Read and understand this manual. Improper installation, adjustment, alteration,
service or maintenance can cause serious injury, property damage or even death.
For assistance or additional information consult a qualified installer, service
agency or the gas supplier.
CAUTION
Glass doors on gas fireplaces are extremely hot while the fireplace is on and
remain hot even after the fireplace has been turned off. Safety screens are
available and can reduce the risks of severe burns. Please keep children away
from the fireplace at all times.
®
CUS
WARNING
Do not store or use gasoline or any other flammable vapors and liquids in the vicinity of
this or any other gas burning appliance. A fire or explosion my occur causing serious
injury, property damage or even death.
NOTICE
Installer: Leave this manual with the appliance. Do not remove.
Consumer: Retain this manual for maintenance and future reference. Do not Discard.
DANGER
IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
XG0185100511
Canadian Heating Products Inc. Langley, BC V4W 4A1 | Montigo Del Ray Corp. Ferndale, WA 98248
L52DF-ST* Indoor Gas Fireplace
NOTICE
You must read and understand this manual prior to installation, operation or
troubleshooting this appliance. Please retain this owner’s manual for furure reference
and maintenance.
Honeywell gas control and pilot ........................... 12
Page 2
Part No. XG0811 -100511
L52DF-ST* Indoor Gas Fireplace
High voltage
Toxic
Flammable materials
Corrosive
Fork lift trucks
Danger overhead crane
Explosion risk
Blank
Safety Alert Key
DANGERWARNING
Indicates a hazardous situation which, if not
avoided, WILL result in death or serious
injury or property damage.
CAUTIONNOTICE
Indicates a hazardous situation which, if not
avoided, WILL result in minor or moderate
injury.
Introduction
INTRODUCTION
Congratulations on your purchase of a Montigo Fireplace.
With over 30 years of experience, Montigo is committed to providing
you with a gas replace that is not only a beautiful addition to your
space, but that is also designed and manufactured to the highest
safety, reliability and engineering standards.
We strongly encourage you to read and carefully follow the
instructions laid out in this Installation, Operation and Maintenance
Manual and retain it for your future reference. Pay special attention
to all cautions, warnings, and notices throughout this manual
intended to ensure your safety.
This manual covers installation, operation and maintenance.
Lighting, operation and care of this replace can be easily
performed by the homeowner. All installation and service work
should be performed by a qualied or licensed installer, plumber
or gastter as certied by the state, province, region or governing
body where the replace is being installed.
Indicates a hazardous situation which, if not
avoided, COULD result in death or serious
injury or property damage.
Address practices that are important, but
not related to personal injury
This installation, operation and maintenance manual is applicable
to the models described below. Refer to your rating plate to
verify included options. Throughout this manual instructions
are applicable to all models designated as L52DF-ST* unless
otherwise noted.
MODEL
L52FSDNX40,000XX
L52FSDNEX40,000XX
L52FSDLX40,000XX
L52FSDLEX40,000XX
L52FSDNIX40,000X
L52FSDLIX40,000X
Natural Gas
Liquid Propane
Gas Rating
(BTU hr)
Linear Burner w/
Glass Accessories
Standard Pilot
Ignition
Honeywell Hot
Surface Ignition
SIT Electronic
Ignition
NOTE: L(S)52DF-ST* Units are stainless steel construction
Part No. XG0811 -100511
WARNING
Hot glass will cause
burns. Do not touch
glass until unit is cooled.
Never allow children to
touch glass.
Warranty and Installation Information
The Montigo warranty will be voided by, and Montigo disclaims any
responsibility for, the following actions:
► Modication of the replace and/or components including DirectVent assembly or glass doors.
► Use of any component part not manufactured or approved by
Montigo in combination with this Montigo replace system.
► Installation other than as instructed in this manual.
Consult your local Gas Inspection Branch on installation requirements
for factory-built gas replaces. Installation & repairs should be done by
a qualied contractor.
