Moore Industries 531 User Manual

5 3 1
5 3 1
PLC, DCS, PC CONTROL BACKUP STATION USER'S MANUAL
M531 V7, MARCH 207
CONTENTS
FIGURE LIST .......................................................................................... iii
CHAPTER 1
INTRODUCTION ............................................................................. 1
Conforming What Is Included.......................................................... 1
Order Code ...................................................................................... 2
Basic Operation ............................................................................... 3
Where To Go Next........................................................................... 3
Text Formatting in This Manual ...................................................... 3
CHAPTER 2
INTERFACE & BASIC OPERATION ............................................. 5
Displays ............................................................................................ 5
Icons................................................................................................. 5
Keys ................................................................................................. 6
Basic Operating Procedures ........................................................... 7
Alarms .............................................................................................. 8
Contents
About This Manual:
Throughout this User’s Manual will appear NOTEs, CAUTIONs and WARNINGs, usually in boldface. Please heed these safety and good practice notices for the protection of you and your equipment.
CHAPTER 3
HARDWARE CONFIGURATION.................................................... 9
Accessing and Changing Jumpers ............................................... 11
Adding or Changing Output Modules............................................ 12
Where to Go Next.......................................................................... 13
CHAPTER 4
MOUNTING AND WIRING............................................................ 15
System Planning............................................................................ 15
Mounting the Station...................................................................... 15
Wiring the 531 Inputs..................................................................... 16
A.AC Power .......................................................................... 17
B.Process Variable............................................................... 17
C.Digital Inputs ..................................................................... 18
D.Remote Setpoint Indicator................................................ 19
Wiring the 531 Outputs.................................................................. 19
A.CV Output ......................................................................... 19
B Mechanical Relay Output ................................................. 19
C Solid State Relay (Triac) Output...................................... 19
D.DC Logic (SSR Drive) Output ..........................................19
Wiring for Serial Communications................................................. 20
Where to Go Next.......................................................................... 20
CHAPTER 5
SOFTWARE CONFIGURATION .................................................. 21
Mode Overview.............................................................................. 21
Menus............................................................................................. 22
Smart Menus..................................................................................22
Software Configuration Procedures.............................................. 23
Guide to Set up Parameters.......................................................... 25
CONFIG................................................................................. 25
LOCAL OUT. ......................................................................... 28
PV INPUT .............................................................................. 29
CUST. LINR. ......................................................................... 31
531 User's Manual Table of Contents i
Contents
RSP INPUT ............................................................................ 32
ALARMS ................................................................................ 33
SECURITY ............................................................................. 35
SER. COMM........................................................................... 36
OPERATION .......................................................................... 37
Parameter Value Charts.................................................................. 39
CHAPTER 6
531 APPLICATIONS ...................................................................... 45
531 Operation ................................................................................. 45
Alarms............................................................................................. 46
Digital Inputs ................................................................................... 50
Watchdog Monitor........................................................................... 51
Process Variable and Setpoint ........................................................ 51
Input Linearization........................................................................... 53
Thermocouple and RTD Linearization .................................... 53
Square Root Linearization ...................................................... 53
Custom Linearization.............................................................. 53
Ramp to a Control Value................................................................. 54
Security........................................................................................... 55
Process Variable Reading Correction ............................................. 56
Serial Communications ................................................................... 56
APPENDIX A
MODE, MENU & PARAMETER FLOWCHART............................ A-1
APPENDIX B
PARTS LIST................................................................................. B-1
APPENDX C
TROUBLESHOOTING ................................................................. C-1
APPENDIX D
CALIBRATION ............................................................................. D-1
Regarding Calibration ................................................................... D-1
RTD and VmA Input Calibration .................................................... D-2
Thermocouple & Cold Junction Calibration ................................... D-3
Milliamp Output Calibration ........................................................... D-4
Reset Menu Data .......................................................................... D-4
Hardware Scan ............................................................................. D-5
Quick Calibration Procedure ......................................................... D-5
APPENDIX E
SPECIFICATIONS........................................................................ E-1
ii Table of Contents 531 U ser's Manual
Figure.............Title ............................................................................ Page
Figure 2.1 ......531 Operator Interface .........................................................5
Figure 2.2 ......Before and After Acknowledging an Alarm ............................. 8
Figure 3.1......Location of Printed Circuit Boards ......................................... 9
Figure 3.2......Jumper Locations on Microcontroller Board ......................... 10
Figure 3.3......The Option Circuit Board .................................................... 10
Figure 3.4......The Power Supply Circuit Board ......................................... 10
Figure 3.5......Output Module ................................................................... 13
Figure 4.1 ......531 Instrument Panel and Cutout Dimensions ..................... 15
Figure 4.2 ......Mounting Brackets ............................................................. 16
Figure 4.3 ......531 Rear Terminals ............................................................ 17
Figure 4.4 ......Output Wiring for the 531 .................................................... 19
Figure 4.5 ......Serial Communications Terminals....................................... 20
Figure 5.1 ......Menu Flowchart for Set Up ................................................. 21
Figure 5.2 ......Independent vs. Dependent Parameters ............................. 22
Figure 5.3 ......Keys to Enter and Move Through Set Up Mode.................... 23
Figure 6.1 ......Alarm Examples................................................................. 49
Figure 6.2 ......Square Root Linearization Formula ..................................... 53
Figure 6.3 ......Custom Linearization Curve................................................ 54
Figure D.1 .....Flowchart to Access Parts of Calibration Menu Block ......... D-1
Figure D.2 .....Microcontroller Circuit Board ............................................. D-2
Figure D.3 .....Calibration Wiring ............................................................. D-2
Figure D.3a ...Calibration Wiring (continued) ........................................... D-3
Figure D.4 .....Thermocouple & Cold Junction Calibration Wiring .............. D-3
Figure D.5 .....Milliamp Calibration Wiring................................................ D-4
Contents
531 User's Manual Table of Contents iii
Contents
iv Table of Contents 531 User's Manual
CHAPTER 1 INTRODUCTION
Introduction
The 531 PID Backup Station ensures the integrity of your processes with maximum reliability. Isolated inputs and outputs guard against electrical inter­ference, the front face meets NEMA 4X standards for watertight operation, and the rugged case and sturdy rubber keys enhance durability.
The 531 has three digital display areas, two of which offer up to 9 characters of true alphanumerics. The bright, crisp vacuum fluorescent displays offer better readability than any other display technology. Additional operator friendly fea­tures include: custom programmable alarm messages, keys that illuminate when in use, and an easy-to-use menu system.
INPUTS
OUT
HOST Signal
Process Variable
Remote Setpoint
Digital Inputs
Serial Communications
1 2 ALM 1 2
Thank you for selecting the 531 PID Backup Station. It is the most sophisticated instrument in its class and will provide you with years of reliable, trouble-free performance.
OUTPUTS
HOST Signal Control Output Alarm(s) Serial Communications
The 531 automatically provides PID backup control for critical control loops. In Host Mode, the control signal passes from the Host device through the 531 without any degradation. A Host device may be a PLC, DCS, or process con­troller. The 531 switches to Automatic (PID) Mode upon keypad selection, digital input, or loss of the Host signal, and generates a control signal based on its own PID calculations. The control setpoint may be one or two preset setpoints, or transmitted to the 531. The 531 can also be switched to Manual Mode, in which the operator can manually adjust the output. The 531 will trans­fer/return to Host Mode upon keypad selection, opening of the digital input or return of the Host signal.
CONFIRMING WHA T IS INCLUDED
With your 531 PID Backup Station, you should have received:
1 531 User’s Manual
Mounting hardware set
1 sheet of engineering unit adhesive labels
1 Terminal label You can determine the installed outputs of your station by comparing your product
number to the Order Code below. The product number is printed on the label on the top of the controller case.
Specifications and information subject to change without notice.
Note: that the 531 PID Backup Station is not a point of failure; removing it from the case or powering down while in Host Mode will not disturb the Host signal.
531 User's Manual Chapter 1, Introduction 1
Introduction
ORDER CODE*
BASIC OPERA TION
There are three operating modes for the 531:
531 -
OUTPUT 1 — (ALARM ONLY)
None .........................................................................................0
Mechanical relay .......................................................................1
Solid state relay (1 amp triac) ...................................................3
DC logic (SSR drive) .................................................................4
OPTIONS
ENTER “0” IF NOT DESIRED
None .........................................................................................0
24 VAC Operation .....................................................................F
ENTER “0” IF NOT DESIRED
None .........................................................................................0
Set of five digital inputs .............................................................D
Certification ..........................................................................H
Set of five digital inputs and
SERIAL COMMUNICATIONS
ENTER “0” IF NOT DESIRED
None .........................................................................................0
RS-485 serial communications .................................................S
Certification .............................J
ORDER CODE
11B002
* Note: Base instrument contains universal PV input, remote setpoint input and 4-20 mA CV (control) output with internal hard wired by-pass relays.
NOTE:
Altering the factory configuration of the modules will render the product label code invalid.
2 Chapter 1, Introduction 531 User's Manual
Host Mode: The 531 operates as a remote station that passes a CV di­rectly from a host to a controlled device. In this mode, the SP but not the CV (output) can be altered. Special “set up” parameters can be accessed, and the 531 can be transferred into either of the other operating modes.
Automatic Mode: The 531 sends output to the final device as provided by its own PID calculations. In this mode, the SP but not the CV (output) can be altered. The “set up” parameters may not be accessed, but the 531 can be transferred to either of the other operating modes.
Manual Mode. An operator provides manual output to the controlled de­vice. Both the SP and the CV can be altered, and the 531 can be transferred to either of the other two operating modes.
The 531 also has a set up, or “configuration” mode in which the user configures the special functions of the 531, like inputs and outputs, alarms and PID opera­tion. There are 9 menus in set up mode: eight are for instrument set up, and the ninth, OPERATION, configures the operational aspects of the 531.
WHERE TO GO NEXT
First time users should read through this entire manual. Continue to Chap­ter 2 for basic interface and operation information. Then read Chapter 3 for important installation guidelines.
Experienced users may continue on to Chapter 5 for details on the configu­ration features of the 531.
Appendix 1 contains flowchart references for all 531 parameters, menus and modes.
Introduction
TEXT FORMA TTING IN THIS MANU AL
Feature Format Mode Automatic, Manual, Host Mode KEYS SET PTDISPLAY
or
SET PT
ICONS OUT, ALM MENUS CONFIG., TUNING
PARAMETERS CYCLE TM:1, MIN.OUT2 PARAMETER VALUES OFF, SETPOINT, LAST OUT. DISPLAY MESSAGES TOO HOT, OUT%,
DISPLAY
531 User's Manual Chapter 1, Introduction 3
Introduction
4 Chapter 1, Introduction 531 User's Manual
CHAPTER 2 INTERF A CE AND BASIC OPERA TION
The individual software and hardware options of your station determine the in­formation it displays. Compare the product number on the unit label to the Order Code in Chapter 1 for more information. A “smart menu” feature of the 531 al­lows only those messages relevant to your individual hardware (and software) configuration to appear in the displays.
531
Icons
OUT 1 2 ALM 1 2
1st Display
nd
2
Display
rd
Display
3
Interface/Operation
NOTE::
Any modifications to the factory settings of the output modules will alter the Model Number displayed upon power-up from the original the Product Code on the label.
Figure 2.1 531 Operator Interface
Location for
identification label
MANUAL
DISPLAY
ACK
Keys
HOST
MENU
FAST
1st Display
5 digits, seven segments. Height is 15mm (0.6in).
Normally displays the Process Variable (PV). If station loses signal, “--------” displays.
2nd Display
9 characters, 14 segment alphanumeric. Height is 6mm (0.25in).
Displays the CV output (OUT) or the setpoint (SP). To change the displayed value, press the DISPLAY key.
When in configuration menus, displays the menu and parameter names
3rd Display
9 characters, 14 segment. Height is 6mm (0.25in).
Displays user-selectable station name if no alarms are queued.
Displays any error or alarm in two-second alternating messages.
When in configuration menus, displays the parameter values.
ICONS:
ALM 1, ALM2: Indicates respective alarm(s) is/are active.
OUT 1, OUT2: Indicates respective output(s) is/are active.
531 User's Manual Chapter 2, Interface and Basic Operation 5
ALM ALM ALM 1212
OUT OUT OUT 1212
Interface/Operation
KEYS
MANUAL
HOST
DISPLAY
MENU
ACK
FAST
Press Key (s)
Transfers station from Host or Automatic Mode to Manual Mode, or from Manual to Automatic.
Toggles between Host and either Automatic or Manual Mode (depending on validity of the PV).
Exits the configuration (set up) menus and returns station to operating mode.
Provides entry into the OPERA­TION set up menu.
Acknowledges alarms.
Functions as a “shift” key or for use with other keys.
Illuminated Key
Station is in Manual Mode. When not illuminated, the station is in either Host or Automatic Mode.
531 is passing Host signal through.
Key does not light.
531 is in configuration (set up) mode.
An acknowledgable alarm exists.
Key does not light.
FAST
or
+
or
FAST
FAST
NOTE:
Refer to Chapter 3, or Appendix 1 for details on menu, mode and parameter transitions
+
+
MENU
Increases or decreases the value or selection of the current parameter.
Changes parameter value or selection at a faster rate.
In Host or Manual Mode, provides entry into the other eight set up menus. When under configuration, advances from menu to menu.
Keys do not light.
N/A
N/A
6 Chapter 2, Interface and Basic Operation 531 User's Manual
BASIC OPERA TING PR OCEDURES
To transfer from Host to Automatic Mode
1. Press the HOST key once. The 531 will transfer to Automatic Mode as long as the PV input is valid (else, it transfers to Manual Mode).
2. The HOST key and MANUAL key will be off.
3. The 531 stops passing the Host signal, and transmits its own output that based on PID, with a bumpless transfer.
To transfer from Host to Manual Mode
1. Press the MANUAL key. The 531 will transfer to Manual Mode.
2. The HOST key will extinguish, and the MANUAL key will light.
3. The 531 stops passing the Host signal, and transmits a manual output to the final control element. This will be a bumpless transfer.
To transfer from Automatic to Manual Mode
1. When in Automatic Mode, press the MANUAL key.
2. The MANUAL key will light.
3. The 531 stops transmitting the PID output and transmits a manual output to the final control element. This will be a bumpless transfer.
To transfer from Automatic/Manual Mode to Host Mode
1. Press the HOST key. The 531 will transfer to Host Mode as long as the CV signal is valid (otherwise, it remains in the previous mode).
2. The 531 will stop transmitting its own output (CV) signal, and pass the sig­nal from the Host device to the final control element. This will be a direct transfer.
3. To provide a ramped transfer, the ramping rate (HOST RAMP) can be set in the OPERATION menu.
To change output values
1. Press MANUAL key to shift to Manual Mode from Automatic or Host.
2. The second display will display OUT%.
▲▲
3. Use
To override security or reset the controller
1. If someone attempts a locked operation, SECURITY appears in the 2nd display, and a security code prompt (0) appears in the 3rd display.
2. Use two seconds of key inactivity.
If no code was entered (value left at 0), SECURITY disappears and
the station resumes operation.
If the value is incorrect, INCORRECT appears in the 3rd display. After
2 seconds, the station prompts you to enter a new code.
If the code is correct, CORRECT appears in the 3rd display. After two
seconds, all displays clear and you have temporary access to all pre­viously locked features. Security will automatically rearm (lock) the station once after one minute of key inactivity.
If the correct Security Override Code is entered, RESET appears in
the 3rd display. After two seconds, all displays clear and the stations functions are reset to their factory defaults (unlocked).
and
▲▲
▲▲
and
▲▲
▼▼
keys to change the output (CV) value.
▼▼
▼▼
keys to select a code value. The value will be entered after
▼▼
Interface/Operation
NOTE:
For more information on operating modes, see Chapter 6.
NOTE:
For more information on Security functions, see Chapter 6.
531 User's Manual Chapter 2, Interface and Basic Operation 7
Interface/Operation
NOTE:
Powering down the controller acknowl­edges/clears all latched alarms. When powering up, all alarms will be reset ac­cording to their power-up configuration (see Chapter 6).
NOTE: All alarms are internal alarms unless tied
to an output relay in the set up mode.
ALARMS
IMPORTANT! Alarms can be used to provide warnings of unsafe conditions.
Therefore, all 531 operators must know how the alarms are configured, how to react to alarm conditions, and the consequences of acknowledging (noting and clearing) an alarm.
The 531 indicates alarms by:
Lighting icons
Displaying messages; and
Lighting the ACK key, if an alarm is in an acknowledgeable state.
To acknowledge an alarm:
1. Press the ACK key to acknowledge Alarm 1. This clears the alarm (and releases the relay, if applicable.
2. Both the icon and message indicators disappear, and the relay (if applicable) changes state.
3. If a second alarm is active and acknowledgeable, press the ACK key again to acknowledge Alarm 2.
Figure 2.2 shows the controller face during an alarm condition, and after the alarm has been acknowledged.
OUT 1 2 ALM 1
BEFORE
531
OUT 1 2
AFTER
531
Figure 2.2 Before and After Acknowledging an Alarm
MANUAL
DISPLAY
MENU
ACK
FAST
MANUAL
HOST
DISPLAY
MENU
ACK
FAST
HOST
Latching Alarms
A latching alarm holds its alarm state even after the process leaves the alarm condition. This is useful for stations that will not be continuously monitored by an operator. A latching alarm can be configured to be acknowledgeable while in the alarm condition, OR only after the process leaves the alarm condition. A non-latching alarm will clear itself as soon as the process leaves the alarm condition.
Limit Sequence
An alarm can be configured to be both latching and not acknowledgeable. In this case, the alarm is acknowledgeable only after the process has left the alarm condition. This is often referred to as a limit sequence.
For more on alarms, see Chapter 6.
8 Chapter 2, Interface and Basic Operation 531 User's Manual
CHAPTER 3 HARDWARE CONFIGURA TION
Hardware
The 531 hardware configuration determines which outputs are available and the types of indicator signals that will be used.
Your station comes factory set with the following:
All the specified modules and options installed (see product label and compare to Order Code in Chapter 1).
Process variable and remote setpoint inputs set to accept a milliamp input.
CAUTION!
Static discharge will cause damage to equipment. Always ground your­self with a wrist grounding strap when handling electronics to prevent static discharge.
Relay outputs set to normally open
The locations of certain jumpers and modules on the printed circuit boards will allow different types of inputs and outputs to be connected to the sta­tions. Figure 3.1 shows the position of these circuit boards inside the station. To access these boards:
1. With power off, loosen the two captive front screws with a Phillips screwdriver.
2. Gently slide the chassis out of the case by pulling on the front face plate assembly at the bezel. Remove the two screws.
NOTE:
If you would like your controller con­figured at the factory, please consult an application engineer.
NOTE:
Your hardware configuration will influence the available set up options in Chapter 5.
NOTE:
Any changes you make to the output modules will render the code on the product label invalid.
MICROCONTROLLER
BOARD
POWER SUPPLY
BOARD
531 User's Manual Chapter 3, Hardware Configuration 9
Figure 3.1 Location of Printed Circuit Boards for Hardware Configuration
OPTION BOARD
Hardware
Process Variable Indicator Type
The 531 will accept several different types of Process Variable Signals. You specify the type of signal by adjusting the PV jumper location on the Micro- controller Circuit Board, as shown in Figure 3.2. You will also need to set the particular sensor range in the software (Chapter 5).
V Voltage signal MA Milliamp TC t Thermocouple with downscale burnout TC s Thermocouple with upscale burnout RTD RTD
EPROM
Figure 3.2 Jumper Locations on Microcontroller Board
Figure 3.3 The Option Circuit Board, with Output 4
CAUTION!! Do not change configuration of outputs
2, 3, and 4. Do not change position of jumpers J2 and J3.
Figure 3.4 The Power Supply Circuit Board, with Outputs 1 through 3
BATTERY
5-Pin Connector
Male 22-Pin
Connector
4-Pin Connector
Output 4
Female 44-Pin Connector
4
Retransmitted (Remote) SP
PV Input Jumper
Female 22-Pin ConnectorFemale 22-Pin Connector
Male 22-Pin
Connector
Male 44-Pin Connector
Module
Retention
over Outputs 1,2,3
Configuration
Configuration
Plate
3 2
1
V
MA
V
MA TC TC
RTD
TB2
2ND
PV1
TB1
NO J3 NC
NO J2 NC
NO J1 NC
10 Chapter 3, Hardware Configuration 531 User's Manual
Jumpers
NO and NC
Setpoint Type (retransmitted)
You specify the type of retransmitted setpoint by adjusting the jumper location on the Microcontroller Board, as shown in Figure 3.2:
V Voltage signal MA Milliamp signal (factory default)
Mechanical Relays
There is one output module socket on the Option Board (Figure 3.3), and three on the Power Supply Circuit Board (Figure 3.4). The position of the jumper next to each socket determines whether the relay is configured for Normally Open (NO) or Normally Closed (NC). The output on the options board is always fac­tory set to Normally Open (NO).
