Montague C36 SHB Installation Manual

INSTRUCTION MANUAL
MONTAGUE
Radiglo Heavy Duty Gas
Fired Over Fired Broilers
MODELS: 36W36, 43W36, 136W36, V136W36, 236W36, 243W36, C36,
C45, C36 SHB, C45 SHB, C36SHBPL, C45SHBPL
These instructions should be read thoroughly before attempting installation.
Set up and installation should be performed by qualified installation personnel.
Keep area around appliances free and clear from combustibles.
PLEASE RETAIN THIS MANUAL
FOR FUTURE REFERENCE.
THE MONTAGUE COMPANY
1830 Stearman Avenue
Hayward, CA 94540-4954
TEL: (510) 785-8822 FAX: (510) 785-3342
IMPORTANT
TABLE OF CONTENTS
Important (Cautions and Warnings) .............................................................. Page 1
Introduction .................................................................................................. Page 2 - 3
Installation .................................................................................................... Page 4 - 10
Operation ...................................................................................................... Page 11 - 12
Maintenance ................................................................................................. Page 13 - 15
Maintenance Schedule ................................................................................ Page 16
Service .......................................................................................................... Page 17 - 27
Orifice Size Chart - Drill Size ....................................................................... Page 28
Exploded View and Parts List ..................................................................... Page 29 - 32
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected and packed by skilled personnel before leaving the factory. The transportation company assumed full responsibility for safe delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE - Be certain this is noted on freight bill or express receipt, and signed by person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY - Regardless of the extent of damage.
3. CONCEALED LOSS OR DAMAGE - If damage is unnoticed until merchandise is unpacked,
notify transportation company or carrier immediately, and file “concealed damage” claim with
them. This should be done within fifteen (15) days of date that delivery was made to you. Be sure to retain container for inspection.
We cannot assume responsibility for damage incurred in transit. We will, however, be glad to furnish you with the necessary documents to support your claim.
IMPORTANT
FOR YOUR SAFETY
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the operating and maintenance instructions thoroughly before installing or servicing this equipment.
WARNING
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
NOTE: This manual has been prepared for personnel qualified to install commercial equipment who should perform the initial field start-up and the adjustments of the equipment covered by this manual.
NOTE: Instructions to be followed in the event the user smells gas must be posted in a prominent location. This information may be obtained by consulting the local gas supplier.
1
INTRODUCTION
GENERAL
The Gas Broilers covered in this manual are manufactured for use with the type of gas indicated on the nameplate. Some models include a cabinet, conventional oven, or convection oven.
Montague Gas Broilers are produced with the best possible material and workmanship. Proper installation is essential for safe, efficient, trouble-free operation.
MODELS
Model Features
Typical I.D. Plate
(Figure 1)
36W36
Cabinet Based Broiler with
Warming Oven
Cabinet Based Broiler with
43W36
Warming Oven
Broiler with Conventional
136W36
Oven and Warming Oven
Broiler with Convection
V136W36
Oven
236W36 Double Broiler
243W36 Double Broiler
C36 Broiler Only
C45 Broiler Only
SERIAL NUMBER LOCATION
RECEIVING & INSPECTING THE
EQUIPMENT
Care should be taken during unloading so the equipment is not damaged while being moved into the building.
1. Visually inspect the exterior of the package and skid or container. Any damage should be noted and reported to the delivering carrier immediately.
2. If damaged, open and inspect the contents with the carrier.
3. In the event that the exterior is not damaged, yet upon opening, there is concealed damage to the equipment, notify the carrier. Notification should be made verbally as well as in written form.
4. Request an inspection by the shipping company of the damaged equipment. This should be done within 10 days from receipt of the equipment.
Always have the serial number of your unit available when calling for parts and service. The serial number is on the nameplate that also includes the model number. A typical identification plate is shown in Figure 1.
5. Freight carriers can supply the necessary damage forms upon request.
6. Retain all shipping materials until an inspection has been made or waived.
2
INTRODUCTION
ORIFICES
Fixed for specified Gas type:
Gas Inlet Size: 3/4” NPT at lower left rear (all
models).
# Burners
Model
(Broilers Only)
Natural Gas: #33 DMS
Propan Gas: #48 DMS
Manifold Pressure
Natural Gas Propane Gas
6” W.C. 10” W.C.
Natural BTU/h Propone BTU/h Total BTU/h
36W36 2 42,000 ea. 42,000 ea. 84,000
43W36 3 42,000 ea. 42,000 ea. 126,000
136W36 2 42,000 ea. 42,000 ea. 124,000
V136W36 2 42,000 ea. 42,000 ea. 129,000
236W36 4 42,000 ea. 42,000 ea. 168,000
243W36 6 42,000 ea. 42,000 ea. 252,000
C36 2 42,000 ea. 42,000 ea. 84,000
C45 3 42,000 ea. 42,000 ea. 126,000
3
INSTALLATION
This manual has been prepared for personnel qualified to install gas equipment, who should perform the initial field start-up and adjustments of the equipment covered by this manual.
Qualified installation personnel are individuals, a firm, corporation, or company which either in person or through a representative are engaged in and are responsible for:
1. The installation or replacement of gas piping or the connection, installation, repair or servicing of equipment, who is experienced in such work familiar with all precautions required, and have complied with all requirements of state or local authorities having jurisdiction. reference: National Fuel Gas Code, ANSI Z223.1, section 1.4, latest addenda.
2. The installation of electrical wiring from the electric meter, main control box or service outlet to the electric appliance. Qualified installation personnel must be experienced in such work, be familiar with all precautions required and have complied with all requirements of state and local authorities having jurisdiction. Reference: National Electric Code, ANSI / NFPA No. 70, latest addenda.
individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.45 kpa).
