Moore Inductries STA User Manual

April 2009 225-748-01A1
Programmable Current/Voltage
Safety Trip Alarm
STA
Programmable Current/Voltage
Safety Trip Alarm
STA
All product names are registered trademarks of their respective companies.

STA (HLPRG) Quick Start Guide

Use the front pushbuttons to quickly and easily set-up the STA for your application. After programming your alarm using the diagram below, install the unit into your application using the connection diagrams and terminal designation table located in this manual.
This menu is intended to aid
in the configuration of your instrument.
However, proper use of the STA at its intended safety level cannot be
STA in Safety Instrumented Systems Section of this manual.
Front Panel
Pushbuttons
DOWN
UP
SYS
LOCK
Security Jumper installed in No Acess position.
Configure Input:
Choose input type.
Trim Input:
Match the actual reading of your
STA to a calibrated or known
value.
Configure Analog Output:
Select volt or current output.
Choose damping value
and fail mode.
(Requires -AO Option)
Trim Analog Output:
Connect the STA into a calibration
set-up as shown in the manual and
trim the analog output. (Requires -AO Option)
Password:
View or change password.
Exit Configuration Menu:
Return to process display.
acheived without thorough review of the
SELECT
CONFG
INPUT
D
SCALE
INPUT
D
TRIM
INPUT
D
CONFG
ALARM
D
CONFG
AOUT
D
SCALE
AOUT
D
AOUT
D
CONFG OPTNS
D
CONFG
PASS
D
RESET
FAULT
D
CONFG
D
WARNING:
Security Jumper installed in Full Acess position.
U
U
U
U
U
U
TRIM
U
U
U
U
EXIT
Use the UP and DOWN pushbuttons to scroll through menus and sub-menus. Use the SELECT pushbutton to access menus and/or make a choice.
Security Jumper installed in Password Required position.
Enter the password
ENTER
code to enable
PASS
settings changes. (Default = 1) (
If the incorrect password is entered,
access to the configuration menus is denied.)
Scale Input: Set the values to be displayed at zero and full scale without calibration equipment.
Configure Alarm: Set trip point, dead band, high/low trip and latching/non-latching.
Scale Analog Output: Set the values for output at zero and full input (Requires -AO Option)
Configure Options: Display mode, decimal places, 50/60Hz filter, display test and factory reset.
Reset Fault: Reset fault option, select “Yes” or “No”.

Table of Contents

Introduction .............................................................................................................................................6
About This Manual ...........................................................................................................6
Model and Serial Numbers...............................................................................................6
STA Description................................................................................................................6
Inputs ...............................................................................................................................6
Alarms ..............................................................................................................................6
Options .............................................................................................................................6
Confi gur ation ....................................................................................................................6
STA Application Examples ............................................................................ 7
Alarm T erminology .........................................................................................8
STA Diagnostics & Fault Alarms ...................................................................9
Specifi cations ............................................................................................... 10
Dimensions ....................................................................................................................11
Security Settings ..........................................................................................13
Password Setting ...........................................................................................................13
STA Confi guration ........................................................................................ 14
View Menu .....................................................................................................................14
Main Confi guration Menu ...............................................................................................15
Confi guring the Input ......................................................................................................17
Scaling the Input ............................................................................................................18
Input Trimming ................................................................................................................19
Confi guring the Alarm(s) ................................................................................................21
Confi guring the Analog Output (-AO Option) .................................................................23
Scaling the Analog Output (-AO Option) ........................................................................24
Trimming the Analog Output (-AO Option) .....................................................................24
Confi guring the Options .................................................................................................26
Password Confi guration .................................................................................................27
Reset Fault .....................................................................................................................27
Confi gur ation Exit ...........................................................................................................28
STA Diagnostic Messages ........................................................................... 28
STA Transfer Utility Software ....................................................................... 30
Installing the Transfer Utility Software ............................................................................30
Connecting the STA to the PC .......................................................................................30
Transfer Utility Software Summary .............................................................31
Menu and Tool Bar Legend ............................................................................................32
File Management ...........................................................................................................32
Save a File ....................................................................................................................32
Load a File ....................................................................................................................32
Installation ..................................................................................................... 33
Mounting ........................................................................................................................33
Making the Electrical Connections .................................................................................33
Recommended Ground Wiring Practices .......................................................................33
CE Conformity ................................................................................................................33
Operation ....................................................................................................... 33
Maintenance ...................................................................................................................33
Customer Support ........................................................................................ 33
STA in Safety Instrumented Systems ......................................................... 34
Functional Safety Description ........................................................................................34
Failure Rate Data ...........................................................................................................34
Product Life ....................................................................................................................34
Installation ......................................................................................................................34
Confi guration ..................................................................................................................34
Process Safety Time ......................................................................................................34
Analog Output - Non-Safety ...........................................................................................34
Sensor Types ..................................................................................................................35
Broken Wire Detection ...................................................................................................35
Sensor Trimming Enable/Disable ...................................................................................35
Latching Mode Enable/Disable ......................................................................................35
Remote Manual Reset ...................................................................................................35
Operation and Maintenance ...........................................................................................35
Proof Test Steps .............................................................................................................36
Declaration of Conformity............................................................................37
Return Procedures and Warranty Information ........................................... 38
STA
Programmable Current/Voltage Safety Trip Alarm

Introduction

This is the user’s manual for Moore Industries’ STA (HLPRG): Programmable Current/Voltage Safety Trip Alarm.
The Moore Industries’ Safety Trip Alarm (STA) is designed and manufactured to provide a high level of availability for safety critical applications and for use as a component part of a safety instrumented system.
This manual contains all of the information needed to confi gure, install, operate and maintain this product. When the STA is used in a SIL rated safety application (as defi ned by IEC 61508), the Safety Instrumented Systems section of this manual must be read and followed in order for the STA to meet it’s IEC 61508 certifi cation requirements.

About this Manual

Wherever you see a “Note”, “ Caution” or “WARNING” pay particular attention.
WARNING - Hazardous procedure or condition that could injure the operator.
Caution - Hazardous procedure or condition that could damage or destroy the unit.
The STA is typically used to activate a warning light, bell or buzzer; or to initiate a system shutdown. Thus, the instrument acts as a simple, but highly reliable and effective means of monitoring and safe-guarding a process.
The STA is confi gured using front panel push buttons and a confi guration can also be saved and downloaded using the PC transfer utility. A large 5-digit display shows menu prompts during push button confi guration and process variable and status messages during normal operation.

Inputs

The STA (HLPRG) supports either current inputs from 0-50mA (1mA minimum span) or voltage inputs from 0-10V (250mV minimum span). These inputs can be trimmed and scaled, refer to the Confi guring Inputs section of this manual for additional information.

TX Power

A transmitter excitation power supply (24Vdc ±10%@24mA) is standard on the STA (HLPRG). You may access this externally at the terminals shown in Figure 5.
Note - Information that is helpful for a procedure, condition, or operation of the unit.

Model and Serial Numbers

Moore Industries uses a system of model and serial numbers to keep track of all of the information on every unit it sells and services. If a problem occurs with your STA, check for a tag affi xed to the unit listing these numbers. Supply the Customer Support representative with this information when calling.

STA Description

Moore Industries’ STA (HLPRG) is a programmable current/voltage safety trip alarm.
The STA monitors a process variable and provides two fully user-confi gurable contact closure outputs that can be individually programmed to trip whenever the input falls outside a user-set, high or low trip point. It also has one fault alarm output which is triggered by a self-diagnosed failure of the input or the STA itself.

Alarms

The STA has three (-3PRG) contact closure alarms. One relay is factory confi gured as a Fault alarm and the remaining two relays are user-confi gurable Trip alarms. A dual color LED (Red/Green) is provided with each alarm to indicate its condition.
The fault alarm trips on a self-diagnosed failure within the STA or on any of its inputs. This alarm is latching and has to be reset by the user. Only user confi guration faults will clear automatically once the confi guration is valid. Input faults can be cleared by the “RESET FAULT” menu, and self-diagnosed faults can only be cleared by power cycling the unit. For more information refer to the Diagnostics and Fault Alarm section.
The Trip alarms are confi gurable for high or low trip with an adjustable dead band. These alarms can be latching or non-latching. Latched alarms are reset through the Manual Reset (MR) terminals.
6 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm
The relay outputs have a 3A@250Vac or 3A@30Vdc, 50/60Hz non-inductive contact rating. The contact arrangement is SPDT. All outputs are fail safe and will de-energize to trip (DET) with NO & NC relay contacts.
Refer to the Alarm Terminology and Confi guring the Alarms sections of this manual for additional information.

Options Analog Output (-AO)

The Analog Output can be confi gured to provide a voltage (0-10V) or current (0-20mA) output. The current output can be sink or source. Refer to the Confi guring the Analog Output section of this manual for additional information.
Note:
The Analog Output is not part of the safety path in
the STA.
Confi guration
The STA can be confi gured from either the front panel keyboard or by downloading a proven confi guration using the PC Transfer Utility.

