Montague VG26 Operators Manual

Model Nos.
VG Series
These Instructions should be read thoroughly before attempting Installation.
Set up and Installation should be performed by qualified Installation personnel.
Keep area around appliances free and clear from combustibles.
PLEASE RETAIN THIS
MANUAL FOR FUTURE
CONTENTS
INSTALLATION 1 MAINTENANCE 14 OPERATION 8 SERVICE 17 COOKING HINTS 11 RENEWAL PARTS 29
INSTALLATION
The Montague Grizzly gas convection oven type ranges are manufactured
for use with the type of gas indicated on the nameplate.
The Montague Grizzly gas convection oven type ranges are produced with the best possible material and workmanship. PROPER INSTALLATION IS ESSENTIAL FOR SAFE AND EFFICIENT TROUBLE-FREE OPERATION.
THE INSTALLATION INSTRUCTIONS CONTAINED HEREIN ARE FOR THE USE OF QUALIFIED INSTALLATION AND SERVICE PERSONNEL ONLY. INSTALLATION OR SERVICE BY OTHER THAN QUALIFIED PERSONS MAY RESULT IN DAMAGE TO THE RANGE AND/OR INJURY TO THE OPERATOR.
Qualified installation personnel are individuals, a firm, corporation or company which either in person or through a representative are engaged in, and are responsible for:
A. The installation or replacement of gas piping or the
connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all requirements of state or local authorities having jurisdiction. Reference:
National Fuel Gas Code Z223.1 -1990, Section 1.4.
B. The installation of electrical wiring from the electric
meter, main control box or service outlet to the electric appliance. Qualified installation personnel must be experienced in such work, be familiar with all precautions required and have complied with all requirements of state and local authorities having jurisdiction. Reference: National Electrical Code, ANSI/NFPA No. 70-1988.
READ CAREFULLY AND FOLLOW THESE INSTRUCTIONS
THE RANGE(S) MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL FUEL GAS CODE, ANSI Z223.1-1988, INCLUDING:
1. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. (3.45 kPa).
2. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig. (3.45 kPa).
1
INSTALLATION
THE UNIT, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE, ANSI/NFPA NO. 70-1990.
VENTILATING HOOD
hood. The hood should extend at least 6" beyond all sides of the unit. The hood should be connected to an adequate mechanical exhaust system.
hoods may be obtained from the "Standard for the Installation of Equipment for the Removal of Smoke and Grease Laden Vapors from Commercial Cooking Equipment", NFPA No. 96-1987, available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
PROVISIONS MUST BE MADE FOR ADEQUATE AIR SUPPLY TO THE UNIT.
The range(s) must be installed under a properly designed ventilating
Information on the construction and installation of ventilating
It is also necessary that sufficient room air ingress be allowed to compensate for the amount of air removed by the ventilating system. Otherwise, a subnormal atmospheric pressure will occur which may interfere with burner performance or may extinguish the pilot flame. In case of unsatisfactory range performance, check with the exhaust fan in the "OFF" position.
CLEARANCES
Adequate clearance must be provided at the side, back and in the aisle to allow the doors to open sufficiently to permit the removal of the racks and for serviceability. Adequate clearance for air openings into the combustion chamber must be provided.
CLEARANCES
COMBUSTIBLE NONCOMBUSTIBLE CONSTUCTION CONSTRUCTION BACK 5" 5"
LEFT & RIGHT SIDE 11" 2"
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR FROM THE RANGE. KEEP THE APPLIANCE AREA FREE AND CLEAR FROM COMBUSTIBLES.
CAUTION
2
INSTALLATION
ASSEMBLY
DO NOT LIFT RANGE BY THE FRONT RAIL.
Uncrate range as near to final location as possible. Remove all shipping wire from burners and all packing material and accessories from oven interior.
IF RANGE IS EQUIPPED WITH A FRYTOP SECTION, REMOVE WOOD
SHIPPING STRIPS LOCATED BELOW THE GREASE TROUGH.
Then assemble as follows:
1. Screw the adjustable feet of the legs in all the way. Then tightly screw the complete leg assembly into mounting holes at each corner of the range.
2. Install door handle and secure with screws that are provided. See diagram for correct orientation.
3. Lift high shelf or stub back above the range and slide channels into position. Secure to range back with screws that are provided.