: (See Appendix B)
Page 3
L52DF-ST* Indoor Gas Fireplace
Installation
IMPORTANT MESSAGE: SAVE THESE INSTRUCTIONS
The L52DF-ST* Direct Vent replace must be installed
in accordance with these Instructions. Carefully read all the
Instructions in this manual rst. Consult the Local Gas Branch to
determine the need for a permit prior to starting the installation.
It is the responsibility of the installer to ensure this replace is
installed in compliance with the manufacturers instructions and
all applicable codes.
BEFORE YOU START:
INSTALLATION AND REPAIRS SHOULD BE DONE
BY AN AUTHORIZED SERVICE TECHNICIAN. THE
APPLIANCE SHOULD BE INSPECTED BEFORE USE
AND AT LEAST ANNUALLY BY A PROFESSIONAL
SERVICE TECHNICIAN. MORE FREQUENT CLEANING
MAY BE REQUIRED DUE TO EXCESSIVE LINT
FROM CARPETING, BEDDING MATERIAL, ETC. IT
IS IMPERATIVE THAT CONTROL COMPARTMENTS,
BURNERS AND CIRCULATING AIR PASSAGEWAYS
OF THE FIREPLACE ARE KEPT CLEAN.
Installation Checklist
Determine the desired install location of your replace.
See Section 1, Dimensions on Page 5, and refer to the Framing
Section 2 for details.
Select the location of your termination and resulting vent run.
Your selected termination location must be the highest point
in the Direct Vent installation.
Should it be impossible to meet the venting requirements laid
out in Section 3: Venting, please contact Montigo regarding the
use of a Montigo Power Vent.
Lay out the Vent run; calculating the required elbows and straight
runs of 5"/8" flex or rigid pipe.
Layout Electrical Requirements Refer to Section 4: Wiring, for
Details.
Refer to Section 5: Installing the Gas Line, for details on the
gas connection and access.
Refer to local codes and guidelines for installation requirements.
Installation and repairs should be done by a qualied
contractor and must conform to:
• Installations inCanada must conform to the current
CAN/CGA B-149.1 and .2 Gas Installation Code and local regulations.
CAUTION!
Due to its high operating temperatures, the appliance should
be located out of trafc & away from furniture and draperies.
Children and adults should be alerted to the hazards
of the high surface temperature, which could cause
burns or clothing ignition.
Young children should be carefully supervised when
they are in the same room as the appliance.
Clothing or other ammable materials should not be
placed on or near the appliance.
WARNING!
When this appliance is installed directly on any combustible
material other than wood ooring, it must be installed on a
metal or wood panel extending the full width and depth of
the appliance.
• Installations in the USA must conform to local codes,
or in the absence of local codes to the National Fuel Gas Code, ANSI
Z223.1.
• See Appendix C for installation within the State of Massachusetts. This replace must comply with NFPA-54 Chapter
10.
Page 4
Part No. XG0811 -100511
L52DF-ST* Indoor Gas Fireplace
Installation
Section 1: Installation Overview and Product Dimensions
Please review the Installation Checklist on Page 4 for general information on preparing for a successful installation of your replace.
The L52DF-ST* replace may be installed in any location that maintains proper clearances to air conditioning ducts, electrical wiring and plumbing. Safety, as well as efciency of operation, should be considered when selecting the replace location. Try to select a location that does not
interfere with room trafc, has adequate ventilation and offers an accessible path for Direct Vent installation.
The replace dimensions are shown below:
G
E
B
D
C
B
F
A
Front View
H
J
K
I
A
Top View
Unit Di mensions
ABCDEFGHIJ K
L52DF- ST52" 33¼" 21⅛" 47"6⅞"5¼" 23⅞" 58 "5"8"12"
Part No. XG0811 -100511
Figure 1. Fireplace dimensions.
Page 5
L52DF-ST* Indoor Gas Fireplace
”
-
C
Installation
Section 2: Framing
1). Frame in the enclosure for the unit with framing materials. The
framed opening for the assembled replace is 60" wide, x 39" high
x 23 3/4" deep, see Figure 2
NOTE: When constructing the framed opening, please ensure
there is access to install the gas line when the unit is installed.
See Figure 22.
