Montigo HT34 PV User Manual

f i r e f e a t u r e
C US
www.montigo.com
Installation Operation & Maintenance Manual
Check local codes and read all instructions prior to installation.
HT34-PV
HT-Series PV Gas Fireplace
Warning:
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualied installer, service agency or the gas supplier.
Safety Notice:
Glass doors on gas fireplaces are extremely hot while the fireplace is on and remain hot even after the fireplace has been turned off. Safety screens are available and can reduce the risks of severe burns.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Indoor
Warning:
What to do if you smell gas
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the re department.
XG0530 Canadian Heating Products Inc. Langley, BC V4W 4A Montigo Del Ray Corp. Ferndale, WA 98248 041510
• Installer: Leave this manual
®
with the appliance.
• Consumer: Leave this manual for future reference.
HT34-PV Series Power Vent Gas Fireplace
Warning:
Read this manual before installing, operating or troubleshooting this
appliance. Please retain this owner's manual for future reference.
Congratulations
Congratulations on selecting a Montigo gas replace, an elagent and well designed gas replace built to your specications. The Montigo gas replace you have selected is designed to provide the utmost in safety, reliability, and engineering standards.
As the owner of this new replace, you'll want to read and care­fully follow all the instructions contained in this Installation, Operations and Maintenance manual. Pay special attention to all cautions, warnings, and Important warnings.
This owner's manual should be retained for future reference. We suggest that you keep it with all your other important documents and product manuals.
The information contained in this owner's manual, unless noted otherwise, applies to all models, and gas control systems.
Your new Montigo gas replace will give you years of durable, reliable use. Welcome to the Montigo family of gas replace products.
Safety Alert Key:
• DANGER!
Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
• Important: Used to address practices not related to personal injury.
Table Of Contents
Congratulations
Safety Alert Key
Introduction ............................................................................... 3
Installation
Installing and Framing the Fireplace .............................. 4
Installing the Gasline ...................................................... 5
Vent Installation .............................................................. 5
Installation Requirements .................................. 5
Vent Terminations .............................................. 6
Installing the Standoffs ......................................6
Converting Vent Runs .................................................... 7
Power Vent Runs ........................................................... 8
Finishing around the replace
Fireplace Facing ................................................ 8
Mantels and Surrounds ................................8 - 9
Wiring ....................................................................9 - 10
Removing and Installing the Door ......................... 10 - 11
Operation .........................................................................12 - 14
Maintenance .................................................................... 14 - 15
General ........................................................................14
Troubleshooting ............................................................ 15
Spare Parts .................................................................. 15
Warranty ................................................................................. 16
Appendix
A. Termination Locations .............................................. 17
B State of Massachusetts / Amendment ..................... 18
Notes: ......................................................................... 19
Page 2
Part No. XG0530 - 041510
Introduction
HT34-PV Series Power Vent Gas Fireplace
Thank You for choosing a Montigo Gas Fireplace.
About this Fireplace:
The HT34-PV Series is an replace that is designed to compliment your home and decor. This replace can be converted to both a Top Vent or Rear Vent application, but requires a Power Vent for safe and trouble free operation. (Refer to the Index)
The HT34DF-PV Series is available in the specic models below.
The HT34-PV is rated for Natural Gas and Liquid Propane at 30,000 Max. BTU/H (8.45) Kilowatts Input.
► HT34-PV-I; Top or Rear Vent convertible, Intermittent Pilot (HSI)
► HT34-PV-F; Top or Rear Vent convertible, (SIT Electronic Ignition).
This manual covers installation, operation and maintenance. Lighting, operation and care of this replace can be easily performed by the homeowner. However, all installation and service work should be performed by a qualied or licensed installer, plumber, or gas tter who is qualied or licensed by the state, province, region, or governing body in which the appliance is being installed.
This manual covers all models and unless otherwise specied, the designation HT34-PV refers to all variations of the model above. Sections which are specic to a particular variation are marked with a symbol, plus the appropriate model number.
Warranty and Installation Information:
The Montigo warranty will be voided by, and Montigo disclaims any responsibility for, the following actions:
► Modication of the replace and/or components including Direct-Vent assembly or glass doors.
► Use of any component part not manufactured or approved by Montigo in combination with this Montigo replace system.
► Installation other than as instructed in this manual.
Consult your local Gas Inspection Branch on installation requirements for factory-built gas replaces. Installation & repairs should be done by a qualied contractor.
