Montague UF-18R Installation Manual

INSTRUCTION MANUAL
MONTAGUE
Heavy Duty
Underfired Gas Broilers
Radiant Models:
Range Match: UF (-24R, -30R, -36R, -48R, -60R, -72R)
Freestanding: UFS (-24R, -30R, -36R, -48R, -60R, -72R)
Low-Profile Counter: UFLC (-24R, -30R, -36R, -48R, -60R, -72R)
Modular: UFSM (-24R, -30R, -36R, -48R, -60R, -72R)
Counter: UFSC (-24R, -30R, -36R, -48R, -60R, -72R)
Shallow Counter: UFLCS (-24R, -30R, -36R, -48R, -60R, -72R)
These instructions should be read thoroughly before attempting installation.
Set up and installation should be performed by qualified installation personnel.
Keep area around appliances free and clear from combustibles.
PLEASE RETAIN THIS MANUAL
FOR FUTURE REFERENCE.
THE MONTAGUE COMPANY
1830 Stearman Avenue P.O. BOX 4954
HAYWARD,CA 94540-4954
TEL: 510/785-8822 FAX: 510/785-3342
CONTENTS
INSTALLATION ………. 3 MAINTENANCE ……….6 OPERATION …………... 7 SERVICE ………………. 8
IMPORTANT
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the operating and maintenance instructions thor­oughly before installing or servic-
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable vapors and liq­uids in the vicinity of this or any other appliance.
ing this equipment.
INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE USER SMELLS GAS MUST BE POSTED IN A PROMINENT LOCATION. THIS INFORMATION MAY BE OBTAINED BY CONSULTING THE LOCAL GAS SUPPLIER.
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected and packed by skilled personnel before leaving the factory. The transportation company assumes full responsibility for safe delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE—Be certain this is noted on freight bill or express receipt, and signed by person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY—Regardless of the extent of damage.
3. CONCEALED LOSS OR DAMAGE—If damage is unnoticed until merchandise is un- packed, notify transportation company or carrier immediately, and file ―concealed dam­age‖ claim with them. This should be done within fifteen (15) days of date that delivery was made to you. Be sure to retain container for inspection.
We cannot assume responsibility for damage incurred in transit. We will, however, be glad to furnish you with necessary documents to support your claim.
2
INSTALLATION
The MONTAGUE gas broilers are produced with the best possible materials and workmanship. PROPER INSTALLATION IS ESSENTIAL FOR SAFE AND EFFICIENT TROUBLE-FREE OPERATION.
THE INSTALLATION INSTRUCTIONS CONTAINED HEREIN ARE FOR THE USE OF
QUALIFIED INSTALLATION AND SERVICE PERSONNEL ONLY. INSTALLATION OR
SERVICE BY OTHER THAN QUALIFIED PERSONNEL MAY RESULT IN DAMAGE TO THE
OVEN/INJURY TO THE OPERATOR.
Qualified installation personnel are individuals, a firm, corporation, or company which either in person or through a representative are engaged in, and are responsible for:
A. The installation or replacement of gas piping or the connection, installation, repair or servic-
ing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all requirements of state or local authorities having jurisdiction. Reference: National Fuel Gas Code Z223.1-NFPA54– latest addenda, Section 3.3.175.
B. The installation of electrical wiring from the electric meter, main control box, or service outlet
to the electric appliance. Qualified installation personnel must be experienced in such work be familiar with all precautions required and have complied with all requirements of state and local authorities having jurisdiction. Reference: National Electric Code, N.F.P.A. No. 70 – latest addenda.
READ CAREFULLY AND FOLLOW THESE INSTRUCTIONS
THE OVEN MUST BE INSTALLED IN ACCORDANCE WITH THE LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL FUEL GAS CODE, ANSI Z223.1-NFPA54-LATEST ADDENDA OR THE NATURAL GAS AND PROPANE INSTALLATION CODE CSA B149.1 AS APPLICABLE, INCLUDING:
1. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. (3.45 kPa).
2. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig. (3.45 kPa).
PROVISIONS MUST BE MADE FOR ADEQUATE AIR SUPPLY TO THE UNIT.
