Moore FDY Installation Manual

Page 1
November 2013 165-730-00E1
PC-Programmable Frequency
Transmitter and Display
FDY
PC-Programmable Frequency
Transmitter and Display
FDY
Page 2
Table of Contents
The FDY .............................................................................................................. 3
About this Manual ................................................................................................................3
Specifi cations .................................................................................................... 4
PC Confi guration Software ............................................................................... 6
Programming the FDY ....................................................................................... 8
Connecting the FDY to the PC .............................................................................................8
Programming the Basic Parameters ....................................................................................9
Programming the Input Parameters .....................................................................................9
Programming the Range Parameters .................................................................................10
Programming the Output Parameters ................................................................................11
Programming the Trimming Parameters .............................................................................12
Sensor Trimming ...................................................................................................................................... 12
Output Trimming ...................................................................................................................................... 13
Loop Test ................................................................................................................................................. 13
Programming the Custom Curve Parameters ....................................................................14
Editing the Custom Curve Table .........................................................................................15
Downloading the Confi guration File ...................................................................................15
Installing the FDY ............................................................................................ 16
Customer Service ............................................................................................ 17
Appendix-A Intrinsically-Safe Applications .................................................. 18
2 The Interface Solution Experts
Page 3
FDY
PC-Programmable Frequency
Transmitter and Display
The FDY
This is the user’s manual for the Moore Industries’ FDY PC-Programmable Frequency Transmitter and Display. Incredibly versatile, the FDY programs in less than a minute to accept varying frequency signals from AC or DC fl ow measurement devices such as
About this Manual
Wherever you see a “ Note”, “ Caution” or “ WARNING ” pay particular attention.
• A “Note” provides information to help you in avoiding minor inconveniences during calibration, installation or operation of the FDY.
turbine meters and magnetic pick-up coils.
• A “Caution” provides information on steps to take
The FDY monitors the signal, outputting the selected variable (frequency, period, high pulse width, low pulse width or contact closure) both to its display and to a 4-20mA signal that is linear and input-scaleable. The FDY features a large integral display that shows
in avoiding procedures and practices that could risk damage to the FDY or other equipment.
• A “WARNING ” provides information on steps to take in avoiding procedures and practices that could pose safety risks to personnel.
real-time process status.
Figure 1. The FDY Accepts a Frequency Signal and Outputs a Scaleable 4-20mA Signal
eight
Measurement
Device
elt peed
Magnetic Pick- p,
Tachometer enerator,
all ffect ensor, or
other Frequency sensor
Input
FDY
6027.8
HZ
P
P
0
0
The Interface Solution Experts 3
CM
4-20mA
MD or
Weighing
ystem
Page 4
FDY
PC-Programmable Frequency Transmitter and Display
Specifi cations
Performance
Input Accuracy:
See Tables 2-7 Output Accuracy: ±0.015% of span Overall Accuracy: The overall accuracy of the unit is the combined input and output accuracies. It includes the combined effects of linearity, hysteresis, repeatability and adjustment resolution. Does not include ambient temperature effect. Input Hysteresis: See Tables 5-7 Input Threshold: See Tables 5-7
Stability: See Table 1 Minimum Frequency: Twice
the lower range Digital Input Filter: 3dB point is at 10kHz
Step Response Time:
300msec maximum, 200msec typical from the time an input is applied to the output reaching 90% of its fi nal value + actual input Rise Time: 100msec maximum for the output to change from 10% to 90% of its scale of an input step change of 0% to 100% + actual input Isolation: 500Vrms between input, output, and case continuous, and will withstand a 500 Vac dielectric strength test for one minute with no breakdown Ripple: 10mV peak-to-peak measured across a 250 ohm resistor Overcurrent Limiting: 25mA maximum Maximum Voltages: 48Vdc output, maximum; DC input, 48Vdc, maximum; AC input, 30Vac maximum for
0.02-30AC model, 250Vac maximum for 10-250AC model
Performance
(Continued)
Input Impedance:
>30kohms for DC and contact closure inputs; 2kohms for input >6V, 4kohms typical@50Hz and 56kohms typical@1kHz for input <6V for
0.02-30AC model; >125kohms for 10-250AC model Load Capability: (508 ohms@24V)
Supply Voltage - 12V
0.0236A
Output Current Limiting:
3.8mA and 21.4mA for input under range and over range; 3.6mA and 23.6mA for input failure
Load Effect (current outputs): Negligible within
specifi ed power limits Power Supply Effect: ±0.002% of span per 1V change Startup Time: Performance within specifi cation less than 1sec after power is applied for frequency higher than 100Hz and average of 8 samples Damping: Adjustable from 0 to 30 seconds with PC software Linearization: Confi gurable up to 128 points with PC software Moving Average: Confi gurable up to 16 segments with PC software Low Pass Filter: On/Off is software confi gurable
=
Ohms
Display
Ambient
Conditions
Weight
Type: LCD; Top Row,
10.16mm (0.4 in) high black digits on a refl ective background; Bottom Row,
5.72mm (0.225 in) high black digits on a refl ective background Display Update Rate: 100msec Format: Top row is fi ve alphanumeric characters, plus sign and decimal point; bottom is fi ve alphanumeric characters
Range: -99999 to 99999 Minimum Display Span:
1.00
Operating & Storage Range:
-40 to +85°C (-40°F to +185°F); I.S. Operating Range:
-40° to +65°C (-40°F to +149°F); Relative Humidity: 0-95%, non-condensing
Ambient Temperature Effect: Input to output,
±0.007% of span/°C maximum; Digital Accuracy, ±0.003% of span/°C maximum RFI/EMI Immunity: 30V/m when tested according to SAMA 33.1 abc with 0.5% of span or less error. 20V/m@ 80-1000MHz, 1kHz AM, when tested according to IEC1000-4-3-1995 Noise Rejection: Common mode, 120dB typical@100mVp-p input
FDY HP: 227g (5.3 oz) FDY in BH housing with glass cover: 1.45kg
(3 lbs, 12.4 oz)
FDY in D-BOX housing:
811g (1 lb, 6.3 oz)
Specifi cations and information subject to change without notice.
