Montague UF-36C Installation Manual

INSTRUCTION MANUAL
MONTAGUE
Heavy Duty Underfired
Gas Broilers
CERAMIC MODELS:
Range Match: UF (24C, 30C, 36C, 48C, 60C, 72C)
Freestanding: UFS (24C, 30C, 36C, 48C, 60C, 72C)
Modular: UFSM (24C, 30C, 36C, 48C, 60C, 72C)
Counter: UFSC (24C, 30C, 36C, 48C, 60C, 72C)
These instructions should be read thoroughly before attempting installation.
Keep area around appliances free and clear from combustibles.
PLEASE RETAIN THIS MANUAL
FOR FUTURE REFERENCE.
THE MONTAGUE COMPANY
1830 Stearman Avenue
P.O. BOX 4954
Hayward, CA 94540-4954
TEL: (510) 785-8822 FAX: (510) 785-3342
IMPORTANT
TABLE OF CONTENTS
Important (Cautions and Warnings) .............................................................. Page 1
Installation .................................................................................................... Page 2 - 6
Operation ...................................................................................................... Page 7
Maintenance ................................................................................................. Page 8 - 9
Maintenance Schedule ................................................................................ Page 10
Service .......................................................................................................... Page 11
Orifice Size Chart - Drill Size ....................................................................... Page 12
Exploded View ............................................................................................. Page 13
Exploded View Parts List ............................................................................ Page 14
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected and packed by skilled personnel before leaving the factory. The transportation company assumed full responsibility for safe delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE - Be certain this is noted on freight bill or express receipt, and signed by person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY - Regardless of the extent of damage.
3. CONCEALED LOSS OR DAMAGE - If damage is unnoticed until merchandise is unpacked,
notify transportation company or carrier immediately, and file “concealed damage” claim with
them. This should be done within fifteen (15) days of date that delivery was made to you. Be sure to retain container for inspection.
We cannot assume responsibility for damage incurred in transit. We will, however, be glad to furnish you with the necessary documents to support your claim.
IMPORTANT
FOR YOUR SAFETY
WARNING
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, INJURY OR DEATH. READ THE OPERATING AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS EQUIPMENT.
WARNING
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
NOTE: This manual has been prepared for personnel qualified to install commercial equipment who should perform the initial field start-up and the adjustments of the equipment covered by this manual.
NOTE: Instructions to be followed in the event the user smells gas must be posted in a prominent location. This information may be obtained by consulting the local gas supplier.
1
INSTALLATION
The Montague gas broilers are produced with the best possible materials and workmanship.
Proper installation is essential for safe and efficient trouble-free operation.
NOTE: The installation instructions contained
herein are for the use of qualified installation and service personnel only. Installation or service by other than qualified personnel may result in damage to the broiler and/or injury to the operator.
Qualified installation personnel are individuals, a firm, corporation, or company which either in person or through a representative are engaged in, and are responsible for:
The installation or replacement of gas piping or the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all requirements of state or local authorities having jurisdiction. Reference: National Fuel Gas Code Z223.1, 1988, Sec. 1.4.
The installation of electrical wiring from the electric meter, main control box, or service outlet to the electric appliance. Qualified installation personnel must be experienced in such work be familiar with all precautions required and have complied with all requirements of state and local authorities having jurisdiction. Reference: Reference: National Electric Code, N.F.P.A. No. 70, 1988.
Read carefully and follow these instructions.
The oven must be installed in accordance with the local codes, or in the absence of local codes, with the national fuel gas code, ANSI Z223.11988, including:
The appliance and its individual shutoff valve must be disconnected from the gas
supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. (3.45 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig. (3.45 kPa).
Provisions must be made for adequate air supply to the unit.
VENTILATING HOOD
The broiler must be installed under a properly designed ventilating hood. The hood should
extend at least 6” beyond all sides of the unit.
The hood should be connected to an adequate mechanical exhaust system.
Information on the construction and installation of ventilation hoods may be
obtained from the “Standard for the Installation
of Equipment for the Removal of Smoke and Grease Laden Vapors from Commercial Cooking Equipment,” NFPA No. 96-1987, available from the National Fire Protection Association, Batterymarch Park, Quincy, MA
02269.
It is also necessary that the sufficient room air ingress be allowed to compensate for the amount of air removed by the ventilation system. Otherwise, a subnormal atmospheric pressure will occur which may interfere with burner performance or may extinguish the pilot flame. In case of unsatisfactory oven performance, re-check performance with the exhaust fan turned “OFF.”
CLEARANCES
Adequate clearances must be provided in the aisle in front of the broiler for safe operation, removal of racks, drip tray and grease container, and for serviceability. Adequate
2
INSTALLATION
clearance for air openings into the combustion chamber must also be provided.
UF, UFS, UFSC & UFSM
Models
Noncombustible
Construction
Back 0”
Left & Right Side
0”
For use in noncombustible locations only.