STA Application Examples

The following are examples of typical STA confi gurations.
Figure 2. High Availability example
INPUT TRIP 1 TRIP 2
READY
COM
TAG
17.29
MA
DOWN
UP
STA
SAFETY TRIP ALARM
SELECT
FAULT
Process
Trip 1
Process
Trip 2
Fault
Alarm
NC1
CM1
NO1
NC2
CM2
NO2
NC3
CM3
NO3
Final Element
Logic Solver/
SIF Alarm
This confi guration (Figure 2) offers higher system availability. The Fault alarm is wired separately to inform the safety system that there is a fault alarm and that this component’s ability to carry out its portion of Safety Instrumented Function cannot be performed. This confi guration can be used in applications where it is safe to keep the process running for a short time while a defective instrument is repaired. The output process trip relays are connected 1oo2 to trip providing security against a single relay failure, however this confi guration will NOT trip if an STA fault is diagnosed.
This type of confi guration must be used with care in a safety system. The end user must determine how long the process is allowed to continue after a STA fault is detected and ensure that the unit can be repaired or replaced within this time.
Figure 1. High Integrity example
DEG C
UP
DOWN
SELECT
FAULT
Process
Trip 1
Process
Trip 2
Fault
Alarm
NC1
CM1
NO1
NC2
CM2
NO2
NC3
CM3
NO3
Final Element
INPUT TRIP 1 TRIP 2
READY
126.39
COM
TAG
STA
SAFETY TRIP ALARM
This confi guration (Figure 1) offers the highest trip integr
ity. Since all three relays are wired in series, any trip alarm or STA fault will trip the fi nal element or logic solver. This provides security against one process relay failure and any unit failures. However this confi guration is vulnerable to spurious trips as STA safe failures will also trip the fi nal element.
The Interface Solution Experts 7
STA
Programmable Current/Voltage Safety Trip Alarm

Alarm Terminology

Before setting up the STA, or incorporating the unit in your application, Moore Industries suggests that all users take a few moments to become familiar with some of the terms associated with the use of process instrumentation alarms. Figure 3 illustrates the way the STA alarms operate.
The Trip Point is the process input level at which the user wants an alarm relay to change state, typically going into an alarm condition, or “tripping”. In the STA, the user sets the trip point for each installed relay.
High/Low Alarms; High Alarms trip when the process input goes above the trip point. Low Alarms trip when the process input drops below the trip point. Each of the STA relay outputs can be set by the user to function independently as either high or low alarms.
Latching and Non-latching Alarms; once tripped, a latching alarm remains in an alarm state until the input returns to a non-alarm level AND is manually reset. Non-latching alarms return to a non-alarm state whenever the process input returns to the Reset Point. The STA relays can be set by the user to function as either latching or non-latching.
Figure 3. How Alarms Work with the Process Input
IN ALARM
HIGH ALARM
TRIP POINT
RESET
RESET
LOW ALARM
TRIP POINT
DEADBAND
TIME
IN NON-ALARM
DEADBAND
The Reset Point is the process input level at which the user wants an alarm relay to change state, typically going from alarm to non-alarm. The reset point is not necessarily the same as the trip point, because most applications call for a buffer zone or dead band around the trip point to allow for minute fl uctuations in the process input. In the STA, the reset point is determined by the dead band setting. Latching STA alarms will not “clear” unless the reset point has been reached or passed AND the manual reset contacts have been shorted.
The Dead band is the range in which an alarm remains tripped even after the process input has returned to or passed the trip point. Dead band is not required. When it is not incorporated into an alarm application, the trip point and reset point are the same. The dead band of the STA is set by the user.
Failsafe Alarms are de-energized when tripped, energized when the process input is at a non-alarm level. Non-failsafe alarms are energized whenever tripped, de-energized when the process input is at a non-alarm level. The relays in the STA are failsafe only.
Normal is the term used to describe the “shelf-state” of relay contacts. The contacts of a Normally Open relay are open (infi nite resistance) when the relay is not energized. The contacts of a Normally Closed relay are open when the relay is energized (closed when not energized).
Note:
Sometimes a non-alarm input level is
referred to as being in a “normal” condition.
This practice is intentionally avoided in this
manual. Do not confuse the term “normal”,
as in Normally Open or Normally Closed, with
a non-alarm input condition. In this manual,
“normal” is an exclusive reference to the shelf
state or quiescent state of an alarm’s relay
contacts, whether open or closed.
8 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm

STA Diagnostics & Fault Alarms

The STA has a high level of diagnostic capability to continually monitor itself and its input. This section outlines these diagnostics and functionality of the alarms. For a full list of diagnostic messages and corrective actions please refer to Table 7.

Internal diagnostics

On power up the unit runs through a thorough diagnostic test (RAM and ROM TEST messages are displayed) and an initialization process (SYS INIT is displayed) before the fault alarm is cleared. If any failure is found during power up, the fault alarm will not be cleared and an error message will be displayed. Once in operation, the unit continues diagnostic tests in the background and will set the fault alarm on any failure.
All internal diagnostic faults are latched on the fault alarm relay. The fault alarm must be cleared by power cycling the unit. If a fault is still present on power up then please contact Customer Service for further assistance.

Input diagnostics

The STA has extensive hardware diagnostics of the input to detect broken wire and saturation. It also detects out of range and linearization errors.