Only the Output 1 relay (if used) may be configured for normally open or nor­mally closed. Do not make any changes to J2 and J3.
ACCESSING AND CHANGING JUMPERS
Jumper connectors either slip over adjacent pins, or have pins which insert into adjacent holes. “Changing the jumper” means moving the jumper connectors to alternate pins/holes.
Equipment needed:
Needle-nose pliers (optional)
Phillips screwdriver (#2)
Wrist grounding strap
1. With power off, loosen two captive front screws with a Phillips screwdriver.
2. Slide the chassis out of the case by pulling on front face plate assembly at the bezel. Remove the two screws now. You will not need to disassemble the chassis to make these adjustments.
3. Refer to Figures 3.2 and 3.4 to locate the jumper connector you want to change.
4. With either your fingers or the needle nose pliers, pull the jumper connector straight up, being careful not to bend the pins (see Photo 4)
5. Move the jumper connector over the desired location and press it straight down, making sure it is seated firmly. Repeat steps 3 and 4 for any other jumpers you wish to change.
6. When you are ready to reassemble the unit, align the boards on the chassis with the case's top and bottom grooves. Press firmly to slide the chassis into the case. If you have difficulty, check that you have properly oriented the chassis and that there are no screws interfering with the case.
7. Carefully insert and align screws. Tighten them until the bezel is seated firmly against the gasket. Do not overtighten.
Hardware
CAUTION!!
Static discharge will cause damage to equipment. Always ground yourself with a wrist grounding strap when handling electronics to prevent static discharge.
4. REMOVE JUMPERS
531 User's Manual Chapter 3, Hardware Configuration 11
Hardware
CAUTION!!
Static discharge will cause damage to equipment. Always ground yourself with a wrist grounding strap when handling electronics to prevent static discharge.
ADDING OR CHANGING OUTPUT MODULES
The 531 has provisions for four output modules. The units come factory config­ured with specified modules installed in appropriate locations. You can make field adjustments by properly removing and/or plugging the modules into the appropriate sockets.
Important Notes:
Only the Output 1 relay (if used) may be changed.
Output modules 2, 3 and 4, and Jumpers J2 and J3 must not be changed from their factory installation.
Any output module with a sold state relay or analog module MUST have its jumper set at normally open (NO).
Output 4 is always normally open (NO).
Three of the output sockets are located on the Power Supply Circuit Board. A fourth output socket is located on the Option Board.
Equipment needed:
Wrist grounding strap
Phillips screwdriver (#2)
Small flat blade screwdriver
Wire cutters or scissors
1. With power off, loosen two captive front screws with a Phillips screwdriver.
2. Slide the chassis out of the case by pulling on front face plate assembly at the bezel. Remove the two screws now.
3. Locate the retention clips holding the front face assembly to the rest of the chassis. Pry apart these retention clips gently with a screwdriver to sepa­rate the printed circuit board group from the front face assembly. Take care not to break the clips or scratch the circuit board. See Photo 3.
The Microcontroller Board and Power Supply Board remain attached to the Operator Interface Assembly by wired connectors.
4. See Photo 4. The Microcontroller and Power Supply board are attached to either side of the Option board by male/female pin connectors. Use a gentle rocking motion and carefully apply pressure to separate the larger two boards from the Option Board.
CAUTION!
Do not scratch the boards or bend the pins of the connectors.
12 Chapter 3, Hardware Configuration 531 User's Manual
3. PRY CLIPS
4. SEPARATE BOARDS
5. A retention plate and tie wrap hold Output modules 1, 2, and 3 (on the Power Supply board) firmly in place. To remove the retention plate, snip the tie wrap with wire cutters (or scissors) as shown in Photo 5.
Always snip the tie wrap on top of the Retention Plate to prevent damage to the surface mount components.
6. A disposable tie wrap holds Output module 4 (on the Option board) in place. To remove the module, snip tie wrap like in Photo 6.
7. Inspect each module before installation to make sure the pins are straight (Figure 3.5). Align the pins with the socket holes and carefully insert the module. Press down to seat it firmly on the board (see Photo 7).
Hardware
Figure 3.5 Output Module
5. REMOVE RETENTION PLATE
8. Use new tie wraps to secure the Retention Plate and Output Module 4. Failure to use the tie warps may result in the module loosening
and eventual failure. All individually ordered modules come with tie wraps. Extra sets of tie wraps are available; order Part #535-
665.
9. To reassemble the unit: Align the connector pins on the Option Board with
the connector sockets on the Microcontroller and Power Supply boards. Squeeze them together, making certain all three are properly seated against one another. Check along the side edges for gaps. Also, check that the cable assemblies are not pinched.
10. Align the board assembly with the front face assembly, with the Option board
at the bottom (see Figure 3.1). Reinstall the retention clips. Align the boards into the slots of the front face assembly and the clips will snap into place.
11. When you are ready to reassemble the unit, align the boards on the chassis
with the top and bottom grooves on the case. Press firmly to slide the chas­sis into the case. If you have difficulty, check that you have properly oriented the chassis, and there are no screws interfering with the case.
12. Carefully insert and align screws. Tighten them until the bezel is seated firmly
against the gasket. Do not overtighten.
6. SNIP TIE WRAP 7. ADD/CHANGE MODULE
WHERE T O GO NEXT
For a step-by-step guide on mounting and wiring your 531 PID Backup Station, see Chapter 4.
531 User's Manual Chapter 3, Hardware Configuration 13
Hardware
14 Chapter 3, Hardware Configuration 531 User's Manual
CHAPTER 4 MOUNTING AND WIRING
The 531 PID Backup Station is thoroughly tested, calibrated and “burned in” at the factory, so your station is ready to install. But before you begin, read this chapter carefully and take great care in planning your system. A properly designed system can help prevent problems such as electrical noise distur­bances and dangerous conditions.
SYSTEM PLANNING
A. Consider the Noise Factor
For improved electrical noise immunity, install the station as far away as possible from motors, relays and other similar noise generators.
Do not run low power (sensor input) lines in the same bundle as AC power lines. Grouping these lines in the same bundle can create electrical noise interference.
B. Wiring Practice Resources
An excellent resource about good wiring practices is the IEEE Standard No. 518-1982 and is available from IEEE, Inc., 345 East 47th Street, New York, NY 10017, (212) 705-7900.
Mount/Wire
WARNING!
To avoid electric shock, DO NOT connect AC power wiring at the source distribution panel until all wiring connections are complete.
To avoid shock hazard and reduced noise immunity for your system,
terminal 9 must be grounded.
MOUNTING THE STA TION
A. Make the panel cutout
The station fits in a standard 1/4 DIN cutout. You may mount your station in any panel with a thickness from .06 to .275 inches (1.5 mm to 7.0 mm). See Figure 4.1 for dimensions.
If you make a mistake in the panel cutout, you can use a “Goof Plate” (Repair Part #512-014).
B. Establish a waterproof seal
The station front face (keys, display, and bezel) are NEMA 4X rated (waterproof).
7.180 (182.37) OVERALL LENGTH
1.180 (29.97) PANEL
PV2 OUT 1 2 ALM 1 2
3.770 (95.76)
3.770 (95.76)
Figure 4.1 531 Instrument Panel and Cutout Dimensions
3.622 (92.00) MIN.
3.653 (92.80) MAX.
3.653 (92.80) MAX.
3.585 (91.06)
3.622 (92.00) MIN.
BEZEL
FRONT
531 User's Manual Chapter 4, Mounting and Wiring 15
GASKET
6.000 (152.40)
SIDE
CUTOUT
Mount/Wire
To obtain a waterproof seal between the station and the panel, make sure:
1. The panel cutout is precise.
2. You use a fresh gasket.
3. The edge of the cutout is free from burrs and “waves”.
4. The case of the station are centered in the cutout. If you require a waterproof seal but have difficulty with these requirements,
apply a bead of caulk or silicone sealant behind the panel around the pe­rimeter of the case.
Figure 4.2 Mounting Brackets
Bezel
MOUNTING BRACKET (1 EA. SIDE)
C. Mount station into panel:
The instrument enclosure mounting must be grounded. You will need a long Phillips screw driver (#2).
1. Place bezel gasket around the station case (starting at the back of the station). Then, slide the gasket against the back of the bezel.
2. With the bezel gasket in place, insert the station into the panel cutout from the front of the panel.
3. From behind the panel, insert the mounting clips (one on each side), as shown in Figure 4.2.
4. Gradually tighten the mounting bracket screws.
5. Tighten the screws securely and check bezel gasket to ensure a tight,
even seal.
Housing
Slide gasket on from this end.
NOTE:
All wiring and fusing should conform to the National Electric Code and to any locally applicable codes.
16 Chapter 4, Mounting and Wiring 531 User's Manual
WIRING THE 531 INPUTS
Figure 4.3 shows the rear terminal configurations for the 531. The actual instru­ment has only the top and bottom numbers of each column marked. Refer to this diagram for the following input and output wiring instructions.
IMPORTANT!!
When wiring the 531 terminals, DO NOT use alligator clips (they create an open circuit).
AC Power
LINE
Mount/Wire
Optional Contact Inputs from HOST (if installed)
1
9
EARTH GND
DIN
GND
17
25
NC
NEUTRAL
Optional Local Flag
to HOST
or Alarm
4–20 mA
Control
Signal
+
I
P
Any Final Control Element
A. AC Power
Terminals 1 and 2 are for power.Terminal 9 is earth ground.
POWER
OUT 1–
OUT 1+
CV OUT –
CV OUT+
1 2
NC
NC
2 3 4
5 6 7 8
9
GROUND
NC
10
NC
11
NC
12
NC
13
CV IN+
14
CV IN–
15
NC
16
PC, PLC, DCS
DIN 1
18
DIN 2
19
DIN 3
20
DIN 4
21
DIN 5
22
N/A
23
N/A
24 32
4–20 mA Control Signal
HOST
COMM–
26
COMM+
27
SP IND.–
28
SP. IND+
29
RTD 3rd
30
PV IND.–
31
PV IND.+
A special PC Board covers terminals 5,6,7,8,13,14,15, and 16.
Figure 4.3 531 Rear Terminals
NOTE:
Use a 0.5 Amp, 250 V, fast-acting fuse in line with your AC power connection (terminal 1).
RSP from HOST
PV Sensor
B. Process Variable
The station accommodates the following types of process variable inputs: Thermocouple, RTD , Voltage, Milliamp, Voltage and Millivolt.
1. Thermocouple Input Use terminals 31 and 32 as shown.
31
+
32
531 User's Manual Chapter 4, Mounting and Wiring 17
T/C Input
Mount/Wire
2. RTD Input
For 2, 3 or 4 wire RTD, use terminals 30, 31 and 32 as shown.
RTD INPUT 2-WIRE
Jumper wire
30 31
RTD
32
RTD INPUT 3-WIRE
Same color
Third leg of RTD
RTD INPUT 4-WIRE
30 31 32
DO NOT connect 4th leg
3. Voltage Input
Use terminals 31 and 32 as shown.
4. Milliamp Input -External Power Supply
Use terminals 31 and 32 with a 2-Wire transmitter.
31 32
Transmitter
+
+
Same color
Third leg of RTD
30 31 32
Same color
MILLIAMP INPUT - EXT. POWERVOLTAGE INPUT
– External +
31 32
Power Supply
– Transmitter +
C. Digital Inputs
1. With a Switch
Use terminal 17 with the appropriate digital input terminal as shown.
2. With a Relay (dry contact)
Signal-type relay is recommended. Use terminal 17 with the appropriate digital input terminal as shown.
3. With an Open Collector (transistor)
11mA typical. 50 max. resistance. 50 max. loop resistance. Use ter­minals 17with the appropriate digital input terminal as shown.
SWITCH / RELAY
17
#
DIN 1
18
DIN 2
19
DIN GND
DIN #
OPEN COLLECTOR
DIN 3
20
DIN 4
21
17
#
DIN GND
DIN #
DIN 5
22
18 Chapter 4, Mounting and Wiring 531 User's Manual
D. Remote Setpoint Indicator
3
4
_
+
Load
_
+
DC LOGIC (SSR DRIVE)
3
4
Line Power
Load
MECHANICAL RELAY
3
4
Line Power
Load
-
+
­+
SSR (TRIAC)
5
6
_
+
CV
CV OUTPUT
7
8
Use terminals 28 and 29 as shown.
28
29
Source
+
+
Mount/Wire
WIRING THE 531 OUTPUTS
Output 1 is available for use as an ALARM or HOST FLAG with installa­tion of a Mechanical Relay, Solid State Relay (Triac) module, or SSR Drive.
The 531 is factory configured with an Analog module in Output 2.
The 531 is factory configured with Mechanical Relays in Outputs 3 and 4.
The 531 cannot be wired for retransmission.
A small PC board fits over rear terminals 5 to 8 and 13 to 16.
These instructions explain proper wiring of the 531 for any output module. If you do not know which module(s) have been installed in your station, compare the number on the product label with the Order Code on page 3. To add or change position of jumper 1 or output module 1, refer to Chapter 3.
A. CV Output
Use terminals 5 and 8 for CV Output as shown in Figure 4.4.
Use terminals 14 and 15 for CV Input.
B. Mechanical Relay Output
Use terminals 3 and 4 as shown in Figure 4.4.
Jumper J1 can be set to normally open (NO) or normally closed (NC)
as desired.
C. Solid State Relay (Triac) Output
Use terminals 3 and 4 as shown in Figure 4.4.
Jumper J1 must be set to normally open (NO).
D. DC Logic (SSR Drive) Output
Use terminals 3 and 4 as shown in Figure 4.4.
Jumper J1 must be set to normally open (NO).
WARNING!
DO NOT make any modifications to the factory setting of output modules 2, 3 and 4; this will place the product in an invalid and undefined state.
Figure 4.4 Output Wiring for the 531
531 User's Manual Chapter 4, Mounting and Wiring 19
Mount/Wire
531 Terminals
PC
or other host
The shield needs to be connected continuously but only tied to one ground at the host. Failure to follow these proper wiring practices could result in transmission errors and other communication problems.
Figure 4.5 Serial Communications Terminals
To "Comm –" terminal of next Powers device
To "Comm +" terminal of next Powers device
RS-485
port
Twisted, shielded
Comm Ð
Comm +
26
27
Use a 60 to 100 terminating resistor connected to the two data terminals of the final device on the line.
WIRING FOR SERIAL COMMUNICA TIONS
You must have this option installed on your 531 in order to use serial commu­nications. Refer to Figure 4.5.
Use a twisted shielded pair of wires to connect the host and field units. Belden #9414 foil shield has superior noise rejection characteristics. #8441 braid shield 22-gauge wire has more flexibility.
The maximum recommended length of the RS 485 line is 4000 ft.
Termination resistors are required at the host and the last device on the line. Some RS 485 cards/converters already have a terminating resistor. We recommend using RS-232/RS-485 converter (prod. no. 500-485).
WHERE T O GO NEXT
For a step-by-step guide on setting up the software features for your control­ler, see Chapter 5.
20 Chapter 4, Mounting and Wiring 531 User's Manual
CHAPTER 5 SOFTW ARE CONFIGURATION
MODE OVERVIEW
Upon power up, as well as during “normal” operation, the 531 is in one of its operating modes - Host, Automatic or Manual.
The 531 also has a set up (configuration) mode that lets you access options for adjusting the operation and display of the station. “Set up” is divided into two groups; one for the first eight menus (as listed below), and another for the OPERATIONS menu by itself.
Figure 5.1 illustrates the relationships among the three operating modes and nine set up menus.
The 8 set up menus can by accessed only when the 531 is in Host or Manual Mode. The OPERATIONS set up menu can be accessed when the 531 is in
Automatic, Host or Manual Mode.
Software
AUTOMATIC operating mode
HOST or MANUAL operating modes
DISPLAY
to return to operating modes
OPERATIONS
DISPLAY
or ACK to return to operating modes
MENU + FAST
for other set up menus
8 set up menus
CONFIG.
LOCAL OUT.
PV INPUT
CUST. LINR.
RSP INPUT
1 set up menu
MENU + FAST
for other set up menus
MENU + FAST
to move from menu to menu
MENU for Operations set up menu
Figure 5.1 Menu Flowchart for Set Up
531 User's Manual Chapter 5, Software Configuration 21
ALARMS
SECURITY
SER. COMM.
Software
MENUS
A menu is a group of configuration control parameters. While in these set up menus, the name of the menu will appear in the 2nd display. The names of the different parameters within that menu group will then replace the menu name in the 2nd display. The values/options for each parameter will then appear in the 3rd display. Figure 5.1 displays the parts of the menu as used by this manual.
The (possible) menus for the 531 are:
OPERATIONS To set up special PID control parameters and make adjustments to the transition functions (among operating modes) of the station.
CONFIG. To configure the input and output hardware assignments.
LOCAL OUT. To configure the local output control.
PV INPUT To configure the process variable.
CUST. LINR To configure the custom linearization curve for the process variable.
RSP INPUT To configure the remote set point.
ALARMS To configure alarms.
SECURITY To configure the security function.
SER. COMM. To configure serial communications.
Independent
Parameter
CONFIGURE
UNLOCKED
Figure 5.2 Independent vs. Dependent Parameters
Dependent
Parameter
RSP TYPE
(D)
SMART MENUS
This chapter outlines, in sequence, all menus, parameters, and selections available for the 531. However, the “smart menu” feature of the station allows only those Menus and Parameters to appear that are relevant to your hard­ware and software configuration, i.e., parameters which do not apply to your
application will not appear on your station’s display.
Parameters that apply to all configurations appear in this manual as a white on white box (Figure 5.2, left). These parameters are independent of your configuration.
Parameters that depend on the configuration of the individual station ap- pear as a black on white box (Figure 5.2, right).
Changing one parameter’s selection (or value) may affect another parameter. Refer to the section on the PV INPUT menu for an example on how this can affect your low and high range values.
22 Chapter 5, Software Configuration 531 User's Manual
Software
FAST
SOFTW ARE CONFIGURA TION PR OCEDURES
On the bottom of each page is a guide to the keypad, to use during your configuration.
To access the 8 set up menus
1. Hold down the FAST key and press MENU. (see Figure 5.3). The MENU key will illuminate. The first Menu, CONFIG., appears alone in the 2nd display.
2. Press FAST + MENU to advance to the next menu. The menu name will appear in the 2nd display.
To access the OPERATIONS set up menu
1. Press MENU. The MENU key will illuminate. OPERATION will appear in the 2nd display.
To advance through parameters and select a parameter value
1. When you reach your chosen menu, press MENU. The first parameter of this menu appears in the 2nd display, replacing the menu name. The first values/selection for the particular parameter appears in the 3rd display.
▲▲
2. Press
3. Press MENU to advance to next parameter.
To return to operating mode from configuration
1. Press the DISPLAY key. The station will return to the operating mode.
Scrolling through the choices to make selections will affect the opera­tion of the instrument since changes to parameter selections occur in "real time" or immediately.
DO NOT MAKE ANY CHANGES DURING ON LINE OPERATION!
▼▼
or
, with or without the FAST key.
▲▲
▼▼
WARNING!!
MENU
FAST
MENU
Figure 5.3 Keys to Enter and Move through Set Up Mode
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 5, Software Configuration 23
DISPLAY
MENU
MENU
+
or
Software
24 Chapter 5, Software Configuration 531 User's Manual
FAST
MENU
GUIDE TO SET UP PARAMETERS
Only parameters and selections relevant to your hardware and other software selections will appear on your station.
Parameter Value
(R) Parameter Range (D) Default Setting
Software
CONFIG.
For configuring the input and output hardware assignments.
1. LOST HOST
Selects the type of local backup if 531 loses the host CV signal.
MAN. OUT1 Switch to Manual Mode, use preset output MAN. OUT1
MAN. OUT2 Switch to Manual Mode, use preset output MAN. OUT2
MAN. LAST Go to Manual Mode using the last known output (D) AUTO.LOCAL Go to Automatic (PID)Mode
AUTO.TRACK Go to Automatic (PID)Mode using last PV as the local SP
2. HOST.RESTR.
Selects the 531 mode upon host CV restoration.
