All product names are registered trademarks of their respective companies.
STA (HLPRG) Quick Start Guide
Use the front pushbuttons to quickly and easily set-up
the STA for your application. After programming your
alarm using the diagram below, install the unit into
your application using the connection diagrams and
terminal designation table located in this manual.
This menu is intended to aid
in the configuration of your instrument.
However, proper use of the STA at
its intended safety level cannot be
STA in Safety Instrumented Systems Section of this manual.
Front Panel
Pushbuttons
DOWN
UP
SYS
LOCK
Security Jumper
installed in No
Acess position.
Configure Input:
Choose input type.
Trim Input:
Match the actual reading of your
STA to a calibrated or known
value.
Configure Analog Output:
Select volt or current output.
Choose damping value
and fail mode.
(Requires -AO Option)
Trim Analog Output:
Connect the STA into a calibration
set-up as shown in the manual and
trim the analog output.
(Requires -AO Option)
Password:
View or change password.
Exit Configuration Menu:
Return to process display.
acheived without thorough review of the
SELECT
CONFG
INPUT
D
SCALE
INPUT
D
TRIM
INPUT
D
CONFG
ALARM
D
CONFG
AOUT
D
SCALE
AOUT
D
AOUT
D
CONFG
OPTNS
D
CONFG
PASS
D
RESET
FAULT
D
CONFG
D
WARNING:
Security Jumper
installed in Full
Acess position.
U
U
U
U
U
U
TRIM
U
U
U
U
EXIT
Use the UP and DOWN pushbuttons
to scroll through menus and sub-menus.
Use the SELECT pushbutton to access
menus and/or make a choice.
Security Jumper
installed in Password
Required position.
Enter the password
ENTER
code to enable
PASS
settings changes.
(Default = 1)
(
If the incorrect password is entered,
access to the configuration menus is denied.)
Scale Input:
Set the values to be displayed
at zero and full scale without
calibration equipment.
Configure Alarm:
Set trip point, dead band,
high/low trip and
latching/non-latching.
Scale Analog Output:
Set the values for output at
zero and full input
(Requires -AO Option)
Configure Options:
Display mode, decimal places,
50/60Hz filter, display test and factory reset.
Reset Fault:
Reset fault option,
select “Yes” or “No”.
Operation and Maintenance ...........................................................................................35
Proof Test Steps .............................................................................................................36
Declaration of Conformity............................................................................37
Return Procedures and Warranty Information ........................................... 38
STA
Programmable Current/Voltage
Safety Trip Alarm
Introduction
This is the user’s manual for Moore Industries’ STA
(HLPRG): Programmable Current/Voltage Safety Trip
Alarm.
The Moore Industries’ Safety Trip Alarm (STA) is
designed and manufactured to provide a high level of
availability for safety critical applications and for use
as a component part of a safety instrumented system.
This manual contains all of the information needed to
confi gure, install, operate and maintain this product.
When the STA is used in a SIL rated safety application
(as defi ned by IEC 61508), the Safety Instrumented
Systems section of this manual must be read and
followed in order for the STA to meet it’s IEC 61508
certifi cation requirements.
About this Manual
Wherever you see a “Note”, “ Caution” or “WARNING”
pay particular attention.
WARNING - Hazardous procedure or condition that
could injure the operator.
Caution - Hazardous procedure or condition that
could damage or destroy the unit.
The STA is typically used to activate a warning light,
bell or buzzer; or to initiate a system shutdown. Thus,
the instrument acts as a simple, but highly reliable and
effective means of monitoring and safe-guarding a
process.
The STA is confi gured using front panel push
buttons and a confi guration can also be saved and
downloaded using the PC transfer utility. A large
5-digit display shows menu prompts during push
button confi guration and process variable and status
messages during normal operation.
Inputs
The STA (HLPRG) supports either current inputs from
0-50mA (1mA minimum span) or voltage inputs from
0-10V (250mV minimum span). These inputs can be
trimmed and scaled, refer to the Confi guring Inputs
section of this manual for additional information.
TX Power
A transmitter excitation power supply (24Vdc
±10%@24mA) is standard on the STA (HLPRG). You
may access this externally at the terminals shown in
Figure 5.
Note - Information that is helpful for a procedure,
condition, or operation of the unit.
Model and Serial Numbers
Moore Industries uses a system of model and serial
numbers to keep track of all of the information on
every unit it sells and services. If a problem occurs
with your STA, check for a tag affi xed to the unit
listing these numbers. Supply the Customer Support
representative with this information when calling.
STA Description
Moore Industries’ STA (HLPRG) is a programmable
current/voltage safety trip alarm.
The STA monitors a process variable and provides
two fully user-confi gurable contact closure outputs
that can be individually programmed to trip whenever
the input falls outside a user-set, high or low trip point.
It also has one fault alarm output which is triggered by
a self-diagnosed failure of the input or the STA itself.
Alarms
The STA has three (-3PRG) contact closure alarms.
One relay is factory confi gured as a Fault alarm and
the remaining two relays are user-confi gurable Trip
alarms. A dual color LED (Red/Green) is provided
with each alarm to indicate its condition.
The fault alarm trips on a self-diagnosed failure
within the STA or on any of its inputs. This alarm is
latching and has to be reset by the user. Only user
confi guration faults will clear automatically once the
confi guration is valid. Input faults can be cleared by
the “RESET FAULT” menu, and self-diagnosed faults
can only be cleared by power cycling the unit. For
more information refer to the Diagnostics and Fault
Alarm section.
The Trip alarms are confi gurable for high or low trip
with an adjustable dead band. These alarms can be
latching or non-latching. Latched alarms are reset
through the Manual Reset (MR) terminals.
6 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm
The relay outputs have a 3A@250Vac or 3A@30Vdc,
50/60Hz non-inductive contact rating. The contact
arrangement is SPDT. All outputs are fail safe and
will de-energize to trip (DET) with NO & NC relay
contacts.
Refer to the Alarm Terminology and Confi guring
the Alarms sections of this manual for additional
information.
Options
Analog Output (-AO)
The Analog Output can be confi gured to provide a
voltage (0-10V) or current (0-20mA) output. The
current output can be sink or source. Refer to the
Confi guring the Analog Output section of this manual
for additional information.
Note:
The Analog Output is not part of the safety path in
the STA.
Confi guration
The STA can be confi gured from either the front panel
keyboard or by downloading a proven confi guration
using the PC Transfer Utility.
STA Application Examples
The following are examples of typical STA
confi gurations.
Figure 2. High Availability example
INPUTTRIP 1 TRIP 2
READY
COM
TAG
17.29
MA
DOWN
UP
STA
SAFETY
TRIP
ALARM
SELECT
FAULT
Process
Trip 1
Process
Trip 2
Fault
Alarm
NC1
CM1
NO1
NC2
CM2
NO2
NC3
CM3
NO3
Final Element
Logic Solver/
SIF Alarm
This confi guration (Figure 2) offers higher system
availability. The Fault alarm is wired separately to
inform the safety system that there is a fault alarm
and that this component’s ability to carry out its
portion of Safety Instrumented Function cannot
be performed. This confi guration can be used in
applications where it is safe to keep the process
running for a short time while a defective instrument
is repaired. The output process trip relays are
connected 1oo2 to trip providing security against a
single relay failure, however this confi guration will
NOT trip if an STA fault is diagnosed.
This type of confi guration must be used with care in a
safety system. The end user must determine how long
the process is allowed to continue after a STA fault is
detected and ensure that the unit can be repaired or
replaced within this time.
Figure 1. High Integrity example
DEG C
UP
DOWN
SELECT
FAULT
Process
Trip 1
Process
Trip 2
Fault
Alarm
NC1
CM1
NO1
NC2
CM2
NO2
NC3
CM3
NO3
Final Element
INPUTTRIP 1 TRIP 2
READY
126.39
COM
TAG
STA
SAFETY
TRIP
ALARM
This confi guration (Figure 1) offers the highest trip
integr
ity. Since all three relays are wired in series,
any trip alarm or STA fault will trip the fi nal element
or logic solver. This provides security against one
process relay failure and any unit failures. However
this confi guration is vulnerable to spurious trips as
STA safe failures will also trip the fi nal element.
The Interface Solution Experts 7
STA
Programmable Current/Voltage
Safety Trip Alarm
Alarm Terminology
Before setting up the STA, or incorporating the unit
in your application, Moore Industries suggests that
all users take a few moments to become familiar with
some of the terms associated with the use of process
instrumentation alarms. Figure 3 illustrates the way
the STA alarms operate.
The Trip Point is the process input level at which the
user wants an alarm relay to change state, typically
going into an alarm condition, or “tripping”. In the
STA, the user sets the trip point for each installed
relay.
High/Low Alarms; High Alarms trip when the
process input goes above the trip point. Low Alarms
trip when the process input drops below the trip point.
Each of the STA relay outputs can be set by the user
to function independently as either high or low alarms.
Latching and Non-latching Alarms; once tripped,
a latching alarm remains in an alarm state until the
input returns to a non-alarm level AND is manually
reset. Non-latching alarms return to a non-alarm
state whenever the process input returns to the Reset
Point. The STA relays can be set by the user to
function as either latching or non-latching.