4. Install Open Top and Hot Top sections as shown in diagram below. Install burner bowls and grates on Open Top section.
3
INSTALLATION
5. Install top burner valve handles and thermostat knob(s). If
6. When range is in permanent position, level unit by placing
Fry Top Ranges:
Leveling bolts are at the rear of the range under the Fry Top plate. Adjust leveling bolts so that the plate is pitched to the front to provide for grease runoff. Be sure wooden strips have been removed from below the grease trough.
top burner valve handles fit loose on valve shaft, spread slot on end of shaft slightly with screwdriver blade so that handle will fit snug.
carpenter's level on oven rack and level from front to back and side to side.
Adjust by turning the foot of the adjustable leg. Make sure the leg does not turn.
GAS PRESSURE REGULATOR
THIS RANGE IS DESIGNED FOR USE WITH A GAS PRESSURE REGULATOR.
orifices for use with a manifold pressure of 6.0" water column for natural gas and 10.0" water column for propane gas.
THE REGULATOR SUPPLIED WITH THIS UNIT MUST BE USED.
FOR NATURAL GAS: This gas pressure regulator is factory adjusted for 6.0" W.C. manifold pressure. The rated inlet pressure to the regulator is 1/2 psig (3.45kPa).
FOR PROPANE GAS: This gas pressure regulator is factory adjusted for 10.0" W.C. manifold pressure. The rated inlet pressure to the regulator is 1/2 psig (3.45kPa).
Unless otherwise specified, the range is equipped with fixed
4
INSTALLATION
GAS CONNECTION
Before connecting the range to the gas supply line, be sure that all new piping has been cleaned and purged to prevent any foreign matter from being carried into the controls by the gas. In some cases, filters or drops are recommended. A separate Gas Shut Off Valve must be installed upstream from the gas pressure regulator adjacent to the range and located in an accessible area.
It is important that adequately sized piping be run directly to the point of connection at the range, with as few elbows and tees as possible. Consult local gas company for proper piping size and gas pressure.
PIPE JOINT COMPOUND OR THREAD SEALANT THAT IS USED SHOULD BE RESISTANT TO ACTION OF LIQUEFIED PETROLEUM GASES.
Install the gas pressure regulator with gas flowing as indicated by the arrow on the regulator. Use pipe compound or thread sealant and carefully thread regulator to pipe so that there is no cross threading, etc., which could cause leakage.
Apply wrench only to the flat areas around the pipe tapping at the end being threaded to the pipe to avoid possible damage to the regulator body which could result in leakage.
Connect the gas supply line from the Service Gas Shut Off Valve to the inlet side of the gas pressure regulator using 3/4" pipe. If flexible or semi-flexible connectors are used, an AGA listed flexible connector with an I.D. equal to 5/4" pipe must be used. DO NOT USE A DOMESTIC APPLIANCE TYPE GAS FLEXIBLE CONNECTOR. Avoid kinks or sharp bends that could restrict gas flow.
Turn Gas Shut Off Valve "ON" and immediately check carefully for gas leaks. Do this before attempting to operate the range.
TEST ALL PIPE JOINTS FOR LEAKS BEFORE OPERATING RANGE. THIS INCLUDES ALL GAS CONNECTIONS THAT MAY HAVE LOOSENED DURING SHIPMENT. USE A RICH SOAP SOLUTION (OR OTHER ACCEPTED LEAK TESTER) AROUND ALL PIPE CONNECTIONS AND ALL OTHER JOINTS. DO NOT USE AN OPEN FLAME. ABSOLUTELY NO LEAKAGE SHOULD OCCUR, OTHERWISE THERE IS A DANGER OF FIRE OR EXPLOSION DEPENDING UPON CONDITIONS. NEVER USE IF
LEAKAGE IS DETECTED.
5
INSTALLATION
ELECTRICAL CONNECTION
Unless otherwise specified, the oven is equipped with a 6 ft. flexible supply cord for 115 VAC, 60 Hertz. A terminal block is provided for 208-240 VAC, 60 or 50 Hertz, single phase units. The wiring diagram is located on the back of the range.
THIS APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE, ANSI/NFPA NO. 70-1990.
I. 115 VAC - 60 Hz - Single Phase
three-wire cord and three-prong plug which fits any standard three-prong grounded receptacle. A separate 15 amp. supply is needed for each oven.
Ranges with this electrical rating are factory supplied with a
WARNING: ELECTRICAL GROUNDING INSTRUCTIONS
THIS APPLIANCE IS EQUIPPED WITH A THREE-PRONG (GROUNDING) PLUG FOR YOUR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG.
II. 208-240 VAC - 60 Hz - Single Phase (2 Wire)
Ranges with this electrical rating are factory equipped with a terminal block. To connect supply wires, remove cover from connection box at right rear of range. Route supply wires and ground wire through hole with strain relief fitting at bottom of connection box. Attach supply wires to proper terminal of terminal block. Attach ground wire to ground lug inside connection box. See wiring diagram located on the back of the range for proper connection.