LOCAL Remain in Manual (or Automatic) Mode
(D) HOST MODE Go to Host Mode
3. CONTACT 1
Defines the operation of the 1st digital input.
MAN. LAST Switch to Local Manual Mode, use last output
MAN. OUT1 Switch to Manual Mode, use preset output MAN. OUT1
MAN. OUT2 Switch to Manual Mode, use preset output MAN. OUT2
ALARM ACK. Acknowledge alarms
UP KEY Remote
DOWN KEY Remote
COMM.ONLY Make status readable through communications
DISP. KEY Remote DISPLAY key
MENU KEY Remote MENU key
FAST KEY Remote FAST key
RST.INHBT. Inhibits PID reset action
REMOTE SP Selects the Remote SP for Automatic Mode
LOCAL SP Selects the Local SP for Automatic Mode (D) AUTO.LOCAL Go to Automatic Mode
HOST MODE Go to Host Mode
WATCHDOG Monitors the Host device for failure.
▲▲
key
▲▲ ▼▼
key
▼▼
CONFIG
LOST HOST
AUTO.LOCAL
HOST.RESTR.
HOST
CONTACT1
AUTO.LOCAL
NOTE:
Refer to Chapter 6 for more on the Watchdog Monitor.
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 5, Software Configuration 25
DISPLAY
MENU
+
or
Software
CONFIG
CONTACT 2
MAN.LAST
CONT ACT 3
LOCAL SP
4. CONTACT 2
Defines the operation of the 2nd digital input.
(D) MAN. LAST Switch to Local Manual Mode, use last output
MAN. OUT1 Switch to Manual Mode, use preset output MAN. OUT1
MAN. OUT2 Switch to Manual Mode, use preset output MAN. OUT2
ALARM ACK. Acknowledge alarms
U P K E Y Remote key
DOWN KEY Remote
COMM.ONLY Make status readable through communications
DISP. KEY Remote DISPLAY key
MENU KEY Remote MENU key
FAST KEY Remote FAST key
RST.INHBT. Inhibits PID reset action
REMOTE SP Selects the Remote SP for Automatic Mode
LOCAL SP Selects the Local SP for Automatic Mode
AUTO.LOCAL Go to Automatic Mode
HOST MODE Go to Host Mode
WATCHDOG Monitors the Host device for failure
key
5. CONTACT 3
Defines the operation of the 3rd digital input.
MAN. LAST Switch to Local Manual Mode, use last output
MAN. OUT1 Switch to Manual Mode, use preset output MAN. OUT1
MAN. OUT2 Switch to Manual Mode, use preset output MAN. OUT2
ALARM ACK. Acknowledge alarms
UP KEY Remote
DOWN KEY Remote
COMM.ONLY Make status readable through communications
DISP. KEY Remote DISPLAY key
MENU KEY Remote MENU key
FAST KEY Remote FAST key
RST.INHBT. Inhibits PID reset action
REMOTE SP Selects the Remote SP for Automatic Mode (D) LOCAL SP Selects the Local SP for Automatic Mode
AUTO.LOCAL Go to Automatic Mode
HOST MODE Go to Host Mode
WATCHDOG Monitors the Host device for failure.
▲▲
key
▲▲
key
Escape to operating mode Next parameter Next menu Next value
DISPLAY
26 Chapter 5, Software Configuration 531 User's Manual
MENU
FAST
MENU
+
or
Software
FAST
MENU
CONFIG
6. CONTACT 4
Defines the operation of the 4th digital input.
MAN. LAST Switch to Local Manual Mode, use last output
MAN. OUT1 Switch to Manual Mode, use preset output MAN. OUT1
MAN. OUT2 Switch to Manual Mode, use preset output MAN. OUT2 (D) ALARM ACK. Acknowledge alarms
UP KEY Remote
DOWN KEY Remote
COMM.ONLY Make status readable through communications
DISP. KEY Remote DISPLAY key
MENU KEY Remote MENU key
FAST KEY Remote FAST key
RST.INHBT. Inhibits PID reset action
REMOTE SP Selects the Remote SP for Automatic Mode
LOCAL SP Selects the Local SP for Automatic Mode
AUTO.LOCAL Go to Automatic Mode
HOST MODE Go to Host Mode
WATCHDOG Monitors the Host device for failure.
▲▲
key
▲▲ ▼▼
key
▼▼
7. CONTACT 5
Defines the operation of the 5th digital input.
MAN. LAST Switch to Local Manual Mode, use last output
MAN. OUT1 Switch to Manual Mode, use preset output MAN. OUT1
MAN. OUT2 Switch to Manual Mode, use preset output MAN. OUT2
ALARM ACK. Acknowledge alarms
UP KEY Remote
DOWN KEY Remote
COMM.ONLY Make status readable through communications
DISP. KEY Remote DISPLAY key
MENU KEY Remote MENU key
FAST KEY Remote FAST key
RST.INHBT. Inhibits PID reset action
REMOTE SP Selects the Remote SP for Automatic Mode
LOCAL SP Selects the Local SP for Automatic Mode
AUTO.LOCAL Go to Automatic Mode (D) HOST MODE Go to Host Mode
WATCHDOG Monitors the Host device for failure.
▲▲
key
▲▲ ▼▼
key
▼▼
CONT A CT 4
ALARM ACK
CONT A CT 5
HOST MODE
8. WATCHDOG
Defines function of the watchdog contact(s) for monitoring the Host.
(D) DISABLED
ENABLED
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 5, Software Configuration 27
DISPLAY
MENU
WATCHDOG
DISABLED
+
or
Software
CONFIG.
LINE FREQ.
60 Hz
OUTPUT 1
OFF
PID ACTION
REVERSE
STN. NAME
BYPASSER
9. LINE FREQ.
Specifies the power source frequency.
(D) 60 Hz
50 Hz
10. OUTPUT 1
Defines the function of the 1st output.
(D) OFF Deactivates output
ALARM (Digital only)
COMM.ONLY Output addressable only through communications
11. PID.ACTION
Select the PID control action.
DIRECT
(D) REVERSE
12. STN. NAME
Allows you to enter a nine character message to name the station. To use: The first character of the 3rd display will be flashing. Use the to scroll through characters. Press FAST to enter the selection and move to next digit. Press MENU to advance to next parameter.
(D) BYPASSER
▲▲
and keys
▲▲
LOCAL OUT .
AUTO.LO.LIM.
0%
AUTO.HI.LIM.
100%
MAN. OUT1
0.0%
MAN. OUT2
100.0%
LOCAL OUT.
To configure the local output control.
1. AUTO.LO.LIM.
Selects how low the Automatic PID output can be adjusted.
(R) 0% to 100% (D) 0%
2. AUTO.HI.LIM.
Selects how high the Automatic PID output can be adjusted.
(R) 0% to 100% (D) 100%
3. MAN. OUT1
Selects the Manual Mode preset output #1.
(R) –5.0% to 105.0% (D) 0.0%
4 MAN. OUT2
Selects the Manual Mode preset output #2.
(R) –5.0% to 105.0% (D) 100.0%
Escape to operating mode Next parameter Next menu Next value
28 Chapter 5, Software Configuration 531 User's Manual
DISPLAY
MENU
FAST
MENU
+
or
Software
FAST
MENU
LOCAL OUT .
5. PWR.UP:MODE
Selects the power-up mode for the 531.
MANUAL Manual Mode
HOST MODE Host Mode (D) LAST MODE
AUTO.LOCAL Automatic Mode (must have a valid PV signal )
6. MAN. PWR.UP
Determines the output percentage when the 531 powers up in Manual Mode .
(R) –0.5% to 105% (D) LAST OUT
PV INPUT
For configuring the process variable (PV) input. The whole menu appears only if PV indicator is enabled.
1. PV TYPE
Selects the particular sensor or input range.
F
OR
T/C I
NPUT
:
(D) J T/C
E T/C
K T/C
B T/C
N T/C
R T/C
S T/C
T T/C
W T/C
W5 T/C
PLAT.II T/C
FOR RTD I (D) DIN RTD
JIS RTD
SAMA RTD
NPUT
:
FOR V
OLTAGE INPUT
(D) 1-5 V
0-5 V
0-10 mV
0-30 mV
0-60 mV
0-100 mV
+/–25 mV
:
F
OR CURRENT (M
(D) 4-20 mA
0-20 mA
A)
NPUT
PWR.UP:MODE
LAST MODE
MAN. PWR.UP
LAST OUT
PV INPUT
PV TYPE
:
(D)
2. DEG. F/C/K
Selects the temperature unit if using a thermocouple or RTD.
(D) FAHR.
CELSIUS
KELVIN
3. DECIMAL
Specifies the decimal point position.
FOR V/MA INPUT:FOR RTD INPUT: (D) XXXXX (D) XXXXX
XXXX.X XXXX.X
XXX.XX
XX.XXX
X.XXXX
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 5, Software Configuration 29
DISPLAY
MENU
DEG. F/C/K
FAHR.
DECIMAL
XXXXX
+
or
Software
PV INPUT
LINEARIZE
NONE
LOW RANGE
(D)
HI RANGE
(D)
FILTER
0
4. LINEARIZE
Specifies how to linearize the input. For V/mA Inputs only (Thermocouple and RTD inputs are automatically linearized).
(D) NONE Normal linearization (2 point)
SQR. ROOT Square root linearization
CUSTOM 15-point custom linearization curve
5. LOW RANGE
Specifies the engineering unit value corresponding to the lowest input value, e.g. 4 mA. For V/mA input only.
(R) –9999 to 99999 (Maximum is HI RANGE) (D) Dependent upon the input selection
6. HI RANGE
Specifies the engineering unit value corresponding to the highest input value, e.g. 20 mA. For V/mA input only.
(R) –9999 to 99999 (Minimum is LOW RANGE) (D) Dependent on the input selection
7. FILTER
Defines the setting in seconds for the low pass input filter.
(R) 0 to 120 (D) 0
PV OFFSET
0
PV GAIN
1.000
PV BREAK
0%
PV.RESTORE
AUTO.LOCAL
8. PV OFFSET
Defines the offset to the process variable in engineering units.
(R) –9999 to 99999 (D) 0
9. PV GAIN
Defines the gain to the process variable. For V/mA input only.
(R) 0.100 to 10.000 (D) 1.000
10. PV BREAK
Determines the manual output value if the PV input is broken (station switches to Manual Mode).
(R) –5% to 105% (D) 0%
11. PV.RESTORE
Determines manual output (source) upon PV restoration.
MAN. LAST Maintain the last output from Manual Mode
(D) AUTO.LOCAL Return to Automatic Control (and output)
Escape to operating mode Next parameter Next menu Next value
30 Chapter 5, Software Configuration 531 User's Manual
DISPLAY
MENU
FAST
MENU
+
or
Software
FAST
MENU
CUST . LINR.
Defines a custom linearization curve for the process variable input. The curve may be either ever increasing or ever decreasing. However, plateaus or flat spots (adjacent points with the same PV) are allowable.
The curve has 15 points. Points 1 and 15 are fixed to the low and high end of the input range (respectively) and only require you to set a corresponding PV value. Points 2 through 14 (the X points) require you to set both the input and PV values.
NOTE: Changing the PV TYPE parameter in the PV INPUT menu clears the custom linearization curve and resets the linearization type to NORMAL. You must again select CUSTOM for the linearization type and reenter your curve, adjusted for the new input type.
1. 1ST. INPUT
Specifies the input signal for to the first point.
(D) The low end of the appropriate input range (e.g. 4.00 mA)
2. 1ST. PV
Specifies the engineering unit value for to the first point.
(R) –9999 to 99999 (D) 0
3. XTH. INPUT
Specifies the input signal for to the XTH point (X is 2 to 14) .
(R) Any value greater than the first input (D) The low end of the appropriate input range (e.g. 4.00 mA)
CUST . LINR.
1ST . INPUT
(D)
1ST . PV
0
XTH. INPUT
(D)
4. XTH. PV
Specifies the engineering unit value for to the XTH point (X is 2 to 14).
(R) –9999 to 99999 (D) 0
You do not have to use all 15 points. Whenever the XTH INPUT becomes the high end of the input range, that will be the last point in the table.
XTH. PV
0
5. 15TH. INPT.
Specifies the input signal for to the 15th point.
(R) –9999 to 99999 (D) The high end of the appropriate input range (e.g. 20.00 mA)
15TH. INPT.
(D)
6. 15TH. PV
Specifies the engineering unit value for to the 15th point.
(R) –9999 to 99999 (D) 0
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 5, Software Configuration 31
DISPLAY
MENU
+
15TH. PV
0
or
Software
RSP INPUT
RSP TYPE
(D)
RSP LO W
0
RSP HIGH
1000
RSP OFFSET
0
RSP INPUT
For configuring the remote setpoint (if enabled).
1. RSP TYPE
Specifies type of input signal that will be used for the setpoint indicator.
IF THE JUMPER IS IN THE MA POSITION IF THE JUMPER IS IN THE V POSITION: (D) 4-20 mA (D) 1-5 V
0-20 mA 0-5 V
2. RSP LOW
Specifies the engineering unit value corresponding to the lowest setpoint indicator input value, e.g. 4 mA.
(R) –9999 to 99999 (D) 0
3. RSP HIGH
Specifies the engineering unit value corresponding to the highest setpoint indicator input value, e.g. 20 mA.
(R) –9999 to 99999 (D) 1000
4. RSP.OFFSET
Defines the offset to the remote setpoint in engineering units.
(R) –9999 to 99999 (D) 0
5. RSP GAIN
RSP GAIN
1.000
Defines the gain to the remote setpoint.
(R) 0.100 to 10.000 (D) 1.000
6. TRACKING
TRACKING
YES
Determines whether or not the local SP will track the remote SP (upon RSP break, or switch to local from remote SP).
(D) YES
NO
7. RSP.RESTOR.
RSP.RESTOR.
REMOTE SP
Escape to operating mode Next parameter Next menu Next value
DISPLAY
Determines RSP (source) upon RSP input restoration.
LOCAL SP
(D) REMOTE SP
MENU
FAST
MENU
+
or
32 Chapter 5, Software Configuration 531 User's Manual
Software
FAST
MENU
ALARMS
For configuring alarms.
1. ALM. TYPE:1
This defines the type of alarm for alarm 1.
(D) OFF Deactivates the first alarm
LOCAL Causes an alarm when in local control (Host flag)
HIGH PV High alarm based on the process variable
LOW PV Low alarm based on the process variable
RATE Selects a rate-of-change alarm
BAND
DEVIATION
HIGH CV High alarm based on the control value
LOW CV Low alarm based on the control value
2. ALARM SP:1
Specifies the alarm set point for alarm 1.
FOR ALM. TYPE:1 =
RATE HIGH CV (R) –9999 to 99999 units (R) 0.0–100.0% (R) The PV range (D) 0 (D) 0.0% (D) Dependent on
value
OR LOW CV ANY OTHER TYPE
ALARMS
ALM. TYPE:1
OFF
ALARM SP:1
(D)
LOW RANGE
3. DEADBAND:1
Defines the deadband for alarm 1.
FOR ALM. TYPE:1 =
HIGH CV OR LOW CV ANY OTHER TYPE (R) 0.1%–100.0% (R) 1 to 9999 (D) 0.2% (D) 2
4. RELAY:1
Defines the state of the relay in the alarm condition for alarm 1.
(D) RELAY ON
RELAY OFF
5. LATCHING:1
Defines the latching sequence of alarm 1.
(D) LATCH
NO LATCH
6. ACK.:1
Defines whether alarm 1 may be acknowledged.
(D) ENABLED Allows the alarm to be acknowledged
DISABLED Prevents existing alarm from being acknowledged
DEADBAND:1
2
RELAY:1
RELAY ON
LATCHING:1
LATCH
A CK.:1
ENABLED
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 5, Software Configuration 33
DISPLAY
MENU
+
or
Software
ALARMS
POWER UP:1
NORMAL
MESSAGE:1
ALARM 1
ALM. TYPE:2
OFF
7. POWER UP:1
Defines how alarm 1 will be treated on power up.
(D) NORMAL Alarm depends on process variable
ALARM Power up in alarm regardless of PV
DELAYED Must leave alarm condition and reenter before activating the alarm
8. MESSAGE:1
Allows you to enter a nine character message associated with alarm 1. The first character of the 3rd display will be flashing. To enter message, press arrow keys to scroll through character set. Press FAST to enter the selec­tion and move to next digit. Press MENU to advance to next parameter.
(D) ALARM 1
9. ALM. TYPE:2
This defines the type of alarm for alarm 2.
(D) OFF Deactivates the first alarm
LOCAL Causes an alarm when in local control (Host flag)
HIGH PV High alarm based on the process variable
LOW PV Low alarm based on the process variable
RATE Selects a rate-of-change alarm
BAND
DEVIATION
HIGH CV High alarm based on the control value
LOW CV Low alarm based on the control value
10. ALARM SP:1
Specifies the alarm set point for alarm 2.
ALARM SP:2
(D)
FOR ALM. TYPE:2 =
RATE HIGH CV (R) –9999 to 99999 units (R) 0.0–100.0% (R) The PV range (D) 0 (D) 0.0% (D) Dependent on
OR LOW CV ANY OTHER TYPE
11. DEADBAND:2
DEADBAND:2
2
Defines the deadband for alarm 2.
FOR ALM. TYPE:2 =
HIGH CV OR LOW CV ANY OTHER TYPE (R) 0.1%–100.0% (R) 1 to 9999 (D) 0.2% (D) 2
12. RELAY:2
RELAY:2
RELAY ON
Escape to operating mode Next parameter Next menu Next value
DISPLAY
Defines the state of the relay in the alarm condition for alarm 2.
(D) RELAY ON
RELAY OFF
MENU
FAST
MENU
+
LOW RANGE value
or
34 Chapter 5, Software Configuration 531 User's Manual
FAST
MENU
13. LATCHING:2
Defines the latching sequence of alarm 2.
(D) LATCH
NO LATCH
Software
ALARMS
LATCHING:2
LATCH
14. ACK.:2
Defines whether alarm 2 may be acknowledged.
(D) ENABLED Allows the alarm to be acknowledged
DISABLED Prevents the alarm acknowledgment while alarm condition exists.
15. POWER UP:2
Defines how alarm 2 will be treated on power up.
(D) NORMAL Alarm depends on process variable
ALARM Always power up in alarm regardless of process variable
DELAYED Must leave alarm condition and reenter before activating the alarm
16. MESSAGE:2
Allows you to enter a nine character message associated with alarm 2. The first character of the 3rd display will be flashing. To enter message, press arrow keys to scroll through character set. Press FAST key to enter the selection and move to next digit. Press MENU key to advance to next pa­rameter.
(D) ALARM 2
17. RATE TIME
Defines the time period (in seconds) over which a rate-of-change alarm condition will be determined.
(R) 1 to 3600 (D) 5
A CK.:2
ENABLED
POWER UP:2
NORMAL
MESSAGE:2
ALARM 2
RATE TIME
5
SECURITY
For configuring the security function.
1. SEC. CODE
Defines security code for temporarily unlocking the station.
(R) –9999 to 99999 (D) 0
2. HOST KEY
Defines lockout status of the HOST key (mode changes via the HOST key).
(D) UNLOCKED
LOCKED
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 5, Software Configuration 35
DISPLAY
MENU
SECURITY
SEC. CODE
0
HOST KEY
UNLOCKED
+
or
Software
SECURITY
MAN. KEY
UNLOCKED
MAN. OUT
UNLOCKED
LOCAL SP
UNLOCKED
ALARM ACK UNLOCKED
3. MAN. KEY
Defines lockout status of the MANUAL key (mode changes via the MANUAL key).
(D) UNLOCKED
LOCKED
4. MAN. OUT
Defines lockout status of the changes to the local output (via the keys).
(D) UNLOCKED
LOCKED
5. LOCAL SP
Defines lockout status of the changes to the local setpoint (via the
▼▼
keys).
▼▼
(D) UNLOCKED
LOCKED
6. ALARM ACK.
Defines lockout status of the ACK key (alarm acknowledgment).
(D) UNLOCKED
LOCKED
▲▲
and
▲▲
▲▲
and
▲▲
▼▼
▼▼
OPERATION
UNLOCKED
CONFIGURE UNLOCKED
SER. COMM.
STATION
1
7. OPERATION
Defines lockout status of the OPERATION menu parameters.
(D) UNLOCKED
LOCKED
8. CONFIGURE
Defines lockout status of the other 8 configuration parameters.