Figure 3. How Alarms Work with the Process Input
IN ALARM
HIGH ALARM
TRIP POINT
RESET
RESET
LOW ALARM
TRIP POINT
DEADBAND
TIME
IN NON-ALARM
DEADBAND
The Reset Point is the process input level at which
the user wants an alarm relay to change state,
typically going from alarm to non-alarm. The reset
point is not necessarily the same as the trip point,
because most applications call for a buffer zone or
dead band around the trip point to allow for minute
fl uctuations in the process input. In the STA, the
reset point is determined by the dead band setting.
Latching STA alarms will not “clear” unless the reset
point has been reached or passed AND the manual
reset contacts have been shorted.
The Dead band is the range in which an alarm
remains tripped even after the process input has
returned to or passed the trip point. Dead band is not
required. When it is not incorporated into an alarm
application, the trip point and reset point are the
same. The dead band of the STA is set by the user.
Failsafe Alarms are de-energized when tripped,
energized when the process input is at a non-alarm
level. Non-failsafe alarms are energized whenever
tripped, de-energized when the process input is at
a non-alarm level. The relays in the STA are failsafe
only.
Normal is the term used to describe the “shelf-state”
of relay contacts. The contacts of a Normally Open
relay are open (infi nite resistance) when the relay is
not energized. The contacts of a Normally Closed
relay are open when the relay is energized (closed
when not energized).
Note:
Sometimes a non-alarm input level is
referred to as being in a “normal” condition.
This practice is intentionally avoided in this
manual. Do not confuse the term “normal”,
as in Normally Open or Normally Closed, with
a non-alarm input condition. In this manual,
“normal” is an exclusive reference to the shelf
state or quiescent state of an alarm’s relay
contacts, whether open or closed.
8 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm
STA Diagnostics & Fault Alarms
The STA has a high level of diagnostic capability to
continually monitor itself and its input. This section
outlines these diagnostics and functionality of the
alarms. For a full list of diagnostic messages and
corrective actions please refer to Table 7.
Internal diagnostics
On power up the unit runs through a thorough
diagnostic test (RAM and ROM TEST messages are
displayed) and an initialization process (SYS INIT
is displayed) before the fault alarm is cleared. If
any failure is found during power up, the fault alarm
will not be cleared and an error message will be
displayed. Once in operation, the unit continues
diagnostic tests in the background and will set the
fault alarm on any failure.
All internal diagnostic faults are latched on the fault
alarm relay. The fault alarm must be cleared by power
cycling the unit. If a fault is still present on power
up then please contact Customer Service for further
assistance.
Input diagnostics
The STA has extensive hardware diagnostics of the
input to detect broken wire and saturation. It also
detects out of range and linearization errors.
Broken wire is automatically set on the STA and
enables the system to distinguish between a low
trip condition (which sets the trip alarm) and a failed
transmitter or open input (which sets the fault alarm).
See Confi guring the Input for more information.
WARNING:
For high level inputs, if Lower Range value is set to
0(V/mA) then brok
the safety function is invalidated.
All input faults are latched on the fault alarm relay.
The fault alarm can be cleared by fi rst clearing the
input failure and then using the confi guration menus
to reset faults. If there is degradation of sensor wires,
false readings could occur before the wire breaks
and the trip alarm could be activated before the fault
alarm. (Slow degradation is characterized by events
that occur over a span of a second or so).
en wire detection is disabled and
Note:
The trip alarms are independent from the
fault alarms and will be unaffected by the fault
alarms (however they may be affected by the
specifi c failure in the unit).
Confi guration diagnostics
On power up the stored confi guration is validated. If
it is invalid then the fault alarm will be set. To clear
the alarm, use the menu system, to reset to the
factory confi guration (FCTRY CONFG selection in the
options menu), then confi gure as appropriate for the
application.
Before saving a new confi guration to the unit, it will be
checked for validity. If it is invalid, the fault alarm will
be set. Once the confi guration is corrected, the fault
alarm will be cleared.
Note:
The trip alarms are independent from the
fault alarm and will be unaffected by the fault
alarm. Therefore if the trip alarm has already
been activated it will remain so but will
NOT be activated by a broken wire or input
saturation error. For broken wire detection,
this only applies if the input is immediately
broken. If there is degradation present such
that on the way to being broken, the input
(current or voltage) enters the region between
the low alarm trip point and the broken wire
level, the low trip alarm WILL be tripped.
(Slow degradation is characterized by events
that occur over a span of a second or so)
The Interface Solution Experts 9
STA
Programmable Current/Voltage
Safety Trip Alarm
Specifi cations
Performance
Specifi cations and information subject to change without notice.
Table 1. Long-Term Stability
(% of maximum span)
Input Range: Current Input
0-50mA (1mA minimum
span); Voltage Input 0-11V
(250mV minimum)
Input Accuracy and Alarm
Trip Repeatability:
Current inputs, 2microamps
(0.01% of 20mA span);
Voltage inputs, 1mV (0.01%
of maximum span)
Overall Accuracy:
The overall accuracy of the
unit is the combined input
and output accuracies. It
includes the combined
effects of linearity, hysteresis,
repeatability and adjustment
resolution. It does not include
ambient temperature effect.
Stability: Refer to
Table 1
Dead Band: 11V or 50mA,
maximum in Linear Mode;
equivalent of maximum input
range in user-set engineering
units in Scaling/Custom Mode
Input to Output Trip
Response Time:
256msec maximum from step
change on input to alarm
state change when alarm is
set to trip at mid-point of step
Alarm Trip Delay:
Programmable from 0-120
seconds
Isolation: 500Vrms between
case, input, output, and
power
Dielectric Strength: 1966Vdc
for 2 seconds, between case,
input, output, and power
Power Supply:
24DC range, 18-30Vdc; UAC
range, 90-260Vac
Power Consumption:
3.5W maximum for DC
supply; 4W maximum for UAC
supply
Load Capability: Source mode
(inter
0-1 kohms for current output;
2 kohms for voltage output; Sink
Mode (External Power Supply),
42Vdc Max.
Load Effect (current outputs):
±0.01% of span from 0 to
maximum load resistance on
current output
Operating Range:
-40°C to +85°C
(-40°F to +185°F)
(90% of X), 23.6mA
nal power supply),
5yrs
0.18
0.21
1yr
0.047
0.066
Ambient
Conditions
(continued)
Adjustments
Indicator
Weight
Input to Relay (Years)
0.114
Relay Range:
-40°C to +85°C
(-40°F to +185°F)
Storage Range:
-40°C to +85°C
(-40°F to +185°F)
Ambient Temperature Effect:
Current, 2 microamps/°C;
Voltage, 1mV/°C; Output,
±0.009% of max. span/°C
Relative Humidity:
0-95%, non-condensing
RFI/EMI Protection:
20V/m@80-1000MHz, 1kHz
AM, when tested to IEC61326
with 0.5% of span or less error
Noise Rejection: Common
Mode, 100dB@50/60Hz
Normal Mode, Current Input,
70dB typical @ 50mAp-p@
50/60Hz; Voltage Input, 70dB
typical@1Vp-p@ 50/60Hz
Front panel push-buttons for
parameter confi gurations;
Internal jumper and menu
password protect parameter
settings
LCD: 2x5 14-segment
s
characters, backlit,
alphanumeric readout
accurate to the nearest digit.
Range: -99999 to 99999;
Decimal point can be user-set
LED Type:
INPUT LED:
indicates input failure
READY LED: Green LED
indicates unit is operating
properly
ALARM 1 and 2 LED: Dual
color LED per relay indicates
alarm status
FAULT LED: Green LED
indicates unit is operating
properly; Red LED indicates
unit has fault or is latched.
Display Accuracy:
±1 digit; when scaling the
display (or in custom mode),
high input-to-display span
ratios decrease display
accuracy
513 g to 564 g
(18.1 oz to 19.9 oz)
3yrs
0.81
0.105
0.147
Dual color LED
5yrs
10 The Interface Solution Experts
Figure 4. STA (HLPRG) Dimensions
55mm
(2.1 in)
118mm
(4.6 in)
REF.
Programmable Current/Voltage
Safety Trip Alarm
136mm
REF.
131mm
(5.17 in)
(5.35 in)
STA
DOWN
FAULT
SELECT
100mm
(3.9 in)
INPUTTRIP 1 TRIP 2
READY
COM
TAG
STA
SAFETY
TRIP
ALARM
UP
Table 2. STA (HLPRG) Terminal Designations
Input Type
T1T2T3T4T5T6T7T8T9T10
Current
Voltage
TX
TX
+I
Not
Used
123mm
(4.8 in)
Top Terminals (Left to Right)
COM
COM+VMRMR
Not
Used
MRMR
+Io Source
+Io Source+Vo
-Io Source
+Io Sink
-Io Source
+Io Sink
+Vo
REF.
REF.
52mm
(2.06 in)
47mm
(1.87 in)
-Vo
-Io Sink
-Vo
-Io Sink
C
L
Output Type
111213
Fault Alarm
(SPDT Relays)
Output/Power T ype
NO3CM3NC3
B1B2B3B4B5B6B7B8B9B10
3PRG
(SPDT Relays)
NOTES:
1. Terminal blocks can accommodate 14-22 AWG solid
wiring.