III. 220 VAC - 50 Hz - Single Phase (2 Wire)
Follow steps outlined in (II.) above. Refer to wiring diagram for proper connection.
6
INSTALLATION
PILOT ADJUSTMENT - TOP BURNERS
OPEN TOP: The front and rear pilots are controlled by one valve. To adjust pilot, turn adjusting screw counterclockwise to increase or clockwise to decrease pilot flame. Adjust flame to a point where only a trace of yellow tip remains.
FRY TOP and HOT TOP: Each pilot is controlled by a pilot valve. Turn adjusting screw until pilot flame is 1/2" high.
BURNER ADJUSTMENT
The efficiency of the range depends on a delicate balance between the supply of air and the volume of gas so that complete combustion is achieved. Whenever this balance is disturbed, poor operating characteristics occur.
The air supply is controlled by an air shutter on the front of the burner. The air shutter openings should be increased until the flame on the burner begins to "lift". The air shutter should then be closed slightly and locked in place. A yellow streaming flame indicates insufficient air. This condition can be corrected by increasing the air shutter opening.
FRY TOP AND OVEN THERMOSTATS
The by-pass (minimum burner flame) has been adjusted at the factory and should require no further adjustment.
THE BY-PASS FLAME MUST BE RECHECKED WHEN PERFORMING CHECKOUT OF RANGE PRIOR TO PLACING EQUIPMENT IN SERVICE. THE BY-PASS MUST BE SET CAREFULLY AND ACCURATELY. REFER TO SERVICE SECTION OF THIS MANUAL FOR PROPER PROCEDURE.
7
OPERATION
OPERATING INFORMATION FOR THE RANGE HAS BEEN PREPARED FOR USE BY QUALIFIED AND/OR PROFESSIONAL OPERATING PERSONNEL.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR TO THE RANGE. KEEP THE APPLIANCE AREA FREE AND CLEAR FROM COMBUSTIBLES.
GAS CONTROLS
IN THE EVENT A GAS ODOR IS DETECTED, SHUT DOWN UNITS AT MAIN SHUT OFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR SERVICE.
Top Burners—Open Top, Hot Top and Manual Fry Top
Check that pilots are burning. Then rotate valve handles counterclockwise to full on, burner will ignite automatically. Adjust flame height as desired. To shut down, rotate valve handle clockwise to "OFF" position.
CAUTION
Fry Top—Thermostat Controlled
Check that pilot(s) are burning. Then push thermostat dial inward and rotate dial counterclockwise to maximum thermostat setting, burner(s) will ignite automatically. After ignition turn thermostat dial to desired setting. To shut down, rotate thermostat dial clockwise to "OFF" position.
OVEN A. Lighting
Turn thermostat knob to "OFF" position and wait five (5) minutes.
1. Remove burner compartment cover and open pilot access door.
2. Press and hold red button in (Safety Pilot Valve) and apply lighted match to pilot burner.
3. After pilot burner ignites, continue to hold red button depressed for 30 to 45 seconds or until pilot remains burning when button is released. If pilot goes out, repeat process.
8
4. Close pilot access door and replace burner access panel.
5. Push thermostat dial inward and rotate dial counterclockwise to desired temperature setting.
6. Turn on fan. Fan should be on at all times during cooking operation.
7. IN THE EVENT OF PILOT FAILURE, ROTATE THERMOSTAT DIAL CLOCKWISE TO "OFF" POSITION AND WAIT FIVE (5) MINUTES FOR UNBURNED GAS TO ESCAPE FROM RANGE.
B. Shut Down
1. Stand by
a. Rotate thermostat dial clockwise to "OFF" position.
b. Turn fan off.
2. Complete a. Turn all gas valves to "OFF" position.
OPERATION
b. Turn fan off.
c. Turn electrical service off or disconnect electrical supply cord from wall receptacle.
C. Relighting
1. Rotate thermostat dial clockwise to "OFF" position.
2. Wait five (5) minutes then follow "lighting" instructions in section "A".
USING A CONVECTION OVEN
Your modern gas convection oven assures speedy cooking and quality
performance. Its proper use will result in gas energy conservation.
The convection oven is a different type of oven which offers many features and advantages to the food service operation. The operation of the oven is not difficult to understand or control.
The convection oven is the sealed type whereby the combustion products are separated from the air inside the oven. The heat is transferred through the oven surface into the cooking cavity. The air inside the oven cavity is continuously recirculated over the heat source and the product.
9
Loading...
+ 24 hidden pages