Montigo Homefire plus MD38-DV-2, Homefire plus MD38DR-2, Homefire plus MD38DT-I-2, Homefire plus MD38DR-I-2 Operation Manual

Installation
Questions? Email us at fireplaces@montigo.com or visit our website at www.montigo.com.
Operation & Maintenance
MD38-DV-2
Warning:
Improper installation, adjustment, altera­tion, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional infor­mation consult a qualified installer, service agency or the gas supplier.
For Your Safety:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
What To Do If You Smell Gas:
 Do not try to light any appliance.  Do not touch any electrical switch; do not use any phone in your building.  Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
 If you cannot reach your gas supplier, call the fire department.
Modular Gas Fireplace
n Check local codes and
read all instructions prior to installation.
n Leave this manual with
the owner.
MD38-DV-2 Homefire
Table Of Contents
Introduction ............................................................................. 2
Installation
Installing the Fireplace Shell ......................................... 3
Installing the Gasline .....................................................4
The Remote Switch....................................................... 4
Direct Vent Installation .................................................. 4
General Requirements...................................... 4
Terminations .....................................................5
Top Vent Models with horizontal runs ............... 6
Top Vent Models with vertical runs ...................8
Rear Vent Models .............................................9
Construction around the fireplace
Facing............................................................. 10
Mantels and Surrounds................................... 10
Wiring ................................................................10 - 11
Installing the Logset .................................................... 11
Removing and Installing the Insert ..............................11
Removing and Installing the Door ............................... 11
Operation ........................................................................ 13 - 15
Maintenance ...................................................................15 - 16
Warranty................................................................................. 19
Appendix
A. Accessories ............................................................ 18
B. Termination Locations ............................................19
Introduction
About the M38 Series Modular Fireplaces:
The MD38-DV-2 includes a 27,000 BTU dual burner and embers. All 38 Series Modular Fireplaces allow quick and easy upgrades in the future. The MD38-DV-2 can be upgraded to a Wildfire Burner. Contact your dealer for more information. The MD38-DV-2 model is available in four versions:
nTop Vent (Product Code MD38DT-2) nRear Vent (Product Code MD38DR-2) nIntermittent Pilot - Top Vent (Product Code MD38DT-I-2) nIntermittent Pilot - Rear Vent (Product Code MD38DR-I-2)
The MD38-DV-2 is rated for Natural Gas at 27,000 BTU/H (8.5 Kilowatts) Input or Propane at 27,000 BTU/H 8.5 Kilowatts) Input.
How to use this manual:
This manual covers all models and unless otherwise specified, the designation MD38-DV-2 refers to all models. Sections which are specific to a particular model are marked with a symbol, plus the appropriate model number.
Warranty and Installation Information:
The Montigo warranty will be voided by, and Montigo disclaims any responsibility for, the following actions:
n Modification of the fireplace and/or components including Direct-
Vent assembly or glass doors.
n Use of any component part not manufactured or approved by
Montigo in combination with this Montigo fireplace system.
n Installation other than as instructed in this manual.
Consult your local Gas Inspection Branch on installation requirements for factory-built gas fireplaces. Installation & repairs should be done by a qualified contractor.
Installations in Canada must conform to the current CAN/CGA B-
149.1 and .2 Gas Installation Code and local regulations. If the
optional air-circulating fan kit is installed, it must be electrically grounded in accordance with CSA C22.1 Canadian Electrical Code Part 1 and/or Local Codes.
Installations in the USA must conform to local codes, or in the absense of local codes to the National Fuel Gas Code, ANSI Z223.1-
1988. If the optional air-circulating fan is installed, it must be grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70-1987.
Page 2
CAUTIONS
Due to its high operating temperatures, the appliance should be located out of traffic & away from furniture and draperies.
n Children and adults should be alerted to the hazards
of the high surface temperature, which could cause burns or clothing ignition.
n Young children should be carefully supervised when
they are in the same room as the appliance.
n Clothing or other flammable materials should not be
placed on or near the appliance.
Part No. XG0111
Installation
Installing The Fireplace Shell
MD38-DV-2 Homefire
The fireplace may be installed in any location that maintains proper clearances to air conditioning ducts, electrical wiring and plumbing. Safety, as well as efficiency of operation, must be considered when selecting the fireplace location. Try to select a location that does not interfere with room traffic, has adequate ventilation, and offers an accessible pathway for Direct Vent installation. Refer to page 4 - Vent Installation for more information.
The fireplace dimensions are shown below:
33
5 1/2
Ø4
38
C
Ø7
14 3/4
Top Vent
14 3/4
34 3/4
28 3/4
Framing
Figure 2. Framing dimensions.
Ø7 Ø4
24 1/8
43 7/8
15 1/2
37 3/4
40 3/4
* When sheetrock is not used behind the fireplace, framing depth may be reduced to 14 3/4"
0" clearance to corners only
Front View
Rear Vent
Figure 1. Fireplace dimensions.