2. ±Io/±Vo labeling is present only when the unit is equipped
with the Analog Output (-AO) option.
3. Your input power requirement (AC or DC / ACC or DCC)
will depend upon your unit’s power need.
NOCM1NC1
Middle Terminals
(Left to Right)
KEY:
AC or DC = Power Input
ACC or DCC = Power Input
CM = Relay Common
GND = Ground
Bottom Terminals (Left to Right)
NO2
CM2NC2
Io = Current Output
MR = Manual Reset
NO = Normally Open
NC = Normally Closed
Not
Used
AC
or
DC
Sink = Current Sink
Source = Current Source
SPDT = Single-Pole/Double-Throw
Vo = Voltage Output
ACC
or
DCC
GND
The Interface Solution Experts 11
STA
Programmable Current/Voltage
Safety Trip Alarm
Figure 5. STA (HLPRG) Hook-Up Diagram
VOLTAGE
SOURCE
CURRENT
SOURCE
_
+
_
+
2-WIRE
TRANSMITTER
AC OR DC
POWER
SUPPLY
_
+
INPUTTRIP 1 TRIP 2
READY
COM
TAG
STA
SAFETY
TRIP
ALARM
UP
DOWN
FAULT
SELECT
GND-+
12 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm
Security Settings
The password security function of the STA is
controlled by a single jumper inside the top of the
unit housing. You will need to remove the top cover
in order to access the jumper. The password jumper
setting will default to Password Required (Pins 1
and 2).
The default security password is 1. This is valid until
the password is changed to another value.
Password Setting
The STA can operate in one of three password modes.
Full Access (Security Jumper set to Pins
2 and 3)– Complete access to the STA confi guration
menu is permitted with no password required for any
read or write operations.
Figure 6. Setting the Internal Jumper for Password Security ON or OFF
Password Required (Security Jumper set to
Pins 1 and 2)– A one to four-digit access code is
required to gain access to the STA confi guration
menu. If the correct code is entered, full read and
write operation is permitted. If an incorrect code is
entered, “WRONG PASWD” will appear for 3 seconds,
and return user to View menu, with read-only access
to the View menu (see Figure 7).
No Access (Security Jumper removed)– The user
is limited to read-only access to the View menu.
“SYS LOCK” will appear if user attempts to enter Main
menu by entering “SEL”. Enter “SEL” a second time to
return to View Menu.
Note:
These security settings are only applicable to
access via the front panel pushbuttons. Security
can be bypassed using the Transfer Utility Software.
See Transfer Utility Software section for more
information.
REMOVE PANEL
BY UNSCREWING
TOP FOUR SCREWS
FRONT
STA (HLPRG) TOPSIDE
SET PASSWORD SECURITY
PASSWORD SECURITY
IS OFF. NO PASSWORD
REQUIRED.
PASSWORD SECURITY
IS ON. PASSWORD
REQUIRED.
BACK
NO ACESS.
The Interface Solution Experts 13
STA
Programmable Current/Voltage
Safety Trip Alarm
STA Confi guration
The STA (HLPRG) operating parameters are set using
the pushbuttons found on the instrument’s front panel.
This section describes the steps in order to confi gure
your STA.
There are three pushbuttons on the unit’s front panel;
UP, DOWN and SELECT. Together with the prompts
displayed on the LCD, these are used to access
menus, and to view and change the settings.
Use SELECT as your “Enter” button, to make your
selections.
Use the UP and DOWN buttons to navigate within the
menus.
View Menu
Figure 7 gives an overview of the View menu.
Upon power-up, the STA displays a ‘SYS INIT’
message until the power up self test is complete.
In normal operation the View menu will display the
variable as confi gured. This can be the process
variable, the analog output variable, or both being
toggled (Refer to Confi guring the Options Menu for
more details).
1. From the display, press DOWN.
2. If the -AO option is present, and the unit is
NOT confi gured to toggle, the other variable
will be displayed. Continue pressing DOWN
to view the Analog output zero, Analog output
full, trip point (AL1), trip point (AL2) and fi nally
returning to display measured value.
3. Enter Main Menu at any point by pressing
SELECT.
Note:
If the Security jumper is removed (see Figure 7.)
entering SELECT will cause “SYS LOCK” to appear
if user attempts to enter Main menu.
Under fault conditions, the STA will display the error
message describing the fault (see Table 7 for list of
messages) which can be cleared from the Reset Fault
menu or by power cycling the unit.
Figure 7. View Menu
(Display of Variable)
If toggling vars
If no Analog Output
TOP LEVEL
MENU
D
Display of
other var
D
XXXXX
ZERO
D
XXXXX
FULL
D
XXXXX
AL1 X*
D
XXXXX
AL2 X*
SEL
U
U
SEL
If toggling vars
U
SEL
U
SEL
U
SEL
U
SEL
MAIN Menu
MAIN Menu
If no Analog Output
MAIN Menu
MAIN Menu
MAIN Menu
MAIN Menu
14 The Interface Solution Experts
D
U
STA
Programmable Current/Voltage
Safety Trip Alarm
Main Confi guration Menu
Figure 9 gives an overview of the Main Confi guration
menu.
Upon power-up, the STA displays the variable(s) as
confi gured via the Confi gure Options menu. Pressing
the SEL button accesses a series of displays that
show, in succession, the settings currently stored in
unit memory.
Depending upon whether or not the Security Jumper
has been installed (Figure 6), pressing SELECT will
access either the fi rst screen in the main confi guration
menu, “CONFG INPUT”, the password code query
screen, “ENTER PASS” or the “SYS LOCK” screen.
Once the Main Menu has been accessed, the DOWN
button is used to move through all of the sub-menus
in a loop. Pressing the SELECT button accesses the
fi rst screen of the sub-menu shown on the LCD.
Note:
STA is programmed to time out from the
confi guration menu after 5 minutes of inactivity.
When trimming the unit, 30 minutes of inactivity are
allowed before the time out. If the unit times out, the
previous settings will be reapplied.
3. If you have entered the correct password, the
sensor confi guration menu, “CONFG INPUT”,
will be accessed. If not, the display will show a
“WRONG PASS” message.
4. From “WRONG PASS”, wait three seconds to
go back to the View menu. Use the UP and
DOWN buttons to view the settings in the View
menu.
Note:
The menu to set or change the password stored
in STA memory is detailed in the Password
Confi guration section of the manual.
Password
This menu is bypassed if the Password Security is
OFF (if the jumper is not installed then no access is
allowed). To access the security jumpers, you must
remove the top cover (refer to Figure 6). Refer to the
Password Confi guration section of this manual for a
more detailed description of the password feature.
1. If the Password Security is ON, pressing
SELECT from the display of the process
variable input will bring up the “ENTER PASS”
screen.
2. Press SELECT again to enter the “PASS”
screen. Use the UP and DOWN buttons
to select correct password (default value is
“1”). When the password is displayed, press
SELECT.
Note:
If the correct password is not known, the
password can be determined by either setting
password security to OFF and entering the
menu system, or using the PC Transfer Utility
to download a confi guration with a known
password.
The Interface Solution Experts 15
STA
Programmable Current/Voltage
Safety Trip Alarm
Figure 8. Main Menu
WRONG
PASS
SEL (if incorrect PW)
ENTER
PASS
SEL
PASS
XXXX
SEL (if correct PW)
SEL (PW required)
U = Inc. count
D = Dec. count
PROCESS VALUE
DISPLAY
SEL (Full access)
SEL (No Access)
U
CONFG
INPUT
D
U
SCALE
INPUT
D
U
TRIM
INPUT
D
SEL
SEL
SEL
UP
VIEW
menu
DOWN
VIEW
menu
SYS
LOCK
SEL LOCK MODE
CONFG INPUT
menu
SCALE INPUT
menu
TRIM INPUT
menu
U = UP Key
D = DOWN Key
SEL = SELECT Key
U = No action
D = No action
PW = Password
If no
-AO option
CONFG
D
CONFG
D
D
D
CONFG
OPTNS
D
CONFG
PASWD
D
D
CONFG
D
ALARM
AOUT
SCALE
AOUT
TRIM
AOUT
RESET
FAULT
EXIT
U
SEL
CONFG ALARM
menu
U
SEL
U
SEL
-AO option
If no
U
SEL
U
SEL
U
SEL
U
SEL
U
SEL
CONFG AOUT
menu
SCALE AOUT
menu
TRIM AOUT
menu
CONFG OPTNS
menu
CONFG PASWD
menu
RESET FAULT
CONFG EXIT
menu
16 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm
Confi guring the Input
Figure 9 gives an overview of the Confi guration Input
menu. This allows you to select type of signal input
used with the STA unit.
If the Password Security is OFF, the password
sub-menu is bypassed, and the “CONFG INPUT”
menu is accessed by pressing SELECT from the View
menu.
1. From the “CONFG INPUT” display, press
SELECT.
2. At “INPUT TYPE” press SELECT. Use the UP
or DOWN arrow buttons to scroll and select
from “CURNT” or “VOLTS”, for input type. The
default display for this menu is always the
current confi guration.
3. When the display shows the type of input that
you choose to use, press SELECT.
4. Next, the “INPUT ZERO” appears. Press
SELECT and use the UP or DOWN buttons to
defi ne the input range. Press SELECT when
correct value has been displayed.