4 The Interface Solution Experts
Page 5
Table 1. Stability for All Models*
Input-to-Display (% of Reading)
1 year
Frequency/Period
1 Sec Pulse
Width
0.1 Sec
*Combine Input-to-Display and Display-to-Output values to determine overall stability. **Consult factory for improved long-term drift specifi cations.
0.001
0.001
0.0015
3 years
0.0017
0.0017
0.0026
5 years
Display-to-Output (% of Output Span**)
1 year
0.0022
0.0022
0.0034
0.08
Table 2. DC Input Range and Accuracy for All FDY Models
Input Type
Frequency
Period
Pulse Width
Contact Closure
Input Range
Frequency
0.02Hz to 5kHz
0.02Hz to 25kHz
200µsec to 50sec
40µsec to 50sec
0.5msec to 50sec
<20Hz
Amplitude
100mV-30V
200mV
-30V
100mV-30V
200mV-30V
1-30V
Accuracy
(% of reading)
0.01±1LSD
0.05±1LSD
0.01±1LSD
0.05±1LSD
0.05±1LSD ±2µsec
0.01±1LSD
Min.
Span
See
Table 8
500µsec
500µsec
0.1Hz
3 years
0.139
5 years
0.179
NOTE: AC indicates zero-crossing signal. DC indicates non-zero crossing signal.
FDY
PC-Programmable Frequency
Transmitter and Display
Table 3. AC Input Range and Accuracy for PRG Input Type
Input Type
Frequency
Period
Input Range
Frequency
0.5Hz to 25kHz
1Hz to 5kHz
1Hz to 25kHz
10Hz to 5kHz
40µsec to 2sec
200µsec to 1sec
40µsec to 50sec
200µsec to 100msec
Amplitude
1-30V
200mV
200mV-30V
20mV-30V
1-30V
200mV-30V
200mV-30V
20mV
(% of Reading)
-30V
-30V
Accuracy
0.05±1LSD
0.01±1LSD
0.05±1LSD
0.01±1LSD
0.05±1LSD
0.01±1LSD
0.05±1LSD
0.01±1LSD
Table 5. Frequency Input Parameters
Input Range
100mV-30V (DC)
20mV-30V (AC)
10V-250V(AC)
Threshold
Resolution
1mV
Range
0.01-2.5V
Hysteresis
Resolution
1mV
1mV
1mV
Range
0.01-1.5V
0.002-0.15V
0.002-0.15V
Table 6. Period Input Parameters
Input Range
100mV-30V (DC)
20mV-30V (AC)
10V-250V (AC)
Threshold
Resolution
1mV
Range
0.01-2.5V
Hysteresis
Resolution
1mV
1mV
1mV
Range
0.01-1.5V
0.002-0.15V
0.002-0.15V
Table 7. Pulse Width Input Parameters
Input Range
100mV-30V (DC)
Threshold
Resolution
1mV
Range
0.01-2.5V
Hysteresis
Resolution
1mV
Range
0.01-1.5V
Min.
Span
See
Table 8
500µsec
Table 4. AC Input Range and Accuracy for 10-250V Input Type
Filter
(3db Point)
10kHz
10kHz
10kHz
Filter
oint)
(3db P
10kHz
10kHz
10kHz
Filter
oint)
(3db P
10kHz
Input Type
Frequency
Period
Measured
Frequency
0.02Hz to 25kHz
0.5Hz to 25kHz
0.5Hz to 25kHz
Measured
Period
40µsec to 50sec
40µsec to 2sec
40µsec to 2sec
Measured
Pulse Width
0.2msec to 50sec
Input Range
Frequency
1Hz to 5kHz
1Hz to 25kHz
200µsec to 1sec
40µsec to 50sec
Amplitude
10-250V
10-250V
10-250V
10-250V
Table 8. Frequency Range Minimum Span
Maximum
Frequency
Range
10Hz
5kHz
25kHz
Accuracy
(% of reading)
0.01±1LSD
0.05±1LSD
0.01±1LSD
0.05±1LSD
Minimum
Span
0.1Hz
1Hz
25Hz
Min.
