only):
±0.005°C per °C change of
ambient temperature
Relative Humidity:
0-95%, non-condensing
Ambient Temperature
Effect: ±0.015% of
maximum span/°C
RFI/EMI Immunity
(Standard Unit):
10V/m@20-1000MHz, 1kHz
when tested according to
IEC1000-4-3-1995 with
0.5% of span or less error
RFI Immunity (with -RF
Option):
30V/m@20-1000MHz, 1kHz
AM when tested according
to
IEC1000-4-3-1995 with
0.5% of span or less error
Noise Rejection: Common
mode,
100dB@50/60Hz;
Normal Mode,
See Table 2
653 g (21 oz)
Specifi cations and information subject to change without notice.
Table 1. Long-Term Stability
Stability
(% of maximum
span)
RTD, Ohm, & Pot Inputs
T/C & mV Inputs
Input-to-Analog
Output (Years)
1
0.066
0.047
3
0.114
0.082
5
0.147
0.106
Input-to-Relay
Output (Years)
1
0.47
0.081
0.008
0.014
Table 2. Normal Mode Rejection Ratio Table
Sensor Type
T/C: J, K, N, C, E
5
3
0.104
0.019
T/C: T, R, S, B
Pt RTD: 100, 200, 300 ohms
Pt RTD: 400, 500, 1000 ohms
Ni: 120 ohms
Cu: 9.03 ohms
Resistance mV
1-4kohms 250-1000
0.25-1kohms 62.5-250
0.125-0.25kohms 31.25-62.5
The Interface Solution Experts 5
Max. p-p Voltage Injection for
100dB at 50/60Hz
150mV
80mV
250mV
1V
500mV
100mV
1V
250mV
100mV
CPA
PC-Programmable RTD, T/C, Ohms, mV
and Potentiometer Limit Alarm Trips
Table 3.Accuracy with RTD, Thermocouple, Ohms, Potentiometer and Millivolt Inputs
Input Type α Ohms
RTD
(2-, 3-,
4-Wire)
0.003850
Platinum
0.003902
0.003916
Nickel
Copper
Direct Resistance
Ohms
Potentiometer
0.00672
0.00427
n/a
4000 max.
100
200
300
400
500
1000
100
200
400
500
1000
100
120
9.035
0-4000
Conformance
Range
-200 to 850°C
-328 to 1562°F
-100 to 650°C
-148 to 1202°F
-200 to 510°C
-328 to 950°F
-80 to 320°C
-112 to 608°F
-50 to 250°C
-58 to 482°F
0-4000ohms
0-100%
Minimum
Span
10°C
(18°F)
10ohms
10%
Accuracy/Repeatability
Input
±0.1°C
(±0.18°F)
±0.85°C
(±1.53°F)
±0.4ohms
±0.1%
Maximum
Range
-240 to 960°C
-400 to 1760°F
-150 to 720°C
-238 to 1328°F
-240 to 580°C
-400 to 1076°F
-100 to 360°C
-148 to 680°F
-65 to 280°C
-85 to 536°F
0-4000ohms
0-100%
T/C
mV
J
K
E
T
R
S
B
N
C
DC
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
-180 to 760°C
-292 to 1400°F
-150 to 1370°C
-238 to 2498°F
-170 to 1000°C
-274 to 1832°F
-170 to 400°C
-274 to 752°F
0 to 1760°C
32 to 3200°F
0 to 1760°C
32 to 3200°F
400 to 1820°C
752 to 3308°F
-130 to 1300°C
-202 to 2372°F
0 to 2300°C
32 to 4172°F
-50 to 1000mV
35°C
63°F
40°C
72°F
35°C
63°F
35°C
63°F
50°C
90°F
50°C
90°F
75°C
135°F
45°C
81°F
100°C
180°F
4mV
±0.25°C
(±0.45°F)
±0.3°C
(±0.54°F)
±0.2°C
(±0.36°F)
±0.25°C
(±0.45°F)
±0.55°C
(±0.99°F)
±0.55°C
(±0.99°F)
±0.75°C
(±1.35°F)
±0.4°C
(±0.72°F)
±0.8°C
(±1.44°F)
±15 microvolts
-210 to 770°C
-346 to 1418°F
-270 to 1390°C
-454 to 2534°F
-270 to 1013°C
-454 to 1855.4°F
-270 to 407°C
-454 to 764.6°F
-50 to 1786°C
-58 to 3246.8°F
-50 to 1786°C
-58 to 3246.8°F
200 to 1836°C
392 to 3336.8°F
-270 to 1316°C
-454 to 2400.8°F
0 to 2338°C
32 to 4240.4°F
-50 to 1000mV
6 The Interface Solution Experts