It is required by law that all gas appliances are installed by competent persons in accordance with
the LOCAL GAS SAFETY REGULATIONS. Failure to install appliance correctly can lead to
prosecution. It is in your own interests and that of safety to insure that there is compliance with the
law.
IF YOU SMELL GAS
1. TURN OFF THE APPLIANCE AT THE
GAS INLET COCK AND OPEN ALL
DOORS AND WINDOWS.
2. DO NOT OPERATE ANY ELECTRICAL
SWITCHES AND EXTINGUISH ALL
NAKED FLAMES.
3. CONTACT THE LOCAL GAS
AUTHORITY IMMEDIATELY.
THE FOLLOWING INSTRUCTIONS
SHOULD BE READ CAREFULLY AS
THE MANUFACTURER CANNOT BE
HELD RESPONSIBLE FOR ANY
DAMAGE TO PROPERTY, PERSONS
OR ANIMALS CAUSED BY
INCORRECT INSTALLATION OR
OPERATION OF THE APPLIANCE.
PLEASE RETAIN THIS MANUAL
FOR FUTURE REFERENCE.
THE MONTAGUE COMPANY
1830 Stearman Avenue P.O. BOX 4954
HAYWARD,CA 94540-4954
TEL: 510/785-8822 FAX: 510/785-3342
IMPORTANT
WARNING:
Improper installation, adjustment,
alteration, service, or maintenance
can cause property damage, injury
or death. Read the operating
and maintenance instructions
thoroughly before installing or
Do not store or use gasoline or
other flammable vapors and
liquids in the vicinity of this or
any other appliance.
FOR YOUR SAFETY:
servicing this equipment.
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected
and packed by skilled personnel before leaving the factory. The transportation company
assumes full responsibility for safe delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE—Be certain this is noted on freight bill or express receipt,
and signed by person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY—Regardless of the extent of damage.
3. CONCEALED LOSS OR DAMAGE—If damage is unnoticed until merchandise is
unpacked, notify transportation company or carrier immediately, and file “concealed
damage” claim with them. This should be done within fifteen (15) days of date that
delivery was made to you. Be sure to retain container for inspection.
We cannot assume responsibility for damage incurred in transit. We will, however, be glad
to furnish you with necessary documents to support your claim.
2
INSTALLATION
STATUTORY REGULATIONS
The installation of this appliance must be carried out by a competent person and in accordance
with the relevant regulations, standards, codes of practice, and the related publications of the
country of destination.
1. Check carton or crate for possible damage sustained during transit. Carefully remove unit from
carton or crate and again check for damage. Any damage to the appliance must be reported to
the carrier immediately.
2. All other packing material must be removed from unit. Any protective material covering
stainless steel parts must also be removed.
3. The type of gas and supply pressure that the equipment was set up for at the factory is noted
on the data plate and on the packaging. This type of gas supply must be used.
4. Do not remove permanently affixed labels, warnings, or data plates from the appliance, for this
may invalidate the manufacturer’s warranty.
TECHNICAL SPECIFICATIONS
GAS SUPPLY
The gas pipe connection is made at the top right hand side of the equipment. The size of the pipe
work supplying the appliance must not be less than the inlet connection which is 1/2” pipe. An
isolating cock is recommended to be close to the appliance to allow shut down during an
emergency or routine servicing. After installation, the complete pipe work must be checked for
soundness.
DATA PLATE LOCATION
The data plate is readily accessible, located on left hand side of inner liner. It contains all of the
pertinent information required by the installer.
NOTE: The pressure must be measured at the pressure test nipple located on the
manifold pipe with the burner lit.
TABLE C: AERATION SHUTTER SETTING / PILOT FLAME LENGTH
2nd FAMILY, GROUP H 3rd FAMILY, GROUP 3P
MODEL
SBE3418 25 1.0 32 1.25 12.5 0.5
SBE3618 25 1.0 32 1.25 12.5 0.5
(G20 @ 20 mbar) (G31 @37 mbar)
NATURAL GAS PROPANE
mm Ins. mm Ins. mm Ins.
4
PILOT FLAME LENGTH
INSTALLATION
GENERAL INSTALLATION
SITING
The floor on which the range and salamander broiler are to be sited must be capable of
adequately supporting the weight of the appliance and any ancillary equipment. Once in position,
check that the unit is level, both front to back and side to side. Adjust, if necessary, using the
adjusting foot on each leg of range.
VENTILATION AIR
The following notes are intended to give general guidance. For detailed recommendations, refer to
the applicable codes(s) in the country of destination.
Note 1: The room containing the appliance is required to have a permanent air vent. The minimum effective area of the vent is related to the maximum rated heat input of the appliance and shall be 4.5cm² per kW in excess of 7 kW.
Note 2: Air vents should be of such a size to compensate for the effects of any extract fan in the premises.
GAS SUPPLY
The local gas region should be consulted at the installation planning stage in order to establish the
availability of an adequate supply of gas and to ensure that the meter is adequate for the required
flow rate. The pipe work from the meter to the appliances must be of an appropriate size. Where a
number of appliances are installed in a battery, no more than five should be served by any one
supply pipe.
All fixed (non-mobile) appliances MUST be fitted with a manual gas cock upstream of the
appliance to provide a means of isolation for servicing or cleaning purposes. A union or similar
means of disconnection must be provided between the gas cock and the appliance. A manually
operable valve must be fitted to the gas supply to the kitchen to enable it to be isolated in an
emergency. Wherever practical, this shall be located either outside the kitchen or near to an exit in
a readily accessible position.
Where it is not practical to do this, an automatic isolation valve system shall be fitted which can be
operated from a readily accessible position near to the exit.
At locations where the manual isolation valve is fitted or the automatic system can be reset, a
notice must be fitted stating:
“ALL DOWNSTREAM BURNER AND PILOT VALVES MUST BE TURNED OFF PRIOR TO
ATTEMPING TO RESTORE THE SUPPLY. AFTER EXTENDED SHUT OFF, PURGE BEFORE
RESTORING GAS.”
5
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.