WARNING
For HIGH LEVEL INPUT, the Lower Range Value
(LRV) must be set higher than zero. If set to zero,
Broken Wire Detection will be disabled and the
safety function is invalidated.
7. “EXIT INPUT” appears. If all values in this
parameter have been set, press SELECT. If
not, return to the menu and set your values.
8. The next display is the “SCALE INPUT” menu.
To skip the rest of the confi guration menus and
return to the process variable display, press
the DOWN until you reach “CONFG EXIT”,
and press SELECT. Refer to “CONFG EXIT”
section of this manual for more information.
Figure 9. CONFG INPUT Menu
CONFG
INPUT
SEL
INPUT
D
INPUT
D
D
TYPE
ZERO
INPUT
FULL
U
SEL
U
SEL
U
SEL
Selection:
CURNT
VOLTS
SEL
SEL
Value Change:
XX.XX
Sensor EGU
Value Change:
XX.XX
Sensor EGU
5. Next, the “INPUT FULL” appears. Press
SELECT and use the UP or DOWN buttons to
defi ne the input range. Press SELECT when
correct value has been displayed.
Note:
If the input variable goes 1% out of the range
defi ned by INPUT ZERO and INPUT FULL, the fault
relay will latch in an error state, and the ERROR
OOR (Out of Range) status message will be
displayed.
6. Next, the “BWIRE” appears. Press SELECT
and use the UP or DOWN buttons to defi ne
the point at which broken wire error will be
activated. Press SELECT when correct value
has been displayed.
Note:
Broken Wire Detection “BWIRE” can only be set if
the
Lower Range Value (LRV) is set higher than zero
(refer to the “INPUT ZERO” step 4).
BWIRE
LEVEL
D
EXIT
INPUT
D
SEL
U
SEL
Value Change:
XX.XX
U
U
SCALE INPUT menu
Sensor EGU
SEL
The Interface Solution Experts 17
STA
Programmable Current/Voltage
Safety Trip Alarm
Scaling the Input
Figure 10 gives an overview of the Input Scaling
menu.
Scaling allows you to take your PV (Process Variable)
reading and transform it to a custom engineering units
range. PV is the unit read after selecting your input
type. For example, choosing a Current input would
then produce a PV displayed in mA.
Also known as “Smart Ranging”, scaling of the STA
(TPRG) allows you to set the zero and full scale
values of the input from the intended application,
without having to connect the unit to any calibration
equipment.
1. At the “SCALE INPUT” display, press SELECT.
2. “SCALE MODE” appears; press SELECT.
Choose whether or not to enable scaling. This
will be confi gured in the next menu. Select
“SCALE OFF” or “SCALE ON” and press
SELECT.
Scale Mode– This allows you to customize
your display for your application. For example,
if your process is sending a 6mA-17mA
reading to the STA and you wish to view
the input as 0-100% then this can be
accomplished with the Scale Mode feature.
3. The “SCALE EGU” prompt is brought up.
Press SELECT and choose the desired fi ve
character string to be displayed. While editing
the string, the current position being edited
will be alternated with a “^” character. Use the
UP and DOWN button to select the correct
character. Pressing SELECT will move to the
next position.
If you selected “SCALE OFF” in the “SCALE
MODE” menu, the menu skips to Step 6. If you
selected “SCALE ON”, proceed to Step 4.
5. “SCALE FULL” appears. Press SELECT to
enter the menu. Enter the value you wish as
your full scaled range. This value will appear
when you are at the full end of your range.
Press SELECT.
6. “EXIT SCALE” appears. If all scaling
parameters have been set, press SELECT.
The next menu selection to appear is “TRIM
INPUT”.
Figure 10. SCALE INPUT Menu
SCALE
INPUT
SEL
U
SCALE
MODE
D
D
SCALE
EGU
D
SCALE
ZERO
D
SCALE
FULL
D
EXIT
SCALE
D
SEL
U
SEL
U
SEL
U
SEL
U
U
Selection:
SCALE ON
SCALE OFF
SEL ON
Set Chars:
X----
SEL
Value Change:
XX.XX
SCALED EGU
SEL
Value Change:
XX.XX
SCALED EGU
SEL
SEL OFF
4. Next, “SCALE ZERO” is displayed. Use the UP
and DOWN buttons to adjust your scaled zero
value. This is the value that will be displayed
when you are at the zero end of the input
range. Press SELECT.
18 The Interface Solution Experts
SEL
TRIM INPUT menu
STA
Programmable Current/Voltage
Safety Trip Alarm
Input T rimming
Figure 11 gives an overview of the Input Trimming
menu.
Sensor trimming increases the measurement
accuracy of your instrument by matching the reading
of its actual input to its scaling. The STA offers the
use of a factory-confi gured trimming feature (“FCTRY
TRIM”) or user-set, one-point or two-point (“USER 1
PNT” OR “USER 2 PNT”) trimming.
Unit default is “FCTRY TRIM”. If another trimming
selection had been made and you wish to return to
the “FCTRY TRIM” feature follow the instructions
below.
1. Press SELECT at the “TRIM INPUT” screen.
Once “TRIM MODE” appears, press SELECT.
2. Use the UP and DOWN buttons to reach
the “FCTRY TRIM” display, and then press
SELECT. This takes you to the “EXIT TRIM”
screen.
3. To exit, press SELECT. Proceed to the
“ALARM CONFG” menu
3. “TRIM ZERO” appears. To program, press
SELECT. Your present zero-scale trimming
value is shown, use the UP and DOWN
buttons to change value, to “APPLY” your
value; press SELECT. Once your value is
present and fl ashing, press SELECT again. If
you selected “USER 1 PNT” trimming, “EXIT
TRIM” appears. Press SELECT to reach the
“CONFG ALARM” menu. Proceed to Step 4
for “USER 2 PNT” trimming.
4. If you selected “USER 2 PNT” trimming, repeat
the instructions in Step 2 for the “TRIM FULL”
setting. Press SELECT when “EXIT TRIM”
is displayed to reach the “CONFG ALARM”
menu.
Note:
In the event that captured values for TRIM ZERO
and/or TRIM FULL are incorrect, ERROR TRIM
will be displayed after values are applied. Press
SELECT to exit ERROR TRIM, which will prompt
EXIT TRIM. Use the UP and DOWN buttons to
return to TRIM ZERO and/or TRIM FULL to make
changes needed.
To input user-specifi c trim values, perform the
following steps: Refer to Table 6 for necessary
equipment.
1. At the “TRIM INPUT” display, press SELECT.
When “TRIM MODE” appears, press SELECT
again. Use the UP and DOWN buttons to
reach the user-set trimming menus. Press
SELECT once the desired parameter is
displayed– “USER 1 PNT” or “USER 2 PNT”.
2. “RESET TRIM ” appears, press SELECT. Use
the UP and DOWN buttons to the desired
parameter, “RESET NO?” or “RESET YES?”.
Select “RESET YES?” to clear previous
trimming adjustment values, or “RESET NO?”
to keep them.
Resetting will keep trimming enabled, however
no adjustment will be made to the input value.
If the input is about to be trimmed, then this
step is unnecessary
The Interface Solution Experts 19
STA
TRIM
MODE
D
U
RESET
TRIM
Selection:
RESET NO
RESET YES
D
U
TRIM
ZERO
D
U
D
U
U
TRIM
FULL
TRIM
INPUT
SEL
SEL
U
SEL
SEL
Change Value:
XX.XX
APPLY
SEL
Capture Value:
XX.XX
(Flashing)
SEL FCTRY TRIM
FCTRY TRIM
FCTRY TRIM
Selection:
FCTRY TRIM
USER 1 PNT
USER 2 PNT
D
EXIT
TRIM
SEL
SEL
Change Value:
XX.XX
APPLY
SEL
Capture Value:
XX.XX
(Flashing)
SEL
USER 1PT
SEL 1PT
SEL 2PT
USER 1PT
1PT
SEL 2PT
ERROR
TRIM
SEL
ERROR
TRIM
SEL
SEL
CONFG ALARM menu
Programmable Current/Voltage
Safety Trip Alarm
Figure 11. TRIM INPUT Menu
Table 6. Necessary Equipment to Confi gure Input trimming on the STA (HLPRG)
Device Specifi cations
Current or Voltage, 2-Wire
Power Supply
Multimeter
Variable; Accurate to ±0.05% of unit span
24Vdc, ±10% or 117/230Vac, 110Vdc (depending on model)
Accurate to ±0.009% of span; e.g., HP Model 3478A
20 The Interface Solution Experts
STA
Programmable Current/Voltage
Safety Trip Alarm
Confi guring the Alarm(s)
The STA has one relay which is a Fault alarm and
two user-confi gurable Trip alarms. The Fault alarm is
not confi gurable by the user. The instructions below
will explain the steps to follow in order to set the Trip
alarms.
For more information about trip points, damping, etc.,
please reference the Alarm Terminology section of this
manual.
1. At the “CONFG ALARM” menu, press
SELECT. Use the UP and DOWN buttons to
toggle between both alarms. When the desired
alarm appears, press SELECT.
2. At the “CONFG ALRM1” menu press SELECT.
At “ENTER TRIP”, press SELECT and enter
your alarm trip value. Use the UP and
DOWN buttons to select your trip value; press
SELECT.