Broken wire is automatically set on the STA and

enables the system to distinguish between a low trip condition (which sets the trip alarm) and a failed transmitter or open input (which sets the fault alarm). See Confi guring the Input for more information.
WARNING:
For high level inputs, if Lower Range value is set to 0(V/mA) then brok
the safety function is invalidated.
All input faults are latched on the fault alarm relay. The fault alarm can be cleared by fi rst clearing the input failure and then using the confi guration menus to reset faults. If there is degradation of sensor wires, false readings could occur before the wire breaks and the trip alarm could be activated before the fault alarm. (Slow degradation is characterized by events that occur over a span of a second or so).
en wire detection is disabled and
Note:
The trip alarms are independent from the
fault alarms and will be unaffected by the fault
alarms (however they may be affected by the
specifi c failure in the unit).
Confi guration diagnostics
On power up the stored confi guration is validated. If it is invalid then the fault alarm will be set. To clear the alarm, use the menu system, to reset to the factory confi guration (FCTRY CONFG selection in the options menu), then confi gure as appropriate for the application.
Before saving a new confi guration to the unit, it will be checked for validity. If it is invalid, the fault alarm will be set. Once the confi guration is corrected, the fault alarm will be cleared.
Note:
The trip alarms are independent from the
fault alarm and will be unaffected by the fault
alarm. Therefore if the trip alarm has already
been activated it will remain so but will
NOT be activated by a broken wire or input
saturation error. For broken wire detection,
this only applies if the input is immediately
broken. If there is degradation present such
that on the way to being broken, the input
(current or voltage) enters the region between
the low alarm trip point and the broken wire
level, the low trip alarm WILL be tripped.
(Slow degradation is characterized by events
that occur over a span of a second or so)
The Interface Solution Experts 9
STA
Programmable Current/Voltage Safety Trip Alarm
Specifi cations
Performance
Specifi cations and information subject to change without notice.
Table 1. Long-Term Stability
(% of maximum span)
Input Range: Current Input
0-50mA (1mA minimum span); Voltage Input 0-11V (250mV minimum)
Input Accuracy and Alarm Trip Repeatability:
Current inputs, 2microamps (0.01% of 20mA span); Voltage inputs, 1mV (0.01% of maximum span)
Overall Accuracy:
The overall accuracy of the unit is the combined input and output accuracies. It includes the combined effects of linearity, hysteresis, repeatability and adjustment resolution. It does not include ambient temperature effect. Stability: Refer to Table 1 Dead Band: 11V or 50mA, maximum in Linear Mode; equivalent of maximum input range in user-set engineering units in Scaling/Custom Mode
Input to Output Trip Response Time:
256msec maximum from step change on input to alarm state change when alarm is set to trip at mid-point of step
Alarm Trip Delay:
Programmable from 0-120 seconds Isolation: 500Vrms between case, input, output, and power Dielectric Strength: 1966Vdc for 2 seconds, between case, input, output, and power
Power Supply:
24DC range, 18-30Vdc; UAC range, 90-260Vac
Power Consumption:
3.5W maximum for DC supply; 4W maximum for UAC supply
Power Supply Effect:
±0.002% of span per 1% line voltage change
Input Over-Range Protection: Current,
±100mA, maximum; Voltage, ±30Vdc, maximum Input Impedance: Current, 20 ohms; Voltage, 1Mohm
Stability
Current Inputs Voltage Inputs
Input to Non-Safety Critical Analog Output (Years)
1yr
0.081
0.093
Performance
(continued)
Performance
of Analog
Output
(-AO Option)
Ambient
Conditions
3yrs
0.14
0.16
TX Power Supply: 24Vdc, ±10% @ 24mA (regulated)
Output Relays
Dual Process Relays and One Fault Relay (Relays are single-pole/double-throw SPDT, 1 form C, rated 3A@250Vac or 3A@30Vdc, 50/60Hz, non-inductive)
Non-Safety-Critical Analog Output Option
Output Accuracy: Current,
±0.01% of maximum span (±2 microamps); Voltage, ±0.01% of max. span (±1mV)
Input to Analog Output Response Time:
256msec for the output to change 10% to 90% of its scale for an input step change of 0 to 100%
Analog Output Step Response Time:
100msec maximum
Analog Output Ripple (up to 120Hz): 50mV peak-to-peak
maximum on voltage output; 10mV peak-to-peak measured across a 250 ohm load resistor for current output
Analog Output Current Limiting:
Current outputs,
Output
Failure Limits
0-20mA 0, 23.6mA 4-20mA 3.6, 23.6mA X-20mA (0<X<4)
Voltage output, -0.50 -11.0V
Load Capability: Source mode (inter 0-1 kohms for current output; 2 kohms for voltage output; Sink Mode (External Power Supply), 42Vdc Max.
Load Effect (current outputs):
±0.01% of span from 0 to maximum load resistance on current output
Operating Range:
-40°C to +85°C (-40°F to +185°F)
(90% of X), 23.6mA
nal power supply),
5yrs
0.18
0.21
1yr
0.047
0.066
Ambient
Conditions
(continued)
Adjustments
Indicator
Weight
Input to Relay (Years)
0.114
Relay Range:
-40°C to +85°C (-40°F to +185°F)
Storage Range:
-40°C to +85°C (-40°F to +185°F)
Ambient Temperature Effect:
Current, 2 microamps/°C; Voltage, 1mV/°C; Output, ±0.009% of max. span/°C
Relative Humidity:
0-95%, non-condensing
RFI/EMI Protection:
20V/m@80-1000MHz, 1kHz AM, when tested to IEC61326 with 0.5% of span or less error Noise Rejection: Common Mode, 100dB@50/60Hz Normal Mode, Current Input, 70dB typical @ 50mAp-p@ 50/60Hz; Voltage Input, 70dB typical@1Vp-p@ 50/60Hz
Front panel push-buttons for parameter confi gurations; Internal jumper and menu password protect parameter settings
LCD: 2x5 14-segment
s
characters, backlit, alphanumeric readout accurate to the nearest digit. Range: -99999 to 99999; Decimal point can be user-set
LED Type:
INPUT LED: indicates input failure READY LED: Green LED indicates unit is operating properly ALARM 1 and 2 LED: Dual color LED per relay indicates alarm status FAULT LED: Green LED indicates unit is operating properly; Red LED indicates unit has fault or is latched.
Display Accuracy:
±1 digit; when scaling the display (or in custom mode), high input-to-display span ratios decrease display accuracy
513 g to 564 g (18.1 oz to 19.9 oz)
3yrs
0.81
0.105
0.147
Dual color LED
5yrs
10 The Interface Solution Experts
Figure 4. STA (HLPRG) Dimensions
55mm
(2.1 in)
118mm
(4.6 in)
REF.
Programmable Current/Voltage
Safety Trip Alarm
136mm
REF.
131mm
(5.17 in)
(5.35 in)
STA
DOWN
FAULT
SELECT
100mm
(3.9 in)
INPUT TRIP 1 TRIP 2
READY
COM
TAG
STA
SAFETY TRIP ALARM
UP
Table 2. STA (HLPRG) Terminal Designations
Input Type
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10
Current
Voltage
TX
TX
+I
Not
Used
123mm
(4.8 in)
Top Terminals (Left to Right)
COM
COM +V MR MR
Not
Used
MR MR
+Io Source
+Io Source +Vo
-Io Source +Io Sink
-Io Source +Io Sink
+Vo
REF.
REF.
52mm
(2.06 in)
47mm
(1.87 in)
-Vo
-Io Sink
-Vo
-Io Sink
C
L
Output Type
11 12 13
Fault Alarm
(SPDT Relays)
Output/Power T ype
NO3 CM3 NC3
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10
3PRG
(SPDT Relays)
NOTES:
1. Terminal blocks can accommodate 14-22 AWG solid wiring.
2. ±Io/±Vo labeling is present only when the unit is equipped with the Analog Output (-AO) option.
3. Your input power requirement (AC or DC / ACC or DCC) will depend upon your unit’s power need.
NO CM1 NC1
Middle Terminals
(Left to Right)
KEY:
AC or DC = Power Input ACC or DCC = Power Input CM = Relay Common GND = Ground
Bottom Terminals (Left to Right)
NO2
CM2 NC2
Io = Current Output MR = Manual Reset NO = Normally Open NC = Normally Closed
Not
Used
AC
or
DC
Sink = Current Sink Source = Current Source SPDT = Single-Pole/Double-Throw Vo = Voltage Output
ACC
or
DCC
GND
The Interface Solution Experts 11
STA
Programmable Current/Voltage Safety Trip Alarm
Figure 5. STA (HLPRG) Hook-Up Diagram
VOLTAGE
SOURCE
CURRENT
SOURCE
_
+
_
+
2-WIRE
TRANSMITTER
AC OR DC
POWER SUPPLY
_
+
INPUT TRIP 1 TRIP 2
READY
COM
TAG
STA
SAFETY TRIP ALARM
UP
DOWN
FAULT
SELECT
GND - +
12 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm

Security Settings

The password security function of the STA is controlled by a single jumper inside the top of the unit housing. You will need to remove the top cover in order to access the jumper. The password jumper setting will default to Password Required (Pins 1 and 2).
The default security password is 1. This is valid until the password is changed to another value.

Password Setting

The STA can operate in one of three password modes.
Full Access (Security Jumper set to Pins 2 and 3)– Complete access to the STA confi guration
menu is permitted with no password required for any read or write operations.
Figure 6. Setting the Internal Jumper for Password Security ON or OFF
Password Required (Security Jumper set to Pins 1 and 2)– A one to four-digit access code is
required to gain access to the STA confi guration menu. If the correct code is entered, full read and write operation is permitted. If an incorrect code is entered, “WRONG PASWD” will appear for 3 seconds, and return user to View menu, with read-only access to the View menu (see Figure 7).
No Access (Security Jumper removed)– The user
is limited to read-only access to the View menu. “SYS LOCK” will appear if user attempts to enter Main menu by entering “SEL”. Enter “SEL” a second time to return to View Menu.
Note:
These security settings are only applicable to
access via the front panel pushbuttons. Security
can be bypassed using the Transfer Utility Software.
See Transfer Utility Software section for more
information.
REMOVE PANEL
BY UNSCREWING
TOP FOUR SCREWS
FRONT
STA (HLPRG) TOPSIDE
SET PASSWORD SECURITY
PASSWORD SECURITY IS OFF. NO PASSWORD REQUIRED.
PASSWORD SECURITY IS ON. PASSWORD REQUIRED.
BACK
NO ACESS.
The Interface Solution Experts 13
STA
Programmable Current/Voltage Safety Trip Alarm
STA Confi guration
The STA (HLPRG) operating parameters are set using the pushbuttons found on the instrument’s front panel. This section describes the steps in order to confi gure your STA.
There are three pushbuttons on the unit’s front panel; UP, DOWN and SELECT. Together with the prompts displayed on the LCD, these are used to access menus, and to view and change the settings.
Use SELECT as your “Enter” button, to make your selections.
Use the UP and DOWN buttons to navigate within the menus.