3
INSTALLATION
INSTALLATION
VENTILATING HOOD
The broiler must be installed under a properly designed ventilating hood. The hood should extend at least 6‖ beyond all sides of the unit. The hood should be connected to an adequate mechanical exhaust system.
Information on the construction and installation of ventilation hoods may be obtained from the ―Standard for the Installation of Equipment for the Removal of Smoke and Grease Laden Vapors from Commercial Cooking Equipment‖, NFPA No. 96-latest addenda, available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
It is also necessary that the sufficient room air ingress be allowed to compensate for the amount of air removed by the ventilation system. Otherwise, a subnormal atmospheric pressure will occur which may interfere with burner performance or may extinguish the pilot flame. In case of unsat­isfactory oven performance, re-check performance with the exhaust fan turned ―OFF‖.
Clearances
Adequate clearance must be provided in the aisle and at the side and back to allow the doors to open sufficiently to permit the removal of the racks and for serviceability. Adequate clearance for air openings into the combustion chamber must be provided.
CAUTION!
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR TO THE
BROILER(S). KEEP THE APPLIANCE AREA FREE AND CLEAR FROM
COMBUSTIBLES.
CLEARANCES
COMBUSTIBLE NONCOMBUSTIBLE
CONSTRUCTION CONSTRUCTION
UF, UFS, UFSC & UFSM MODELS:
BACK: 4” 0” LEFT & RIGHT SIDE: 8” 0” UFLC MODELS: BACK: 6” 0” LEFT & RIGHT SIDE: 9” 0”
UF, UFS & UFSM MODELS: SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOORS.
UFSC MODELS: FOR USE ONLY ON NONCOMBUSTILBLE COUNTERS. UFLC MODELS: EQUIPPED WITH 4” HIGH LEGS FOR INSTALLATION ON NONCOMBUSTIBLE COUNTER. FOR USE ONLY WITH NONCOMUSTIBLE FLOORS.
4
INSTALLATION
Setting in Place
1. Uncrate unit and put into place. For easier and lighter handling of the broiler, remove cast iron top grids, grid frame, drip tray, grease container, and debris screen.
2. Wire ties securing burners are for shipping purposes only and must be removed when installing the appliance. This will permit the burners to be readily removed during future servicing. Remove all other packing material from burner box.
3. FOR FLOOR MODELS, a set of 6‖ legs is packed in the top section of the broiler (unless unit is specifically ordered without legs). A threaded receptacle is located on each corner (and in the middle of units larger than 36‖) of the base of the unit. Each leg has a similar mating thread. Raise unit sufficiently to allow legs to be screwed into the threaded receptacles. Level unit by adjusting legs. AN UNLEVELED UNIT WILL ADVERSELY AFFECT PERFORMANCE.
4. COUNTER UNITS must be installed on a level table or stand, and Modular units must be leveled by adjusting the legs.
Battery Arrangements
1. Place the first unit in the exact position it will occupy in the battery.
2. Using a carpenter’s level, level the unit from front to rear and side to side. Adjust as follows:
FLOOR INSTALLATION ON LEGS: Adjust by turning foot on adjustable legs.
CURB INSTALLATION: Place shim under the low side. This operation is important since
variations in floors and curbs are common. Unless units are level, difficulty will be encountered in aligning the gas supply manifold and the units will not butt together tightly.
3. Remove the upper valve panel from unit.
4. Move the next unit into position.
5. Engage union nut on manifold with make fitting on next unit and draw up union nut hand tight. Be sure appliances butt together both front and rear. If manifolds do not align, then ranges are not level. In extreme cases, it may be necessary to loosen manifold bolts and adjust.
6. Continue leveling and connecting gas supply manifolds together until all appliances in the battery are connected.
7. Tighten manifold union gas tight. Use back up wrench to prevent manifold from rotating.
FAILURE TO DO THIS MAY RESULT IN DAMAGE TO PILOTS AND GAS VALVES.
C CHECK ENTIRE SYSTEM FOR GAS LEAKS.
5
Loading...
+ 10 hidden pages