Span
See
T
able 8
500µsec
The Interface Solution Experts 5
Page 6
FDY
FRONT VIEW
SIDE VIEW
61mm
(2.40 in)
83mm
(3.25 in)
62mm
(2.45 in)
64mm
(2.50 in)
66mm
(2.58 in)
76mm
(3.00 in)
43mm
(1.70 in)
18mm
(0.70 in)
FDY
COM
+PS
0
+
–
–PS
0
6027.8
HZ
GND
1/2 NPT
PC-Programmable Frequency Transmitter and Display
Figure 2. FDY Dimensions
Figure 3. BH Enclosure Dimensions
129mm
10mm
(5.06 in)
(0.38 in)
102mm
(4.00 in)
25mm
(1.00 in)
66mm
(2.60 in)
TOP VIEW
FDY
6027.8
HZ
–
+
–PS
+PS
0
0
COM
65mm
(2.55 in)
124mm
(4.90 in)
119mm
(4.70 in)
(3.00 in)
76mm
SIDE VIEW
102mm
(4.00 in)
GND
1/2 NPT
124mm
(4.90 in)
6 The Interface Solution Experts
Page 7
Figure 4. D-BOX Enclosure Dimensions
11 mm
4.65 in
13 mm
5.12 in
FDY
116mm
4.56 in
FDY
PC-Programmable Frequency
Transmitter and Display
CNDIT
FITTIN
DY
C
6027.8
HZ
CM
–
–PS
PS
PC Confi guration Software
The FDY PC Confi guration Software is used to program all of the FDY’s parameters. For detailed information on how to use our confi guration software, access our HelpMap Navigation System. The PC Software is made up of these sections:
1. Program Status & Device ID–The Program Status portion of the screen displays the activity of the connected unit. It will show you if the unit is Idle, Uploading, Downloading or Monitoring. Device ID displays the type of device that is being polled and its ID number.
2. Tag/Descriptor/Message–These boxes are used to program a FDY with an individual tag, descriptor or message used for easily identifying the unit. The Programmed Date stores the last time that the unit’s confi guration was updated.
3. Device Confi guration–Displays the current confi guration of the attached FDY.
1mm
3.2 in
4mm
3.3 in
INST M NT
T
27mm
1. 5 in
4. Measurement Mode–The drop-down menu selects which type of measurement the FDY will monitor.
5. Variables/Device Status/Communications– These sections display the status of the FDY and its process. The Variables section displays the input to the FDY, FDY output and the percent of span. The Device Status provides advanced diagnostic information on the FDY. The Communications box displays the status of the FDY’s communication with the PC Program.
6. Input/Range/Output/Trimming/Custom Curve Tabs–These tabs change the right side of the screen to allow you to set the appropriate part of the FDY’s confi guration. See corresponding sections of this manual for additional information on these tabs.
7. Quickset Buttons –These buttons allow you to program just one part of the FDY’s confi guration program. From left to right, they program: Fail Mode, Display Mode, Tag and Message.
The Interface Solution Experts 7
Page 8
FDY
PC-Programmable Frequency Transmitter and Display
Figure 5. All of the FDY Operating Parameters can be set from the Main Screen of the Confi guration Program.
7
6
1
2
5
4
3
Default/Factory Confi gurations
The following are the default factory settings for your unit:
Input: Measurement Mode: Frequency 0-100Hz Input Hysteresis: 10mV Timeout Period: 10s AC/DC Input: AC Low Pass Filter: Disabled Averaging Filter: 8 Minimum Debounce Period: 10mS Scaling Disabled Output: 4-20mA Damping: 0s Fail Mode: High (23.6mA) Display Mode: Primary Variable
8 The Interface Solution Experts
Page 9
FDY
FDY
COM
+PS
0
+
–
–PS
0
6027.8
HZ
–
+
–+
POWER SOURCE 12-42Vdc
MULTIMETER
4-20mA
–+
CALIBRATED
DC INPUT
SIMULATOR
FDY COMMUNICATION CABLE
803-040-26 FOR NON-ISOLATED
803-039-26 FOR ISOLATED
or Optional USB Cable 208-836-00
CALIBRATED
AC INPUT
SIMULATOR
OR
250 ohms
FREQ.
COUNTER
FREQ.
COUNTER
PC-Programmable Frequency
Transmitter and Display
Programming the FDY
All operating parameters of the FDY are set using a PC, a serial communication cable and Moore Industries’ Intelligent PC Confi guration software. When the PC Confi guration program is loaded and running, most of the parameters for the connected transmitter are shown on a single screen. This makes it easy to determine which aspects of transmitter operation need to be changed to suit the application requirements.
Once the software settings are made, they are downloaded to the transmitter in the form of a confi guration fi le and stored in the non-volatile unit memory. You can choose to save a backup copy of the fi le on your PC hard drive or external media.
Program the FDY by connecting the FDY to the PC, setting the appropriate parameters in the PC program, and downloading the confi guration.