View Menu

Figure 7 gives an overview of the View menu.
Upon power-up, the STA displays a ‘SYS INIT’ message until the power up self test is complete. In normal operation the View menu will display the variable as confi gured. This can be the process variable, the analog output variable, or both being toggled (Refer to Confi guring the Options Menu for more details).
1. From the display, press DOWN.
2. If the -AO option is present, and the unit is NOT confi gured to toggle, the other variable will be displayed. Continue pressing DOWN to view the Analog output zero, Analog output full, trip point (AL1), trip point (AL2) and fi nally returning to display measured value.
3. Enter Main Menu at any point by pressing SELECT.
Note:
If the Security jumper is removed (see Figure 7.)
entering SELECT will cause “SYS LOCK” to appear
if user attempts to enter Main menu.
Under fault conditions, the STA will display the error message describing the fault (see Table 7 for list of messages) which can be cleared from the Reset Fault menu or by power cycling the unit.
Figure 7. View Menu
(Display of Variable)
If toggling vars
If no Analog Output
TOP LEVEL
MENU
D
Display of
other var
D
XXXXX
ZERO
D
XXXXX
FULL
D
XXXXX
AL1 X*
D
XXXXX AL2 X*
SEL
U
U
SEL
If toggling vars
U
SEL
U
SEL
U
SEL
U
SEL
MAIN Menu
MAIN Menu
If no Analog Output
MAIN Menu
MAIN Menu
MAIN Menu
MAIN Menu
14 The Interface Solution Experts
D
U
STA
Programmable Current/Voltage
Safety Trip Alarm
Main Confi guration Menu
Figure 9 gives an overview of the Main Confi guration menu.
Upon power-up, the STA displays the variable(s) as confi gured via the Confi gure Options menu. Pressing the SEL button accesses a series of displays that show, in succession, the settings currently stored in unit memory.
Depending upon whether or not the Security Jumper has been installed (Figure 6), pressing SELECT will access either the fi rst screen in the main confi guration menu, “CONFG INPUT”, the password code query screen, “ENTER PASS” or the “SYS LOCK” screen.
Once the Main Menu has been accessed, the DOWN button is used to move through all of the sub-menus in a loop. Pressing the SELECT button accesses the fi rst screen of the sub-menu shown on the LCD.
Note:
STA is programmed to time out from the
confi guration menu after 5 minutes of inactivity.
When trimming the unit, 30 minutes of inactivity are
allowed before the time out. If the unit times out, the
previous settings will be reapplied.
3. If you have entered the correct password, the sensor confi guration menu, “CONFG INPUT”, will be accessed. If not, the display will show a “WRONG PASS” message.
4. From “WRONG PASS”, wait three seconds to go back to the View menu. Use the UP and DOWN buttons to view the settings in the View menu.
Note:
The menu to set or change the password stored
in STA memory is detailed in the Password
Confi guration section of the manual.
Password
This menu is bypassed if the Password Security is OFF (if the jumper is not installed then no access is allowed). To access the security jumpers, you must remove the top cover (refer to Figure 6). Refer to the Password Confi guration section of this manual for a more detailed description of the password feature.
1. If the Password Security is ON, pressing SELECT from the display of the process variable input will bring up the “ENTER PASS” screen.
2. Press SELECT again to enter the “PASS” screen. Use the UP and DOWN buttons to select correct password (default value is “1”). When the password is displayed, press
SELECT.
Note:
If the correct password is not known, the
password can be determined by either setting
password security to OFF and entering the
menu system, or using the PC Transfer Utility
to download a confi guration with a known
password.
The Interface Solution Experts 15
STA
Programmable Current/Voltage Safety Trip Alarm
Figure 8. Main Menu
WRONG
PASS
SEL (if incorrect PW)
ENTER
PASS
SEL
PASS XXXX
SEL (if correct PW)
SEL (PW required)
U = Inc. count
D = Dec. count
PROCESS VALUE
DISPLAY
SEL (Full access)
SEL (No Access)
U
CONFG
INPUT
D
U
SCALE
INPUT
D
U
TRIM
INPUT
D
SEL
SEL
SEL
UP
VIEW
menu
DOWN VIEW
menu
SYS
LOCK
SEL LOCK MODE
CONFG INPUT
menu
SCALE INPUT
menu
TRIM INPUT
menu
U = UP Key D = DOWN Key SEL = SELECT Key
U = No action
D = No action
PW = Password
If no
-AO option
CONFG
D
CONFG
D
D
D
CONFG OPTNS
D
CONFG PASWD
D
D
CONFG
D
ALARM
AOUT
SCALE
AOUT
TRIM
AOUT
RESET FAULT
EXIT
U
SEL
CONFG ALARM
menu
U
SEL
U
SEL
-AO option
If no
U
SEL
U
SEL
U
SEL
U
SEL
U
SEL
CONFG AOUT
menu
SCALE AOUT
menu
TRIM AOUT
menu
CONFG OPTNS
menu
CONFG PASWD
menu
RESET FAULT
CONFG EXIT
menu
16 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm
Confi guring the Input
Figure 9 gives an overview of the Confi guration Input menu. This allows you to select type of signal input used with the STA unit.
If the Password Security is OFF, the password sub-menu is bypassed, and the “CONFG INPUT” menu is accessed by pressing SELECT from the View menu.
1. From the “CONFG INPUT” display, press SELECT.
2. At “INPUT TYPE” press SELECT. Use the UP or DOWN arrow buttons to scroll and select from “CURNT” or “VOLTS”, for input type. The default display for this menu is always the current confi guration.
3. When the display shows the type of input that you choose to use, press SELECT.
4. Next, the “INPUT ZERO” appears. Press SELECT and use the UP or DOWN buttons to defi ne the input range. Press SELECT when correct value has been displayed.
WARNING
For HIGH LEVEL INPUT, the Lower Range Value
(LRV) must be set higher than zero. If set to zero,
Broken Wire Detection will be disabled and the
safety function is invalidated.
7. “EXIT INPUT” appears. If all values in this parameter have been set, press SELECT. If not, return to the menu and set your values.
8. The next display is the “SCALE INPUT” menu. To skip the rest of the confi guration menus and return to the process variable display, press the DOWN until you reach “CONFG EXIT”, and press SELECT. Refer to “CONFG EXIT” section of this manual for more information.
Figure 9. CONFG INPUT Menu
CONFG
INPUT
SEL
INPUT
D
INPUT
D
D
TYPE
ZERO
INPUT
FULL
U
SEL
U
SEL
U
SEL
Selection:
CURNT
VOLTS
SEL
SEL
Value Change:
XX.XX
Sensor EGU
Value Change:
XX.XX
Sensor EGU
5. Next, the “INPUT FULL” appears. Press SELECT and use the UP or DOWN buttons to defi ne the input range. Press SELECT when correct value has been displayed.
Note:
If the input variable goes 1% out of the range
defi ned by INPUT ZERO and INPUT FULL, the fault
relay will latch in an error state, and the ERROR
OOR (Out of Range) status message will be
displayed.
6. Next, the “BWIRE” appears. Press SELECT and use the UP or DOWN buttons to defi ne the point at which broken wire error will be activated. Press SELECT when correct value has been displayed.
Note:
Broken Wire Detection “BWIRE” can only be set if
the
Lower Range Value (LRV) is set higher than zero
(refer to the “INPUT ZERO” step 4).
BWIRE LEVEL
D
EXIT
INPUT
D
SEL
U
SEL
Value Change:
XX.XX
U
U
SCALE INPUT menu
Sensor EGU
SEL
The Interface Solution Experts 17
STA
Programmable Current/Voltage Safety Trip Alarm

Scaling the Input

Figure 10 gives an overview of the Input Scaling menu.
Scaling allows you to take your PV (Process Variable) reading and transform it to a custom engineering units range. PV is the unit read after selecting your input type. For example, choosing a Current input would then produce a PV displayed in mA.
Also known as “Smart Ranging”, scaling of the STA (TPRG) allows you to set the zero and full scale values of the input from the intended application, without having to connect the unit to any calibration equipment.
1. At the “SCALE INPUT” display, press SELECT.
2. “SCALE MODE” appears; press SELECT. Choose whether or not to enable scaling. This will be confi gured in the next menu. Select “SCALE OFF” or “SCALE ON” and press
SELECT.
Scale Mode– This allows you to customize
your display for your application. For example, if your process is sending a 6mA-17mA reading to the STA and you wish to view the input as 0-100% then this can be accomplished with the Scale Mode feature.
3. The “SCALE EGU” prompt is brought up. Press SELECT and choose the desired fi ve character string to be displayed. While editing the string, the current position being edited will be alternated with a “^” character. Use the UP and DOWN button to select the correct character. Pressing SELECT will move to the next position.
If you selected “SCALE OFF” in the “SCALE MODE” menu, the menu skips to Step 6. If you selected “SCALE ON”, proceed to Step 4.
5. “SCALE FULL” appears. Press SELECT to enter the menu. Enter the value you wish as your full scaled range. This value will appear when you are at the full end of your range. Press SELECT.
6. “EXIT SCALE” appears. If all scaling parameters have been set, press SELECT. The next menu selection to appear is “TRIM INPUT”.
Figure 10. SCALE INPUT Menu
SCALE
INPUT
SEL
U
SCALE MODE
D
D
SCALE
EGU
D
SCALE
ZERO
D
SCALE
FULL
D
EXIT
SCALE
D
SEL
U
SEL
U
SEL
U
SEL
U
U
Selection:
SCALE ON
SCALE OFF
SEL ON
Set Chars:
X----
SEL
Value Change:
XX.XX
SCALED EGU
SEL
Value Change:
XX.XX
SCALED EGU
SEL
SEL OFF
4. Next, “SCALE ZERO” is displayed. Use the UP and DOWN buttons to adjust your scaled zero value. This is the value that will be displayed when you are at the zero end of the input range. Press SELECT.
18 The Interface Solution Experts
SEL
TRIM INPUT menu
STA
Programmable Current/Voltage
Safety Trip Alarm