CAUTION
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR TO THE BROILER(S). KEEP THE APPLIANCE AREA FREE AND CLEAR FROM COMBUSTIBLES.
SETTING IN PLACE
1. Uncrate unit and put into place. For easier and lighter handling of the broiler, remove coals, cast iron top grids, grid frame, drip tray, grease container, and debris screen.
leveled by adjusting the legs.
BATTERY ARRANGEMENTS
1. Place the first unit in the exact position it will occupy in the battery.
2. Using a carpenter’s level, level the unit from front to rear and side to side. Adjust as follows:
FLOOR INSTALLATION ON LEGS
Adjust by turning foot on adjustable legs.
CURB INSTALLATION
Place shim under the low side. This operation is important since variations in floors and curbs are common. Unless units are level, difficulty will be encountered in aligning the gas supply manifold and the units will not butt together tightly.
3. Remove the valve panel from unit.
4. Move the next unit into position.
2. Wire ties securing burners are for shipping purposes only and must be removed when installing the appliance. This will permit the burners to be readily removed during future servicing. Remove all other packing material from burner box.
3. For floor models, a set of 6” legs is packed in the top section of the broiler (unless unit is specifically ordered without legs). A threaded receptacle is located on each corner (and in the middle of units larger
than 36”) of the base of the unit. Each leg
has a similar mating thread. Use lift with proper weight capacity to suspend unit in order to allow legs to be screwed into the threaded receptacles. Level unit by adjusting legs. An unleveled unit will adversely affect performance.
4. Counter units must be installed on a level table or stand, and modular units must be
5. Engage union nut on manifold with male fitting on next unit and draw up union nut hand tight. Be sure appliances butt together both front and rear. If manifolds do not align, then ranges are not level. In extreme cases, it may be necessary to loosen manifold bolts and adjust.
6. Continue leveling and connecting gas supply manifolds together until all appliances in the battery are connected.
7. Tighten manifold union gas tight. Use back up wrench to prevent manifold from rotating. Failure to do this may result in
damage to pilots and gas valves. Check entire system for gas leaks.
GAS HOOK UP
An adequate gas supply is imperative. Undersized or low pressure lines will restrict
3
INSTALLATION
the flow of gas required for satisfactory performance. A steady supply pressure
between 7” and 8” WC for natural gas and 11” and 12” WC for propane gas is required. With
all units operating simultaneously, the manifold pressure on all units should not show any appreciable drop. Fluctuation of more than 25% on natural gas and 10% on propane gas will create pilot problems and affect burner operating characteristics. Contact your gas company for correct supply line sizes.
The unit should be connected only to the type of gas for which it is equipped. Check type of gas on rating plate.
1. 1-1/4” Front Manifold
The gas manifold of this appliance or of the battery which it is a part must be connected to a gas appliance pressure regulator adjusted for the manifold pressure marked on the rating plate.
IMPORTANT
For Propane Gas
The gas pressure regulator is factory adjusted
for 10.0” WC manifold pressure. The
maximum inlet pressure to the regulator should not exceed the manufacturer specification of 1/2 psi or damage to the regulator may occur.
2. Manifold pressure must be maintained at the pressure marked on the rating plate. Improper pressure can result in faulty or unsafe operation and/or premature component failure.
3. Use a pipe joint compound which is suitable for use with propane gas on all threaded connections.
4. Turn off all burner valves.
5. Turn on gas supply and check all unions for leaks. Use soapy water only for testing on all gases. Never use an open flame to check gas leaks.
THIS UNIT IS EQUIPPED WITH FIXED ORIFICES FOR THE TYPE OF GAS MARKED ON THE RATING PLATE. THE ORIFICES ARE SIZED FOR THE FOLLOWING MANIFOLD PRESSURE:
NATURAL: 6.0” WC
PROPANE GAS: 10.0” WC
1” Rear Manifold (Standard)
The gas pressure regulator supplied with this unit must be used.
For Natural Gas
The gas pressure regulator is factory adjusted
for 6.0” WC manifold pressure. The maximum
inlet pressure to the regulator should not exceed the manufacturer specification of 1/2 psi or damage to the regulator may occur.
IMPORTANT
IF PRESSURE TESTING PLEASE DO NOT EXCEED FACTORY SPECIFICATION OF 1/2 PSI OR DAMAGE TO REGULATOR MAY OCCUR.
FINAL ASSEMBLY
1. Reassemble the broiler by inserting the bottom grates (that will be used to hold the char-rock coals) with the flat surface facing down and properly positioned in their supports so they do not touch the burners. Spread the coals randomly over the grates to a maximum depth of 1-1/2”. Rearrange the coals to eliminate void areas and large openings. The proper amount of char-rock coals are as follows:
24C: 7 lb., 30C: 10 lb., 36C: 12 lb., 48C: 14 lb., 60C: 20 lb., 72C: 24 lb.
4
Loading...
+ 12 hidden pages