Installations in Canada must conform to the current CAN/CGA B-149.1 and .2 Gas Installation Code and local regulations. If the optional air­circulating fan kit is installed, it must be electrically grounded in accordance with CSA C22.1 Canadian Electrical Code Part 1 and/or Local Codes.
Installations in the USA must conform to local codes, or in the absence of local codes to the National Fuel Gas Code, ANSI Z223.1-1988. If the optional air-circulating fan is installed, it must be grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70-1987. See Appendix for installation within the State of Massachusetts. This replace must comply with NFPA-54 Chapter 10.
CAUTION!
Due to its high operating temperatures, the appliance should be located out of traffic & away from furniture and draperies.
Children and adults should be alerted to the hazards
of the high surface temperature, which could cause burns or clothing ignition.
Young children should be carefully supervised when
they are in the same room as the appliance.
Clothing or other flammable materials should not be
placed on or near the appliance.
Part No. XG0530 - 041510
WARNING!
When this appliance is installed directly on carpeting, tile or any combustible material other than wood ooring, it must be installed on a metal or wood panel extending the full width and depth of the appliance.
Page 3
HT34-PV Series Power Vent Gas Fireplace
4
Installation
Installing The Fireplace Shell
The replace may be installed in any location that maintains proper clear­ances to air conditioning ducts, electrical wiring and plumbing. Safety, as well as efciency of operation, must be considered when selecting the replace location. Try to select a location that does not interfere with room trafc, has adequate ventilation, and offers an accessible pathway for Power Vent installation. Refer to page 4 - Vent Installation for more information.
The replace dimensions for HT34-PV models are shown below:
22”
4”
7”
17 3/8”
1 1/4”
5 1/2”
37 1/8”
Opening
5 1/4”
8”
17 3/8”
Side View
7”
4”
40 1/4”
47 3/8”
9 1/2”
C
L
33 7/8”
Top View
31 3/8”
1 1/4
1 1/4”
47 7/8”
1”
Opening
Front View
Figure 1. Fireplace dimensions.
Framing
53 3/4”
34”
* When sheetrock is not used behind the fireplace, framing depth may be reduced by 5/8"
20”
Figure 2. Framing dimensions.
0” clearance to corners only
37 3/8”
34”
52 5/8”
Figure 3. Minimum Corner framing dimensions, using a 45° elbow.
When installing a shelf over the top of the replace, the following guidelines must be adhered to: For Rear Vent applications the minimum clearance from the top of the replace to a shelf is 9". For Top Vent applications, the minimum clearance is 17 1/2". (Minimum 2" clearance must still be maintained around the vent pipes.)
Clearances
These clearances apply to all dimensions except the framed opening, where the clearance to combustibles is 0". The HT34-PV Series clearances to combustible materials are:
HT34-PV Top - Rear Vent * Top - Top Vent Back Sides Floor Mantle**
9"
17 1/2”
2" 1" 0"
* Clearances from the top of the replace to a combustible ceiling within the replace enclosure.
** Refer to page 14.
Unprotected combustible walls which are perpendicular to the replace opening, must not project beyond the shaded area shown in Figure 25.
For protection against freezing temperatures, it is recommended that outer walls of the chase be insulated with a vapor barrier. This will reduce the possibility of a cold-air convection current on the replace.
Page 4
Note: PV venting Not exactly as shown.
MEL Short
Header
Shelf
Power Vent
9”
L
S
M
T
Rear Vent
Header
Shel
17 1/2”
Top Vent
f
Figure 4. Framing for shelves over the replace.
WARNING!
When this appliance is installed directly on carpeting, tile or any combustible material other than wood ooring, it must be installed on a metal or wood panel extending the full width and depth of the appliance.
Part No. XG0530 - 041510
M
Installation
Figure 5b. Gas line access.
HT34-PV Series Power Vent Gas Fireplace
Installing The Gas Line
The gas line must be installed before nishing the HT34-PV Series Fireplace. Natural Gas requires a minimum inlet gas supply pressure of 5.5" W.C. & a manifold pressure of 3.5" W.C. Propane Gas requires a minimum inlet gas supply pressure of 11" W.C. & a manifold pressure of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged tapping and be accessible for test gauge connection immediately upstream of the gas supply controls to the appliance. The replace gas connection and the main operating gas valve is located behind the removable trim at the bottom of the unit and need only be attached to the gas line with an approved tting, as required by the applicable installation codes.