Input T rimming

Figure 11 gives an overview of the Input Trimming menu.
Sensor trimming increases the measurement accuracy of your instrument by matching the reading of its actual input to its scaling. The STA offers the use of a factory-confi gured trimming feature (“FCTRY TRIM”) or user-set, one-point or two-point (“USER 1 PNT” OR “USER 2 PNT”) trimming.
Unit default is “FCTRY TRIM”. If another trimming selection had been made and you wish to return to the “FCTRY TRIM” feature follow the instructions below.
1. Press SELECT at the “TRIM INPUT” screen. Once “TRIM MODE” appears, press SELECT.
2. Use the UP and DOWN buttons to reach the “FCTRY TRIM” display, and then press SELECT. This takes you to the “EXIT TRIM” screen.
3. To exit, press SELECT. Proceed to the “ALARM CONFG” menu
3. “TRIM ZERO” appears. To program, press SELECT. Your present zero-scale trimming value is shown, use the UP and DOWN buttons to change value, to “APPLY” your value; press SELECT. Once your value is present and fl ashing, press SELECT again. If you selected “USER 1 PNT” trimming, “EXIT TRIM” appears. Press SELECT to reach the “CONFG ALARM” menu. Proceed to Step 4 for “USER 2 PNT” trimming.
4. If you selected “USER 2 PNT” trimming, repeat the instructions in Step 2 for the “TRIM FULL” setting. Press SELECT when “EXIT TRIM” is displayed to reach the “CONFG ALARM” menu.
Note:
In the event that captured values for TRIM ZERO
and/or TRIM FULL are incorrect, ERROR TRIM
will be displayed after values are applied. Press
SELECT to exit ERROR TRIM, which will prompt
EXIT TRIM. Use the UP and DOWN buttons to
return to TRIM ZERO and/or TRIM FULL to make
changes needed.
To input user-specifi c trim values, perform the following steps: Refer to Table 6 for necessary equipment.
1. At the “TRIM INPUT” display, press SELECT. When “TRIM MODE” appears, press SELECT again. Use the UP and DOWN buttons to reach the user-set trimming menus. Press SELECT once the desired parameter is displayed– “USER 1 PNT” or “USER 2 PNT”.
2. “RESET TRIM ” appears, press SELECT. Use the UP and DOWN buttons to the desired parameter, “RESET NO?” or “RESET YES?”. Select “RESET YES?” to clear previous trimming adjustment values, or “RESET NO?” to keep them.
Resetting will keep trimming enabled, however no adjustment will be made to the input value. If the input is about to be trimmed, then this step is unnecessary
The Interface Solution Experts 19
STA
TRIM
MODE
D
U
RESET
TRIM
Selection:
RESET NO
RESET YES
D
U
TRIM
ZERO
D
U
D
U
U
TRIM FULL
TRIM
INPUT
SEL
SEL
U
SEL
SEL
Change Value:
XX.XX
APPLY
SEL
Capture Value:
XX.XX
(Flashing)
SEL FCTRY TRIM
FCTRY TRIM
FCTRY TRIM
Selection: FCTRY TRIM USER 1 PNT USER 2 PNT
D
EXIT
TRIM
SEL
SEL
Change Value:
XX.XX
APPLY
SEL
Capture Value:
XX.XX
(Flashing)
SEL
USER 1PT
SEL 1PT
SEL 2PT
USER 1PT
1PT
SEL 2PT
ERROR
TRIM
SEL
ERROR
TRIM
SEL
SEL
CONFG ALARM menu
Programmable Current/Voltage Safety Trip Alarm
Figure 11. TRIM INPUT Menu
Table 6. Necessary Equipment to Confi gure Input trimming on the STA (HLPRG)
Device Specifi cations
Current or Voltage, 2-Wire
Power Supply
Multimeter
Variable; Accurate to ±0.05% of unit span
24Vdc, ±10% or 117/230Vac, 110Vdc (depending on model)
Accurate to ±0.009% of span; e.g., HP Model 3478A
20 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm
Confi guring the Alarm(s)
The STA has one relay which is a Fault alarm and two user-confi gurable Trip alarms. The Fault alarm is not confi gurable by the user. The instructions below will explain the steps to follow in order to set the Trip alarms.
For more information about trip points, damping, etc., please reference the Alarm Terminology section of this manual.
1. At the “CONFG ALARM” menu, press SELECT. Use the UP and DOWN buttons to toggle between both alarms. When the desired alarm appears, press SELECT.
2. At the “CONFG ALRM1” menu press SELECT. At “ENTER TRIP”, press SELECT and enter your alarm trip value. Use the UP and
DOWN buttons to select your trip value; press SELECT.
If you prefer to capture the input trip value
instead of entering it, you must use the “INPUT TRIP” menu. To do so, bypass the “ENTER TRIP” menu by using the DOWN button to scroll to the menu; press SELECT. Ensure that the value you wish to capture is present then press SELECT.
The manual reset terminals, labeled “MR” are
located on the top row of terminals on the STA (see Table 5).
6. At the “ENTER DELAY” display, press SELECT. Using the UP and DOWN buttons enter the desired value (range is 0-120 seconds); press SELECT.
Delay– When your unit is in an alarm
condition, the delay is the amount of time you set (0-120sec) to elapse before a relay trips.
7. If you are to program Alarm 2, use the UP and DOWN buttons to reach “CONFG ALRM2” and repeat the steps performed from Alarm 1 using the appropriate values and settings.
If you have completed your alarm
confi gurations, use the UP and DOWN b to bypass the alarm menu. To exit, press SELECT at the “EXIT ALRMx” display.
8. At the “EXIT ALARM” display, press SELECT, this will exit the “CONFG ALARM” menu.
uttons
3. Press SELECT at “ENTER DB” and enter your dead band value using the UP and DOWN buttons. Press SELECT once your desired setting appears.
4. Pressing SELECT at the “SET HI/LO” menu directs you to confi gure the alarm as an “ALARM HI” or “ALARM LO”. Use the UP and DOWN buttons to reach your selection and press SELECT.
ALARM LO– You are notifi ed if your process
input drops below your trip point setting.
ALARM HI– You are notifi ed if your process
input exceeds your trip point setting.
5. At the “SET LATCH” display, press SELECT and choose “LATCH ON” or “LATCH OFF” using the UP and DOWN buttons; press SELECT.
Latching Alarm– When a STA is confi gured
with latching alarms, an alarm condition will not “clear” (the relay will not change states) until the input returns to a non-alarm state AND manual reset terminals are shorted.
The Interface Solution Experts 21
STA
Programmable Current/Voltage Safety Trip Alarm
Figure 12. CONFG ALARM Menu
CONFG
ALRM1
D
CONFG
D
ALARM
D
CONFG ALARM
SEL
ALRM2
EXIT
ENTER
TRIP
D
U
U
SEL
U
SEL
EXIT ALRM1
U
EXIT ALRM2
INPUT
TRIP
D
U
ENTER
DB
D
U
SET
HI/LO
D
U
SET
LATCH
D
U
ENTER
DELAY
D
U
EXIT
ALRMx
D
SEL
SEL
SEL
SEL
SEL
SEL
Value Change:
XX.XX
EGU
SEL
Capture PV:
XX.XX
EGU
SEL
Value Change:
XX.XX
EGU
SEL
Selection: ALARM HI ALARM LO
SEL
Selection: LATCH ON
LATCH OFF
SEL
Value Change:
X
SEC
SEL
SEL
22 The Interface Solution Experts
SEL
CONFG AOUT menu
STA
Programmable Current/Voltage
Safety Trip Alarm
Confi guring the Analog Output (-AO Option)
Figure 13 gives an overview of the Analog Output Confi guration menu.
If your unit is equipped with the -AO option, use this menu for confi guration.
1. Press SELECT at the “CONFG AOUT” display. This sends you to the “SEL AOUT” section. Press SELECT and use the UP and DOWN buttons to toggle between current and voltage. When the selection you desire is displayed, press SELECT.
2. Once you reach the “SET DAMP” fi eld, you may skip the damping parameter, by using the DOWN button to reach the next fi eld. To set damping, proceed to Step 3.
Damping– Output damping applies fi ltering
to slow the response of the output so that momentary input variations reduce output spikes. The time setting (0-30 seconds) defi nes how long it takes for the output to reach 63% of the target value.
3. To set damping, press SELECT at the “SET DAMP” display. Use the UP and DOWN buttons to enter a value between 0 and 30 seconds; press SELECT.
4. Press SELECT at “FAIL MODE” to program the setting. Choose from “FAIL HIGH”, “FAIL LOW” or “HOLD LAST” then press SELECT. This sends you to “EXIT AOUT”.
HIGH/LOW– Choosing either of these options
will send the output to a High or Low (see Specifi cations table), respectively. This can also be translated as 90% of the output’s zero value.
HOLD LAST– This will output the last value
present before the failure.
Figure 13. CONFG AOUT Menu
CONFG
AOUT
SEL
AOUT
D
SET
DAMP
D
FAIL
MODE
D
EXIT
AOUT
D
SEL
U
SEL
U
SEL
U
SEL
U
Selection:
VOLT
CURNT
SEL
Value Change:
XX
SEC
SEL
Selection: FAIL HIGH FAIL LOW
HOLD LAST
SEL
SEL
SCALE AOUT menu
The Interface Solution Experts 23
STA
Programmable Current/Voltage Safety Trip Alarm

Scaling the Analog Output (-AO Option)

Figure 14 gives an overview of the Analog Output Scaling menu.
Follow these instructions to scale the analog output after you have performed the confi guration.
Note:
When using the front panel pushbuttons to enter
your scaling values, you may enter only values to
two decimal places (hundredths).
1. At the “SCALE AOUT” display, press SELECT.
2. Press SELECT at the “AOUT ZERO” parameter and enter the value you want to output when your input is at zero. Press
SELECT.
3. Press SELECT at the “AOUT FULL” screen. Enter the value you want to output when your input is at full scale. Press SELECT.
4. “EXIT SCALE” appears. If all scaling parameters have been set, press SELECT.
Figure 14. SCALE AOUT Menu
SCALE
AOUT
SEL
U
AOUT ZERO
D
AOUT
D
SCALE
D
FULL
EXIT
SEL
U
SEL
U
Value Change:
XX.XX
MA/VOLT
SEL
Value Change:
XX.XX
MA/VOLT
SEL

Trimming the Analog Output (-AO Option)