Connecting the FDY to the PC
The fi rst step in confi guring the FDY is connecting the transmitter to the PC program and attaching the appropriate input devices. Connect the FDY as shown in Figure 6 below; refer to Table 9 for a description of required equipment. After the FDY is confi gured, you can begin programming the basic parameters.
Table 9. Assembling the Necessary Equipment
Device
Frequency Input
ulator
Sim
Power Supply
Precision Load Resistor
Multimeter
Per
sonal
Computer
Communications Cable
Communications Software
Variable, accurate to ±0.005% of reading
12-42Vdc
250 ohms, ±0.01%
Accurate to ±0.025% of reading
Microsoft Windows based PC; 16Mb free RAM; 20MB free disk space on hard
drive Microsoft Windows XP, Vista or 7
1 (one) serial port or one available USB port (with optional USB cable)
Isolated cable P/N: 803-039-26 Non-isolated cable P/N: 803-040-26 or optional USB cable P/N: 208-836-00
Version 1.0 or greater, part number: 750-75E05-01
Device
Figure 6. Connecting the FDY to the PC
The Interface Solution Experts 9
Page 10
FDY
PC-Programmable Frequency Transmitter and Display
Programming the Basic Parameters
Programming the Basic Parameters involves selecting the desired parameters in the PC Program, then downloading those parameters to the FDY. Begin by entering the device identifi cation and measurement mode parameters into the confi guration software.
Device Identifi cation Information
The Tag (8 characters, maximum), Descriptor (16 characters, maximum) and Message (32 characters, maximum) boxes allow you to assign a unique identity to each FDY.
Measurement Mode
Select from Frequency, Period, Pulse Width High, Pulse Width Low and Contact Closure. This selects the variable to be measured and displayed. (Unless a custom EGU is selected in the Custom Curve tab.) (See Figure 5, section 4).
Programming the Input Parameters
When setting input parameters, please read the following information for guidance. All input voltages above 3V are internally clamped at 3V and all AC signals are squared and measured at the zero crossing. Therefore the settings for input threshold and hysteresis assume a maximum input of 3V.
Use the Input tab in Figure 7 to enter the following parameters:
AC / DC Input: Select the type of input the FDY will measure.
Input Threshold: Input threshold is applicable to DC inputs only. Input Threshold is the input voltage above which the input is considered high. For input voltages above 3V, it is recommended to set this to the default setting of 2V (maximum is 2.5V). For input voltages below 3V, it is recommended to set this to 2/3 of the peak-to peak (p-p) input signal voltage plus the low state signal voltage.
Input Hysteresis: This is the difference between high and low voltage points at which the input circuit detects changes of input state. For DC inputs this must be less than the threshold. For example, if the threshold is set for 2V, and the hysteresis is set for 1.2V, the FDY will detect high for >2V and low for <0.8V.
- For DC input voltages above 3V, it is recommended to set this to the default setting of
1.2V (maximum is 1.5V).
- For DC input voltages below 3V, it is recommended to set this to 1/3 of the peak-to peak (p-p) input signal voltage plus the low state signal voltage.
- For AC inputs the hysteresis is used to minimise noise interference. Above 3V, it is recommended to set this to 150mV.
- For AC inputs below 3V, it is recommended to set this to 10% of the signal voltage level.
Figure 7. Input Parameters Tab
10 The Interface Solution Experts
Timeout Period: The number of seconds that the input will remain at lower range value before the FDY declares a hardware error, if the Fail On Input Timeout box is checked. The Timeout Period can be confi gured at minimum of 0.5sec to a maximum of 600sec, factory default is set to 10sec.
NOTE:
The timeout period must be set greater than the
Lower Range Value period if Fail On Input Time-out is
enabled.
Fail On Input Timeout: If your input is lower than the allowed Lower Range Value and the Fail On Input Timeout feature is enabled, Broken Wire (in the Device Status section of the PC Program) or Broke Input (on
the FDY display) is declared after the set Timeout Period has passed.
Page 11
FDY
PC-Programmable Frequency
Transmitter and Display
NOTE:
If the Lower Range Value is set to 0Hz in the Input
Range the Fail On Input Time-out feature will not be
available, the Lower Range Value must be set to a value greater than zero to enable this feature (box
must be checked to apply feature) .
Low Pass Filter Enable: Reduces noise by fi ltering out
high frequency signals.
NOTE:
Moore Industries recommends having the Low-Pass
fi lter turned on when the upper input range value is
less than 150Hz (especially on the 10VAC - 250VAC
units).
Averaging Filter: Shows the number of readings
the FDY averages together to provide the displayed reading. This can be used to compensate for bent blades in a monitored turbine by setting the value to equal the number of blades on the turbine. (i.e. if the turbine has four blades, set the Averaging Filter to 4).
Minimum Debounce Period: Available only when contact closure is selected in measurement mode. This value eliminates noise from a contact closure input, but lowers the maximum measurable frequency.
You are given the option of scaling your process variable reading. To do this, click the Enabled check box in the Scaling section. Scaling allows you to take your process variable and manipulate the reading to a more customized range.