To access the replace gas connection the main burner must be removed as shown below in gure 5b.
• Only use gas shut-off valves approved for use by the state, province, region, or governing body, in which the appliance is being installed, or as required by the applicable installation codes.
• Flexible gas connectors must not exceed 3 feet in length, unless it is allowable within applicable installation codes.
Gasline Acces
0.875 dia.
2
7
to center
Figure 5a. Gas line access.
Vent Installation
This section covers the installation of direct venting and terminations.
Installation Requirements
H
T34D-PV Series fireplaces are certified for use with Montigo Standard
Series (4" / 7") venting components.
Minimum clearance to combustible construction around the vent pipe is 1" on all sides, except on horizontal venting where the top of the pipe
must have a clearance of at least 2".
Use only certied Montigo vent components. (Use of other parts will void the Montigo warranty, and may impede the operation of the fireplace.)
All joints must be secured with a minimum of two screws per joint
Vent terminations must not be recessed in walls or siding
Horizontal runs must be supported by a minimum of two supports per horizontal run. A minimum of one screw on each side of support is also required
Flex vent sections may be stretched up to 50% of their total length (eg. a 24" section may be stretched to 36")
Solid vent sections may be cut less than half way from the female end
Venting components can be used in any combination of solid/rigid pipe or flex pipe and in any orientation (Male connectors can face in any direction)
Vent Terminations
Selecting A Termination Location
Choosing your vent termination location will help to determine whether you need to use a top vent or rear vent replace. Figure 6a, below, shows typical replace locations and the venting options they provide.
For a more detailed diagram of allowed termination locations, see Ap- pendix A.
The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
Note: After gas line is connected, each appliance connection,
valve and valve train must be checked while under normal
operating pressure with either a liquid solution, or leak detection device, to locate any source of leak. Tighten any areas where bubbling appears or leak is detected until bubbling stops completely or leak is no longer detected.
DO NOT use a ame of any kind to test for leaks.
Part No. XG0530 - 041510
Burner Tray Gasket
Figure 6. Fireplace locations and vent terminations.
Cautions:
Vent terminations can be very hot. If the termination is less than 7 feet above a public walkway, it should be fitted with a certified Montigo Heat Guard. (Part no. PTKOG).
Do not obstruct, or attempt to conceal the vent termination.
These actions will affect the operation of the fireplace, and may be hazardous.
In heavy snow areas, take extra care to prevent snow buildup
from obstructing the vent termination.
Use Montigo Vinyl Heat Shield (Part no. VSS) when using on ap-
plications with vinyl siding to guard against possible damage.
Page 5
HT34-PV Series Power Vent Gas Fireplace
12
12
11
11
1212
12
Installation
Installing Terminations with Built-In Frames
MTO-3F (4"/7")
Figure 6a. Installing a MTO termination.
1. Frame the termination opening to 11" x 11".
2. Fasten the termination to the studs using a minimum of 4 screws.
Installing Terminations with MSR Frames
MSR
Installing Heat Guards over Terminations
MTKOG (4"/7") PTKOG (5"/8")
Figure 6d. Installing a MTO termination heat guard.
1. Ensure that the two long mounting brackets are facing the bottom of the termination. (See inset). This will provide more heat protection at the top of the termination, where temperatures are highest.
2. Attach to the faceplate of the termination using four sheet metal screws.
3. If installing the termination over Vinyl siding, Use the VSS Termination shield. Montigo Installation document, XG1301.
MTO-3F (4"/7")
Figure 6b. Installing a PTO termination with the MSR frame.
1. Frame the termination opening to 12" x 12".
2. Fasten the termination to the studs using a minimum of 4 screws.
Installing Terminations with MOSR Frames
MOSR
MTO-3F (4"/7")
Figure 6c. Installing a PTO termination with the MOSR frame.
1. Frame the termination opening to 12" x 12".
2. Fasten the MOSR frame to the interior side of the studs using a minimum of 4 screws.
3. Insert the termination into the MOSR frame as shown here, and attach by screwing through the four pilot holes in the termination.
Page 6
Figure 6e. Installing the VSS Vinyl Shield.
Installing The Standoffs
To avoid elevated mantel temperatures, all HT34-PV Series gas replaces are required to have the supplied standoffs installed.
The replace is supplied with two standoffs. Bend and install these standoffs on top of the replace ensuring that the height of the standoff maintains a 6" clearance.
Figure 7. Installing the standoff's.
Part No. XG0530 - 041510