.
60”
MODEL
Top - Top Vent
Sides
L52DF-ST 30" 1"0"4" 1"
Top vent
N.G. & L.P
Min. 1”
ombustible
Header
7”
Floor
Alcove over
Fireplace Non
Combustible
Materials Only
Non
Combustible
Header
7”
Mantel
10”
Rear
39”
Both walls Typical.May
not be exactly as shown.
Figure 2. Framing dimensions.
39”
23 3/4
Figure 3. Non Combustible Framing with alcove above replace,
door
opening
Floor
33 1/4”
Right side. Combustible Framing above replace, Left side, see
Frame the replace cavity according to Figure 2.
gure 2. (Top Vent).
Slide the replace into the cavity. Tack four studs (Vertical) in place
as shown in Figure 2a. Secure the replace in position by nailing into
these cleats. (Minimum 2" clearance must still be maintained around the vent pipes.)
60”
Figure 2a. Framing dimensions, (Back-framing)
Clearances
These clearances apply to all dimensions except the framed opening,
where the clearance to combustibles is 0". The L52DF-ST clearance to
unprotected combustible walls which are perpendicular to the replace
opening, must not project beyond the shaded area shown in Fig. 24.
For protection against freezing temperatures, it is recommended that
outer walls of the chase be insulated with a vapor barrier. This will reduce
the possibility of a cold-air convection current on the replace.
Page 6
Part No. XG0811 -100511
Installation
L52DF-ST* Indoor Gas Fireplace
Section 3: Venting
Montigo supplies a variety of direct venting and termination options.
The direct vent termination location MUST be selected such that
it is the highest point in the venting assembly. It should also be
selected such that it provides the shortest vent run possible. Should
it be impossible to ensure that the termination is the highest point or
should it be impossible to meet the venting guidelines laid out below
please contact your Montigo dealer to discuss power venting options.
NOTES FOR PLANNING VENTING:
Venting can terminate through the roof or through an
exterior wall.
Refer to Appendix A - Termination Locations to ensure the
planned termination location is acceptable.
Once the termination location has been established, refer
to the appropriate section below for installation details
All replaces shipped from the factory are Top vent.
Section 3-2: INSTALLING A ROOF MOUNTED DIRECT VENT
TERMINATION (PVTK-1)
This section applies to installations where the direct vent termination will be roof mounted.
Roof mounted Terminations
The following details are some possible congurations for Roof
mounted terminations. See below.
PVTK1 Termination
Figure 11. Top vent, Roof mounted termination with no offset in
vent run.
Section 3-2-1: VENTING LAYOUT
Selection of components and details of venting lay out should
adhere to the following guidelines:
The maximum termination point is 32’ above the replace (NOTE:
if the maximum termination height is used, the ame pattern
may be affected).
The Vertical termination must be a minimum 2’ higher than where
the termination exits the roong materials, (asphault shingles,
cedar shakes, etc). This distance should be measured from the
high side of the roof slope where the ue ashing intersects the
roong materials. (see Figures 11 to 11c *).
Termination location must be a minimum 6’ from a mechanical
air inlet.
Termination location must be a minimum 18” from a parapet wall.
A maximum of two offsets (each offset is made up of 2-90°
bends) may be made.
Install a restop at any location where venting passes through
combustible materials and construction.
Utilize support straps, or support plates, and rings (as required)
to meet acceptable building practices.
Install all roof ashing and storm collars as shown.
PVTK1 Termination
Figure 11a.Top vent, Roof mounted with 1 offset (1 offset= two 90°
bends).
Part No. XG0811 -100511
Page 7
L52DF-ST* Indoor Gas Fireplace
Installation
PVTK1 Termination
Figure 11b.Top vent, Roof mounted with 2 offsets (1 offset= two 90°
bends).
Section 3-2-2: VENTING COMPONENTS
Select from the following components and associated Montigo
part numbers for installation of a Roof Mounted Termination.
Use only Montigo Vent Components. Use of non-Montigo parts
will void the warranty and may impede operation of the replace.