Figure 15 gives an overview of the Analog Output Trimming menu.
Output trimming increases the measurement accuracy of the STA by calibrating its analog output to the device that is receiving the output. This ensures that the instrument is being correctly interpreted.
Connect the unit as shown in Figure 16 and allow fi ve minutes for warm up and stabilization.
1. At the “TRIM AOUT” display, press SELECT.
2. “TRIM ZERO” appears. Press SELECT. The value 0.00 (mA or V depending on the set up) is shown. While monitoring your reading on the meter, use the UP and DOWN buttons to adjust the output to the desired level. Use the meter in the set up to monitor the output as it is adjusted. When the output is set as desired, press SELECT.
Note:
The value on the LCD is an adjustment to the AOUT
ZERO or FULL value. This adjustment is limited to
10% of span.
3. Press SELECT at “TRIM FULL” and repeat Step 2. Press SELECT. “FCTRY TRIM” is shown on the display.
4. If you wish to reset the user-confi gured
trimming values and use factory trimming, press SELECT at the “FCTRY TRIM” screen. Use the UP and DOWN buttons to choose “YES”; press SELECT. “TEST AOUT” is brought up on the display.
By selecting “NO” at the “FCTRY TRIM”
screen, the user-confi gured trim values will be used.
5. In order to check output performance and accuracy, you may want to perform an output test. If you choose to enable this test, follow the instructions in Step 6. To bypass this feature, use the DOWN button and scroll to “EXIT TRIM”.
SEL
24 The Interface Solution Experts
TRIM AOUT menu
6. To enable the analog output test, press SELECT at the “TEST AOUT” display. Use the UP and DOWN buttons to set your output test value and press SELECT. “EXIT TRIM” appears; press SELECT.
STA
Programmable Current/Voltage
Safety Trip Alarm
Figure 15. TRIM AOUT Menu
TRIM
AOUT
SEL
U
TRIM
ZERO
D
U
TRIM FULL
D
U
FCTRY
TRIM
D
U
TEST
AOUT
D
U
EXIT
TRIM
D
SEL
SEL
SEL
SEL
Value Change:
XX.XX
MA/VOLT
SEL
Value Change:
XX.XX
MA/VOLT
SEL
Selection:
RESET NO
RESET YES
SEL
Value Change:
XX.XX
MA/VOLT
SEL
Figure 16. STA (HLPRG) Trimming Hook-Up Diagram
_
VOLTAGE SOURCE
+
_
CURRENT
SOURCE
+
_
2-WIRE
MULTIMETER
OR
DCS
-
+
CURRENT OUTPUT SOURCE
TRANSMITTER
GND +-
+
AC OR DC
POWER
SUPPLY
HOOK-UPS FOR OUTPUT TRIMMING
MULTIMETER
OR
DCS
CURRENT OUTPUT SINK
NPUT TRIP 1 TRIP 2
READY
COM
TAG
EXTERNAL
POWER SUPPLY +
+
-
-
STA
SAFETY TRIP ALARM
FAULT
DOWN
SELECT
UP
VOLTAGE OUTPUT
MULTIMETER
OR
DCS
-
+
SEL
CONFG OPTNS menu
The Interface Solution Experts 25
STA
CONFG OPTNS
D
U
D
U
DSPLY
MODE
SET DPS
SET
FILTR
SEL
D
D
U
U
DSPLY
TEST
CONFG PASWD menu
D
U
Selection:
PV
AOUT
PV + AOUT
SEL
SEL
SEL
Selection:
AUTO XXXXX XXXX.X XXX.XX XX.XXX
SEL
SEL
Selecton:
50 HZ 60 HZ
Display test is executed,
returns to
FCTRY CONFG.
SEL
SEL
Selecton:
RESET NO
RESET YES
SEL
SEL
EXIT
OPTNS
D
U
FCTRY
CONFG
Programmable Current/Voltage Safety Trip Alarm
Confi guring the Options
Figure 17 gives an overview of the Options Confi guration menu.
You may confi gure the process variable display, decimal places, 50/60Hz fi lter selection, display mode, and the run a display test from this menu.
To confi gure STA options, follow the steps below.
1. At the “CONFG OPTNS” screen, press
SELECT.
2. “DSPLY MODE” appears. Press SELECT to enter the menu. Choose between “PV”, “AOUT” and “PV + AOUT” by using the UP and
DOWN buttons. Press SELECT.
3. Next, the “SET DPS” display appears. Press SELECT. Scroll through the available choices by using the UP and DOWN buttons and press SELECT once you have made your selection.
Figure 17. CONFG OPTNS Menu
4. “SET FILTR” appears; press SELECT. Here, you must select the proper line frequency of your AC source–50Hz or 60Hz; press SELECT.
5. “DSPLY TEST” appears; press SELECT. Display test is executed and iterates through fi ve different character patterns (this ensures all LCD segments function properly).
6. “FCTRY CONFG” appears. Using the UP and DOWN buttons choose between “RESET NO?” and “RESET YES?”; press SELECT.
When resetting unit to factory default, unit is set with the following confi guration:
4 wire resistance: 0-4000 ohms
Scaling: disabled Alarms trip: 2000, at high Current output: 4-20
7. “EXIT OPTNS” appears. Press SELECT. Proceed to the “CONFG PASWD” menu.
26 The Interface Solution Experts
STA
D
D
D
U
U
U
CONFG PASWD
CONFG PASWD
EXIT
PASWD
Value Change:
XXXX PASS
SEL
SEL
RESET FAULT menu
Programmable Current/Voltage
Safety Trip Alarm
Password Confi guration
Figure 18 gives an overview of the Password Confi guration menu.
The “CONFG PASWD” menu, is for setting a new password.
1. At “CONFG PASWD”, press SELECT. This puts you in the “PASS” menu. The previously saved password appears.
2. Use the UP and DOWN buttons to set a new password to any number between 0 and 9999. Press SELECT.
3. The “EXIT PASWD” appears. Press SELECT , to exit, “RESET FAULT” menu will appear.
Figure 18. CONFG PASWD Menu

Reset Fault

Figure 19 gives an overview of the Reset Fault menu.
1. At “RESET FAULT”, press SELECT.
2. Use the UP and DOWN buttons between “RESET NO?” and “RESET YES?”. Press SELECT.
3. The “CONFG EXIT” option appears. Press SELECT , to exit Main Confi guration Menu or use the UP and DOWN buttons cycle through Main Confi guration Menu.
RESET FAULT will clear all input related faults. All unit faults must be cleared by power cycling the unit. If a fault is still present after these steps, please contact Customer Service for further assistance. Refer to Table 7 for a full list of STA diagnostic messages and corrective actions.
Figure 19. RESET FAULT
RESET
FAULT
SEL
Selection:
RESET YES?
RESET NO?
SEL
CONFG EXIT
The Interface Solution Experts 27
STA
Programmable Current/Voltage Safety Trip Alarm
Confi guration Exit
Figure 20 gives an overview of the Confg Exit menu.
1. At “CONFG EXIT”, press SELECT.
2. If no error is present use the UP and DOWN buttons between “SAVE NO?” and “SAVE YES?”.
3. If “SAVE NO?” is selected, you will be returned to View menu and no changes will be applied to unit (previous confi guration will remain unchanged).
4. If “SAVE YES?” is selected, you will be returned to View menu and changes will be applied to unit and stored in non-volatile memory.
5. If error is present two options are available “ERROR LIST” and “ERROR UNDO”. Use the UP and DOWN buttons to cycle these two options.
6. If “ERROR LIST” is selected, you see the list of confi guration errors, press SELECT and this will return you to the Main menu to make changes where needed.

STA Diagnostic Messages

Every STA is subjected to a complete suite of operational checks and tests prior to its shipment. Occasionally, however, units can sustain damage in transit from the factory to the user.
The STA is also equipped with a full set of internal diagnostics that check operation and confi guration upon power-up. If there are problems with the unit, or with confl icting operating parameter settings, the LCD will display an error message upon unit start-up, and the fault alarm will remain set. Identical diagnostics are performed in the background during run time. If a fault is detected, the fault alarm will immediately be set, and an error message will be displayed. Table 7 provides a full list of diagnostic messages and corrective actions.
7. If “ERROR UNDO” is selected, you will be returned to View menu and no changes will be applied to unit (previous confi guration will remain unchanged).
Figure 20. CONFG EXIT Menu
CONFG
EXIT
SEL (no error)
SEL (error)
Selection:
SAVE NO?
SAVE YES?
Selection:
ERROR LIST?
ERROR UNDO?
SEL LIST
Errors List:
XXXXX XXXXX XXXXX
SEL
SEL UNDO
SEL
VIEW menu
MAIN menu
28 The Interface Solution Experts
Table 7. STA Diagnostic messages and corrective actions.
STA
Programmable Current/Voltage
Safety Trip Alarm
Error Message
SYS INIT
ERROR CKSUM
ERROR CONFIG
WIREn BROKE
WIRES BROKE
ERROR OUTOF/ LIMIT
ERROR INSAT
What it Means
The system is completing initialization
The configuration stored in non-volatile memory is invalid
User has reconfigured the unit with an illegal configuration
A specific wire was detected as broken
Undetermined wire broken
The measured resistance / voltage was outside the RTD or Thermocouple table’s range
Input saturation condition (input reached 110% of calibrated range)
What to Do
Wait. Operation should commence in a few seconds.
Using the menu system, trigger the unit to use the FCTRY CONFG selection in the options menu causing it to reset to factory configuration. Next configure as appropriate for the application.
Usually caused by changing the input range, or scaled range such that the trip points and/ or deadband settings have become illegal. Reconfigure with legal values.
Repair the broken wire(s), and use the menu system to RESET FAULTS or cycle power.
Check the input and/or the selected input mode/sensor type (specifically a RTD’s alpha value), and use the menu system to RESET FAULTS or cycle power.
Check the input signal to ensure that it is within the sensor limits and use the menu system to RESET FAULTS or cycle power.
ERROR OOR
ERROR LINE/ RES
ERROR CALIB
ERROR FCTRY/ INFO
ERROR ADC
ERROR RJC
ERROR RLAYF
ERROR RLAY1
ERROR RLAY2
ERROR SWARE
ERROR HWARE
Input has gone outside the legal range (as defined by the input LRV and URV by more than 1%)
Excessive lead resistance
Calibration data is bad
Factory information is bad
General ADC failure
Reference Junction Compensation RTD burnout
Fault alarm failure
Trip alarm 1 hardware failure
Trip alarm 2 hardware failure General software failure detected by
diagnostics
General hardware failure detected by diagnostics
Note:
The Manual Reset (MR) contact does not affect the fault relay.
Check the input and/or the input Upper and Lower Range settings and use the menu system to RESET FAULTS or cycle power.
Check sensor lead resistance. A resistance over 35 ohms is excessive (5 ohms for the Cu RTD). Use the menu system to RESET FAULTS or cycle power.
Cycle power to the unit. If the error occurs again, contact MII Customer Support to arrange for a return.
The Interface Solution Experts 29
STA
Programmable Current/Voltage Safety Trip Alarm

STA Transfer Utility Software

Provided with the STA is a Transfer Utility Software program. This allows you to upload/download, view and print your instrument’s confi guration.