(D) UNLOCKED
LOCKED
SER. COMM.
For configuring the serial communications features.
1. STATION
Defines the unit’s station address.
(R) 1 to 99
OFF Disables the communications function.
(D) 1
Escape to operating mode Next parameter Next menu Next value
36 Chapter 5, Software Configuration 531 User's Manual
DISPLAY
MENU
FAST
MENU
+
or
Software
FAST
MENU
SER. COMM.
2. BAUD RATE
Defines the baud rate.
1200 BPS
2400 BPS
4800 BPS
(D) 9600 BPS
19200 BPS
3. CRC
Defines whether CRC (cyclic redundancy check) is being calculated.
(D) YES
NO
OPERATION
For modifications to the transition functions. Use the same PID parameters as your HOST device.
1. PROP. BAND
Defines the proportional band for the PID set.
(R) 0.1% to 999.0% (D) 50.0%
BA UD RATE
9600
CRC
YES
OPERATION
PROP. BAND
50.0%
2. RESET
Defines the integral time for the PID set.
(R) 1 to 9999 seconds/repeat (D) 30
3. RATE
Defines the derivative time for the PID set.
(R) 0 to 600 seconds (D) 1
4. LOADLINE
Defines the loadline (manual reset) for the PID set.
(R) 0% to 100% (D) 0%
5. SP SOURCE
Selects a local or remote setpoint.
(D) LOCAL SP
REMOTE SP (only for 2nd input V or mA)
RESET
20
RATE
1
LOADLINE
0%
SP SOURCE
LOCAL SP
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 5, Software Configuration 37
DISPLAY
MENU
+
or
Software
OPERATION
MAN. RAMP
OFF
HOST RAMP
OFF
6. MAN. RAMP
Determines ramping value for output to a defined Manual output value (MAN. OUT1, MAN. OUT2 or PV BREAK) upon transfer to Manual Mode.
(R) 0.1% to 999.9% per minute (D) OFF
7. HOST RAMP
Determines ramping value for output to the Host Mode CV value, upon transfer to Host Mode.
(R) 0.1% to 999.9% per minute (D) OFF
Escape to operating mode Next parameter Next menu Next value
38 Chapter 5, Software Configuration 531 User's Manual
DISPLAY
MENU
FAST
MENU
+
or
Software
PARAMETER VALUE CHARTS
Record the values for the various configuration menu parameters on the charts in this section.
NOTE:
You may want to photocopy these pages instead of entering the values on the master sheets.
CONFIG.
For configuring the input and output hardware assignments.
1. LOST HOST Selects the type of local backup when host CV breaks.
2. HOST. RESTR. Selects the 531 mode upon host CV restoration.
3. CONTACT 1 Defines the operation of the 1st digital input.
4. CONTACT 2 Defines the operation of the 2nd digital input.
5. CONTACT 3 Defines the operation of the 3rd digital input.
6. CONTACT 4 Defines the operation of the 4th digital input.
7. CONTACT 5 Defines the operation of the 5th digital input.
8. WATCHDOG Defines function of Host watchdog monitor.
9. LINE FREQ. Specifies the power source frequency.
10. OUTPUT 1 Defines the function of the 1st output.
11. PID.ACTION Select the PID control action.
12. STN. NAME Specifies a nine character message to name the station.
LOCAL OUT .
To configure the local output control.
1. AUTO.LO.LIM. Selects low limit for adjusting the Automatic PID output.
2. AUTO.HI.LIM. Selects high limit for adjusting the Automatic PID output.
3. MAN. OUT1 Selects the Manual Mode preset output #1. 4 MAN. OUT2 Selects the Manual Mode preset output #2.
5. PWR.UP:MODE Selects the power-up mode for the 531.
6. MAN. PWR.UP Determines output % for in Manual Mode power up.
531 User's Manual Chapter 5, Software Configuration 39
Software
PV INPUT
For configuring the process variable (PV) input. The whole menu appears only if PV indicator is enabled.
1. PV TYPE Selects the particular sensor or input range.
2. DEG. F/C/K Selects the temperature unit for a T/C or RTD.
3. DECIMAL Specifies the decimal point position.
4. LINEARIZE Specifies how to linearize the input.
5. LOW RANGE Specifies the lowest input value (engineering units).
6. HI RANGE Specifies the highest input value (engineering units).
7. FILTER Defines setting in seconds for the low pass input filter.
8. PV OFFSET Defines offset to the PV in engineering units.
9. PV GAIN Defines gain to the PV.
10. PV BREAK Determines the manual output if PV input breaks.
11. PV.RESTORE Determines manual output (source) upon PV restoration.
40 Chapter 5, Software Configuration 531 User's Manual
CUST . LINR.
Defines a custom linearization curve for the process variable input.
1. 1ST. INPUT Specifies the input signal for the 1st point.
2. 1ST. PV Specifies the engineering unit value for the 1st point.
3. 2ND. INPUT Specifies the input signal for the 2nd point.
4. 2ND. PV Specifies the engineering unit value for the 2nd point.
5. 3RD. INPUT Specifies the input signal for the 3rd point.
6. 3RD. PV Specifies the engineering unit value for the 3rd point.
7. 4TH. INPUT Specifies the input signal for the 4th point.
8. 4TH. PV Specifies the engineering unit value for the 4th point.
9. 5TH. INPUT Specifies the input signal for the 5th point.
10. 5TH. PV Specifies the engineering unit value for the 5th point.
Software
11. 6TH. INPUT Specifies the input signal for the 6th point.
12. 6TH. PV Specifies the engineering unit value for the 6th point.
13. 7TH. INPUT Specifies the input signal for the 7th point.
14. 7TH. PV Specifies the engineering unit value for the 7th point.
15. 8TH. INPUT Specifies the input signal for the 8th point.
16. 8TH. PV Specifies the engineering unit value for the 8th point.
17. 9TH. INPUT Specifies the input signal for the 9th point.
18. 9TH. PV Specifies the engineering unit value for the 9th point.
19. 10TH. INPT. Specifies the input signal for the 10th point.
20. 10TH. PV Specifies the engineering unit value for the 10th point.
21. 11TH. INPT. Specifies the input signal for the 11th point.
22. 11TH. PV Specifies the engineering unit value for the 11th point.
23. 12TH. INPT. Specifies the input signal for the 12th point.
24. 12TH. PV Specifies the engineering unit value for the 12th point.
25. 13TH. INPT. Specifies the input signal for the 13th point.
26. 13TH. PV Specifies the engineering unit value for the 13th point.
27. 14TH. INPT. Specifies the input signal for the 14th point.
28. 14TH. PV Specifies the engineering unit value for the 14th point.
29. 15TH. INPT. Specifies the input signal for the 15th point.
30. 15TH. PV Specifies the engineering unit value for the 15th point.
531 User's Manual Chapter 5, Software Configuration 41
Software
RSP INPUT
For configuring the remote setpoint (if enabled).
1. RSP TYPE Specifies type of input signal for the remote SP.
2. RSP LOW Lowest (engineering unit) value for the remote SP.
3. RSP HIGH Highest (engineering unit) value for the remote SP.
4. RSP.OFFSET Defines the offset to the remote SP in engineering units.
5. RSP GAIN Defines the gain to the remote setpoint.
6. TRACKING Determines whether or not local SP tracks remote SP.
7. RSP.RESTOR. Determines SP (source) upon RSP input restoration.
ALARMS
For configuring alarms.
1. ALM. TYPE:1 Defines the type of alarm for alarm 1.
2. ALARM SP:1 Specifies the alarm set point for alarm 1.
3. DEADBAND:1 Defines the deadband for alarm 1.
4. RELAY:1 Defines the state of the relay for alarm 1.
5. LATCHING:1 Defines the latching sequence of alarm 1.
6. ACK.:1 Defines whether alarm 1 may be acknowledged.
7. POWER UP:1 Defines how alarm 1 will be treated on power up.
8. MESSAGE:1 A nine character message for alarm 1.
9. ALM. TYPE:2 Defines the type of alarm for alarm 2.
10. ALARM SP:2 Specifies the alarm set point for alarm 2.
11. DEADBAND:2 Defines the deadband for alarm 2.
12. RELAY:2 Defines the state of the relay for alarm 2.
13. LATCHING:2 Defines the latching sequence of alarm 2.
14. ACK.:2 Defines whether alarm 2 may be acknowledged.
15. POWER UP:2 Defines how alarm 2 will be treated on power up.
16. MESSAGE:2 A nine character message for alarm 2.
17. RATE TIME Defines the time period for a rate-of-change alarm.
42 Chapter 5, Software Configuration 531 User's Manual
SECURITY
For configuring the security function.
1. SEC. CODE Security code for temporarily unlocking the station.
2. HOST KEY Lockout status of the HOST key.
3. MAN. KEY Lockout status of the MANUAL key.
4. MAN.OUT Lockout status of the changes to the local output.
5. LOCAL SP Lockout status of the changes to the local setpoint.
6. ALARM ACK. Lockout status of the ACK key.
7. OPERATION Lockout status of the OPERATION Menu parameters.
8. CONFIGURE Lockout status of the other 8 configuration parameters.
Software
SER. COMM.
For configuring the serial communications features.
1. STATION Defines the unit’s station address.
2. BAUD RATE Defines the baud rate.
3. CRC Defines whether CRC is being calculated.
OPERATION
For modifications to the transition functions. Use the same PID parameters as your HOST device.
1. PROP. BAND Defines the proportional band for the PID set.
2. RESET Defines the integral time for the PID set.
3. RATE Defines the derivative time for the PID set.
4. LOADLINE Defines the loadline (manual reset) for the PID set.
5. SP SOURCE Selects a local or remote setpoint.
6. MAN.RAMP Determines ramping for output to Manual output value.
7. HOST RAMP Determines ramping for output to the Host Mode CV.
531 User's Manual Chapter 5, Software Configuration 43
Software
44 Chapter 5, Software Configuration 531 User's Manual
FAST
MENU
CHAPTER 6 531 APPLICA TIONS
Applications
The 531 has a variety of user-programmable control features and capabilities. This chapter describes how to apply them.
SECTION.............................................................................................................. PAGE
531 Operation.................................................................................45
Alarms............................................................................................46
Digital Inputs...................................................................................50
Watchdog Monitor ..........................................................................51
Process Variable and Setpoint........................................................51
Input Linearization ..........................................................................53
Ramp to a Control Value .................................................................54
Security ..........................................................................................55
Process Variable Reading Correction .............................................56
Serial Communications...................................................................56
531 OPERATION
The 531 PID Backup Station provides PID based control backup for critical control loops. It is normally installed between a Host device and final control element. The Host device may be a PLC, DCS or single loop controller (SLC). The final control element may be a valve actuator, positioning device, power control unit for an electric heating element, pump or other control device. The control signal must always be a 4-20mA proportional signal.
Host Mode (Default Mode)
The HOST key is lit.
In Host Mode, the 531 is transparent to the control loop; it passes the control signal from the Host device without any degradation.
The 531 constantly monitors the CV and uses the last good signal as a potential CV for the Automatic Mode.
The 531 can be removed from the case without disrupting the Host signal; it is not a point of failure.
The 531 switches to Host Mode due to:
- Return of the Host signal
- Keypad selection
- Closure of a digital contact; or
- Commands through the RS-485 port.
Upon return of the Host signal, the 531 can be programmed to
- Return control to the Host Mode immediately;
- Ramp to the new CV at a predetermined rate; or
- Remain in the current mode, where the operator can determine whether
or not the Host signal is valid.
▲▲
The operator can modify the local SP using the
The operator can enter all the configuration menus.
and
▲▲
▼▼
keys.
▼▼
NOTE:
Available capabilities depend upon the hardware option you specified and ordered.
NOTE:
In this chapter, the following abbreviations are used:
CV - Control signal SP - Set point PV - Process variable
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 6, Applications 45
DISPLAY
MENU
+
or
Applications
Automatic Mode
Neither the HOST nor MANUAL keys are lit.
The 531 switches to Automatic (PID) Mode due to:
- Loss of the Host signal
- Keypad selection
- Closure of a digital contact; or
- Commands through the RS-485 port.
Upon switching to Automatic Mode, the 531 generates a control signal based on PID control.
The 531 executes a bumpless transfer to the new CV while in PID mode (no ramping needed).
▲▲
The operator can modify the local SP using the
and
▲▲
▼▼
keys.
▼▼
The operator can only enter the OPERATION menu (other configuration menus are disabled).
Manual Mode
The MANUAL key is lit.
The 531 switches to Manual Mode due to:
- Loss of the Host signal and PV input
- Keypad selection
- Closure of a digital contact; or
- Commands through the RS-485 port.
In Manual Mode, the 531 can go to a predetermined output. The 531 can also be set to ramp the last Host signal to the new output.
The operator can modify the CV signal using the
The operator can modify the local SP using the
▲▲
and
▲▲
▲▲
and
▲▲
The operator can enter all the configuration menus.
▼▼
keys.
▼▼
▼▼
keys.
▼▼
NOTE:
Refer to Chapter 4 for information on wiring for alarms.
ALARMS
The 531 has 2 alarms available. It indicates alarm conditions by:
Lighting up the alarm icon(s).
NOTE: Refer to “Alarm Operation” in
Chapter 2 for information on operating alarms.
Displaying a custom message in the 3rd display
Illuminating the ACK key if the alarm is acknowledgeable.
Each alarm can be assigned one of 6 different types. Also, by adding an output module, one of the alarms can be tied to a relay output. To assign an alarm:
1. Press FAST + MENU to toggle to the ALARM menu.
2. Press MENU to select the first parameter ALM.TYPE:1 and select its type (choose one of the following) using the
▲▲
and keys:
▲▲
LOCAL
(Host Flag) If tied to a relay output, a local alarm notifies the Host that the 531 has taken over the output in Manual or Automatic mode. You can choose LOCAL for only one of the alarms. Useful when the Host performs logging functions for Statistical Process Control (SPC), or to prevent reset windup.
Escape to operating mode Next parameter Next menu Next value
DISPLAY
MENU
FAST
MENU
+
or
46 Chapter 6, Applications 531 U ser's Manual
FAST
MENU
HIGH PV
Occurs when the process variable exceeds the alarm setpoint.
LOW PV
Occurs when the process variable goes below the alarm setpoint.
RATE
Use to signal an alarm when the PV changes at a rate greater than that specified by the alarm setpoint and time base. For example, if you have an alarm setpoint of 10 and a time base of 5 seconds, an alarm occurs if the PV changes greater than 10 units in 5 seconds.
BAND
Creates a band twice the size of the alarm setpoint [centered] around the control setpoint. Alarm occurs when the process variable travels outside of this band. For example, if your control setpoint is 500 and the alarm setpoint is 25, the alarm occurs if the PV travels outside of the 475 to 525 range.
Alarm is dependent upon retransmission of the control setpoint. As the control setpoint changes, the band centers itself accordingly.
DEVIATION
Creates a band on one side of the control setpoint. Alarm occurs when the process variable deviates from the control setpoint by an amount greater than the alarm setpoint.
For example, if the control setpoint is 500 and the alarm setpoint is +50 (plus 50), an alarm occurs when the process variable exceeds 550. If your alarm setpoint is –50, the alarm occurs when the process variable drops below 450.
Alarm is dependent upon retransmission of the control setpoint. As the control setpoint changes, the band centers itself accordingly.
HIGH CV
Occurs when the control value exceeds the alarm setpoint.
LOW CV
Occurs when the control value goes below the alarm setpoint.
3. Press the MENU key to select the second parameter ALM.TYPE:2 and se­lect its type using the s and t keys.
Each alarm type (except a LOCAL alarm) has a number of corresponding parameters that must also be set up in the ALARM menu (steps 4 - 11).
Press the MENU key to select the rest of the parameters in the ALARM Menu, and choose their values with the
▲▲
and keys.
▲▲
4. ALARM SP:1 and ALARM SP:2 Specifies, in engineering units, the point at which the alarm occurs. For a rate-of-change alarm, it specifies the amount of change that must occur
before the alarm activates. A negative value specifies a negative rate-of­change.
5. DEADBAND:1 and DEADBAND:2 Specifies the range through which the PV must travel before leaving an alarm
condition (see alarm examples at the end of this section).
Applications
NOTE:
The Band and Deviation alarms are not selectable without a PV and a retransmitted SP signal.
NOTE:
The HIGH CV and LOW CV alarms, when selected, operate in both Host and Local modes.
NOTE:
Only those parameters that apply to your particular alarm type will appear as you toggle through the parameters.
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 6, Applications 47
DISPLAY
MENU
+
or
Applications
NOTE:
You can specify whether the relay is Normally Open or Normally Closed when configuring the hardware, with jumper selection only for Output 1.
This prevents frequent alarm oscillation or “chattering” if the process variable has stabilized around the alarm point.
6. RELAY:1 Specifies whether the relay will be on or off. ON means the relay is energized,
while OFF means the relay is de-energized when the station is in the alarm condition.
Most applications require the relay to energize. However, limit applications usually require the relay to de-energize.
7. LATCHING:1 and LATCHING:2 If the alarm is latching (YES), the alarm remains active after leaving the alarm
condition unless acknowledged. If the alarm is non-latching (NO) the alarm returns to its non-alarm state when
leaving the alarm condition without being acknowledged.
8. ACK.:1 and ACK.:2 ENABLED allows the operator to acknowledge an alarm at any time, even if the
control process is still in the alarm condition. DISABLED prevents the operator from acknowledging an alarm while the process
is in the alarm condition. When either alarm is available to be acknowledged, the ACK key will be
illuminated. If both alarms are acknowledgable, press the ACK key once to acknowledge alarm #1, then a second time for alarm #2. A latching alarm can always be acknowledged when it is out of the alarm condition.
9. POWER UP:1 and POWER UP:2 If you want the controller to always power up in alarm, regardless of the alarm
condition, then select ALARM. This is an excellent way to activate an alarm if there has been a power failure.
If you never want the controller to power up in alarm, regardless of alarm condition, select DELAYED. The system must leave and reenter the alarm condition before the alarm will activate. This is typically used to avoid alarms during start up.
If you want the system to power up in alarm only if it is in an alarm condition, select NORMAL.
10. MESSAGE:1 and MESSAGE:2 Allows you to enter a nine character message to display when the respective
alarm is active. The first character of the 3rd display will be flashing. Use
▼▼
and
keys to scroll through character set for each character. Press FAST
▼▼
to enter the selection and move to the next digit. Press MENU to advance to next parameter.
11. RATE TIME Defines the time period over which a specific change in process variable must
occur for the rate alarm to be activated. The amount of change is defined by the alarm setpoint. The rate-of-change is defined as the amount of change divided by the time period. In general, for a given rate-of-change, the shorter the time period, the more sensitive the rate alarm.
▲▲
▲▲
Escape to operating mode Next parameter Next menu Next value
DISPLAY
48 Chapter 6, Applications 531 U ser's Manual
MENU
FAST
MENU
+
or
FAST
MENU
Examples:
1. If the alarm setpoint is set to 10 and the time base is set to 1 second, the rate of change is 10 units per second. The process variable would only have to experience a ten unit change over a short period of time.
2. If the alarm setpoint is set to 100 and the time base set to 10, the rate of change is also 10 units per second. The PV would require a 100 unit change over a ten second period.
Notice that Example 1 is more sensitive than Example 2.