Connection and installation of the vent components should
adhere to the following guidelines:
Use any combination of rigid and Flex pipe as required.
Flex sections may be stretched up to 50% of their total length
(e.g. a 24” section maybe stretched to 36”).
Connect all vent sections using a minimum of three sheet metal
screws on the outer pipe ue.
Ensure the pipe ends male to female slide in a minimum of 1
1/2” of overlap.
Ensure all runs are supported with a minimum of 3 supports
per 10’ of venting.
When hanging/ supporting venting, ensure that 1” clearance
is maintained on sides and bottom of vent runs and 2” above
horizontal vent runs to any combustible material.
Ensure when cutting sections of rigid pipe to maintain integrity
of internal supports.
Place the springs, supplied with the pipe kit, between the outer
and inner pipes to keep the pipes separate and avoid any
possible hot spots.
Montigo recommends the use of a ex section for the nal pipe
connected directly to the replace offering greater exibility of
installation and absorption of movement.
When penetrating a combustible ceiling, a ceiling restop must
be used.
Montigo recommends that all exterior corners and joints be
sealed with exterior caulking however we encourage you to
consult your Building Envelope Engineer or Waterproong
Consultant for further recommendations.
Section 3-3: INSTALLING A WALL MOUNTED DIRECT VENT
TERMINATION
This section applies to installations where the direct vent termination will be wall mounted.
1). Installation of Termination with built in frame
A Termination with a Built-In Frame is installed during framing of a structure.
1. Frame the termination opening to 11" x 11".
2. Install exterior sheathing to the structure framing.
3. Fasten the termination to the sheathing using a minimum of 4 screws.
11”
Framing
Exterior
Sheathing
1”
Fastening Hardware,
minimum 4-screws
PTO-4F (5"/8")
Termination
Figure 13. Installing a PTO-F termination.
2). Installation of termination frame at time of framing
Terminations with a MSR frame allow the installation of the frame prior
to installation of the termination.
1. Frame the termination opening to 12" x 12".
2. Secure the MSR Frame to the exterior sheathing of the structure.
3. Fasten the termination to the MSR Frame using a minimum of 4 screws.
2”
Framing
1
Exterior
Sheathing
12”
Figure 13a. Installing a PTO termination with the MSR frame.
MSR Frame
Fastening Hardware,
minimum 4-screws
PTO-4 (5"/8")
Termination
3). Installation of termination frame at time of framing in
Masonry
Terminations with a BSR frame allow the installation of the frame in
masonry prior to the installation of the termination
1. Frame the BSR opening to 12" x 12".
2. Secure the BSR Frame to the exterior sheathing of the structure.
3. Fasten the termination to the BSR Frame using a minimum of 4 screws.
Framing
Exterior
Sheathing
1
12”
BSR Frame
Fastening Hardware,
minimum 4-screws
PTO-4 (5"/8")
Termination
2”
Figure 13c. Installing a PTO termination with the BSR frame.
4). Installation of termination from inside structure
A Termination with a MOSR Frame is installed from the inside of the
structure. These are commonly used in high-rise construction.
12”
MOSR Frame
PTO-4 (5"/8")
Termination
Fastening Hardware,
minimum 4-screws
Figure 13b. Installing a PTO termination with the MOSR frame.
1. Frame the MOSR opening to 12" x 12".
2. Fasten the MOSR frame to the interior side of the studs, concrete,
or nished wall construction using a minimum of 4 screws.
3. Insert the termination into the MOSR frame as shown here, (from the inside) and attach to the MOSR by installing a min. quantity of
4 bolts into the threaded nuts on the MOSR Frame.
Framing, concrete or other
materials
12”
Exterior Sheathing, concrete or
other materials
Part No. XG0811 -100511
5). Installation of a termination shield for Vinyl Siding
The VSS Termination shieldis installed when the exterior of a structure
is clad with Vinyl siding. It is placed directly above, and on-center with
the termination.
VSS Vinyl shield
PTO-4 (5"/8")
Termination
Exterior Vinyl
siding
Figure 14. Installing the VSS Vinyl Shield.
Page 9