If you prefer to capture the input trip value
instead of entering it, you must use the “INPUT
TRIP” menu. To do so, bypass the “ENTER
TRIP” menu by using the DOWN button to
scroll to the menu; press SELECT. Ensure that
the value you wish to capture is present then
press SELECT.
The manual reset terminals, labeled “MR” are
located on the top row of terminals on the STA
(see Table 5).
6. At the “ENTER DELAY” display, press SELECT.
Using the UP and DOWN buttons enter the
desired value (range is 0-120 seconds); press
SELECT.
Delay– When your unit is in an alarm
condition, the delay is the amount of time you
set (0-120sec) to elapse before a relay trips.
7. If you are to program Alarm 2, use the UP and
DOWN buttons to reach “CONFG ALRM2” and
repeat the steps performed from Alarm 1 using
the appropriate values and settings.
If you have completed your alarm
confi gurations, use the UP and DOWN b
to bypass the alarm menu. To exit, press
SELECT at the “EXIT ALRMx” display.
8. At the “EXIT ALARM” display, press SELECT,
this will exit the “CONFG ALARM” menu.
uttons
3. Press SELECT at “ENTER DB” and enter your
dead band value using the UP and DOWN
buttons. Press SELECT once your desired
setting appears.
4. Pressing SELECT at the “SET HI/LO” menu
directs you to confi gure the alarm as an
“ALARM HI” or “ALARM LO”. Use the UP and
DOWN buttons to reach your selection and
press SELECT.
ALARM LO– You are notifi ed if your process
input drops below your trip point setting.
ALARM HI– You are notifi ed if your process
input exceeds your trip point setting.
5. At the “SET LATCH” display, press SELECT
and choose “LATCH ON” or “LATCH OFF”
using the UP and DOWN buttons; press
SELECT.
Latching Alarm– When a STA is confi gured
with latching alarms, an alarm condition will not
“clear” (the relay will not change states) until
the input returns to a non-alarm state AND
manual reset terminals are shorted.
The Interface Solution Experts 21
STA
Programmable Current/Voltage
Safety Trip Alarm
Figure 12. CONFG ALARM Menu
CONFG
ALRM1
D
CONFG
D
ALARM
D
CONFG
ALARM
SEL
ALRM2
EXIT
ENTER
TRIP
D
U
U
SEL
U
SEL
EXIT ALRM1
U
EXIT ALRM2
INPUT
TRIP
D
U
ENTER
DB
D
U
SET
HI/LO
D
U
SET
LATCH
D
U
ENTER
DELAY
D
U
EXIT
ALRMx
D
SEL
SEL
SEL
SEL
SEL
SEL
Value Change:
XX.XX
EGU
SEL
Capture PV:
XX.XX
EGU
SEL
Value Change:
XX.XX
EGU
SEL
Selection:
ALARM HI
ALARM LO
SEL
Selection:
LATCH ON
LATCH OFF
SEL
Value Change:
X
SEC
SEL
SEL
22 The Interface Solution Experts
SEL
CONFG AOUT menu
STA
Programmable Current/Voltage
Safety Trip Alarm
Confi guring the Analog Output
(-AO Option)
Figure 13 gives an overview of the Analog Output
Confi guration menu.
If your unit is equipped with the -AO option, use this
menu for confi guration.
1. Press SELECT at the “CONFG AOUT” display.
This sends you to the “SEL AOUT” section.
Press SELECT and use the UP and DOWN
buttons to toggle between current and voltage.
When the selection you desire is displayed,
press SELECT.
2. Once you reach the “SET DAMP” fi eld, you
may skip the damping parameter, by using the
DOWN button to reach the next fi eld. To set
damping, proceed to Step 3.
Damping– Output damping applies fi ltering
to slow the response of the output so that
momentary input variations reduce output
spikes. The time setting (0-30 seconds)
defi nes how long it takes for the output to
reach 63% of the target value.
3. To set damping, press SELECT at the “SET
DAMP” display. Use the UP and DOWN
buttons to enter a value between 0 and 30
seconds; press SELECT.
4. Press SELECT at “FAIL MODE” to program the
setting. Choose from “FAIL HIGH”, “FAIL LOW”
or “HOLD LAST” then press SELECT. This
sends you to “EXIT AOUT”.
HIGH/LOW– Choosing either of these options
will send the output to a High or Low (see
Specifi cations table), respectively. This can
also be translated as 90% of the output’s zero
value.
HOLD LAST– This will output the last value
present before the failure.
Figure 13. CONFG AOUT Menu
CONFG
AOUT
SEL
AOUT
D
SET
DAMP
D
FAIL
MODE
D
EXIT
AOUT
D
SEL
U
SEL
U
SEL
U
SEL
U
Selection:
VOLT
CURNT
SEL
Value Change:
XX
SEC
SEL
Selection:
FAIL HIGH
FAIL LOW
HOLD LAST
SEL
SEL
SCALE AOUT menu
The Interface Solution Experts 23
STA
Programmable Current/Voltage
Safety Trip Alarm
Scaling the Analog Output
(-AO Option)
Figure 14 gives an overview of the Analog Output
Scaling menu.
Follow these instructions to scale the analog output
after you have performed the confi guration.
Note:
When using the front panel pushbuttons to enter
your scaling values, you may enter only values to
two decimal places (hundredths).
1. At the “SCALE AOUT” display, press SELECT.
2. Press SELECT at the “AOUT ZERO”
parameter and enter the value you want to
output when your input is at zero. Press
SELECT.
3. Press SELECT at the “AOUT FULL” screen.
Enter the value you want to output when your
input is at full scale. Press SELECT.
4. “EXIT SCALE” appears. If all scaling
parameters have been set, press SELECT.
Figure 14. SCALE AOUT Menu
SCALE
AOUT
SEL
U
AOUT
ZERO
D
AOUT
D
SCALE
D
FULL
EXIT
SEL
U
SEL
U
Value Change:
XX.XX
MA/VOLT
SEL
Value Change:
XX.XX
MA/VOLT
SEL
Trimming the Analog Output
(-AO Option)
Figure 15 gives an overview of the Analog Output
Trimming menu.
Output trimming increases the measurement accuracy
of the STA by calibrating its analog output to the
device that is receiving the output. This ensures that
the instrument is being correctly interpreted.
Connect the unit as shown in Figure 16 and allow fi ve
minutes for warm up and stabilization.
1. At the “TRIM AOUT” display, press SELECT.
2. “TRIM ZERO” appears. Press SELECT. The
value 0.00 (mA or V depending on the set up)
is shown. While monitoring your reading on
the meter, use the UP and DOWN buttons to
adjust the output to the desired level. Use the
meter in the set up to monitor the output as it
is adjusted. When the output is set as desired,
press SELECT.
Note:
The value on the LCD is an adjustment to the AOUT
ZERO or FULL value. This adjustment is limited to
10% of span.
3. Press SELECT at “TRIM FULL” and repeat
Step 2. Press SELECT. “FCTRY TRIM” is
shown on the display.
4. If you wish to reset the user-confi gured
trimming values and use factory trimming,
press SELECT at the “FCTRY TRIM” screen.
Use the UP and DOWN buttons to choose
“YES”; press SELECT. “TEST AOUT” is
brought up on the display.
By selecting “NO” at the “FCTRY TRIM”
screen, the user-confi gured trim values will be
used.
5. In order to check output performance and
accuracy, you may want to perform an output
test. If you choose to enable this test, follow
the instructions in Step 6. To bypass this
feature, use the DOWN button and scroll to
“EXIT TRIM”.
SEL
24 The Interface Solution Experts
TRIM AOUT menu
6. To enable the analog output test, press
SELECT at the “TEST AOUT” display. Use
the UP and DOWN buttons to set your output
test value and press SELECT. “EXIT TRIM”
appears; press SELECT.
STA
Programmable Current/Voltage
Safety Trip Alarm
Figure 15. TRIM AOUT Menu
TRIM
AOUT
SEL
U
TRIM
ZERO
D
U
TRIM
FULL
D
U
FCTRY
TRIM
D
U
TEST
AOUT
D
U
EXIT
TRIM
D
SEL
SEL
SEL
SEL
Value Change:
XX.XX
MA/VOLT
SEL
Value Change:
XX.XX
MA/VOLT
SEL
Selection:
RESET NO
RESET YES
SEL
Value Change:
XX.XX
MA/VOLT
SEL
Figure 16. STA (HLPRG) Trimming Hook-Up Diagram
_
VOLTAGE
SOURCE
+
_
CURRENT
SOURCE
+
_
2-WIRE
MULTIMETER
OR
DCS
-
+
CURRENT OUTPUT SOURCE
TRANSMITTER
GND+-
+
AC OR DC
POWER
SUPPLY
HOOK-UPS FOR OUTPUT TRIMMING
MULTIMETER
OR
DCS
CURRENT OUTPUT SINK
NPUTTRIP 1 TRIP 2
READY
COM
TAG
EXTERNAL
POWER
SUPPLY
+
+
-
-
STA
SAFETY
TRIP
ALARM
FAULT
DOWN
SELECT
UP
VOLTAGE OUTPUT
MULTIMETER
OR
DCS
-
+
SEL
CONFG OPTNS menu
The Interface Solution Experts 25
STA
CONFG
OPTNS
D
U
D
U
DSPLY
MODE
SET
DPS
SET
FILTR
SEL
D
D
U
U
DSPLY
TEST
CONFG PASWD menu
D
U
Selection:
PV
AOUT
PV + AOUT
SEL
SEL
SEL
Selection:
AUTO
XXXXX
XXXX.X
XXX.XX
XX.XXX
SEL
SEL
Selecton:
50 HZ
60 HZ
Display test
is executed,
returns to
FCTRY CONFG.