Installing the Transfer Utility Software

Refer to Table 8 for the equipment needed.
1. Insert the Moore Industries Interface Solution PC Confi guration Software CD into the CD drive of the PC. Access the CD and open the “STA Transfer Utility Software” folder.
2. Double-click the installation program located in the folder. Follow the prompts to correctly
install the program.

Connecting the STA to the PC

To connect the STA unit to your PC use the RS-232 or USB end of the cable to the PC’s COM port.
See Table 8 for information on the necessary equipment.
Figure 21. STA (HLPRG) PC Hook-Up Diagram
PC
TO SERIAL
(COM) PORT
OF PC
To USB
(COM)
Port of PC
NPUT TRIP 1 TRIP 2
READY
COM
TAG
STA
SAFETY TRIP ALARM
FAULT
DOWN
SELECT
UP
*Power Supply for unit is determinded by configuration ordered.
POWER
SUPPLY*
+
GND
-

Table 8. Necessary Equipment for using the STA Transfer Utility

Device Specifi cations
Power Supply
Personal Computer
(Optional)
Moore Industries Transfer
Utility Software
(Optional)
Communication Cable
or USB Cable (Optional)
24Vdc, ±10% or 117/230Vac, 110Vdc (depending on model)
80386-based (or faster) IBM PC, or 100% compatible; 4Mb free RAM; 8Mb recommended; 20Mb free disk space on hard drive (More RAM & hard disk space is required for Windows NT, 2000, XP, or Vista) Microsoft Windows 1 (one) serial port (COM 1, 2, 3, or 4) set to 19.2kbaud, no parity, 8 data bits, and 1 stop bit or one available USB port (with optional USB cable)
Version 1.0 or greater, successfully installed to the hard drive
Part# Communications Cable 803-053-26A or optional USB cable, Part# 208-236-00A
®
NT, 2000, XP, or Vista
30 The Interface Solution Experts

Transfer Utility Software Summary

Figure 22. STA (HLPRG) Main PC Screen
STA
Programmable Current/Voltage
Safety Trip Alarm
The Transfer Utility Software is made up of these sections:
1. Program Status– Displays the activity of the
connected unit. It will display such messages as: Reading STA Info, Idle, Monitoring Variables and Monitor Fail.
2. STA Status– Indicates if there are problems or
faults with the instrument.
3. Process Variables– Displays Process Variable
and Reference Junction Compensation readings.
4. STA Device Info– Indicates device identifi cation
and software revision.
5. Progress– Display indicates instrument
communication progress.
6. Communications– Notifi es user of current PC
connection/communications status.
7. Tool Bar/Status Bar– Drop down menus and
corresponding icons allow you to perform various functions within the Transfer Utility. Refer to the Status and Tool Bar Legend for a complete description.
8. Device Confi guration – Displays current device
confi guration. The window lists data source, model number (if device connected), input type, scaling, display settings, alarm settings, and analog output settings.
The Interface Solution Experts 31
STA
Allows such functions as New, Open, Save As and Print
Allows you to Upload and Download configurations
Select the PC Port (Com Port) that you will use
Allows you to Monitor and Stop monitoring the STA
Controls whether Tool and Status Bars are viewed on the screen
Displays the version of the STA Transfer Utility
Programmable Current/Voltage Safety Trip Alarm

Menu and Tool Bar Legend

Note:
Pressing the New icon or selecting New in the File
menu will discard the current confi guration.

File Management

This section describes the File Management capability which enables you to save, and apply, saved confi gurations to numerous units.
Note:
Transfer Utility can not be used to change the
confi guration. Any changes or resetting of the STA
must be done within the STA unit.

To Save a File

Set the parameters/confi guration you wish to save as a fi le on STA unit. Connect the unit to a PC using Moore Industries communications cable or optional USB cable. Once you have done this, upload fi le to the Transfer Utility, click the Save As button and assign a name to the fi le, click the Save button. Default fi le location where fi le is saved is “C:/My Moore Industries Data/STA”.

To Load a File

To retrieve or reapply a saved confi guration, click the File button, then Open and select the correct fi le name. On the Tool Bar/Status Bar click on the download icon. The settings will appear in the Device Confi guration area.
32 The Interface Solution Experts
Note:
When downloading a saved confi guration using the
Transfer Utility the password for that confi guration
will be transferred along with the all other settings.
User must know what password is to make any
changes to confi guration, or reset password
according to steps in Main Confi guration Menu
section of this manual.
STA
Programmable Current/Voltage
Safety Trip Alarm

Installation

Installation consists of physically mounting the unit and completing the electrical connections.

Mounting

The STA is housed in a “universal” DIN case that can be mounted on both 35mm G-type (EN50035) and 35mm Top-Hat (EN50022) DIN-rail.
To mount the STA on a Top-Hat DIN-rail, seat the upper extrusion on the unit back panel over the top lip of the rail and pivot downward until the housing locks into place.
To mount the unit on a G-type rail, seat the extrusion under the top lip of the rail and again, pivot downward.
When mounting multiple units, like a rack or cabinet, make sure to allow adequate vertical spacing for pivoting the units.

Making the Electrical Connections

Refer to Figure 5 (STA Front Panel Confi guration) and Figure 21 (STA connected to PC) for electrical connections.

Recommended Ground Wiring Practices

Moore Industries recommends the following ground wiring practices:
• Any Moore Industries product in a metal case or housing should be grounded.

CE Conformity

Installation of any Moore Industries’ products that carry the CE certifi cation must adhere to the guidelines as stated in order to meet the requirements set forth in the European EMC and Low Voltage Directives (EN 61326 and EN 61010). Consult the factory for the most current information on products that have been CE certifi ed.

Operation

Once confi gured, installed, and supplied with the correct power, the STA alarm begins to operate immediately. Depending upon environmental conditions, it can be expected to operate unattended for extended periods of time.

Maintenance

Moore Industries suggests a quick check for terminal tightness and general unit condition every 6-8 months. Always adhere to any site requirements for programmed maintenance.

Customer Support

Moore Industries is recognized as the industry leader in delivering top quality to its customers in products and services. We perform a battery of stringent quality assurance checks on every unit we ship. If any Moore Industries product fails to perform up to rated specifi cations, call us for help. Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide timely, accurate, and practical answers to your process instrumentation questions.
• The protective earth conductor must be connected to a system safety earth ground before making any other connections.
• All input signals to, and output signals from, Moore Industries’ products should be wired using a shielded, twisted pair technique. Shields are to be connected to an earth or safety ground at the unit itself.
• The maximum length of unshielded input and/or output signal wiring should be two inches.
Factory phone numbers are listed on the back cover of this manual.
If problems involve a particular STA, there are several pieces of information that can be gathered before you call the factory that will help our staff get the answers you need in the shortest time possible. For fastest service, gather the complete model and serial number(s) of the problem unit(s) and the job number of the original sale.
The Interface Solution Experts 33
STA
Programmable Current/Voltage Safety Trip Alarm

STA in Safety Instrumented Systems

The STA is designed for use as a component part of a safety instrumented system as defi ned by IEC61508-4 para 3.4.1.
This user manual contains all of the information needed to confi gure, install, operate and maintain this product. For safety applications the STA must only be used in accordance with this information and the restrictions and limitations as detailed below.

Functional Safety Description

The STA has been certifi ed, by TUV Rhineland Industries Service GmBH, to IEC 61508 for a single use safety instrumented device up to SIL 2. In addition, the fi rmware of the STA, during the above review, was determine to have measures in place to address systematic errors up to SIL 3. As such, this allows the STA, when confi gured in a redundant system architecture (1oo2, 2oo3, etc), to achieve up to SIL 3 as described in IEC 61508-3.

Failure Rate Data

The STA FMEDA report (Moore Industries’ Document No: 700-702-32) provides the failure data (including PFD and SFF) required for calculations to use the STA as part of a Safety Instrumented System.
Confi guration
The unit can be confi gured using the front panel buttons or transfer utility as described in this manual.
Note:
While the system is in confi guration mode the
system is in an offl ine mode and is not performing
the safety function
Do not attempt to connect the STA Transfer Utility cab
le to the STA while the output relays are
connected to a load.
The following considerations and restrictions will apply when using the STA in a safety application:
One or both trip alarms must be connected to the actuator/equipment under control (EUC). The separate dedicated fault relay must either be connected in series with the trip alarm OR connected to a separate indicator to merely alarm the fault while maintaining the process in normal operation. Refer to Figures 1 and 2 for typical STA confi gurations.
Separating the process and fault loads increases availability but its use must be authorized only after a careful hazard and operability study involving suitably qualifi ed persons.
WARNING
With this confi guration, an internal STA fault would not trip
the EUC
.