Alarm Examples
A.SP = Alarm Setpoint C.SP = Control Setpoint DB = Deadband PV = Process Variable
Applications
Figure 6.1 Alarm Examples
A. BAND ALARM EXAMPLE
IN ALARM
CONDITION
DB
PV
C.SP
DB
RELAY ENERGIZED
ICON OFF
NO ALARM CANNOT
RELAY DE-ENERGIZED
ICON ON
CANNOT ACKNOWLEDGE
RELAY ENERGIZED
ICON OFF
NO ALARM
PARAMETER SETTINGS:
ALM. TYPE:1 = BAND RELAY:1 = RELAY OFF
LATCHING = NO LATCH ACK.:1 = DISABLED
C. DEVIATION ALARM EXAMPLE
IN ALARM
C.SP
CONDITION
IN ALARM
CONDITION
TIME
RELAY DE-ENERGIZED
ICON ON
ACKNOWLEDGE
C.SP +
A.SP
C.SP – A.SP
B. HIGH PROCESS VARIABLE ALARM EXAMPLE
IN ALARM
CONDITION
PV
DB
TIME
RELAY DE-ENERGIZED
ICON OFF
NO ALARM
RELAY ENERGIZED
ICON ON
MAY ACKNOWLEDGE
RELAY DE-ENERGIZED
ICON OFF
NO ALARM
PARAMETER SETTINGS:
ALM. TYPE:1 = HIGH ALRM. RELAY:1 = RELAY ON
LATCHING = NO LATCH ACK.:1 = ENABLED
D. POWER UP ALARM EXAMPLE
PV
A.SP
A.SP
DB
DB
PV
RELAY DE-ENERGIZED
ICON OFF
NO ALARM
RELAY ENERGIZED
ICON ON
MAY ACKNOWLEDGE
MUST ACKNOWLEDGE TO SHUT OFF ICON AND DE-ENERGIZE RELAY
PARAMETER SETTINGS:
ALM. TYPE:1 = DEVIATION RELAY:1 = RELAY ON
Escape to operating mode Next parameter Next menu Next value
LATCHING:1 = LATCH ACK.1 = ENABLED
DISPLAY
531 User's Manual Chapter 6, Applications 49
C.SP + A.SP
TIME
ALARM SP:1 = ( < 0)
UNIT POWER UP
PARAMETER SETTINGS:
ALM. TYPE:1 = HIGH ALM. RELAY:1 = RELAY ON
MENU
RELAY ENERGIZED
ICON ON
MAY ACKNOWLEDGE
ALARM
CONDITION
RELAY ENERGIZED
ICON ON
CANNOT ACKNOWLEDGE
LATCHING:1 = LATCH ACK.:1 = DISABLED
+
TIME
RELAY ENERGIZED
ICON ON
MAY ACKNOWLEDGE
POWER UP:1 = ALARM
or
Applications
NOTE:
To verify your hardware configuration, check your product label on top of the 531, and compare it to the order code in Chapter 1.
DIGIT AL INPUTS
This optional feature is only available if ordered originally from the factory. For a set of 5 digital inputs can be ordered, order Product #531 -xxxxxxDx00.
If more than one digital input is closed, then the last one closed generally has priority over the others.
A closed digital input may be overridden by: another digital input, a keyboard operation, or an automatic function. A closed digital input that was overridden must be opened, in order to be “re-armed”.
If one digital input is closed and selects LOCAL, and then REMOTE is keyboard selected, the keyboard selection takes precedence.
1. Press FAST + MENU to toggle to the CONFIG. menu
▲▲
2. Press MENU to access first parameter, CONTACT:1. Use to the desired function (choose one of the following):
MAN. LAST
Contact closure switches the station to Manual Mode using the last output value.
MAN. OUT1
Contact closure switches the station to Manual Mode using the MAN.OUT1 value.
MAN. OUT2
Contact closure switches the station to Manual Mode using the MAN.OUT2 value.
ALARM ACK.
Contact closure acknowledges all active alarms. The digital input must be opened before it is “re-armed.” If the input remains closed, it will not continue to immediately acknowledge alarms as they become active.
UP KEY and DOWN KEY
Contact closure mimics the
and
keys. If the station is mounted
behind a window, this digital input allows you to use momentary contact push button to change the station’s output.
COMM. ONLY
Contact closure renders digital input status readable through communications. It will have no effect on the functions of the station itself.
DISP. KEY
Contact closure mimics the DISPLAY key.
MENU KEY
Contact closure mimics the FAST key.
FAST KEY
Contact closure mimics the FAST key.
RST. INHBT.
Contact closure inhibits local PID reset action.
REMOTE SP
Contact closure selects the remote setpoint for use in Automatic Mode.
and
▲▲
▼▼
to toggle
▼▼
Escape to operating mode Next parameter Next menu Next value
DISPLAY
50 Chapter 6, Applications 531 U ser's Manual
MENU
FAST
MENU
+
or
FAST
MENU
LOCAL SP
Contact closure selects the local setpoint for use in Automatic Mode.
AUTO.LOCAL
Contact closure switches the station to Automatic Mode.
HOST MODE
Contact closure switches the station to Host Mode.
WATCHDOG
Contact closure activates the watchdog monitor.
2. Press MENU to access contact parameters, CONTACT:2, CONTACT:3,
▲▲
CONTACT:4, and CONTACT:5. Use the
and
keys to toggle to the desired
▲▲
function for these as well.
WA TCHDOG MONIT OR
This feature is only available with the factory installed five digital inputs. The 531 normally uses the presence of the CV for determining Host failure. In
some cases, however, a Host can “lock up” or “hang up,” leaving its mA control output frozen at a constant value.
To protect against this type of Host failure, one of the Host relay outputs may be programmed to provide a pulse, or “watchdog,” output. A 531 digital input can be set to monitor this pulse. If the pulse state does not change (toggle) in a 0.4 to 2.5 second period, then the 531 will record the Host’s CV signal as unreliable, and appropriately report a lost CV as Host failure.
To configure a digital input as a watchdog monitor:
1. Press FAST + MENU to toggle to the CONFIG. menu.
2. Press MENU to access parameter CONTACT:1 (or 2, 3, 4 or 5). Use the
or
key to select the value WATCHDOG.
3. Press MENU to access parameter WATCHDOG. To activate the watchdog monitor, set this value to ENABLED.
▲▲
▲▲
Applications
PROCESS VARIABLE AND SETPOINT
The 531 can be set up to display the process variable and a retransmitted setpoint. The process variable can be a direct input of a thermocouple, RTD, mA or voltage signal. Milliamp and voltage signal can be displayed as 0–100% or scaled in Engineering units. Custom linearization is also available.
Select the Process Variable Display Range
1. Press the FAST + MENU keys to toggle to the PV INPUT menu. Press MENU to access the following parameters. Use the
2. PV TYPE Defines the range of the input signal (T/C, RTD, mA or voltage signal). The type
of signal is governed by the hardware jumper selections (see Chapter 3).
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 6, Applications 51
DISPLAY
▲▲
▼▼
and
keys to assign values.
▲▲
▼▼
MENU
+
or
Applications
3. DEG. F/C/K Selects the units for temperature display (appears only for T/C and RTD input
types).
4. DECIMAL Sets the position of the decimal point (appears only for V/mA and RTD input
types).
5. LINEARIZE Selects the type of PV linearization being used (appears only for V/mA input
types).
6. LOW RANGE Sets the value in engineering units corresponding to the low PV input value
(appears only for v/mA input types).
7. HI RANGE Sets the value in engineering units corresponding to the high PV input value
(appears only for V/mA inputs types).
8. FILTER Sets the amount of PV filtering to be used.
9. PV OFFSET Sets a constant offset to be applied to the PV input.
10. PV GAIN Sets a constant gain to be applied to the PV input (appears only for V/mA
input types).
11. PV BREAK Sets the manual output value if the PV input is broken while running local
PID.
12. PV. RESTORE Sets the mode upon restoration of the PV input.
Set Point Display Range
The 531 can be set up to display a retransmitted setpoint from the Host device.
1. Press FAST + MENU to toggle to the RSP INPUT Menu . Press MENU to
▲▲
access the following parameters, and use
2. RSP TYPE Defines the input signal range: 0-20mA or 4-20mA (or 0-5V or 1-5V).
3. RSP LOW and RSP HIGH Define the range of the set point in engineering units. The correct range will
be dependent on the source of the set point signal.
4. RSP.OFFSET Define the offset of the remote set point in engineering units.
5. RSP GAIN Define the gain to the remote set point in engineering units.
6. TRACKING Determines if the Local SP will track the Remote SP upon RSP break or
transfer to the local SP value.
Escape to operating mode Next parameter Next menu Next value
DISPLAY
MENU
FAST
MENU
+
52 Chapter 6, Applications 531 U ser's Manual
▼▼
and
to assign values.
▲▲
▼▼
or
FAST
MENU
7. RSP.RESTOR. Define the setpoint (source) upon remote set point signal restoration from
break.
INPUT LINEARIZA TION
Thermocouple and RTD Linearization
When you select a thermocouple or RTD input, the station automatically linearizes the incoming signal. The station uses internal lookup tables to provide an accurate reading of the temperature being sensed.
Square Root Linearization
Many flow transmitters generate a nonlinear signal corresponding to the flow being measured. The station must have the square root of this signal in order to use it. The station has the capability to perform this function for itself.
To utilize this feature, you must have a voltage or milliamp input.
1. Press FAST + MENU to toggle to the PV INPUT Menu .
▲▲
2. Press MENU to access the LINEARIZE parameters, and use the assign value SQR. ROOT.
For the first 1% of the input span, the input is treated in a linear fashion. After that, the input is a value calculated using the formula shown in Figure 6.2.
and
▲▲
to
Applications
PV = Low Range + [ (Hi Range – Low Range) (V
Where: Hi Range is the high end of the process variable.
Low Range is the low end of the process variable. V
is the actual voltage or current value of the input.
input
V
is the high end of the input signal range (e.g. 5 volts or 20 mA).
high
V
is the low end of the input signal range (e.g. 1 volt or 4 mA).
low
Example: Process variable range is 0 – 1000.
Input signal range is 1–5 volts Input signal is 3 volts. Therefore, the PV will be—
PV = 0 +
[(1000 – 0) (3-1) / (5–1) ] = 1000 .5 = 707
input
- V
low
/ (V
high
– V
low
) ]
Custom Linearization
Custom linearization allows you to take virtually any nonlinear signal and linearize it using a 15-point straight line approximation curve. Typical applications are linearizing signals from nonlinear transducers, or controlling volume based on level readings for irregularly-shaped vessels. To define the function, you must enter data point pairs—the engineering units corresponding to a particular voltage or current input.
1. Press FAST + MENU to toggle to the INPUT Menu .
▲▲
2. Press MENU to access the LINEARIZE parameters, and use the keys to assign value CUSTOM.
3. Press FAST + MENU to toggle to the CUST.LINR. Menu
4. The parameter 1ST.INPUT is fixed at the low end of the mA or Voltage input range.
and
▲▲
▼▼
▼▼
Figure 6.2 Square Root Linearization Formula
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 6, Applications 53
DISPLAY
MENU
+
or
Applications
5. For parameter 1ST.PV, define the corresponding process variable value in engineering units.
6. For the 2ND.INPUT though XTH.INPUT (X being your last data point number), define the milliamp or voltage input of the corresponding data point.
7. For the 2ND.PV through the XTH.PV (X being your last data point number), define the milliamp or voltage input of the corresponding data point.
Once the various points are defined, the station interpolates the values between the points using a straight line relationship between the points.
15th PV
Figure 6.3 Custom Linearization Curve
NOTE: The resulting linearization curve must
be either ever-increasing or ever­decreasing.
PV VALUE
(IN ENGINEERING
UNITS)
10th PV
5th PV
1st PV
1st Input
5th Input
10th Input
15th Input
INPUT VALUE
(IN MILLIAMPS OR VOLTAGE)
IMPORTANT!! If you make any modifications to a set curve, you must re-enter all points in
order, from 1 to X. Record the data in the Set Up Charts in Chapter 5.
RAMP T O A CONTROL VALUE
The “ramp to control value” function is useful for all other transitions where the rate-of-change of the control value must be limited, or under any circumstances where there is likely to be a significant difference between control values at the mode transition time.
Under normal operating conditions, the 531 passes the Host signal to the final control element without modification, and stores the current CV value with each cycle of the CPU. Upon loss of the Host signal (or switching out of Host Mode), the 531:
Switches to Automatic Mode (LOST HOST = AUTO.LOCAL), automatically initiating a bumpless transfer from the last known good CV to the new PID­derived CV;
Switches to Manual Mode using the last known good value from the Host (LOST HOST = MAN.LAST); or
Switches to Manual Mode using one of two preset outputs (LOST HOST = MAN.OUT1 or MAN.OUT2).
Escape to operating mode Next parameter Next menu Next value
DISPLAY
54 Chapter 6, Applications 531 U ser's Manual
MENU
FAST
MENU
+
or
FAST
MENU
A preset output value may be considerably different from the Host CV, so the transfer may not be bumpless. The ramp to control value function allows the operator to select the ramping time for the output value change, thus smoothing the transition.
1. Press the MENU key to access the OPERATIONS Menu .
2. MAN. RAMP selects the ramping percentage (rate) for gradually changing output to the predefined Manual output value (when switching out of Host Mode).
The choices are OFF, or 0.1% to 999.9% per minute. 0.1% per minute is equal to 6.0% per hour, and 999.9% per minute is equal to 16.7% per second.
3. HOST.RAMP selects the ramping percentage for gradually changing output to the Host CV (when returning to Host Mode).
The choices are OFF, or 0.1% to 999.9% per minute. 0.1% per minute is equal to 6.0% per hour, and 999.9% per minute is equal to 16.7% per second.
SECURITY
Applications
The security function contains parameters that allow the user to lock out the selective functions of the station. Security only locks out the keypad commands — digital inputs and serial communications are not affected.
1. Press the FAST + MENU keys to toggle to the SECURITY Menu . Press MENU to access each of the following parameters, and the and keys to set their values.
2. SEC. CODE Define the security code using the ▲ and ▼ keys. This parameter does not
appear unless all functions are unlocked. The security function is compromised if the security code is left at zero (0).
3. HOST KEY Selects lockout status of the HOST key.
4. MAN. KEY Selects whether the MANUAL key should be LOCKED or UNLOCKED to
prevent the operator from placing the 531 in Manual Mode. Transfer to Manual Mode is then accomplished by loss of Host signal, digital contact closure or Serial Communications.
5. MAN. OUT Selects whether changes to the output (via the and keys) in Manual Mode
should be LOCKED or UNLOCKED.
6. LOCAL SP Selects whether changes to the setpoint (via the and ▼ keys) in any
operating mode should be LOCKED or UNLOCKED.
7. ALARM ACK.
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 6, Applications 55
DISPLAY
MENU
+
or
Applications
NOTE: Be sure to set the SEC. CODE before
locking any other feature. The station
will not display this parameter if any others have been LOCKED. You would have to unlock all other parameters in order to view the SEC. CODE again.
Selects whether the ACK key should be LOCKED or UNLOCKED for acknowledging alarms.
8. OPERATION Selects whether access to the OPERATIONS configuration menu should
be LOCKED or UNLOCKED.
9. CONFIGURE Selects whether changes to the other configuration parameters should be
LOCKED or UNLOCKED. You must set CONFIGURE to LOCKED if you want full security. If not, the operator has access to the security code. LOCKED does allow access to the menus, but prevents changes to the parameters.
Whenever a locked function is attempted, the operator has the opportunity to enter a security code to override the lock. If the correct code is entered, the operator has full access. The security feature reactivates after one minute of keypad inactivity.
The operator also can enter the SECURITY OVERRIDE CODE, which, if entered correctly, resets the whole station to its default settings. The security override
code is 62647. Store this in a secure place. Refer to Chapter 2 for details on the Security Override function.
PROCESS VARIABLE READING CORRECTION
Under certain extraneous conditions — such as an aging thermocouple, out of calibration transmitter, lead wire resistance — the station may display values other than the actual process value. To compensate for these conditions, you can set offset and gain values for the process variable.
1. Press FAST + MENU to toggle to the PV INPUT menu. Press MENU to access
▲▲
each of the following parameters, and the
▼▼
and
keys to set values for
▲▲
▼▼
them.
2. PV OFFSET This either adds or subtracts a set value from the process variable reading
in engineering units. For example, if your thermocouple was always reading 3° too high, you could set the PV OFFSET parameter to –3 to compensate.
3. PV GAIN Multiplies the deviation from the low end of the process variable range by the
gain factor and then adds it to the value of the low end of the range to arrive at the adjusted process variable value.
For example, if your process variable range is 50 to 650 and the process variable reading is 472, a PV GAIN of 0.995 would yield an adjusted process variable equal to [(472 – 50) x. 995] + 50 = 470.
By using a combination of both offset and gain factors, you should be able to compensate for just about any inaccuracy in your sensor or transmitter.
SERIAL COMMUNICA TIONS
Escape to operating mode Next parameter Next menu Next value
DISPLAY
56 Chapter 6, Applications 531 U ser's Manual
Serial communications is an optional feature. It enables the station to communicate
MENU
FAST
MENU
+
or
Applications
FAST
MENU
with a supervisory device, such as a personal computer or programmable logic controller. The circuitry for communications is contained on a modular circuit board that plugs into the Microcontroller Circuit Board.
The station uses communications standard RS-485, which provides a multi-drop system that communicates at a high rate over long distances. Typical limitations are 32 stations per pair of wires over a distance up to 4000 feet.
The station uses a proprietary protocol which provides an extremely fast and accurate response to any command. A Cyclic Redundancy Checksum (CRC) can be enabled to ensure the integrity of any data read by the controller. Through communications, you have access to every set up and operating parameter in the station.
1. Press the FAST + MENU keys to toggle to the SER.COMM. Menu. Press
▲▲
MENU to access each of the following parameters, and use the
and
▲▲
▼▼
keys
▼▼
to set values for them.
2. STATION Specifies the unit’s station address. It is the only way one controller can be
distinguished from another. Each controller on the same RS-485 interface must have a unique station address.
3. BAUD RATE Choose a baud rate from 1200 to 19,200. In general, you want to select the
highest baud rate. However, every station on the RS-485 interface must be set to the same baud rate.
4. CRC Indicates if you are going to take advantage of the Cyclic Redundancy
Checksum feature. If your host program supports it, we highly recommend that you activate it.
NOTE: The Process Variable Reading
Correction feature is provided only as a convenience. The condition
causing the erroneous reading should be corrected!
NOTE:
PV GAIN is only available if using a linear voltage or current input.
NOTE:
For details on the station communications protocol, contact one of our application engineers.
Escape to operating mode Next parameter Next menu Next value
531 User's Manual Chapter 6, Applications 57
DISPLAY
MENU
+
or
Applications
Escape to operating mode Next parameter Next menu Next value
DISPLAY
58 Chapter 6, Applications 531 U ser's Manual
MENU
FAST
MENU
+
or
PRESS HOST (TOGGLE)
PRESS HOST
PRESS MANUAL
Flowcharts
APPENDIX A MODE, MENU & PARAMETER FLOWCHAR T
PRESS MANUAL
(TOGGLE)
OPERATING MODES
Host Mode Manual Mode
PRESS
DISPLAY
or
ACK
OPERATION
PRESS
FAST
+
MENU
PRESS
FAST
+
MENU
CONFIG.
PRESS FAST+MENU to traverse menus
LOCAL OUT.
PV INPUT
CUST. LINR.
PRESS
MENU
Automatic Mode
SET UP MODES
PRESS MENU to traverse parameters for a given menu
PROP. BAND RESET RATE LOADLINE SP SOURCE MAN.RAMP
HOST RAMP
LOST HOST HOST. RESTR. CONTACT 1 CONTACT 2 CONTACT 3
CONTACT 5
AUTO.LO.LIM. AUTO.HI.LIM. MAN.OUT 1 MAN.OUT 2 PWR.UP:MODE MAN. PWR.UP
PV TYPE DEG. F/C/K DECIMAL HI RANGELINEARIZE LOW RANGE HI RANGE
FILTER PV OFFSET PV GAIN
1ST.INPT 1ST.PV 2ND.INPT 2ND P. 15TH.INPT
WATCHDOG LINE FREQ. OUTPUT 1 PID ACTION STN. NAME
PV BREAK RESTORE
CONTACT 4
15TH.PV
RSP INPUT
ALARMS
SECURITY
SER. COMM.
531 User's Manual Appendix A A-1
RSP TYPE RSP LOW RSP HIGH RSP.OFFSET RSP GAIN TRACKING
RSP. RESTOR.
ALM. TYPE:1 RELAY:1 LATCHING:1
POWER UP:1
LATCHING:2
SEC. CODE HOST KEY MAN. KEY MAN. OUT LOCAL SP ALARM ACK.
OPERATION
STATION
ALARM SP:1 DEADBAND:1 ACK:1
MESSAGE:1
ACK:2
CONFIGURE
BAUD RATE CRC
ALM. TYPE:2
POWER UP:2
MESSAGE:2
DEADBAND:2ALARM SP:2
RATE TIME
RELAY:2
Flowcharts
A-2 Appendix A 531 User's Manual
OPERATOR INTERFACE ASSEMBLY
Parts List
APPENDIX B PARTS LIST*
CIRCUIT BOARD SUPPORT (BEZEL INSERT)
MOUNTING BRACKET
GASKET
TERMINAL BLOCK* *Terminal Circuit Board Not Shown
CIRCUIT BOARDS
OUTPUT MODULES Part # 1 Mechanical relay module 535 600 2 531 Analog (mA) module 532 600 4 Solid State Relay (triac) module 535 602 5 DC Logic (solid state relay drive) module 535 603 6 Loop Power Module 535 604 7 RS-485 serial communications board 535 605
* For a complete list of related options
and repair kits for the 531, refer to M500.