SEL
SEL
Selecton:
RESET NO
RESET YES
SEL
SEL
EXIT
OPTNS
D
U
FCTRY
CONFG
Programmable Current/Voltage
Safety Trip Alarm
Confi guring the Options
Figure 17 gives an overview of the Options
Confi guration menu.
You may confi gure the process variable display,
decimal places, 50/60Hz fi lter selection, display mode,
and the run a display test from this menu.
To confi gure STA options, follow the steps below.
1. At the “CONFG OPTNS” screen, press
SELECT.
2. “DSPLY MODE” appears. Press SELECT
to enter the menu. Choose between “PV”,
“AOUT” and “PV + AOUT” by using the UP and
DOWN buttons. Press SELECT.
3. Next, the “SET DPS” display appears. Press
SELECT. Scroll through the available choices by using the UP and DOWN buttons and press
SELECT once you have made your selection.
Figure 17. CONFG OPTNS Menu
4. “SET FILTR” appears; press SELECT. Here,
you must select the proper line frequency of
your AC source–50Hz or 60Hz; press SELECT.
5. “DSPLY TEST” appears; press SELECT.
Display test is executed and iterates through
fi ve different character patterns (this ensures
all LCD segments function properly).
6. “FCTRY CONFG” appears. Using the UP and
DOWN buttons choose between “RESET NO?”
and “RESET YES?”; press SELECT.
When resetting unit to factory default, unit is
set with the following confi guration:
4 wire resistance: 0-4000 ohms
Scaling: disabled
Alarms trip: 2000, at high
Current output: 4-20
7. “EXIT OPTNS” appears. Press SELECT.
Proceed to the “CONFG PASWD” menu.
26 The Interface Solution Experts
STA
D
D
D
U
U
U
CONFG
PASWD
CONFG
PASWD
EXIT
PASWD
Value Change:
XXXX
PASS
SEL
SEL
RESET FAULT menu
Programmable Current/Voltage
Safety Trip Alarm
Password Confi guration
Figure 18 gives an overview of the Password
Confi guration menu.
The “CONFG PASWD” menu, is for setting a new
password.
1. At “CONFG PASWD”, press SELECT. This
puts you in the “PASS” menu. The previously
saved password appears.
2. Use the UP and DOWN buttons to set a new
password to any number between 0 and 9999.
Press SELECT.
3. The “EXIT PASWD” appears. Press SELECT ,
to exit, “RESET FAULT” menu will appear.
Figure 18. CONFG PASWD Menu
Reset Fault
Figure 19 gives an overview of the Reset Fault menu.
1. At “RESET FAULT”, press SELECT.
2. Use the UP and DOWN buttons between
“RESET NO?” and “RESET YES?”. Press
SELECT.
3. The “CONFG EXIT” option appears. Press
SELECT , to exit Main Confi guration Menu or
use the UP and DOWN buttons cycle through
Main Confi guration Menu.
RESET FAULT will clear all input related faults. All
unit faults must be cleared by power cycling the
unit. If a fault is still present after these steps, please
contact Customer Service for further assistance.
Refer to Table 7 for a full list of STA diagnostic
messages and corrective actions.
Figure 19. RESET FAULT
RESET
FAULT
SEL
Selection:
RESET YES?
RESET NO?
SEL
CONFG EXIT
The Interface Solution Experts 27
STA
Programmable Current/Voltage
Safety Trip Alarm
Confi guration Exit
Figure 20 gives an overview of the Confg Exit menu.
1. At “CONFG EXIT”, press SELECT.
2. If no error is present use the UP and DOWN
buttons between “SAVE NO?” and “SAVE
YES?”.
3. If “SAVE NO?” is selected, you will be returned
to View menu and no changes will be applied
to unit (previous confi guration will remain
unchanged).
4. If “SAVE YES?” is selected, you will be
returned to View menu and changes will
be applied to unit and stored in non-volatile
memory.
5. If error is present two options are available
“ERROR LIST” and “ERROR UNDO”. Use
the UP and DOWN buttons to cycle these two
options.
6. If “ERROR LIST” is selected, you see the list
of confi guration errors, press SELECT and
this will return you to the Main menu to make
changes where needed.
STA Diagnostic Messages
Every STA is subjected to a complete suite of
operational checks and tests prior to its shipment.
Occasionally, however, units can sustain damage in
transit from the factory to the user.
The STA is also equipped with a full set of internal
diagnostics that check operation and confi guration
upon power-up. If there are problems with the unit, or
with confl icting operating parameter settings, the LCD
will display an error message upon unit start-up, and
the fault alarm will remain set. Identical diagnostics
are performed in the background during run time. If
a fault is detected, the fault alarm will immediately be
set, and an error message will be displayed.
Table 7 provides a full list of diagnostic messages and
corrective actions.
7. If “ERROR UNDO” is selected, you will be
returned to View menu and no changes will
be applied to unit (previous confi guration will
remain unchanged).
Figure 20. CONFG EXIT Menu
CONFG
EXIT
SEL (no error)
SEL (error)
Selection:
SAVE NO?
SAVE YES?
Selection:
ERROR LIST?
ERROR UNDO?
SEL LIST
Errors List:
XXXXX
XXXXX
XXXXX
SEL
SEL UNDO
SEL
VIEW menu
MAIN menu
28 The Interface Solution Experts
Table 7. STA Diagnostic messages and corrective actions.
STA
Programmable Current/Voltage
Safety Trip Alarm
Error Message
SYS INIT
ERROR CKSUM
ERROR CONFIG
WIREn BROKE
WIRES BROKE
ERROR OUTOF/
LIMIT
ERROR INSAT
What it Means
The system is completing initialization
The configuration stored in non-volatile
memory is invalid
User has reconfigured the unit with an
illegal configuration
A specific wire was detected as broken
Undetermined wire broken
The measured resistance / voltage was
outside the RTD or Thermocouple table’s
range
Input saturation condition (input reached
110% of calibrated range)
What to Do
Wait. Operation should commence in a few
seconds.
Using the menu system, trigger the unit to use the
FCTRY CONFG selection in the options menu
causing it to reset to factory configuration. Next
configure as appropriate for the application.
Usually caused by changing the input range, or
scaled range such that the trip points and/ or
deadband settings have become illegal.
Reconfigure with legal values.
Repair the broken wire(s), and use the menu
system to RESET FAULTS or cycle power.
Check the input and/or the selected input
mode/sensor type (specifically a RTD’s alpha
value), and use the menu system to RESET
FAULTS or cycle power.
Check the input signal to ensure that it is within
the sensor limits and use the menu system to
RESET FAULTS or cycle power.
ERROR OOR
ERROR LINE/
RES
ERROR CALIB
ERROR FCTRY/
INFO
ERROR ADC
ERROR RJC
ERROR RLAYF
ERROR RLAY1
ERROR RLAY2
ERROR SWARE
ERROR HWARE
Input has gone outside the legal range
(as defined by the input LRV and URV
by more than 1%)
Excessive lead resistance
Calibration data is bad
Factory information is bad
General ADC failure
Reference Junction Compensation RTD
burnout
Fault alarm failure
Trip alarm 1 hardware failure
Trip alarm 2 hardware failure
General software failure detected by
diagnostics
General hardware failure detected by
diagnostics
Note:
The Manual Reset (MR) contact does not affect the fault relay.
Check the input and/or the input Upper and Lower
Range settings and use the menu system to
RESET FAULTS or cycle power.
Check sensor lead resistance. A resistance over
35 ohms is excessive (5 ohms for the Cu RTD).
Use the menu system to RESET FAULTS or cycle
power.
Cycle power to the unit. If the error occurs again,
contact MII Customer Support to arrange for a
return.
The Interface Solution Experts 29
STA
Programmable Current/Voltage
Safety Trip Alarm
STA Transfer Utility Software
Provided with the STA is a Transfer Utility Software
program. This allows you to upload/download, view
and print your instrument’s confi guration.
Installing the Transfer Utility Software
Refer to Table 8 for the equipment needed.
1. Insert the Moore Industries Interface Solution PC Confi guration Software CD into the CD
drive of the PC. Access the CD and open the
“STA Transfer Utility Software” folder.
2. Double-click the installation program located
in the folder. Follow the prompts to correctly
install the program.
Connecting the STA to the PC
To connect the STA unit to your PC use the RS-232 or
USB end of the cable to the PC’s COM port.
See Table 8 for information on the necessary
equipment.
Figure 21. STA (HLPRG) PC Hook-Up Diagram
PC
TO SERIAL
(COM) PORT
OF PC
To USB
(COM)
Port of PC
NPUTTRIP 1 TRIP 2
READY
COM
TAG
STA
SAFETY
TRIP
ALARM
FAULT
DOWN
SELECT
UP
*Power Supply for unit is
determinded by configuration
ordered.