Product life

The product life of the STA is 50 years (based on worst case component life data).
However, IEC 61508-2, section 7.4 states that a useful lifetime based on experience has more weight than the calculated fi gures; Note 3 in the section comments that the useful lifetime of a transmitter is most often within 8 to 12 years.

Installation

No special installation is required in addition to the standard installation practices in this user manual. Refer to the specifi cations table of this user manual for ambient conditions and required power input.
34 The Interface Solution Experts

Process Safety Time

Process safety time is the minimum time from the initiation of a hazardous event to the point where the hazardous event is unavoidable. Any safety function designed to either prevent the event or at least mitigate its effect must be capable of performing its specifi ed safety function in a time period very much less than the process safety time.
The STA has a characteristic response time (end to end) of 256mSec.

Analog Output - Non Safety

The STA may optionally be provided with an analog output which can be used for connecting to displays, control systems, etc. The STA analog output is NOT
designed for safety use and must not be used as any part of a safety loop. The analog circuit is isolated from the STA safety circuits and consequently its failure will not compromise the certifi ed safety function of the STA.
STA
Programmable Current/Voltage
Safety Trip Alarm

Sensor Types

The STA is designed for use with a wide variety of inputs. It is the end user’s responsibility to ensure that the chosen sensor is capable of achieving the required loop SIL.

Broken Wire Detection

The STA is provided with the facility to detect both open circuit and short circuit input. This broken wire detection must always be enabled. This is essential to ensure that dangerous failure of the sensor or signal input is detected by the STA and consequently
alarmed.
WARNING
F
or HIGH LEVEL INPUT, the Lower Range Value (LRV)
must be set higher than zero. Broken Wire Detection will
be disabled if LRV is set to zero and will invalidate the
safety function.

Sensor Trimming Enable/Disable

Sensor trimming should be used with extreme care as this facility is allowed to trim the sensor accuracy by as much as 2% of the trimming point value. It is the user’s responsibility to ensure that the safety application can tolerate this.

Operation and Maintenance

Proof Test Procedure

It is normal practice with SIS that the components undergo periodic proof tests to expose dangerous faults that are not detected by internal diagnostic tests. Thus, this section specifi es how the dangerous undetected faults determined during the FMEDA can be detected during proof testing.
Calculation of the required proof test interval can be made using data in the FMEDA report (Moore Industries’ Document No: 700-702-32).
A proof test interval of 3 years is recommended for a single STA used in a typical SIL 2 low demand application (15% of the SIL band being allocated to the STA at 40°C ambient).
The proof tests described in Table 9 are designed to cover all possible dangerous undetected faults that can be detected without opening the unit. Periodically testing the STA, using the proof test steps outlined below, the accumulated PFD to a smaller but non-zero value. To completely test for all possible dangerous undetected faults, the unit must be sent back to the factory for a comprehensive proof test inspection.
AVG value can be reduced

Latching Mode Enable/Disable

The STA is provided with the capability to latch on a trip, i.e. once the output process alarm relays have de-energized they will remain de-energized until either the manual reset contact is closed or the unit is power cycled. The use of this facility will be determined by the application. It is recommended that if the output state is latched externally to the STA, the STA latching option is disabled. Please note that the fault alarm will always be latched.

Remote Manual Reset – Procedural Issues

The STA has a facility for the connection of a remote switch to release the latch on the outputs.
This function is meaningful only when automatic latching of outputs is selected in the confi guration. If the manual reset is made part of the safety procedure, it must only be used under strict supervisory and procedural control. The use of a key operated momentary contact is suggested.

Repair and Replacement

The STA is not intended to be repaired on site and has no components needing maintenance or regular replacement. On device failure, the STA should be returned to Moore Industries World Headquarters in North Hills, CA U.S.A for repair and refurbishment (refer to Returns Procedures at the end of this manual).
The STA is a certifi ed Safety component. Repair or replacement of any component without authorization from Moore Industries will invalidate any remaining warranty and the IEC61508 certifi cation.

Recording and Reporting of STA Performance

It is the end user’s responsibility to maintain records of all safety component failures, especially those that might be classifi ed as potentially dangerous.
This feedback data not only helps the supplier identify and rectify reliability issues but also to provide quantitative data to increase confi dence in the FMEDA analysis of dangerous failure rates. Please ensure that any components returned to Moore Industries Inc are returned with a clear report identifying the fault experienced.
The Interface Solution Experts 35
STA
Programmable Current/Voltage Safety Trip Alarm

Table 9. STA HLPRG proof test steps

Step Action
1 Bypass the safety PLC or take other appropriate action to avoid a false trip
Disconnect all wires from the STA. Using an ohmmeter, measure the resistance between the case
2
3
4
5 Apply a calibrated input near the high limit of the selected input configuration
6
7
8 Apply a calibrated input near the low limit of the selected input configuration
9
10
11 Restore the STA to its original configuration 12 Restore the loop to full operation 13 Remove the bypass from the safety logic solver or otherwise restore normal operation
and all exposed pins on the front. Verify that the measured resistance is greater than 1 MΩ
This tests for shorts between the power or ground to the case
Resupply power. Connect a loop device powered by the TX output. Configure all alarm outputs such that:
i. Each alarm is set to the midpoint of the configured range
Alarm 1 is set to trip when the input is below the midpoint, Alarm 2 is set to trip when the input
ii.
is above the midpoint
Cause the loop device to go to its maximum output value. Verify that the device is not power starved, eg displaying symptoms of power cycling, browning out, etc. Verify that the STA is measuring the input from the loop device correctly by viewing the display or using the STA transfer utility in monitoring mode
This verifies the proper operation of the TX supply circuit and that the supplied current is not below the maximum requirements of the loop device
Verify that the input as reported by viewing the display or using the STA transfer utility in monitoring mode matches what is expected
This tests for failures in the input connections to the A/D converter near the high limit operation
Verify that for each alarm, the output is as expected
This test verifies signaling for the tested relay and for issues in the relay to the output connections
Verify that the input as reported by viewing the display or using the STA transfer utility in monitoring mode matches what is expected
This test completes the full test for failures in the input connections to the A/D converter near the low limit operation. This also covers the CPU and A/D clocks
Verify that for the configured alarms, the output is as expected
This test ensures that there is no crosstalk between the relays
36 The Interface Solution Experts
Declaration of Conformity
EMC Directive 2004/108/EC
Low Voltage Directive 2006/95/EC
Manufacturer’s Name: Moore Industries-International, Inc.
Manufacturer’s Address: 16650 Schoenborn Street
North Hills, CA 91343-6196 USA
Declares that the product(s):
• Product Name: STA HLPRG
MODEL / INPUT / OUTPUT / POWER / OPTIONS / HOUSING
• Model Number(s): STA * * * * *
* Indicates any input, output, option and housing as stated on the product data sheet.
• Conforms to the following EMC specifi cations:
EN 61326-1, 2006, Electromagnetic Compliance (EMC) requirements for electrical equipment for control use
EN 61010-1, 2004, Safety requirements for electrical equipment for measurement and control use
• Supplementary Information:
None
October 22, 2008
Quality Assurance Director Moore Industries-Europe General Mgr.
United States • info@miinet.com
Tel: (818) 894-7111 • FAX: (818) 891-2816
Australia • sales@mooreind.com.au
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
China • sales@mooreind.sh.cn
Tel: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair
If you are unsure if your unit is still under warranty, we can use the unit’s serial number to verify the warranty status for you over the phone. Be sure to include the RMA number on all documentation.
Non-Warranty Repair
If your unit is out of warranty, be prepared to give us a Purchase Order number when you call. In most cases, we will be able to quote you the repair costs at that time. The repair price you are quoted will be a “Not To Exceed” price, which means that the actual repair costs may be less than the quote. Be sure to include the RMA number on all documentation.
2. Provide us with the following documentation: a) A note listing the symptoms that indicate the unit needs repair b) Complete shipping information for return of the equipment after repair c) The name and phone number of the person to contact if questions arise at the factory
3. Use suffi cient packing material and carefully pack the equipment in a sturdy shipping con-
tainer.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries rep­resentative will contact the person designated on your documentation if more information is needed. The repaired equipment, or its replacement, will be returned to you in accordance with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WAR­RANTIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SERVICES SOLD BY THE COMPANY. THE COMPANY DIS­CLAIMS ALL WARRANTIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWLEDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IMPLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANY WAY. ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REM­EDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CON­SEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RE­CEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WARRANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOV­ERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under normal conditions of use and service, Moore Industries (“The Company”) will at its option replace, repair or refund the purchase price for any of its manufactured products found, upon return to the Company (transportation charges prepaid and otherwise in accordance with the return procedures established by The Company), to be defective in material or workmanship. This policy extends to the original Buyer only and not to Buyer’s customers or the users of Buyer’s products, unless Buyer is an engineering contractor in which case the policy shall extend to Buyer’s immediate customer only. This policy shall not apply if the product has been subject to alteration, misuse, accident, neglect or improper application, installation, or operation. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Tel: (818) 894-7111 • FAX: (818) 891-2816
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
© 2004 Moore Industries-International, Inc.
United States • info@miinet.com
Australia • sales@mooreind.com.au
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
Specifi cations and Information subject to change without notice.
China • sales@mooreind.sh.cn
Tel: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
Loading...