REPAIR PARTS Part # 8 Operator interface assembly 531 531 632 10 Power supply circuit board 535 630 11 Microcontroller circuit board 531 531 631 13 Option circuit board 535 620 14 Option circuit board w/5 digital inputs 531 531 621 18 EPROM 531 531 640 20 Lithium battery 093 044 21 Jumper kit (set of all jumper connectors) 535 660 22 Gasket kit (w/panel and bezel gaskets ) 535 662 23 Mounting kit 532 661
(including mounting brackets and screws) 24 Bezel retention screw kit 535 663 25 Module retention kit 535 664
(w/retention plate & tie wrap for outputs 1-3) 26 Module retention tie wrap kit 535 665
(set of 5 tie wraps) 27 Terminal block 535031A 28 Circuit board support/Bezel insert 535 025 29 Sheet of engineering unit labels 535 106 30 531 Bypass board 531 100 31 Goof plate 512 014
531 User's Manual Appendix B B-1
Parts List
B-2 Appendix B 531 User's Manual
APPENDIX C TROUBLESHOOTING
Troubleshooting
Message
DEFAULTS
NEEDS CAL.
LOST CAL
ERROR:ROM
CHECKSUM
OUT1 CONF. OUT2 CONF. OUT3 CONF. OUT4 CONF.
When does it occur?
Whenever the memory is cleared and all parameters revert to factory default settings. This may be done by pur­posely clearing the memory, when the unit is powered up for the first time, or if the software version is changed.
Indicates that calibration values are at factory defaults (as when a battery is replaced).
Indicates that the calibration data has been lost. Occurs when the memory is wiped clean.
On power up, a problem with the ROM is detected. This is a fatal error and requires an EPROM change. Controller locks up until fixed.
Upon power up, controller senses that the modules needed for control as determined by software configuration are not present.
What to do:
Changing any Set Up parameter will clear the message. If due to some­thing other than the user purposely clearing the memory, call factory for assistance.
Recalibrate the unit.
Problem should never occur. Must correct the problem, then recalibrate. Call factory for assis­tance.
Call factory for assistance.
Must power down and install correct module combination or reconfigure the controller to match the current module combination.
LOST CJC
531 User's Manual Appendix C C-1
Sensor not reading properly.
Call factory for assistance.
Troubleshooting
SYMPTOM
Display will not light up
Improper/Lost PV reading
• Voltage/current
Improper/Lost PV reading
• Thermocouple
Improper/Lost PV reading
• RTD
No control output
Can't switch to Host control
Erratic display
PROBLEM
Defective power source Improper wiring Blown in-line fuse Unit not inserted in case properly; or,
screws have not been tightened
Input jumper selection improperly set Input range improperly selected in
software Reverse polarity If station powered up, improperly wired If internal supply for transmitter not
installed. Defective transmitter Defective thermocouple Input jumper selection improperly set Wrong TC type selected in software
Improper wiring Defective RTD Input jumper selection improperly set Improper wiring Output module not installed Output wiring and module location do
not match If SSR, SSR Drive or Milliamp output,
jumpers J1, J2 and J3 are not set properly
Software configuration does not match hardware (OUTx CONF. message)
Host CV signal is not connected or valid
Resetting action due to electrical noise on powerline
SOLUTION
Check power source and wiring. Correct wiring. Check wiring, replace fuse. Remove unit from case (and remove
bezel screws), then reinsert unit and properly tighten screws.
Move jumper to proper location. Select proper range.
Check and correct sensor wiring. Check and correct wiring. Install module.
Replace transmitter. Replace thermocouple. Move jumper to proper location. Select proper thermocouple type in software. Wire properly. Replace RTD. Move jumper to proper location. Wire properly. Install proper output modules. Check and correct wiring or module
location . Move jumper to proper location
(N.O.).
Reconfigure software to match hardware.
Check wiring. Check that Host is supplying a valid CV signal.
Filter power line.
See OUTx CONF. message.
C-2 Appendix C 531 User's Manual
APPENDIX D CALIBRATION
This section provides information on performing calibration for the following:
RTD and VmA Input Calibration
Thermocouple Cold Junction Compensation
Milliamp Output (Standard on 531). Access these parts of the calibration menu as shown in Figure D.1.
REGARDING CALIBRA TION
To maintain optimum performance, once a year calibrate the analog input, cold junction (when a thermocouple is used) and mA Output (when used). To achieve published accuracy specifications, follow directions carefully and use calibrated instruments of like quality to those suggested. Also, if you move a station chas­sis into an alternate case or change its hardware configuration, and you choose to use thermocouple input, you may want to recalibrate the cold junction for op­timal accuracy. Failure to do so may result in small junction temperature (not more than 0.6°C/1.1°F).
Calibration
CALIBRATE
ANLG. IN
PRESS MENU
CALIBRATE COLD JUNC.
PRESS MENU
CALIBRATE
ANLG. OUT
PRESS MENU
RESET
MENU DATA
PRESS MENU
HARDWARE
SCAN
PRESS MENU
PRESS ACK
PRESS ACK
PRESS ACK
PRESS ACK
PRESS ACK
CAL VREF
PV = –150 C
PRESS ACK
PRESS ACK
OUTPUT "X"
PUSH MENU
TO RESET
DISPLAY ONLY
PRESS ACK
5.0000
0 mA
PRESS MENU
PRESS MENU
After two
seconds
PRESS
MENU
before two
seconds
CAL. 120mV, etc.
PRESS ACK
OUTPUT X, etc
PRESS ACK
RESET
SKIPPED
RESET
COMPLETED
Figure D.1 Flowchart to Access Parts of Calibration Menu Block
NOTE:
RESET, HARDWARE SCAN and S/W TEST are functions in the CALIBRATE menu; these functions are covered later in this Appendix.
ATTENTION! The 531 comes from the factory with one milliamp output module installed in
position (output) 2 and relays in position (outputs) 3 and 4. These must not be modified. You may install a mechanical relay, solid state relay or DC logic module in position (output) 1 for alarm functions.
531 User's Manual Appendix D D-1
Calibration
Figure D.2 Microcontroller Circuit Board
Warning! Electric Shock Hazard! Terminals 1 and 2 carry live power. Do
not touch these terminals when AC power is on.
EPROM
Locations for the jumpers for Analog, Thermocouple and Milliamp calibration
2ND
PV1
ERY
ASS'Y
CALIBRATION
JUMPERS—
SELECT V
AND TCs
PV INPUT
JUMPER
CONFIGURATION
V MA
TCs
V MA TCs TCt RTD
TB2
TB1
Input Calibration
Equipment needed for analog input calibration:
Precision 5-1/2 or 6-1/2 digit multimeter, such as a Fluke 8842® or HP3478A® (a 4-1/2 digit meter will sacrifice accuracy)
Two small pieces of wire
Test leads with clips
#2 Phillips screwdriver
23
– +
24
Figure D.3 Calibration Wiring
hook up wire to multi-meter
31 32
+
hook up wire to multi-meter
Additional equipment needed if using thermocouple input:
Precision thermocouple calibrator, such as a Micromite II® by Thermo Electric Instruments
Special limits grade, Type T thermocouple wire
1. Disconnect power to the instrument.
2. Remove chassis from case.
3. On the Microcontroller Circuit Board find jumper locations marked PV1 and 2nd near the edge connector. As shown in Figure D.2, reposition both jumper connectors in the 2nd location onto pins for V and TCs.
4. Connect the hook up wire to terminals 31 and 32 as shown in Figure D.3. The hook up wire connects to the multimeter. Set the meter for DC volts.
5. Reinsert chassis into the case and apply power. The 2nd and 3rd displays should read “CALIBRATE ANLG. IN.” to show you are in the Calibrate Menu, ANLG. IN section.
6. Allow the controller to warm up for at least 30 minutes.
7. Press the ACK key to get to the first step/parameter. The 2nd display should show CAL. VREF; the 3rd display should show a value close to 5.0000.
8. The multimeter should read a value between 4.9750 and 5.0250. Press s and t keys on the controller until the display on the controller matches the meter reading (the FAST key is active if you want to scroll through the num­bers more quickly).
9. Press MENU key. The 2nd display should show “CAL. 120mV” and the 3rd display should show a value close to 120.000.
D-2 Appendix D 531 User's Manual
10.Repeat the sequence of steps 7, 8, and 9 four more times. Each time, you
23 24
32
31
+
+
T/C wire to T/C calibrator
– red
+ blue
move the meter test lead to 23 (connect to small hoop)
move the meter test lead to 24 (connect to small hoop)
23 24
32
31
+
+
hook up wire to multi-meter
+
hook up wire to multi-meter
T/C (floating)
red
blue
should match the displays of the controller and the multimeter. Press ACK when done. The 2nd display should show CALIBRATE; the 3rd display should show COLD JUNC.
11.Turn off power to the unit.
12.If you are using thermocouple, proceed to the Thermocouple Cold Junction Calibration Procedure.
13.For Milliamp output calibration, proceed to the Milliamp Output Calibration Procedure, where steps 1–4 can be skipped and only 10 minutes of warm up is required before proceeding to step 5.
If calibration is complete, place all the jumpers back in their original posi­tions (as specified in Chapter 4).
Thermocouple Cold Junction Calibration
1. Add the T/C wires to terminals 31 and 32 as shown in Figure D.3a. The hook up wire connects to the multimeter. As was set for input calibration, set the meter for DC volts. Make sure the T/C wires are not connected to anything and are not touching each other.
2. Turn on power to the unit and let controller warm up for 30 minutes in the normal horizontal position: while the unit is warming up, the rear face of the controller should be vertical, not horizontal.
3. Press the MENU key until the display indicates “CALIBRATE COLD JUNC.”
4. Press the ACK key. The display should show “BASE VOLT 50.000” .
5. Connect T-Type thermocouple –150°C thermocouple calibrator to thermo­couple wires on PV terminals.
6. Disconnect the hook up wires from the PV rear terminals (31 and 32) to the multimeter. Connect the thermocouple wires to the thermocouple calibra­tor instrument. Connect the meter test leads to the small hoops on termi­nals 23– and 24+ (see Figure D.4).
7. The 2nd display should show BASE VOLT. and the 3rd display should show a value close to 50.000.
8. Press s and t keys to match the controller display with the multimeter's dis­play. Be sure that the multimeter's value is not drifting; wait until it is stable before pressing s and t keys to adjust controller display (the FAST key is active if you want to scroll through the numbers more quickly). When the value displayed on the controller matches the value on the meter, press the MENU key.
9. Disconnect the meter leads from terminals 23 and 24, and press the ACK key.
10.Test the thermocouple input to see if it is within ±1°F.
11.If you will be calibrating the milliamp output, move on to the Millamp Output Calibration, #5, where steps 1–4 can be skipped and only 10 minutes of warm up is required before proceeding to step 5.
If calibration is complete, power down, then place all the jumpers in their original positions (as specified in Chapter 4).
531 User's Manual Appendix D D-3
Calibration
NOTE:
In the United States, the standard negative thermocouple lead is red.
NOTE:
Do not stand the station on its front or back ends; this will disrupt accurate temperature readings.
Figure D.3a Calibration Wiring
Figure D.4 Thermocouple & Cold Junction Calibration Wiring
Calibration
NOTE:
If your multi-meter display does not register a response, check that the jumpers J1, J2 and J3 (on the Power Supply Board) are positioned as Normally Open (NO).
1 2 3
4
9 10 11
12
hook-up
wires to
multi-
meter
OUT 2–
OUT 2+
+
5 6 7 816
Figure D.5 Milliamp Calibration Wiring
13 14 15
MILLIAMP OUTPUT CALIBRA TION
Once a year, calibrate the mA output to maintain optimal performance. Additionally, you should calibrate an output when a new mA module is installed.
The 531 local output should be calibrated at terminals 5 and 6 (OUT2– and OUT2+). The bypass circuitry PC board does not have to be removed to perform the calibration.
Equipment:
Precision 5-1/2 or 6-1/2 digit multimeter, such as a Fluke 8842® or
Hewlett Packard HP3478A
Two small pieces of wire for each milliamp output
Test leads with clip ends
#2 Phillips screwdriver
1. Disconnect power to the instrument.
2. Remove chassis from case.
3. Locate jumpers marked PV 1 and 2nd near the edge connector of the Microcontroller Board (refer to Figure D.2). Relocate both jumper connectors so that one is positioned on the pins marked V of the 2nd jumper and the other on the pins marked TC
4. Connect the small pieces of wire to the terminals assigned to the milliamp output(s) you are calibrating. Figure D.5 shows the hook up wires applied to OUT2+ and OUT2–. Hook up wires need to be applied to all terminals that have corresponding milliamp output modules in their output sockets. Attach the test leads from the multimeter to the wires, and then plug the test leads into the meter. Set the meter for DC milliamps.
5. Reinsert chassis into the case and apply power. The 2nd display should read CALIBRATE while the 3rd display reads ANLG. IN. Press MENU twice to get to the ANLG. OUT Menu.
6. Press ACK. The 2nd display will read OUTPUT 2.
7. The 3rd display should read 4 mA. Your meter should read a value close to 4.00 mA. Wait one minute. Then press and the meter’s display reads 4.00 mA. You may press FAST with key to change the value at a faster rate.
8. Press MENU. The 3rd display should read 20 mA. Let this setting stabilize for one minute. Repeat the procedure from Step 7.
9. To complete calibration, press ACK, and disconnect the power. Remove the station from its case, and place the jumpers in their correct operating positions (as specified in Chapter 4).
You must press the ACK key at the end of any calibration procedure to return to the calibration menu before powering down.
®
▲▲
of the 2nd jumper.
▲▲
▼▼
key on the station until
▼▼
▲▲
▼▼
and
▲▲
▼▼
D-4 Appendix D 531 User's Manual
RESET MENU DA TA
Refer to Figure D.1. This function resets all parameter values back to their factory defaults (except for calibration information). Once inside this Menu Block:
1. Press MENU until the display shows RESET MENU DATA.
2. Press ACK.
3. The display will prompt you to press MENU to reset the menu data. You have two seconds to press MENU to accomplish the reset. If successful, RESET COMPLETED will appear in the display.
4. If you failed to press MENU in time, RESET SKIPPED will appear.
5. To try again, press ACK , and then press MENU within two seconds.
HARDW ARE SCAN
Refer to Figure D.1. This procedure identifies the internal parts of the station. Should you need to determine the hardware inside your station, press ACK to enter this read-only menu. The station will display the types of output hardware and installed options.
The information displayed should match the information on the product label on top of the controller. You can compare this information to the Order Code on page 2. However, any hardware modifications will render the order code on the product label invalid.
QUICK CALIBRA TION PROCEDURE
Calibration
NOTE:
Calibration data will remain intact through the Reset Menu Data function.
This procedure is for the benefit of users that have ISO or other standards that require periodic calibration verification. The procedure enables verification and modification of the volt or mA process variable input you are using without entering the “Factory Configuration” mode. Therefore you do not need to per­form any jumper change.
1. Power down the 531.
2. Replace the process variable (PV) input signal with a suitable calibration
device.
3. Apply power and allow controller to warm up for 30 minutes.
4. Place controller under Manual control.
5. Go to the PV INPUT . Scroll to the PV OFFSET parameter.
5. Adjust your calibration device to an output signal equal to the 0% range value
for your particular input sensor (4mA for a 4-20 mA input).
6. Verify that the value indicated in the 1st display is equal to the 0% range
value for your particular input sensor. If the value is incorrect, use the
▼▼
keys to scroll to the correct value.
▼▼
7. Scroll to the PV GAIN parameter.
8. Adjust your calibration device to an output signal equal to the 100% range
value for your particular sensor.
9. Verify value indicated in the 1st display is equal to the 100% range value for
▲▲
your particular input sensor. If incorrect, use the the correct value.
10.Repeat steps 3 through 8 to verify all values.
11.Return to the operating mode.
and
▼▼
keys to scroll to
▲▲
▼▼
▲▲
and
▲▲
531 User's Manual Appendix D D-5
Calibration
D-6 Appendix D 531 User's Manual
Specifications
APPENDIX E SPECIFICATIONS
ACCURACY
TYPICAL MAXIMUM
LINEAR
(Voltage) ± 0.025% full scale ± 0.100% full scale (Current) ± 0.050% full scale ± 0.150% full scale
RTD
± 0.050% of span ± 0.150% of span
0.1° ± 0.095% of span ± 0.225% of span
THERMOCOUPLE
J, K, N, E (> 0°C) ± 0.060% of span ± 0.150% of span J, K, N, E (< 0°C) ± 0.150% of span ± 0.375% of span T (> 0°C) ± 0.100% of span ± 0.250% of span T (< 0°C) ± 0.250% of span ± 0.625% of span R, S (> 500°C) ± 0.150% of span ± 0.375% of span R, S (< 500°C) ± 0.375% of span ± 0.925% of span B (>500°C) ± 0.150% of span ± 0.375% of span B (<500°C) ± 0.500% of span ± 1.000% of span W, W5 & Platinel II ± 0.125% of span ± 0.325% of span
Display accuracy is ± 1 digit. These accuracy specifcations are at reference conditions (25°C) and only apply for NIST ranges. Detailed accuracy information is available upon request.
CONTROL ALGORITHM
PID, P with manual reset, PI, and PD with manual reset.
TUNING PARAMETERS
Proportional Band: 0.1 to 999% of input range Integral: 1 to 9999 seconds/repeat Derivative: 0-600 seconds Manual Reset: 0-100% output
ISOLATION
Inputs and outputs are grouped into the following blocks:
Block 1 — process variable indication Block 2 — outputs 1, 2, and 4 Block 3 — communications, set of 5 digital inputs, output 3 Block 4 — setpoint and indicator
THERMOCOUPLES RANGE °F RANGE °C
B 104 to 3301 40 to 1816 E – 454 to 1832 –270 to 1000 J –346 to 1832 –210 to 1000 K – 418 to 2500 –250 to 1371 N –328 to 2372 –200 to 1300 R 32 to 3182 0 to 1750 S 32 to 3182 0 to 1750 T –328 to 752 –200 to 400 W 32 to 4172 0 to 2300 W5 32 to 4172 0 to 2300 Platinel II –148 to 2550 –100 to 1399
RTD'S RANGE °F RANGE °C
100W Pt. (DIN) –328 to 1562 –200 to 850
–328.0 to 545.0 –200.0 to 285.0
100W Pt. (JIS) –328 to 1202 –200 to 650
–328.0 to 545.0 –200.0 to 285.0
100W Pt. (SAMA) –328 to 1202 –200 to 650
–328.0 to 545.0 –200.0 to 285.0
TRANSMITTER SIGNALSINPUT RANGE
Milliamps DC 4 to 20
0 to 20
Voltage DC 1 to 5
0 to 5
Millivolts DC 0 to 10
0 to 30 0 to 60 0 to 100
–25 to 25
LINEARIZATION
Thermocouple and RTD inputs are automatically linearized. Transmitter inputs may be linearized with a square root function or user-defineable 15­point straight line linearization function.
TRANSITION TIME
CV signal is restored 250 msec. after the HOST signal break is detected. CV signal is considered lost when it falls below 3.2 mA.
INPUT IMPEDANCE
Current Input: 250 W Thermocouples: 10 MW Voltage Input: 1 MW RTDs: 10 MW
Each block is electrically isolated from the other blocks to withstand a HIPOT potential of 500 Vac for 1 minute or 600 Vac for 1 second, with the exception of blocks 1 and 4, which are isolated to withstand a HIPOT potential of 50 volts peak for 1 minute between each other. Inputs and outputs are not isolated from other inputs and outputs within the same block.
PROCESS VARIABLE INPUTS
Universal input type. Any input type may be selected in the field. Selection of input type (thermocouple, RTD, voltage or current) via jumper. Selection of particular sensor or range is via front panel.
Specifications and information subject to change without notice.
531 User's Manual Appendix E E-1
UPDATE RATE
Input is sampled and output updated 5 times per second. Display is updated 5 times per second. Passage of the HOST signal through the 531 is continuous.
INPUT FILTER
Single pole lowpass digital filter with selectable time constant from 0 to 120 seconds.
(Continued on following page)
Specifications
CALIBRATION
The station comes fully calibrated from the factory and continuously calibrates itself for component aging due to temperature and time, except for reference voltage. Field calibration can be performed easily with a precision multimeter and thermocouple simulator. Process variable offset and gain factors are provided to correct for sensor errors.