Clearances
These clearances apply to all dimensions except the framed opening, where the clearance to combustibles is 0". The MD38-DV-2 clearances to combustible materials are:
Top - Rear Vent* 7 ¼" Top - Top Vent*** 32" Back 0" Side 1 ½" Floor 0" Mantle** 12"
* Clearance from the top of the fireplace to a combustible
ceiling within the fireplace enclosure. ** Refer to page 10. *** If the standard elbow (MEL90) is used with the Low
Clearance Sleeve (CRS30) the Top Clearance is 15".
If the Low Clearance Sleeve (CRS30) is NOT used
over the elbow, the Top Clearance is 32".
Unprotected combustible walls which are perpendicular to the fireplace opening, must not project beyond the shaded area shown in Figure 19b.
For protection against freezing temperatures, it is recommended that outer walls of the chase be insulated with a vapour barrier. This will reduce the possibility of a cold-air convection current on the fireplace.
Figure 3. Corner framing dimensions.
When installing a shelf over the top of the fireplace, the following guidelines must be adhered to: For Rear Vent models (MD38-DR-2), the minimum clearance from the top of the fireplace to a shelf is 7 ¼". For Top Vent models (MD38-DT-2), the minimum clearance when using the CRS30 is 15". (Minimum 1" clearance must still be maintained around the vent pipes.)
Rear Vent
Top Vent
Figure 4. Framing for shelves over the fireplace.
WARNING:
When this appliance is installed directly on carpeting, tile or any combustible material other than wood flooring, it must be installed on a metal or wood panel extending the full width and depth of the appliance.
Part No. XG0111
Page 3
MD38-DV-2 Homefire
Installation
Installing The Gas Line
The gas line must be installed before finishing the MD38-DV-2 Fire­place. Natural Gas requires a minimum inlet gas supply pressure of
5.5" W.C. & a manifold pressure of 3.5" W.C. Propane Gas requires a minimum inlet gas supply pressure of 11" W.C. & a manifold pressure of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged tapping and be accessible for test gauge connection immediately upstream of the gas supply controls to the appliance. The fireplace gas connection and the main operating gas valve is located behind the removable brass trim at the bottom of the unit and need only be attached to the gas line with an approved fitting, as required by the applicable installation codes.
1
Gasline access
2 1/2
Figure 5. Gas line access.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
Note: After gas line is connected, each appliance connection,
valve and valve train must be checked while under
normal operating pressure with either a liquid solution, or leak detection device, to locate any source of leak. Tighten any areas where bubbling appears or leak is detected until bubbling stops completely or leak is no longer detected.
DO NOT use a flame of any kind to test for leaks.
6 x 2 1/2"
Vent Installation
This section covers the installation of direct venting and terminations.
Installation Requirements
n MD38-DV-2 fireplaces are certified for use with Montigo Standard
Series (4" / 7") venting components
n Minimum 1" clearance to combustibles required for vent pipes n Use only certified Montigo vent components. (Use of other parts
will void the Montigo warranty, and may impede the operation of the fireplace.)
n All joints must be secured with a minimum of two screws per joint n Vent terminations must not be recessed in walls or siding n Horizontal runs must be supported by a minimum of two supports
per horizontal run. A minimum of one screw on each side of support is also required
n Flex vent sections may be stretched up to 50% of their total length
(eg. a 24" section may be stretched to 36")
n Maximum horizontal run for a flex section with no vertical rise is 3 feet. n Flex vent sections over 3 feet must fall within the limits set by the
venting graph and must have a minimum vertical rise of 3 inches per foot of flex.
n Solid vent sections may be cut less than half way from the tapered end n Venting components can be used in any combination of solid/rigid
pipe or flex pipe and in any orientation (Male connectors can face in any direction)
Vent Terminations
Selecting A Termination Location
Choosing your vent termination location will help to determine whether you need to use a top vent or rear vent fireplace. Figure 6, below, shows typical fireplace locations and the venting options they provide.
For a more detailed diagram of allowed termination locations, see Appendix B.
Installing The Remote Switch
The MD38-DV-2's gas valve, located behind the lower brass trim, may be connected to a wall switch. The valve generates its own power on a millivolt circuit. Use only low voltage wire, and DO NOT connect any external power to it.
Refer to Figure 26 for wiring requirements. Note: The switch location must not exceed 30' from the fireplace.
Page 4
Figure 6. Fireplace locations and vent terminations.
Cautions:Cautions:
Cautions:
Cautions:Cautions:
n Vent terminations can be very hot. If the termination is less
than 7 feet above a public walkway, it should be fitted with a certified Montigo Heat Guard. (Part no. MTKOG)
n Do not obstruct, or attempt to conceal, the vent termination.
These actions will affect the operation of the fireplace, and may be hazardous.
n In heavy snow areas, take extra care to prevent snow buildup
from obstructing the vent termination.
Part No. XG0111
Installation
MD38-DV-2 Homefire
Installing Terminations with Built-In Frames
11
MTO-3F
11
1. Frame the termination opening to 11" x 11".
2. Fasten the termination to the studs using a minimum of 4 screws.
Installing Terminations with MSR Frames
12
MSR
Installing Heat Guards over Terminations
MTKOG
1. Ensure that the two long mounting brackets are facing the
bottom of the termination. (See inset). This will provide more heat protection at the top of the termination, where temperatures are highest.