POWER
SUPPLY*
+
GND
-
Table 8. Necessary Equipment for using the STA Transfer Utility
Device Specifi cations
Power Supply
Personal Computer
(Optional)
Moore Industries Transfer
Utility Software
(Optional)
Communication Cable
or USB Cable (Optional)
24Vdc, ±10% or 117/230Vac, 110Vdc (depending on model)
80386-based (or faster) IBM PC, or 100% compatible;
4Mb free RAM; 8Mb recommended; 20Mb free disk space on hard drive
(More RAM & hard disk space is required for Windows NT, 2000, XP, or Vista)
Microsoft Windows
1 (one) serial port (COM 1, 2, 3, or 4) set to 19.2kbaud, no parity, 8 data bits, and 1 stop
bit or one available USB port (with optional USB cable)
Version 1.0 or greater, successfully installed to the hard drive
Part# Communications Cable 803-053-26A or optional USB cable, Part# 208-236-00A
®
NT, 2000, XP, or Vista
30 The Interface Solution Experts
Transfer Utility Software Summary
Figure 22. STA (HLPRG) Main PC Screen
STA
Programmable Current/Voltage
Safety Trip Alarm
The Transfer Utility Software is made up of these
sections:
1. Program Status– Displays the activity of the
connected unit. It will display such messages as:
Reading STA Info, Idle, Monitoring Variables and
Monitor Fail.
2. STA Status– Indicates if there are problems or
faults with the instrument.
3. Process Variables– Displays Process Variable
and Reference Junction Compensation readings.
4. STA Device Info– Indicates device identifi cation
and software revision.
5. Progress– Display indicates instrument
communication progress.
6. Communications– Notifi es user of current PC
connection/communications status.
7. Tool Bar/Status Bar– Drop down menus and
corresponding icons allow you to perform various
functions within the Transfer Utility. Refer to the Statusand Tool Bar Legend for a complete description.
8. Device Confi guration – Displays current device
confi guration. The window lists data source, model
number (if device connected), input type, scaling,
display settings, alarm settings, and analog output
settings.
The Interface Solution Experts 31
STA
Allows such functions as New,
Open, Save As and Print
Allows you to Upload and
Download configurations
Select the PC Port
(Com Port) that you will use
Allows you to Monitor and
Stop monitoring the STA
Controls whether Tool and Status
Bars are viewed on the screen
Displays the version of the STA
Transfer Utility
Programmable Current/Voltage
Safety Trip Alarm
Menu and Tool Bar Legend
Note:
Pressing the New icon or selecting New in the File
menu will discard the current confi guration.
File Management
This section describes the File Management
capability which enables you to save, and apply,
saved confi gurations to numerous units.
Note:
Transfer Utility can not be used to change the
confi guration. Any changes or resetting of the STA
must be done within the STA unit.
To Save a File
Set the parameters/confi guration you wish to save
as a fi le on STA unit. Connect the unit to a PC using
Moore Industries communications cable or optional
USB cable. Once you have done this, upload fi le
to the Transfer Utility, click the Save As button and
assign a name to the fi le, click the Save button.
Default fi le location where fi le is saved is “C:/My
Moore Industries Data/STA”.
To Load a File
To retrieve or reapply a saved confi guration, click
the File button, then Open and select the correct
fi le name. On the Tool Bar/Status Bar click on the
download icon. The settings will appear in the Device
Confi guration area.
32 The Interface Solution Experts
Note:
When downloading a saved confi guration using the
Transfer Utility the password for that confi guration
will be transferred along with the all other settings.
User must know what password is to make any
changes to confi guration, or reset password
according to steps in Main Confi guration Menu
section of this manual.
STA
Programmable Current/Voltage
Safety Trip Alarm
Installation
Installation consists of physically mounting the unit
and completing the electrical connections.
Mounting
The STA is housed in a “universal” DIN case that can
be mounted on both 35mm G-type (EN50035) and
35mm Top-Hat (EN50022) DIN-rail.
To mount the STA on a Top-Hat DIN-rail, seat the
upper extrusion on the unit back panel over the top lip
of the rail and pivot downward until the housing locks
into place.
To mount the unit on a G-type rail, seat the extrusion
under the top lip of the rail and again, pivot downward.
When mounting multiple units, like a rack or cabinet,
make sure to allow adequate vertical spacing for
pivoting the units.
Making the Electrical Connections
Refer to Figure 5 (STA Front Panel Confi guration)
and Figure 21 (STA connected to PC) for electrical
connections.
Recommended Ground Wiring
Practices
Moore Industries recommends the following ground
wiring practices:
• Any Moore Industries product in a metal case
or housing should be grounded.
CE Conformity
Installation of any Moore Industries’ products that
carry the CE certifi cation must adhere to the
guidelines as stated in order to meet the requirements
set forth in the European EMC and Low Voltage
Directives (EN 61326 and EN 61010). Consult the
factory for the most current information on products
that have been CE certifi ed.
Operation
Once confi gured, installed, and supplied with the
correct power, the STA alarm begins to operate
immediately. Depending upon environmental
conditions, it can be expected to operate unattended
for extended periods of time.
Maintenance
Moore Industries suggests a quick check for terminal
tightness and general unit condition every 6-8
months. Always adhere to any site requirements for
programmed maintenance.
Customer Support
Moore Industries is recognized as the industry leader
in delivering top quality to its customers in products
and services. We perform a battery of stringent
quality assurance checks on every unit we ship. If
any Moore Industries product fails to perform up
to rated specifi cations, call us for help. Our highly
skilled staff of trained technicians and engineers pride
themselves on their ability to provide timely, accurate,
and practical answers to your process instrumentation
questions.
• The protective earth conductor must be
connected to a system safety earth ground
before making any other connections.
• All input signals to, and output signals from,
Moore Industries’ products should be wired
using a shielded, twisted pair technique.
Shields are to be connected to an earth or
safety ground at the unit itself.
• The maximum length of unshielded input
and/or output signal wiring should be
two inches.
Factory phone numbers are listed on the back cover
of this manual.
If problems involve a particular STA, there are several
pieces of information that can be gathered before you call the factory that will help our staff get the
answers you need in the shortest time possible.
For fastest service, gather the complete model and
serial number(s) of the problem unit(s) and the job
number of the original sale.
The Interface Solution Experts 33
STA
Programmable Current/Voltage
Safety Trip Alarm
STA in Safety Instrumented
Systems
The STA is designed for use as a component part of a
safety instrumented system as defi ned by
IEC61508-4 para 3.4.1.
This user manual contains all of the information
needed to confi gure, install, operate and maintain this
product. For safety applications the STA must only
be used in accordance with this information and the
restrictions and limitations as detailed below.
Functional Safety Description
The STA has been certifi ed, by TUV Rhineland
Industries Service GmBH, to IEC 61508 for a single
use safety instrumented device up to SIL 2. In
addition, the fi rmware of the STA, during the above
review, was determine to have measures in place
to address systematic errors up to SIL 3. As such,
this allows the STA, when confi gured in a redundant
system architecture (1oo2, 2oo3, etc), to achieve up
to SIL 3 as described in IEC 61508-3.
Failure Rate Data
The STA FMEDA report (Moore Industries’ Document
No: 700-702-32) provides the failure data (including
PFD and SFF) required for calculations to use the
STA as part of a Safety Instrumented System.
Confi guration
The unit can be confi gured using the front panel
buttons or transfer utility as described in this manual.
Note:
While the system is in confi guration mode the
system is in an offl ine mode and is not performing
the safety function
Do not attempt to connect the STA Transfer Utility
cab
le to the STA while the output relays are
connected to a load.
The following considerations and restrictions will
apply when using the STA in a safety application:
One or both trip alarms must be connected to the
actuator/equipment under control (EUC). The
separate dedicated fault relay must either be
connected in series with the trip alarm OR connected
to a separate indicator to merely alarm the fault while
maintaining the process in normal operation. Refer to
Figures 1 and 2 for typical STA confi gurations.
Separating the process and fault loads increases
availability but its use must be authorized only after a
careful hazard and operability study involving suitably
qualifi ed persons.
WARNING
With this confi guration, an internal STA fault would not trip
the EUC
.
Product life
The product life of the STA is 50 years (based on
worst case component life data).
However, IEC 61508-2, section 7.4 states that a
useful lifetime based on experience has more weight
than the calculated fi gures; Note 3 in the section
comments that the useful lifetime of a transmitter is
most often within 8 to 12 years.
Installation
No special installation is required in addition to the
standard installation practices in this user manual.
Refer to the specifi cations table of this user manual
for ambient conditions and required power input.
34 The Interface Solution Experts
Process Safety Time
Process safety time is the minimum time from the
initiation of a hazardous event to the point where the
hazardous event is unavoidable. Any safety function
designed to either prevent the event or at least
mitigate its effect must be capable of performing its
specifi ed safety function in a time period very much
less than the process safety time.
The STA has a characteristic response time (end to
end) of 256mSec.