OUTPUT MODULES
One analog output (CV), 4–20 mA into a load up to 1000W . Also available is an additional mechanical relay module that can be tied to an alarm.
CONTROL OUTPUTS
4–20 mA into a load up to 1000W.
ALARMS
The 531 has two powerful software alarms. The 531 provides a LOCAL alarm that indicates when the 531 is in LOCAL mode. When tied to an available output, the HOST device can be flagged as to the change in status. Alternately, a PV High, PV Low, PV Rate, SP Band or SP Deviation alarm may be configured. A 9-character custom alarm message is available for each alarm.
DIGITAL INPUTS
A set of five external dry contacts or open collector driven transistor inputs are available. Each can be configured to perform one of the following functions:
• Select LOCAL control with LAST-OUT or 1 of 2 preset values
• Acknowledge alarms
• Addressable through serial communications only
• s/t Key Emulation
• HOST "watchdog" timer input
SERIAL COMMUNICATIONS
Isolated serial communications is available using an RS-485 interface. Baud rates of up to 19,200 are selectable. The protocol supports CRC data checking.
DIGITAL DISPLAYS
Displayed information depends upon chosen options. Upper display: five-digit, seven-segment. Used exclusively to display PV. Height is 15 mm (0.6 in.). 2nd display: nine-character, 14-segment alphanumeric. Selectable SP or CV indication. During set up, displays configuration information. Height is 6 mm (0.25 in.). 3rd display: nine-character, 14-segment alphanumeric. When no alarm messages are queued, indicates a user-selectable "station" name. During set up, displays configuration information. Height is 6 mm (0.25 in.). All displays are vacuum flourescent. Color is blue-green.
STATUS INDICATORS
ALM 1 icon illuminated: alarm status HOST key illuminated: CV signal from HOST is present MANUAL key illuminated: 531 is in LOCAL MANUAL mode ACK key illuminated: alarm is acknowledgable MENU key illuminated: 531 is in configuration mode
DIMENSIONS
MOUNTING
WIRING CONNECTIONS
POWER CONSUMPTION
WEIGHT
AMBIENT TEMPERATURE
RELATIVE HUMIDITY
VOLTAGE AND FREQUENCY
NOISE IMMUNITY
CONSTRUCTION
AGENCY APPROVALS
MEMORY RETENTION
SECURITY
Meets 1/4 DIN designation as specified in DIN standard number 43 700. See diagram on page 5 for details.
Panel-mounted. See diagram in Chapter 4 for details.
30 screw terminals in the rear of the instrument.
15 VA at 120 VAC, 60 Hz (typical).
Approximately 1 kg (2.2 lbs.).
Operative Limits: 0 to 50°C (32 to 122°F). Storage Limits: – 40 to 70°C (– 40 to 158°F).
10 to 90%, non-condensing.
Universal power supply: 90 to 250 VAC, 48 to 62 Hz.
Common mode rejection (process input): >120 dB. Normal mode rejection (process input): >80 dB. AC line is double filtered and transient protected. Internal snubbers are provided for each relay output.
Case: extruded, non-perforated black anodized aluminum with ABS plastic sleeve. Bezel: black plastic ABS. Chassis assembly: plug-in type. Keys: silicone rubber with diffusion printed graphics. NEMA rating: front panel conforms to NEMA 4X when instrument is properly installed.
(Heavy Industrial)
(Available as an option)
Lithium battery maintains all programming for approximately ten years.
There are two levels of access: restricted and full. A configurable code is used to enter the full access level. Functions not available in the restricted level are configurable.
E-2 Appendix E 531 User's Manual
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair – If you are unsure if your unit is still under warranty, we can use the unit’s serial number to verify the warranty status for you over the phone. Be sure to include the RMA number on all documentation.
Non-Warranty Repair – If your unit is out of warranty, be prepared to give us a Purchase Order number when you call. In most cases, we will be able to quote you the repair costs at that time. The repair price you are quoted will be a “Not To Exceed” price, which means that the actual repair costs may be less than the quote. Be sure to include the RMA number on all documentation.
2. Provide us with the following documentation: a) A note listing the symptoms that indicate the unit needs repair b) Complete shipping information for return of the equipment after repair c) The name and phone number of the person to contact if questions arise at the factory
3. Use sufficient packing material and carefully pack the equipment in a sturdy shipping container.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries representative will contact the person designated on your documentation if more information is needed. The repaired equipment, or its replacement, will be returned to you in accordance with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WARRAN­TIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SER­VICES SOLD BY THE COMPANY. THE COMPANY DISCLAIMS ALL WARRAN­TIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWL­EDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IM­PLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANY WAY.
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REMEDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RECEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DE­FECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WAR­RANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under normal conditions of use and service, Moore Industries ("The Company") will at its option replace, repair or refund the purchase price for any of its manu­factured products found, upon return to the Company (transportation charges prepaid and otherwise in accordance with the return procedures established by The Company), to be defective in material or workmanship. This policy extends to the original Buyer only and not to Buyer's customers or the users of Buyer's products, unless Buyer is an engineering contractor in which case the policy shall extend to Buyer's immediate customer only. This policy shall not apply if the product has been subject to alteration, misuse, accident, ne­glect or improper application, installation, or operation. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSE­QUENTIAL DAMAGES.
United States • info@miinet.com
Tel: (818) 894-7111 • FAX: (818) 891-2816
Australia • sales@mooreind.com.au
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
Tel: 86-21-62491499 • FAX: 86-21-62490635
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
Specifications and Information subject to change without notice.© 2007 Moore Industries-International, Inc.
China • sales@mooreind.sh.cn
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
5 3 1
5 3 1
1/4 DIN PID BACKUP STATION ADDENDUM TO THE USER'S MANUAL
M531 V5A5, © MAY 2002
The 531 controller has been upgraded with a new microprocessor, new case, and modifications to the front panels to improve its NEMA 4x capability. Insert the information in this addendum where appropriate in your M531 V5 manual.
Cover The 500 series controller body has been modified to a 1-piece design, with
a new face plate (4 screws instead of 2 securing it to the body).
531
Chapter 1, Page 1, Figure 1.1 also Chapter 2, Page 5, Figure 2.1 Chapter 2, Page 8, Figure 2.2 Chapter 4, Page 15, Figure 4.1
This drawing shows a basic detail of the new faceplate. Please refer to this drawing for any detail of the controller face.
531
MANUAL DISPLAY ACK
HOST MENU FAST
▲ ▼
Specifications and information subject to change without notice.
Addendum 531 1
531
Chapter 1, Page 2
New Order Code for 531.
531 – 2 1 1 B 00
Output 1: Alarm Order Code None 0 Mechanical Relay 1 Solid State Relay (triac) (1 amp) 3 DC Logic (SSR drive) 4
Options
Enter “0” if not desired
24 VAC/24VDC Operation F Set of Five Digital Inputs D
Certification H
Five Digital Inputs and Certification J Serial Communications
Enter “0” if not desired
RS-485 Serial Communications S
Base instrument contains universal PV input, remote setpoint input, and 4–20 mA CV (control) output with internal hard-wired bypass relays.
2 531 Addendum
531
V MA
TCs RTD
TCt
ASS'Y 535-607
TB1
PV1
2ND
Remote SP
Configuration
PV1
Jumper Location
TB2
EPROM
BATTERY
P2
P1
V MA
TCs RTD
TCt
Chapter 3, Page 9, Figure 3.1
Chapter 3, Page 10, Figure 3.2
This drawing has been modified (due to the new controller body).
MICROCONTROLLER
BOARD
POWER SUPPLY
BOARD
OPTION BOARD
The Microcontroller Board has been modified.
Chapter 4, Page 16, Figure 4.2 A mounting collar replaces the old mounting brackets.
Addendum 531 3
Front panel
Mounting Collar
Collar Clip (1 of 2)
Collar screw (1 of 4)
531
Chapter 4, Page 16
Chapter 5, Page 25
Chapter 5, Page 33
2c. Slide the mounting collar over the back of the case. The collar clip
edges will lock with matching edges on the controller case.
2d. Insert the four mounting collar screws from the rear of the collar.
Gradually tighten the screws to secure the controller against the panel.
In the CONFIG Menu, add the following new parameter after HOST RESTR.
3. CV RANGE
Selects the CV output signal.
(D) 4-20mA
20-4mA
All following parameters are renumbered accordingly. In the ALARMS Menu: two new alarm types have been added, the
respective alarm setpoint parameters have been modified, and four new setpoint parameters (2 per alarm) have been added.
1. ALM. TYPE:1
(D) OFF
LOCAL
HIGH PV
LOW PV
RATE
BAND
DEVIATION
HIGH CV
LOW CV
HI/LO CV Separate High and Low CV setpoints
HI/LO PV Separate High and Low PV setpoints
4 531 Addendum
2. ALARM SP:1
Specifies the alarm set point for alarm 1.
For RATE alarms: For HIGH CV or LOW CV alarms: (R) -9999 to 99999 (R) 0.0 to 100.0% (D) 0 (D) 0.0%
For any other type (except HI/LO CV or HI/LO PV) (R) The PV range (D) Dependent on LOW RANGE value
3. HIGH SP:1
Specifies the high alarm set point for HI/LO CV or HI/LO PV alarm 1.
For HI/LO CV alarms: For HI/LO PV alarms: (R) 0.0% to 100.0% (R) LOW RANGE to HI RANGE (D) 0.0% (D) 0
531
4. LOW SP:1
Specifies the low alarm set point for HI/LO CV or HI/LO PV alarm 1.
For HI/LO CV alarms: For HI/LO PV alarms: (R) 0.0% to 100.0% (R) LOW RANGE to HI RANGE (D) 0.0% (D) 0
11. ALM. TYPE:2
(D) OFF
LOCAL
HIGH PV
LOW PV
RATE
BAND
DEVIATION
HIGH CV
LOW CV
HI/LO CV Separate High and Low CV setpoints
HI/LO PV Separate High and Low PV setpoints
12. ALARM SP:2
Specifies the alarm set point for alarm 2.
For RATE alarms: For HIGH CV or LOW CV alarms: (R) -9999 to 99999 (R) 0.0 to 100.0% (D) 0 (D) 0.0%
For any other type (except HI/LO CV or HI/LO PV) (R) The PV range (D) Dependent on LOW RANGE value
13. HIGH SP:2
Specifies the high alarm set point for HI/LO CV or HI/LO PV alarm 2.
For HI/LO CV alarms: For HI/LO PV alarms: (R) 0.0% to 100.0% (R) LOW RANGE to HI RANGE (D) 0.0% (D) 0
14. LOW SP:2
Specifies the low alarm set point for HI/LO CV or HI/LO PV alarm 2.
For HI/LO CV alarms: For HI/LO PV alarms: (R) 0.0% to 100.0% (R) LOW RANGE to HI RANGE (D) 0.0% (D) 0
Addendum 531 5
531
Chapter 5, Page 39
These parameter set up charts reflect the changes in the set up menus.
CONFIG
Parameter Description Values
1 LOST HOST Defines fundamental controller Set Up 2 HOST. RESTR. Defines the power source frequency 3 CV RANGE Specifies the CV output signal 4 CONTACT 1 Operation of the first digital input 5 CONTACT 2 Operation of the second digital input 6 CONTACT 3 Operation of the third digital input 7 CONTACT 4 Operation of the fourth digital input 8 CONTACT 5 Operation of the fifth digital input 9 WATCHDOG Defines function of Host watchdog monitor 10 LINE FREQ. Specifies the power source frequency 11 OUTPUT 1 Defines the function of the 1st output 12 PID ACTION Selects the PID control action 13 STN. NAME Specifies a 9-character message to name the station
6 531 Addendum
Chapter 5, Page 42
ALARMS
Parameter Description Value
1 ALM. TYPE:1 Type of alarm for alarm 1 2 ALARM SP:1 Alarm setpoint alarm 1 3 HIGH SP:1 High alarm setpoint for HI/LO CV or HI/LO PV alarm 1 4 LOW SP:1 Low alarm setpoint for HI/LO CV or HI/LO PV alarm 1 5 DEADBAND:1 Dead band for alarm 1 6 RELAY:1 State of the relay for alarm 1 7 LATCHING:1 Latching sequence for alarm 1 8 ACK.:1 Whether alarm 1 may be acknowledged 9 POWER UP:1 How alarm 1 will be treated upon power up
531
10 MESSAGE:1 Nine character message associated with alarm 1 11 ALM. TYPE:2 Type of alarm for alarm 2 12 ALARM SP:2 Alarm setpoint alarm 2 13 HIGH SP:2 High alarm setpoint for HI/LO CV or HI/LO PV alarm 2 14 LOW SP:2 Low alarm setpoint for HI/LO CV or HI/LO PV alarm 2 15 DEADBAND:2 Dead band for alarm 2 16 RELAY:2 State of the relay for alarm 2 17 LATCHING:2 Latching sequence for alarm 2 18 ACK.:2 Whether alarm 2 may be acknowledged 19 POWER UP:2 How alarm 2 will be treated upon power up 20 MESSAGE:2 Nine character message associated with alarm 2 21 RATE TIME Time period over which a rate-of-change is determined
Chapter 6, Page 46-47 After LOW CV, insert these two new alarm types:
HI/LO CV
Combination of high and low CV alarms. Occurs when the PV exceeds the individually set high or low CV setpoint.
HI/LO PV
Combination of high and low PV alarms. Occurs when the PV exceeds the individually set high or low setpoint.
Addendum 531 7
531
Appendix A, Page A-1
PRESS MANUAL
PRESS HOST (TOGGLE)
PRESS
DISPLAY
or
ACK
OPERATION
PRESS
FAST
+
MENU
CONFIG.
PRESS FAST+MENU to traverse menus
PRESS
FAST
+
MENU
The Menu Flowchart has been modified accordingly:
PRESS MANUAL
(TOGGLE)
Manual ModeHost Mode Automatic Mode
PRESS
MENU
PRESS MENU to traverse parameters for a given menu
PROP. BAND RESET RATE LOADLINE SP SOURCE MAN.RAMP
HOST RAMP
LOST HOST HOST. RESTR. CV RANGE CONTACT 1 CONTACT 2
CONTACT 4
STN. NAME
OPERATING MODES
SET UP MODES
CONTACT 3
CONTACT 5 WATCHDOG LINE FREQ. OUTPUT 1 PID ACTION
LOCAL OUT.
PV INPUT
CUST. LINR.
RSP INPUT
ALARMS
SECURITY
AUTO.LO.LIM. AUTO.HI.LIM. MAN.OUT 1 MAN.OUT 2 PWR.UP:MODE MAN. PWR.UP
PV TYPE DEG. F/C/K DECIMAL HI RANGELINEARIZE LOW RANGE HI RANGE
FILTER PV OFFSET PV GAIN
1ST.INPT 1ST.PV 2ND.INPT 2ND P. 15TH.INPT
RSP TYPE RSP LOW RSP HIGH RSP.OFFSET RSP GAIN TRACKING
RSP. RESTOR.
ALM. TYPE:1
LATCHING:1
HIGH SP:2
POWER UP:2
SEC. CODE HOST KEY MAN. KEY MAN. OUT LOCAL SP ALARM ACK.
OPERATION
ALARM SP:1 HIGH SP:1 RELAY:1
ACK:1
LOW SP:2
MESSAGE:2
CONFIGURE
POWER UP:1
DEADBAND:2
RATE TIME
PV BREAK RESTORE
LOW SP:1 DEADBAND:1
ALM. TYPE:2MESSAGE:1
RELAY:2
LATCHING:2
15TH.PV
ALARM SP:2
ACK:2
SER. COMM.
STATION
8 531 Addendum
BAUD RATE CRC
531
Appendix B, Page B-1
OPERATOR INTERFACE ASSEMBLY shown with bezel insert in place
CIRCUIT BOARD SUPPORT (BEZEL INSERT)
With the modifications to the case and addition of the mounting collar, the parts drawings have been modified. Also, note the new part numbers.
CIRCUIT BOARDS
BEZEL GASKET
CONTROLLER BODY shown with mounting collar in place
MOUNTING COLLAR
ITEM PART #
Output Modules
Mechanical Relay Module 535 600 Analog (Milliamp Module) 535 601 Solid State Relay Module 535 602 DC Logic (SSR Drive) Module 535 603 Loop Power Module 535 604 RS-485 Communications Module 535 705
Repair/Replacement Parts
Operator Interface Assembly 531 632 Power Supply Circuit Board 535 730 Microcontroller Circuit Board 535 731 Option Circuit Board w/no Options 535 720 Option Circuit Board w/Set of 5 Digital Contacts 535 721 EPROM 531 531 740 Lithium Battery 093 044 Jumper Kit: Set of All Jumper Connectors 535 660 Gasket Kit: 1 Panel Gasket & 1 Bezel Gasket 535 662 Mounting Kit: Mounting Collar & 4 screws 535 761 Bezel Retention Screw Kit 535 663 Module Retention Kit for Outputs 1-3 ( Includes Retention Plate) 535 664 Module Retention Kit for Output 4: Set of 5 Tie Wraps 535 665 Circuit Board Support (Bezel Insert) 535 075 Engineering unit labels (1 sheet) 535 106 531 Bypass board 532 100
Addendum 531 9
531
Appendix C, Page C-1 Changes and additions to the troubleshooting error messages:
Message
DEFAULTS
LOST CAL. or
ERROR: BAD CAL. DATA
ERROR: ROM CHECKSUM
OUT1 CONF or OUT2 CONF or OUT3 CONF or
OUT4 CONF
LOST CJC
ERROR: BAD EEPROM
When does it occur?
Whenever the memory is cleared and all parameters revert to factory default settings. This may be done by pur­posely clearing the memory or when the unit is powered up for the first time or if the software version is changed.
Indicates that the calibration data has been lost. Occurs when there is a total loss of memory.
On power up, a problem with the EPROM is detected. Controller locks up until fixed.
Upon power up, controller senses that the modules needed for control as determined by software configuration are not present.
The cold junction is sensed as lost. During power up an EEPROM failure is
detected. Controller locks up until fixed.
What to do:
Changing any Set Up parameter will clear the message. If due to something other than the user purposely clearing the memory, call factory for assistance.
Problem should never happen. Must correct the situation and recalibrate. Call factory for assistance.
Call factory for assistance.
Must power down and install correct module combination or must reconfigure the controller to match the current module combination.
Call factory for assistance. This is a fatal error and requires and
EEPROM change. Call factory for assistance.
NEEDS CAL.
ERROR: BAD MODEL NUM.
When the controller is powered up with default calibration data (input and output accuracy specifications may be met).
During power up, a discrepancy was found between the EEPROM's and controller's model numbers. Controller locks up until fixed.
Enter calibration menu and recalibrate the controller. Call factory for assistance.
This is a fatal error and requires an EPROM or EEPROM change. Call factory for assistance.
The following pages replace Appendix D of the 531 manual.
10 531 Addendum
APPENDIX D
ANALOG IN
CALIBRATE
ANLG. OUT
CALIBRATE
CAL. 120mV, etc.
OUTPUT X, etc
5.0000
CAL VREF
4 mA
OUTPUT "X"
DISPLAY ONLY
TO RESET
PUSH MENU
COMPLETED
RESET
RESET
SKIPPED
SCAN
HARDWARE
PRESS ACK
PRESS ACK
PRESS ACK
PRESS ACK
PRESS ACK
After two
seconds
PRESS
MENU
before two
seconds
MENU DATA
RESET
PRESS ACK
PRESS MENU
PRESS MENU
mA CALIB.
COMPLETED
mA CALIB.
FAILED
PRESS ACK
PRESS ACK
PRESS MENU
PRESS MENU
PRESS MENU
COLD JUNC.
CALIBRATE
PRESS ACK
PV= –150 C
PRESS ACK
PRESS MENU
PRESS MENU
PRESS MENU
PRESS MENU
PRESS MENU
PRESS MENU
ANA. mA IN
CALIBRATE
JUMPER=mA
SET BOTH
PRESS ACK
PV=20mA
PRESS ACK
Power Down
Move Jumpers
Power Up
PRESS ACK
SP=20mA
Attach 20mA
to PV
Press ACK
Attach 20mA
to SP
Press ACK
If mA calibration values are
OK.
If mA calibration values are
out of range.
CALIBRATION
To maintain optimum performance, once a year calibrate the analog input, the cold junction and milliamp output (when used). To achieve published accuracy specifications, follow directions carefully and use calibrated instruments of like quality to those suggested.