• In the Upper Scaling Value text box, enter the value you wish displayed when your input is at its full range. Repeat the step for the value you wish displayed when your input is at its zero value and enter that into the Lower Scaling Value box.
At the Scaled Mode Display Label box, enter the specifi c EGU (Engineering Unit) that you want as your display.
• The Range Limits section allows you to designate when the input will be considered bad (over or under range). For example, if you have set the
Lower Range Value for 20, you can set the Under Range for 10 and check the Enable box, allowing
the input to decrease below 10Hz before an error is registered. In this case, the display shows
Under/Over range, and the output is in Failure Mode (see Programming Output Parameters).
Figure 8. Range Parameters Tab
After selecting the input parameters, continue by clicking the Range tab and proceeding to the Programming the Range Parameters section.
Programming the Range Parameters
The Range tab permits you to set or capture the acceptable input range and establish range limits.
• Use the Lower Range Value cell to set the input value that will correspond to a 4mA output. In the same way, use the Upper Range Value to set the input value that corresponds to a 20mA output.
• Reverse the output (causing the output to increase as the input decreases) by setting the Lower Range Value higher than the Upper Range Value.
• The Capture Lower Range and Capture Upper Range buttons permit you to trim the upper and lower range of the sensor (if necessary). Just click the appropriate button to begin trimming.
The Interface Solution Experts 11
Page 12
FDY
PC-Programmable Frequency Transmitter and Display
Programming the Output Parameters
The Output section of the PC software is composed of three sections: Output Settings, Failure Mode and Display Mode. Use the functions of Output Settings to set the current range from 3.8 to 21.6mA (usually 4-20mA). The minimum span is 4mA.
Figure 9. Output Parameters Tab
Output Settings
The output can be reversed (causing the output to increase as the input decreases) by setting the Lower
Range Value in the Range tab as higher than the Upper Range Value (See Figure 8).
PV (Primary Variable) Damping precisely reads the
input then specifi es an exponential change in the output by 60% over the time set in the PV Damping box. This reduces the effect of sudden spikes and helps stop unnecessary alarms by smoothing the reading.
Failure Mode
Failure Mode lets you set the output of the transmitter when it is malfunctioning. It will either transmit a 3.6mA (set to Fail Low) or a 23.6mA (set to Fail High) signal.
NOTE:
The Failure Mode has no effect unless one of the fail
conditions is active (i.e. Fail On Input Time-out or Over/
Under Range Limits).
Display Mode
Display Mode selects which variable will be displayed on the transmitter’s display. Choose between Primary Variable, Current, Percentage and Display Toggle. (Display Toggle switches back and forth from the primary variable to current and back in one-second increments). The PC Program’s display is not changed by changing the selection under the Display Mode.
12 The Interface Solution Experts
After the Range parameters have been selected, you can continue on by clicking on the Trimming tab, and proceeding to Programming the Trimming Parameters.
Page 13
FDY
PC-Programmable Frequency
Transmitter and Display
Programming the Trimming Parameters
The Trimming tab includes Sensor (Input) Trimming, Output Trimming and Loop Test functions.
Figure 10. Trimming Parameters Tab
Sensor Trimming
Sensor Trimming increases the measured accuracy of your transmitter by matching the reading of its actual input to either a calibrated source or the master device to which it is transmitting. This causes the FDY’s process variable and output to match its input.
Most transmitters can only trim at the 0% and 100% points of the scale, but the FDY can trim any point along the scale. Note that one-point trimming applies an offset to the sensor reading, while two-point trimming applies both an offset and gain.
Before you attempt to trim the FDY, ensure that the correct sensor is attached to the transmitter, then go to the Trimming tab as shown at the left, and:
1. Select the User radio button under Trim Mode, then answer Ye s to the “Please confi rm that you want to do this” prompt.
2. Select one or two trim points by clicking the appropriate button under Trim Points.
3. Enter the value you want to trim into the Set Value box under Point 1 and click Set. Apply the value you entered in the Set Value section to the FDY. Click on the Trim Pt 1 button. This matches the signal from the sensor to the fi rst point you selected.
4. If you selected two trim points, enter the second value that you want to trim into the Set Value box under Point 2 and click Set. Then apply the value you entered in the Point 2 box to the FDY. Click on the Trim Pt 2 button. This matches the signal from the sensor to the second point you selected.
5. You have now fi nished trimming your sensor and can continue on to Output Trimming.
The Interface Solution Experts 13
Page 14
FDY
PC-Programmable Frequency Transmitter and Display
Output Trimming
Output Trimming increases the accuracy of your transmitter by matching the reading of its recorded output to its actual output. Essentially, this means that it will eliminate any error in the unit that is reading the FDY’s output.
To start trimming the output, hook-up the transmitter in the loop shown in Figure 6, and connect either a multimeter (preferably), or the unit that will be reading the FDY’s signal to the transmitter’s output.
1. Click the Fix Current Low button. This should cause the FDY to output 4mA. If it is outputting a different value, enter the value that the FDY is outputting (in mA) into the Output Current box, then click Trim Low.