Analog Output - Non Safety
The STA may optionally be provided with an analog
output which can be used for connecting to displays,
control systems, etc. The STA analog output is NOT
designed for safety use and must not be used as any
part of a safety loop. The analog circuit is isolated
from the STA safety circuits and consequently
its failure will not compromise the certifi ed safety
function of the STA.
STA
Programmable Current/Voltage
Safety Trip Alarm
Sensor Types
The STA is designed for use with a wide variety of
inputs. It is the end user’s responsibility to ensure
that the chosen sensor is capable of achieving the
required loop SIL.
Broken Wire Detection
The STA is provided with the facility to detect both
open circuit and short circuit input. This broken wire
detection must always be enabled. This is essential
to ensure that dangerous failure of the sensor or
signal input is detected by the STA and consequently
alarmed.
WARNING
F
or HIGH LEVEL INPUT, the Lower Range Value (LRV)
must be set higher than zero. Broken Wire Detection will
be disabled if LRV is set to zero and will invalidate the
safety function.
Sensor Trimming Enable/Disable
Sensor trimming should be used with extreme care
as this facility is allowed to trim the sensor accuracy
by as much as 2% of the trimming point value. It
is the user’s responsibility to ensure that the safety
application can tolerate this.
Operation and Maintenance
Proof Test Procedure
It is normal practice with SIS that the components
undergo periodic proof tests to expose dangerous
faults that are not detected by internal diagnostic
tests. Thus, this section specifi es how the dangerous
undetected faults determined during the FMEDA can
be detected during proof testing.
Calculation of the required proof test interval can
be made using data in the FMEDA report (Moore
Industries’ Document No: 700-702-32).
A proof test interval of 3 years is recommended for
a single STA used in a typical SIL 2 low demand
application (15% of the SIL band being allocated to
the STA at 40°C ambient).
The proof tests described in Table 9 are designed to
cover all possible dangerous undetected faults that
can be detected without opening the unit. Periodically
testing the STA, using the proof test steps outlined
below, the accumulated PFD
to a smaller but non-zero value. To completely test
for all possible dangerous undetected faults, the unit
must be sent back to the factory for a comprehensive
proof test inspection.
AVG value can be reduced
Latching Mode Enable/Disable
The STA is provided with the capability to latch on
a trip, i.e. once the output process alarm relays
have de-energized they will remain de-energized
until either the manual reset contact is closed or the
unit is power cycled. The use of this facility will be
determined by the application. It is recommended
that if the output state is latched externally to the STA,
the STA latching option is disabled. Please note that
the fault alarm will always be latched.
Remote Manual Reset – Procedural Issues
The STA has a facility for the connection of a remote
switch to release the latch on the outputs.
This function is meaningful only when automatic
latching of outputs is selected in the confi guration.
If the manual reset is made part of the safety
procedure, it must only be used under strict
supervisory and procedural control. The use of a key
operated momentary contact is suggested.
Repair and Replacement
The STA is not intended to be repaired on site and
has no components needing maintenance or regular
replacement. On device failure, the STA should be
returned to Moore Industries World Headquarters in
North Hills, CA U.S.A for repair and refurbishment
(refer to Returns Procedures at the end of this
manual).
The STA is a certifi ed Safety component. Repair or
replacement of any component without authorization
from Moore Industries will invalidate any remaining
warranty and the IEC61508 certifi cation.
Recording and Reporting of STA Performance
It is the end user’s responsibility to maintain records
of all safety component failures, especially those that
might be classifi ed as potentially dangerous.
This feedback data not only helps the supplier
identify and rectify reliability issues but also to
provide quantitative data to increase confi dence
in the FMEDA analysis of dangerous failure rates.
Please ensure that any components returned to
Moore Industries Inc are returned with a clear report
identifying the fault experienced.
The Interface Solution Experts 35
STA
Programmable Current/Voltage
Safety Trip Alarm
Table 9. STA HLPRG proof test steps
Step Action
1 Bypass the safety PLC or take other appropriate action to avoid a false trip
Disconnect all wires from the STA. Using an ohmmeter, measure the resistance between the case
2
3
4
5 Apply a calibrated input near the high limit of the selected input configuration
6
7
8 Apply a calibrated input near the low limit of the selected input configuration
9
10
11 Restore the STA to its original configuration
12 Restore the loop to full operation
13 Remove the bypass from the safety logic solver or otherwise restore normal operation
and all exposed pins on the front. Verify that the measured resistance is greater than 1 MΩ
This tests for shorts between the power or ground to the case
Resupply power. Connect a loop device powered by the TX output. Configure all alarm outputs
such that:
i. Each alarm is set to the midpoint of the configured range
Alarm 1 is set to trip when the input is below the midpoint, Alarm 2 is set to trip when the input
ii.
is above the midpoint
Cause the loop device to go to its maximum output value. Verify that the device is not power
starved, eg displaying symptoms of power cycling, browning out, etc. Verify that the STA is
measuring the input from the loop device correctly by viewing the display or using the STA transfer
utility in monitoring mode
This verifies the proper operation of the TX supply circuit and that the supplied current is not below
the maximum requirements of the loop device
Verify that the input as reported by viewing the display or using the STA transfer utility in
monitoring mode matches what is expected
This tests for failures in the input connections to the A/D converter near the high limit operation
Verify that for each alarm, the output is as expected
This test verifies signaling for the tested relay and for issues in the relay to the output connections
Verify that the input as reported by viewing the display or using the STA transfer utility in
monitoring mode matches what is expected
This test completes the full test for failures in the input connections to the A/D converter near the
low limit operation. This also covers the CPU and A/D clocks
Verify that for the configured alarms, the output is as expected
This test ensures that there is no crosstalk between the relays
36 The Interface Solution Experts
Declaration of Conformity
EMC Directive 2004/108/EC
Low Voltage Directive 2006/95/EC
• Manufacturer’s Name: Moore Industries-International, Inc.
• Manufacturer’s Address: 16650 Schoenborn Street
North Hills, CA 91343-6196
USA
Declares that the product(s):
• Product Name: STA HLPRG
MODEL / INPUT / OUTPUT / POWER / OPTIONS / HOUSING
• Model Number(s): STA * * * * *
* Indicates any input, output, option and housing as stated on the product data sheet.
• Conforms to the following EMC specifi cations:
EN 61326-1, 2006, Electromagnetic Compliance (EMC) requirements for electrical equipment for control use
EN 61010-1, 2004, Safety requirements for electrical equipment for measurement and control use
• Supplementary Information:
None
October 22, 2008
Quality Assurance Director Moore Industries-Europe General Mgr.
United States • info@miinet.com
Tel: (818) 894-7111 • FAX: (818) 891-2816
Australia • sales@mooreind.com.au
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
Belgium • info@mooreind.be
Tel: 03/448.10.18 • FAX: 03/440.17.97
The Netherlands • sales@mooreind.nl
Tel: (0)344-617971 • FAX: (0)344-615920
China • sales@mooreind.sh.cn
Tel: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • sales@mooreind.com
Tel: 01293 514488 • FAX: 01293 536852
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair –
If you are unsure if your unit is still under warranty, we can use the unit’s serial number
to verify the warranty status for you over the phone. Be sure to include the RMA
number on all documentation.
Non-Warranty Repair –
If your unit is out of warranty, be prepared to give us a Purchase Order number when
you call. In most cases, we will be able to quote you the repair costs at that time. The
repair price you are quoted will be a “Not To Exceed” price, which means that the
actual repair costs may be less than the quote. Be sure to include the RMA number on
all documentation.
2. Provide us with the following documentation:
a) A note listing the symptoms that indicate the unit needs repair
b) Complete shipping information for return of the equipment after repair
c) The name and phone number of the person to contact if questions arise at the factory
3. Use suffi cient packing material and carefully pack the equipment in a sturdy shipping con-
tainer.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries representative will contact the person designated on your documentation if more information is
needed. The repaired equipment, or its replacement, will be returned to you in accordance
with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WARRANTIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR
OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY
GOODS OR SERVICES SOLD BY THE COMPANY. THE COMPANY DISCLAIMS ALL WARRANTIES ARISING FROM ANY COURSE OF DEALING
OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM
THE COMPANY ACKNOWLEDGES THAT THERE ARE NO WARRANTIES
IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND
OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER
WITH THE COMPANY DO NOT IMPLY THAT THE COMPANY WARRANTS
THE GOODS OR SERVICES IN ANY WAY.
ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY
AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REMEDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR
SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR
OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE
PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS
IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES
, BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE
THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER
FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY
THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RECEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED
DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE
ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED
THE ALLEGED DEFECT OR BREACH, AND NO ACTION FOR THE
BREACH OF ANY WARRANTY SHALL BE COMMENCED BY THE
BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST
DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under
normal conditions of use and service, Moore Industries (“The Company”)
will at its option replace, repair or refund the purchase price for any of its
manufactured products found, upon return to the Company (transportation
charges prepaid and otherwise in accordance with the return procedures
established by The Company), to be defective in material or workmanship.
This policy extends to the original Buyer only and not to Buyer’s customers
or the users of Buyer’s products, unless Buyer is an engineering contractor
in which case the policy shall extend to Buyer’s immediate customer only.
This policy shall not apply if the product has been subject to alteration,
misuse, accident, neglect or improper application, installation, or operation.
THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL
OR CONSEQUENTIAL DAMAGES.