If the controller is moved into an alternate case, or the hardware configura­tion is changed, and the thermocouple input is needed, recalibrate the cold junction for maximum accuracy. Failure to do so may result in small junction temperature (0.6°C/1.1°F).
531
Access the parts of the calibration menu as shown in Figure D.1. ATTENTION! The 531 comes from the factory with one milliamp output module installed in po­sition (output) 2 and relays in position (outputs) 3 and 4. These must not be modified. You may install a mechanical relay, solid state relay or DC logic mod­ule in position (output) 1 for alarm functions.
Addendum 531 11
531
V MA
TCs RTD
TCt
EPROM
BATTERY
ASS'Y
TB1
PV1
V MA
2ND
PV INPUT
JUMPER
CONFIGURATION
TCs RTD
TCt
TB2
CALIBRATION
JUMPERS—
SELECT V
AND TCs
Jumper locations for Analog,Thermocouple and Milliamp calibration
P2
P1
Figure D.2 Microcontroller Circuit Board
WARNING! Electric Shock Hazard!
Terminals 1 and 2 carry live power. Do not touch these terminals when AC power is on.
Figure D.3 Input Calibration
PV–
31
12 531 Addendum
32
PV+
PREP A RA TION FOR ALL INPUT CALIBRA TIONS
Equipment for analog input calibration:
Precision 5-1/2 or 6-1/2 digit multimeter, e.g., Fluke 8842® or HP3478A (a 4-1/2 digit meter will sacrifice accuracy)
Four small pieces of wire
Test leads with clips
#2 Phillips screwdriver
Additional equipment for thermocouple input:
Precision thermocouple calibrator, e.g., Micromite II® by Thermo Electric Instruments
Special limits grade, Type T thermocouple wire
1. Disconnect power to the instrument.
2. Remove chassis from case.
3. On the Microcontroller Circuit Board, locate jumper locations marked PV1 and 2nd near the edge connector. Reposition both jumper connectors in the 2nd location onto pins for V and TC
4. Connect hook up wires between terminals 31 and 32 as shown in Figure D.3, and the multimeter.
Set the meter for DC volts.
5. Reinsert chassis into the case and apply power. The 2nd and 3rd display should read CALIBRATE ANALOG IN.
6. Allow the controller to warm up for at least 30 minutes.
7. Press the ACK key to get to the first step/parameter. The 2nd display should show CAL. VREF; the 3rd display should show a value
close to 5.0000.
8. The multimeter should read a value in the range 4.9750 - 5.0250. Use the
controller matches the meter reading.
9. Press MENU key. The 2nd display should show CAL. 120mV. The 3rd display should show a
value close to 120.000. Match controller display to multimeter value using
▲▲
and
▲▲
▲▲
and
▲▲
▼▼
keys.
▼▼
▼▼
(and FAST) keys on the controller until the display on the
▼▼
▲▲
as shown in Figure D.2.
▲▲
®
10.Press MENU four more times. Each time, match the displays of the controller
23
24
21
22
19
20
17
18
29
30
27
28
25
26
32
31
Type T thermocouple wire (floating)
– red
+ blue
23 24
21 22
19 20
17 18
29 30
27 28
25 26
32
31
PV–
PV+
SP–
Wires to 20mA current (floating)
SP+
and the multimeter. Press ACK when done. The 2nd display should show CALIBRATE; the 3rd display should show ANA.
mA IN.
11.Turn off power to the unit.
12.For thermocouple input, proceed to the Thermocouple Cold Junction Cali­bration.
13.For milliamp input , proceed to Analog Milliamp Input Calibration.
14.For milliamp output calibration, let the controller warm up for 10 minutes, then skip to step 5 of Milliamp Output Calibration.
15.If calibration is complete, place all the jumpers back in their original positions (as specified in Chapter 3).
THERMOCOUPLE COLD JUNCTION CALIBRA TION
1. Connect the two pairs of T/C wire to terminals 31 and 32 as shown in Figure D.4. Make sure the T/C wires are floating (disconnect from the multimeter also), and are not touching each other.
2. Turn on power to the unit and let controller warm up for 30 minutes in the normal horizontal position: while the unit is warming up, the rear face of the controller should be vertical, not horizontal.
3. Press the MENU key until the display indicates CALIBRATE COLD JUNC.
4. Press the ACK key. The display should show PV = -150 C PRESS ACK.
5. Connect both pairs of T/C wires in parallel—do not daisy chain—to a Type T thermocouple calibrator. (Both pairs must be connected or the calibration will not be accurate.)
6. Set the thermocouple calibrator to an output value of -150° C for a Type T ther­mocouple and allow the calibrator to stabilize for a few minutes.
7. Press ACK to initiate calibration of the cold junction.
8. For milliamp output calibration, proceed to Milliamp Output Calibration. Let the controller warm up for 10 minutes, then skip to step 5.
9. If calibration is complete, power down, then place all the jumpers in their origi- nal positions (as specified in Chapter 3).
ANALOG MILLIAMP INPUT CALIBRA TION
531
Figure D.4 Thermocouple Cold Junction Calibration Wiring
Figure D.5 Analog mA Input Calibration
1. Remove the thermocouple wires (if present) from terminals 31 and 32. Replace them with pieces of wire that will be connected to a 20 milliamp input current
(see Figure D.5). Make sure terminal screws are securely tightened, but do not connect the wires yet (leave inputs floating).
2. Turn on power to the unit.
3. Press MENU until the display indicates CALIBRATE ANA. mA IN, then
4. The controller will display SET BOTH JUMPER=mA.
5. Power down the controller and remove chassis from the case.
Addendum 531 13
press ACK. If the display shows PV=20mA PRESS ACK, move ahead to step #8.
531
Figure D.6 Analog mA Input Jumper Position
P1
P2
TB2
RATION
ERS
ECT V
TCs PUT
PER
RATION
V MA TCt TCs RTD
V MA TCt TCs RTD
2ND
PV1
TB1
6. Remove both input jumper connectors from the pins in the 2nd position. Place one of the jumpers on the PV1 position mA pins, and place the other jumper on the 2nd position mA pins, as shown in Figure D.6.
7. Reinsert the chassis into the case and apply power. The controller should dis­play PV=20mA PRESS ACK to indicate it is ready to calibrate the PV milliamp input.
8. Connect a precision 20mA input to the PV terminals (31 is PV-, 32 is PV+). Make sure the terminal connections are fastened tightly and that a 20mA current is flowing through PV. Do not connect the 20mA current to SP yet.
9. Let the controller warm up for at least 10 minutes (keep in normal horizontal position). Make sure the current is flowing, then press ACK to calibrate the PV input.
10.If the controller briefly displays SP=20mA PRESS ACK, PV calibration was suc­cessful. Move on to step 12.
11.If the controller briefly displays mA CALIB. FAILED, PV calibration was not suc­cessful.
Check the 20mA connections, and return to step #3 to recalibrate the PV input.
12.Remove the 20mA input from the PV terminals, and attach it to the SP terminals (see Figure D.5).
Make sure the terminal connections are fastened tightly and that a 20mA cur­rent is flowing through SP terminals.
13.Let the controller warm up for an additional 5 minutes (keep in the normal hori­zontal position). Make sure the current is flowing, then press ACK to calibrate the SP input.
14.If the controller briefly displays mA CALIB. COMPLETED, SP calibration was successful and the analog milliamp calibration procedure has been completed. If calibration is complete, power down. Place the jumpers into their original positions (see Chapter 4).
15.If the controller briefly displays mA CALIB. FAILED, SP calibration was not suc­cessful. Check the 20mA connections, and return to step #3 to recalibrate the PV and SP inputs.
14 531 Addendum
MILLIAMP OUTPUT CALIBRA TION
Once a year, calibrate the milliamp output to maintain optimal performance. Additionally, calibrate an output whenever a new milliamp module is in­stalled. The 531 local output should be calibrated at terminals 5 and 6 (OUT2– and OUT2+). The bypass circuitry need not be removed to perform this calibration.
Equipment needed:
Precision 5-1/2 digit multimeter, e.g., Fluke 8842® or HP3478A® ( 4-1/2 digit
meters sacrifice accuracy)
Two small pieces of wire for every milliamp output
Test leads with clips ends
#2 Phillips screwdriver
1. Disconnect power to the instrument.
2. Remove chassis from case.
531
3. On the Microcontroller Circuit Board locate jumper locations marked PV1 and 2nd near the edge connector. Reposition both jumper connectors in the 2nd location onto pins for V and TC
4. Reinsert chassis into the case and apply power.
5. Allow controller to warm up for at least 30 minutes. The 2nd and 3rd displays should read CALIBRATE ANALOG. IN. (CALI-
BRATE Menu, ANALOG. IN section). Press MENU three times to reach the CALIBRATE ANLG. OUT Menu.
6. Connect hook up wires to the terminals for Output 2 (refer to Figure D. 7). Attach the test leads from the multimeter to the wires, and then plug the test
leads into the meter. Set the meter for DC milliamp.
7. Press ACK. The 2nd display will read OUTPUT2.
8. The 3rd display should read 4 mA. The multimeter should read a value close to 4.00.
9. Wait one minute. Use meter’s display to exactly 4.00 mA.
10.Press MENU. The 3rd display should read 20 mA.
11.Let this setting stabilize for 5 minutes. Use troller to change the meter’s display to exactly 20mA.
12.To complete calibration, press ACK key, disconnect the power and place the jumper connectors back into their original position (refer to Chapter 3).
▲▲
and
▲▲
▲▲
, as shown in Figure D.2
▲▲
▼▼
(and FAST) on the controller to change the
▼▼
▲▲
▼▼
and
(and FAST) on the con-
▲▲
▼▼
Figure D.7 Milliamp Calibration Wiring
Hook up
wires
to multi-
meter
OUT 2–
OUT 2+
+
4 5
6 7
8
RESET MENU DA T A
This function resets all parameter values back to their factory default values (except for calibration information). Refer to the flowchart tin Figure D.1.
1. Disconnect power to the instrument.
2. Remove chassis from case.
3. On the Microcontroller Circuit Board, set jumpers at the 2nd PV location to V and TC
4. Press MENU key until the display shows RESET MENU DATA.
5. Press the ACK key.
6. Press MENU key within two seconds to reset the menu data. If successful, RESET COMPLETED will appear in the display. If failed, RESET SKIPPED will appear instead.
7. To try again, press ACK key, and then press MENU key within two seconds.
8. When complete, return jumpers to their original positions.
▲▲
▲.
▲▲
HARDW ARE SCAN
Use this read-only feature to identify the output hardware and installed options of the controller.
1. Set the jumpers to V and TC ure D.2).
2. Power up the controller
3. Press MENU until HARDWARE SCAN is displayed.
▲▲
on the Microcontroller Circuit Board (see Fig-
▲▲
Addendum 531 15
531
4. Press ACK to initiate the hardware display.
5. When complete, return jumpers to their original positions (as in Chapter 3).
QUICK CALIBRA TION PROCEDURE For mA or V inputs
This procedure is for the benefit of users that have ISO or other standards that require periodic calibration verification. It enables verification and modification of the process variable input without entering the “Factory Configuration” mode.
1. Power down the 531 controller and place the input jumpers in the desired position (refer to Figure D.2 and Figure D.6).
2. Replace the process variable (PV) input signal with a suitable calibration device.
3. Apply power and allow controller to warm up for 30 minutes.
4. Place controller in manual mode. Go to the PV INPUT menu, PV OFFSET parameter.
5. Adjust the calibration device to an output signal equal to the 0% range value for the particular input sensor (for example, 4mA for a 4-20 mA input).
6. Verify value indicated in the 1st display is equal to the 0% range value for
▲▲
the particular input sensor. If incorrect, use the the correct value.
7. For a linear voltage or mA input: Press MENU to scroll to the PV GAIN parameter.
For other inputs: go to step #8.
8. Adjust the calibration device to an output signal equal to the 100% range value for the particular sensor.
9. Verify that the value shown in the 1st display is equal to 100% of the range value for the particular input sensor. If the value is not correct, use the
▲▲
and
10.Repeat steps 4 through 8 to verify all values.
11.Press DISPLAY to return to the Operation mode.
▼▼
keys to scroll to the correct value.
▲▲
▼▼
▼▼
and
keys to scroll to
▲▲
▼▼
16 531 Addendum
531
Appendix F, Page F-1 This section has been added: Appendix F, Isolation Block Diagram
Input
RSP
Input
Input
Slidewire
Input
Digital
Inputs 1-5
N
Line
G
PV
CV
L
ISO
Multiplexer
E
Power
Supply
Output 1
CPU
+V
ISO Ground
Referenced
Output 2
ISO Ground
Referenced
Output 3
ISO Ground
Referenced
Output 4
ISO Ground
Referenced
+Vd
RS485 Serial
Communications
Interface
+Ve
E
Isolated Output Ground
Earth Referenced Ground
E
Internal Ground
Milliamp Module Mechanical Relay
Addendum 531 17
1. Each of the three ground circuits are isolated from each other to withstand a potential of 500 volts for 1 minutes, or 600 volts for 1 second.
2. CV, RSP, Slidewire and the PV & SP inputs are isolated to with­stand 50 volts peak between each other for 1 minute.
3. Milliamp, Loop Power and SSR Drive modules in output posi­tion 1, 2, 3 and 4 are not isolated from each other.
4. Inputs are not isolated from the analog output due to the failsafe pass-through circuit.
+V
SSR Driver
+V
Loop Power
SSR Output
500 SERIES
Process Controllers
5 0 0
Installation
Form M500 V7
Hardware Installation
and Modification
Manual
for Electronic Products
Series 531, 532,
535, 545, 555
Model 2
Installation Guide 500 Series 1
M500 V 7, APRIL 2016
Installation
INTRODUCTION
This technical brochure provides hardware installation and modification instructions for our controllers:
Series 531, 532, 535, 545, and 555. Use these instructions with the following kits:
Display Assembly Kits
531-632 ............... 531 Display Assembly Kit
532-632 ............... 532 Display Assembly Kit
535-632 ............... 535 Display Assembly Kit
545-634 ............... 545 Display Assembly Kit
555-632 ............... 555 Display Assembly Kit
Output and Communications Module Kits
532-600 ............... 531, 532 Analog Module Kit
535-600* .............. Mechanical Relay Module Kit
535-601* .............. Milliamp Module Kit
535-602* .............. SSR Module Kit
535-603* .............. SSR Drive Module Kit
535-604* .............. Loop Power Module Kit
535-705* .............. RS-485 Communications Module Kit
Power Supply Kit
535-730* .............. 90 to 250VAC Power Supply Kit
535-732 ............... 24VAC/VDC Power Supply Kit
Mounting Kit
535-761* .............. Mounting Kit
Miscellaneous Kits
532-100 ............... 531, 532 Bypass Board Kit
535-188* .............. Rear Terminal Upgrade Kit
535-660 ............... 531, 532, 535, 545, 555 Jumper Kit
535-662* .............. Gasket Kit
(1 Panel Gasket, 1 Bezel Gasket)
535-763* .............. Bezel Retention Screw Kit
535-664* .............. Module Retention Kit
(Retention Plate and Tie Wrap)
535-665* .............. Module Retention Tie Wrap Kit
093-128* .............. Lithium Battery
EPROM Kits
531-740................ 531 EPROM Kit
532-740 ............... 532 EPROM Kit
535-741................ 535 EPROM Kit (RSP)
535-775 ............... 535 Profiler EPROM Kit (No RSP)
535-776 ............... 535 Profiler EPROM Kit (RSP)
535-740................ 535 EPROM Kit (No RSP)
545-740................ 545 EPROM Kit (No RSP)
545-741................ 545 EPROM Kit (RSP)
555-740................ 555 EPROM Kit
Microcontroller (MCU) Board Kits
535-731 ............... MCU Board Kit
545-733 ............... MCU Board Kit with CE Option
Option Board Kits
535-720 ............... 531, 532, 535, 545 Option Board Kit
(No Options)
535-721 ............... 531, 532, 535, 545 Option Board Kit
(Digital Inputs)
535-722 ............... 535, 545 Option Board Kit
(Slidewire Feedback)
535-723 ............... 535, 545 Option Board Kit
(Digital Inputs and Slidewire Feedback)
545-724 ............... 531, 532, 535, 545, 555 Option Board Kit
(RSP)
545-725 ............... 531, 532, 535, 545, 555 Option Board Kit
(Digital Inputs and RSP)
545-726 ............... 535, 545, 555 Option Board Kit
(Slidewire Feedback and RSP)
545-727 ............... 535, 545, 555 Option Board Kit
(Digital Inputs, Slidewire Feedback, and RSP)
* Universal Kit (can be used with all 500 Series Controllers)
HOW T O USE THIS MANUAL:
A. CAUTION: Static discharge will cause damage to equipment. Always ground yourself with a wrist grounding
strap when handling electronics to prevent static discharge.
B. Before removing or inserting any hardware on the controller, copy down all configuration parameters. Also,
replacing the battery, EPROM or MCU Board will erase parameter settings and they will need to be reset.
C. For all hardware adjustments, perform steps 1, 2 and 3. D. Follow the guide and complete any additional steps as required by your particular application. E. Complete your hardware adjustments with steps 15, 16, 17, 18, 19 & 20.
EQUIPMENT
To make any hardware changes to the units, you will need the following equipment:
Wrist grounding strap • Phillips screwdriver (#2)
Small flat blade screwdriver • Wire cutters
I.C. Extractor (if changing the EPROM)
2 500 Series Installation Guide
Installation
INSTRUCTIONS
To Disassemble the Unit
For any hardware modifications, disassemble the unit.
1. With power off, loosen four captive front screws with a Phillips screwdriver. Remove the four screws.
Figure 1
Location of Printed Circuit Boards for Hardware Configuration
2. Slide the chassis out of the case by pulling on front face plate assembly at the bezel (see Figure 1).
3. Locate the retention clips holding the front face assembly to the rest of the chassis. Pry apart these retention clips gently with a screwdriver to separate the printed circuit board group from the front face assembly (Photo 3). Take care not to break the clips or scratch the circuit board.
The Microcontroller Board and Power Supply Board remain attached to the Operator Interface Assem­bly by wired connectors.
Photo 3. Pry Clips
one of the larger two boards from the Option Board (Photo 4). Be careful not to bend the connector pins. Separate the other board in the same manner.
Figure 2 (opposite page) shows the Microcontroller Board, Option Board and Power Supply Board.
To Add or Change Output Modules
The 500 Series units have provisions for four output modules. The units come factory configured with specified modules installed in appropriate locations. You can make field modifications by properly remov­ing and/or adding the modules into the appropriate sockets.
Three of the output sockets are located on the Power Supply Circuit Board. A fourth output socket is located on the Option Board (refer to Figure 2).
5. A retention plate and tie wrap hold Output modules 1, 2, and 3 (on the Power Supply board) firmly in place. To remove the retention plate, snip the tie wrap with wire cutters (Photo 5).
Photo 5.
Remove Retention Plate
CAUTION: Always snip the tie wrap on top of the Retention Plate, as shown in photo 5, to prevent damage to the surface mount components.
6. A disposable tie wrap
holds Output module 4 (on the Option board) in place. To remove the module, snip the tie wrap (Photo 6).
4. The Microcontroller and Power Supply board are attached to either side of the Option board by male/female pin connectors. Use a gentle rocking motion and carefully apply pressure in a uniform direction to separate
Photo 4. Separate Boards
Installation Guide 500 Series 3
7. Inspect each module before installation to make sure the pins are straight. Align the pins with the socket holes and carefully insert the module. Press down on the module to seat it firmly on the board.
Photo 6.
Snip Tie Wrap on Mod. 4
Installation
Front of Unit Back of Unit (toward Operator Interface) (toward rear terminals)
EPROM
TB2
BATTERY
5-Pin Connector
Female 22-Pin Connector
Female 22-Pin Connector
V
MA TC TC
RTD
V
MA TC
TC
RTD
2ND
PV1
TB1
NOTE:
If you replace the EPROM chip, you must align the notch facing the front of the unit.
NOTE:
The 5- and 22-Pin connnectors on the boards are all keyed so they will only align one correct way.
Male 22-Pin Connector
Male 12-Pin Connector
12-Pin Female Connector
5-Pin Connector
Remote Setpoint Jumper
Output 4
Male 22-Pin Connector
Male 22-Pin Connector
22-Pin Female Connector
Module
Retention
Plate
over Outputs 1,2,3
Figure 2
Microntroller Board, Option Board, and Power Supply Board
NO J2 NC NO J3 NC
NO J1 NC
Jumpers
NO and NC
4 500 Series Installation Guide
Loading...