2. Attach to the faceplate of the termination using four sheet metal screws.
12
1. Frame the termination opening to 12" x 12".
2. Fasten the termination to the studs using a minimum of 4 screws.
MTO-3
Installing Terminations with MOSR Frames
MOSR
MTO-3
1. Frame the termination opening to 12" x 12".
2. Fasten the MOSR frame to the interior side of the studs using a minimum of 4 screws.
3. Insert the termination into the MOSR frame as shown here, and attach by screwing through the four pilot holes in the termination.
1212
12
Part No. XG0111
Page 5
MD38-DV-2 Homefire
Installation
Top Vent Venting Runs
Before you install any venting, you must determine whether the venting run will be acceptable. Unacceptable venting can affect the fireplace's combustion.
The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of the termination and the horizontal run from the from the fireplace flue collar to the wall flange of the termination. Plot on the Venting Graph (Fig. 7) with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 84" and the horizontal run to the wall flange of the vent termination is 36", this would be an acceptable installation.
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 90" and the horizontal run to the wall flange of the vent termination is 120", this would be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72" and the horizontal run to the wall flange of the vent termination is 84", this would NOT be an
acceptable installation.
108
96 84 72 60 48 36
24
12
0
12 24 36 48 60 72 84 96 108 132120 144 156 168 180
0
Hearth
Figure 7. Venting Graph
Horizontal Run (in.)
Top Vent
Heat Shields
Due to high flue temperatures, heat shields are required on all 38 Series Modular Direct Vent installations (except those with vertical terminations) at the point where the venting connects to the termination. With the heat shield, vent clear­ances can be maintained at 1".
Figure 8. Heat Shield. Install by sliding over the vent pipe where
it passes through combustible construction.
Installation Of Top Vent DV
The following venting components are available for the MD38-DV-2 Top Vent:
A - Termination MTO-3 (3" length)
MTO-3F (3" length)
B - Stucco Kits MSR (stucco frame)
MOSR (stucco can)
BSR (brick can)
D - Flex sections MFL-1 (12" section)
MFL-18 (18" section)
MFL-2 (24" section)
MFL-3 (36" section)
MFL-4 (48" section)
E - Solid sections EXT-18 (18" f/f section)
MEXT-1 (12" m/f section)
MEXT-2 (24" m/f section)
MEXT-3 (36" m/f section)
MEXT-4 (48" m/f section)
F - Elbows
NOTES: All dimension lengths for vertical or horizontal runs are
measured from center of the vent pipe. Venting runs must fall within the limits set by the
venting graph (see Figure 7).
MEL-90M (m/m 90° elbow)
MEL-90F (f/f 90° elbow)
MEL-90FM (f/m 90° elbow)
EEL-45 (f/m 45° elbow)
Page 6
Part No. XG0111
MD38-DV-2 Homefire
Installation
Example 1:
For our shortest venting configuration use components A and F (see Figure 9a). This configuration is suitable for installations where the
fireplace backs directly against 4" stud wall. For deeper walls, use an MEL-90FM elbow and an EXT-18 extension, which can be cut to the required length.
Termination
Heat Shield
MEL-90F/F Elbow
Figure 9a. Typical Top Vent installation. If the 90° elbow is installed
directly on the fireplace, the height to the center of the termination is 44".
Horizontal Venting
90° Elbow
Top Vent
150" max.
30" max.
Heat Shield
Termination
Solid Sections
Exterior
Flex Section
Wall
Hearth
Figure 10. Extended Installation using a combination of solid and
flex venting. Use the vent graph to determine your allowable run, then select appropriate components.
30" Max.
126"
Heat Shield
Heat Shield
Termination
MEXT Section
Figure 9b. Typical Top Vent installation. The solid sections can be
used in various combinations to obtain the desired vent run. The vent run must fall within the limits set by the venting graph.
Example 2:
A 10' section and elbow (MIHR-10) used in conjunction with 3 ft. flex section (MFL-3) will, when extended in a five foot chase, allow for a maximum horizontal run of twelve and one-half feet from the centre of the fireplace to outside wall and a minimum of 7'6" when retracted in opposite direction (see Figure 10 and 11).
"D" flex sections and "E" solid sections may be used in conjunction with one another to obtain different possible horizontal length installations. NOTE: Flex section with no vertical rise must not exceed maximum horizontal length of 3 feet (see Figure 12). Flex runs over 3 feet must fall within the limits set by the venting graph, and must have a minimum vertical rise of 3" per foot of flex.
Solid Section w/ 90° Elbow
Flex Section
Termination
Exterior Wall
Hearth
Figure 11. Retracted Installation using a combination of solid and
flex venting. Use the vent graph to determine your allowable run, then select appropriate components.
3' max.
Flex Section
Heat Shield
Termination
Hearth
Exterior Wall
Figure 12. Horizontal flex installation with no vertical rise.
Part No. XG0111
Page 7
Loading...
+ 15 hidden pages