2. Check what your multimeter displays as the transmitters output. If it is still not precisely 4mA, enter it into the Output Current box again and clickTrim Low again. Repeat until your multimeter displays an acceptable reading.
3. When you are fi nished, click Un-Fix Current. After doing this, the output will still be trimmed, but the output will no longer be fi xed at 4mA.
Loop Test
Use the Loop Test to trim other instruments in the loop.
1. To begin the loop test, enter the mA value you want the FDY to output to the Loop into the Loop Test text box. Click Fix.
2. Monitor the effect of this on the other instruments in the loop, and adjust accordingly.
3. If necessary, repeat steps 1 and 2 and enter a different value in the Output Current box.
4. When you are fi nished, click Unfi x.
After the trimming parameters have been selected, you can continue on by either downloading the confi guration or clicking the Custom Curve tab, and proceeding to the Programming the Custom Curve Parameters section.
4. Continue by clicking the Fix Current High button. This should cause the FDY to output 20mA. If the output is a different value, enter it into the Output Current box, then click Trim High.
5. Check what your multimeter displays as the transmitters output. If it is still not precisely 20mA, enter it into the Output Current again and click Trim High again. Repeat until your multimeter displays an acceptable reading.
6. When you are fi nished, click Un-Fix Current. After doing this, the output will still be trimmed, but the output will no longer be fi xed at 20mA.
NOTE:
Clicking the RESET button will completely undo output
trimming.
14 The Interface Solution Experts
Page 15
FDY
PC-Programmable Frequency
Transmitter and Display
Programming the Custom Curve Parameters
The Custom Curve section of the confi guration software allows you to setup your own custom curve table with up to 128 points. In effect, this allows you to tell the transmitter what it should output when it receives a certain input. Use the Custom Curve tab for customizing the display’s engineering units, reversing the output, signal limiting and creating custom curves.
Figure 11. Custom Curve Parameters Tab
Follow these directions to setup your custom curve table:
1. Check the Enabled box in the Custom Curve section. Click the Set button and wait for the transmitter to fi nish downloading the information.
2. Input the Lower Range and the Upper Range into the appropriate boxes. The point you enter in the Lower Range will become the zero point of the transmitter, and the transmitter will send out a 4mA signal (or the selected output signal, if the zero output is set at a value other than 4mA) when this point is reached. Likewise, the point you enter into the Upper Range will cause the transmitter to output 20mA (or full output signal, if different) when that point is reached.
3. Enter the desired engineering unit into the Display EGU label box. This will control what type of engineering unit (up to 5 alphanumeric characters, excluding symbols) is displayed by the Confi guration Software and on the FDY’s display.
4. Click Set to download all of the information to the transmitter.
NOTE:
“Read” will upload the information from the transmitter
to the confi guration program. This can be used to
take the last table that you have downloaded to the
transmitter and enter it into the PC Confi guration
Software.
5. Click Edit Table to begin creating your own custom curve table (see next page for instructions).
IMPORTANT:
Once you enable the custom curve, you must edit the
table in order for your transmitter to work properly.
The Interface Solution Experts 15
Page 16
FDY
PC-Programmable Frequency Transmitter and Display
Editing the Custom Curve Table
To edit custom table points, click Edit Table in the Custom Curve tab, then follow the directions below.
1. If you have already written a custom table in Microsoft® Excel (and saved it in a .csv format) or in our PC Confi guration Software, you can open it from the Edit Table menu. Go to File (at the top, left corner of the screen, on the command bar), and click Open, then select the appropriate fi le.
2. If you have NOT already written a custom table, begin writing one by clicking the Edit Table button and selecting the number of points you would like to defi ne. Do this in the Number of Points section.
3. Make sure that the Custom Curve Enabled box is checked. If not, check it and click the Set button.
4. Fill in the values in the X and Y columns. X is the input column–it represents the value that is input into the FDY. Y is the output column–it represents the value (in engineering units) that the transmitter will output when the value in the X column is input. It is also the value that will be displayed in the PC Software and on the FDY display. If an input falls in between two X values, then the output will be scaled to match the percentage difference between the two X points.
5. When you have fi lled in all of the custom curve points, click Download. This will download the information from the PC Confi guration Software to the transmitter. If you later want to retrieve the fi le from the transmitter to the PC Confi guration Software, you can reattach the transmitter and click Upload. You are now done confi guring your custom table, and if you have made changes to other parts of the confi guration program, you are ready to download the confi guration fi le.
Downloading the Confi guration File
After the confi guration has been set to your satisfaction, it can be downloaded to the unit by selecting Download from the Transfer Menu or by pressing the Download button ( ) on the status bar. Downloading the confi guration displayed in the PC program overwrites the unit’s current confi guration.
Downloading the confi guration to the FDY may take up to 30 seconds to complete. It is important to let the sequence fi nish before taking any other action.
Once completed, the Device Confi guration portion of the screen (in the bottom-left corner) will change to match the confi guration listed on the rest of the screen. The status indicator in the top left hand corner of the view will then indicate the program has reverted back to its idle mode.
Installing the FDY
Moore Industries suggests installing the FDY by fi rst mounting the unit in its intended application, then making the electrical connections to input, output and power.
Mounting
The FDY is built in a HP housing and can be shipped with one of our durable fi eld-mount enclosures, such as the BH or D-BOX. Use the BH for tough, explosion­proof protection, or the D-BOX for areas where you need durable, reliable protection for your display. The FDY is also versatile enough to be mounted on a surface, relay track, pipe or inside one of our fi eld enclosures.
Electrical Connections
The connections for the various single FDY inputs are shown in the following diagram.
16 The Interface Solution Experts
CE Conformity
Installation of any Moore Industries’ products that carry the CE certifi cation (Commission Electrotechnique) must adhere to the guidelines in Installing the FDY in order to meet the requirements set forth in the applicable EMC (Electromagnetic Compatibility) directive (EN 61326). Consult the factory for the most current information on products that have been CE certifi ed.
Page 17
FDY
PC-Programmable Frequency
Transmitter and Display
Recommended Ground Wiring Practices
Moore Industries recommends the following ground wiring practices:
• Any Moore Industries product in a metal case or
housing should be grounded.
• The protective earth conductor must be connected
to a system safety earth ground before making any other connections.
• All input signals to, and output signals from,
Moore Industries’ products should be wired using a shielded, twisted pair wiring technique. Shields should be connected to an earth or safety ground.
• For the best shielding, the shield should be run
all the way from the signal source to the receiving device. (see Note below)
• The maximum length of unshielded input and
output signal wiring should be 2 inches.
Note:
Some of Moore Industries’ instruments can be
classifi ed as receivers (IPT2, IPX2, etc.) and
some can be classifi ed as transmitters (TRX,
TRY, etc.) while some are both a receiver
and a transmitter (SPA
your shield ground connections should be
appropriate for the type of signal line being
shielded. The shield should be grounded at
the receiver and not at the signal source.
2
, HIM, etc). Hence,
Customer Service
If service assistance is ever required for one of the FDYs in your application, refer to the back cover of this manual for the telephone numbers to Moore Industries STAR Center customer service department.
If possible, make a note of the model number of the offending unit before calling. For fastest assistance, try to gather information on the unit(s) serial number and the job and purchase order number under which it was shipped.
Figure 12. Hook-Up Diagram for Installing the FDY into the Application
+
POWER SOURCE 10-42Vdc
–
250 ohms
–+
READOUT DEVICE, CONTROL SYSTEM
FDY
6027.8
HZ
–
+
–PS
+PS
0
0
AC INPUT
COM
CONTACT CLOSURE
INPUT HOOK-UP
–+
DC INPUT
OR
The Interface Solution Experts 17
OR
–PS
+PS
0
COM
–
+
0
Page 18
FDY
PC-Programmable Frequency Transmitter and Display
Appendix A: Intrinsically-Safe Applications
This page contains information for the FDY instrument when used within an intrinsically-safe system.
The diagram on the following page must be used for units that are to operate in areas requiring intrinsically­safe instrumentation.
Refer to the Special Conditions outlined below before proceeding with installation.
Special Conditions of Use
The following instructions must be adhered to when the FDY is used in hazardous ‘Classifi ed’ locations and potentially explosive atmospheres.
1. The FDY Power Supply/Output must only be connected to a intrinsically-safe certifi ed Barrier or other associated apparatus.
2. Entity parameters must be adhered to, as specifi ed in the following diagram located on next page.
18 The Interface Solution Experts
Page 19
FDY
PC-Programmable Frequency
Transmitter and Display
The Interface Solution Experts 19
Page 20
EC Declaration of Conformity
 
Moore Industries-International, Inc. Date Issued: 21 Oct. 2013 16650 Schoenborn Street No. 100-100-204 Rev. C North Hills, CA 91343-6196 U.S.A. Page 1 of 2
Equipment Description:
PC-Programmable Frequency-to-DC Transmitter with Display Model FDY / * / * / * / * / *
* Indicates any input, output, power, options and housing as stated in the product data sheet.
Directive:
2004/108/EC (EMC)
Specifications Conformed To:
EN 61326-1:2006
Equipment Description:
PC-Programmable Frequency-to-DC Transmitter with Display Model FDY / * / * / * / * / HP
* Indicates any input, output, power and options as stated in the product data sheet.
Directive:
94/9/EC (ATEX)
Provisions of the Directive Fulfilled by the Equipment:
Group II Category 1G EEx ia IIC T4
Notified Body for EC-Type Examination:
LCIE [Notified Body Number 0081] 33, av du Général Leclerc 92260 Fontenay-aux-Roses - France
EC-Type Examination Certificate:
LCIE 03 ATEX 6172 X
Standards and Technical Specifications Used*:
EN 50014:1997 + Amds 1 & 2 EN 50020:2002 Electrical apparatus for potentially explosive atmospheres. Intrinsic safety ”i”.
*Note: The Requirements of these Standards were reviewed against Technical Standards
EN 60079-0:2009 EN 60079-11:2007 Explosive atmospheres Part 11: Equipment protection by intrinsic safety ”i”
and there are no significant changes relevant to this equipment or affecting the latest technical knowledge for the product identified on this declaration.
Electrical equipment for measurement, control and laboratory use - EMC requirements
Electrical apparatus for potentially explosive atmospheres. General requirements.
Explosive atmospher es Part 0: Equipm ent - General requirements
Page 21
EC Declaration of Conformity
 
Moore Industries-International, Inc. Date Issued: 21 Oct. 2013 16650 Schoenborn Street No. 100-100-204 Rev. C North Hills, CA 91343-6196 U.S.A. Page 2 of 2
Equipment Description:
PC-Programmable Frequency-to-DC Transmitter with Display Model FDY / * / * / * / * / BH**E or SB**E
* Indicates any input, output, power and options as stated in the product data sheet. **Indicates any BH or SB Enclosure with the ‘E’ suffix.
Directive:
94/9/EC (ATEX)
Provisions of the Directive Fulfilled by the Equipment:
Group II Category 2G Ex d IIC T6;
Notified Body for EC-Type Examination:
ISSeP [Notified Body Number 0492] Zoning A. Schweitzer 7340 Colfontaine, Belguim
EC-Type Examination Certificate:
ISSeP 08 ATEX 033 X
Technical Standards Used:
EN 60079-0:2006 EN 60079-1:2007 Explosive atmospheres Part 1: Equipment protection by flameproof enclosures "d" EN 61241-0:2006 Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements EN 61241-1:2004
Notified Body for Quality Assurance:
SIRA [Notified Body Number 0518] Rake Lane, Eccleston, Chester, Cheshire, CH4 9JN, England
On Behalf of Moore Industries-International, Inc., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed directives.
Signature: Deanna Esterwold, Quality Manager
Group II Category 2D Ex tD A21 IP66 T85˚C
Explosive atmospheres Part 0: Equipment - General requirements
Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
Page 22
RETURN PROCEDURES
To return equipment to Moore Industries for repair, follow these four steps:
1. Call Moore Industries and request a Returned Material Authorization (RMA) number.
Warranty Repair –
If you are unsure if your unit is still under warranty, we can use the unit’s serial number to verify the warranty status foryou over the phone. Be sure to include the RMA number on all documentation.
Non-Warranty Repair – If your unit is out of warranty, be prepared to give us a Purchase Order number when
you call. In most cases, we will be able to quote you the repair costs at that time. The repair price you are quoted will be a “Not To Exceed” price, which means that the actual repair costs may be less than the quote. Be sure to include the RMA number on all documentation.
2. Provide us with the following documentation: a) A note listing the symptoms that indicate the unit needs repair b) Complete shipping information for return of the equipment after repair c) The name and phone number of the person to contact if questions arise at the factory
3. Use suffi cient packing material and carefully pack the equipment in a sturdy shipping con­tainer.
4. Ship the equipment to the Moore Industries location nearest you.
The returned equipment will be inspected and tested at the factory. A Moore Industries rep­resentative will contact the person designated on your documentation if more information is needed. The repaired equipment, or its replacement, will be returned to you in accordance with the shipping instructions furnished in your documentation.
WARRANTY DISCLAIMER
THE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WAR­RANTIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SERVICES SOLD BY THE COMPANY. THE COMPANY DIS­CLAIMS ALL WARRANTIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, AND ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWLEDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM OR USAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THAT ANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IMPLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANY WAY. ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREES WITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REM­EDIES FOR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CON­SEQUENTIAL OR INCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPT TO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASE THE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALL MONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THE GOODS OR SERVICES.
ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THE COMPANY SHALL BE BARRED UNLESS THE COMPANY RE­CEIVES FROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT OR BREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WARRANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THAN TWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYER COULD REASONABLY HAVE DISCOV­ERED THE ALLEGED DEFECT OR BREACH.
RETURN POLICY
For a period of thirty-six (36) months from the date of shipment, and under normal conditions of use and service, Moore Industries (“The Company”) will at its option replace, repair or refund the purchase price for any of its manufactured products found, upon return to the Company (transportation charges prepaid and otherwise in accordance with the return procedures established by The Company), to be defective in material or workmanship. This policy extends to the original Buyer only and not to Buyer’s customers or the users of Buyer’s products, unless Buyer is an engineering contractor in which case the policy shall extend to Buyer’s immediate customer only. This policy shall not apply if the product has been subject to alteration, misuse, accident, neglect or improper application, installation, or operation. THE COMPANY SHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
United States • [email protected]
Tel: (818) 894-7111 • FAX: (818) 891-2816
Australia • [email protected]
Tel: (02) 8536-7200 • FAX: (02) 9525-7296
© 2013 Moore Industries-International, Inc.
Belgium • [email protected]
Tel: 03/448.10.18 • FAX: 03/440.17.97
The Netherlands • [email protected]
Tel: (0)344-617971 • FAX: (0)344-615920
Specifi cations and Information subject to change without notice.
Tel: 86-21-62491499 • FAX: 86-21-62490635
United Kingdom • [email protected]
Tel: 01293 514488 • FAX: 01293 536852
Loading...