Post in a prominent location the instructions to be followed in the event the smell of gas is detected. This information can be obtained from the local gas supplier.
In the event of a power failure, do not attempt to operate this device.
IMPORTANT
IN THE EVENT A GAS ODOR IS DETECTED, SHUT DOWN UNITS AT MAIN SHUTOFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR SERVICE.
CAUTION
PROVISIONS MUST BE MADE TO ASSURE ADEQUATE AIR SUPPLY TO UNIT FOR PROPER BURNER OPERATION.
CLEARANCES
The following are minimum clearances from combustible and noncombustible materials.
READ CAREFULLY AND FOLLOW THESE
INSTRUCTIONS
The broiler(s) must be installed in accordance with local codes, or in the absence of local codes, with the national fuel gas code, ANSI Z223.1 latest addenda, including:
1. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 kpa).
2. The appliance must be isolated from the gas supply piping system by closing its
Combustible
Noncombustible
Location
Construction
Construction
Back Wall 6” 0”
Left Side 6” 0”
Right Side 6” 0”
With 6” Legs: Suitable for installation on
combustible floors.
Without Legs: For use with special insulated base on noncombustible floors only.
4
INSTALLATION
VENTILATING HOOD
The broiler(s) must be installed under a properly designed ventilating hood. The hood
should extend at least 6” beyond all sides of
the unit. The hood should be connected to an adequate mechanical exhaust system.
Information on construction and installation of ventilating hoods may be obtained from the
“Standard for the Installation of Equipment for
the Removal of Smoke and Grease Laden Vap ors f ro m Com merc ial Co okin g Equipment”, NFPA No. 96-1987, available from the National Fire Protection Association, Batterymarch Park, Quincy, MA. 02269.
It is also necessary that sufficient room air ingress be allowed to compensate for the amount of air removed by the ventilating system. Otherwise, a subnormal atmospheric pressure will occur which may interfere with burner performance or may extinguish the pilot flame. In case of unsatisfactory broiler performance, check with the exhaust in the “OFF” position.
ASSEMBLY
Ceramic radiants, Figure 1 & 2, are located on each side of the burners. Ceramic end pieces are installed at both ends of each burner assembly. Five (5) ceramic radiants are installed on each side of each burner with the pointed side facing down and the holes facing up (See Figure 3).
4 2 3 1
1 Frame
2 Ceramic Radiants
3 Burner
4 Ceramic Ends
Uncrate broiler as near to final location as possible. For easier and lighter handling of broiler, remove grids, grid frame, drip tray and grease container. Remove all packing materials and accessories from broiler interior.
Legs
Some broilers are mounted on legs.
Screw the legs into the modular stand.
Tightly screw the complete leg assembly into the mounting holes in the bottom of the broiler at each corner. If the unit is intended for curb installation, no legs are provided. The curb must be noncombustible material.
Ceramic Radiants
Burner Assembly and Ceramic Radiants,
Top View
(Figure 1)
Burner Assembly and Ceramic Radiants,
Front View
(Figure 2)
5
INSTALLATION
Ceramic Radiant
(Figure 3)
1. Insert ceramic end pieces at front and rear of the burner frame. Four (4) are required for each burner.
2. Tilt ceramic radiants sideways to clear burner and frame assembly, then lower radiant into position with one flange resting on burner ledge and one flange resting on frame edge.
Floor Mounted Ranges
1. Place the first unit in the exact position it will occupy in the battery.
2. Using a carpenter’s level, level the unit front to rear and side to side. An
unleveled unit will adversely affect performance. Adjust as follows:
FLOOR INSTALLATION ON LEGS
Level by turning foot on leg.
CURB INSTALLATION
Place shim under the low side. This operation is important since variations in floors and curbs are common. Unless units are level, aligning the gas supply manifold will be difficult and the units will not fit together tightly.
3. Remove the valve panel from the broiler.
4. Move the unit into position.
3. Install the remaining ceramic radiants so that five (5) ceramic radiants are located on each side of the burner.
LOCATION
Adequate clearance for service and proper operation must be provided at the front, top, sides, and back. The combustion air openings are provided in the front of the unit and must not be obstructed.
LEVELING
After broiler is positioned, check that appliance is level both side-to side and front-to back.
BATTERY ARRANGEMENT
Setting In Place
Model No”s 36W36, 43W36, 136W36, and
V136W36.
5. Engage union nut on manifold with male fitting on next unit and draw up union nut hand tight. Be sure appliances meet together both front and rear. If manifolds do not align, then units are not level. In extreme cases it may be necessary to loosen manifold bolts and adjust.
6. Continue leveling and connecting gas supply manifolds together until all appliances in battery are connected.
7. Tighten manifold gas union. Use backup wrench to prevent manifold from rotating.
Failure to do this may result in damage to the pilots and gas valves.
GAS CONNECTION
Before connecting the broiler(s) to the gas supply line, be sure that all new piping has been cleaned and purged to prevent any foreign matter from being carried into the controls by the gas. In some cases, filters
6
INSTALLATION
or drops are recommended. A separate gas shutoff valve must be installed upstream from the gas pressure regulator adjacent to the broiler and located in an accessible are.
It is important that adequately sized piping be run directly to the point of connection at the broiler with as few elbows and tees as possible. Consult your local gas company for proper piping size and gas pressure. Each
broiler has a 3/4” NPT manifold input located
at the lower left rear of the broiler, Figure 4. On dual broilers, each broiler must have a separate regulator.
NOTE: Pipe joint compound or thread sealant that is used should be resistant to action of liquefied petroleum gases.
3/4” NPT Gas Inlet
Gas Inlet
(Figure 4)
Install the gas pressure regulator with gas flowing as indicated by the arrow on the regulator. The arrow must be pointing in toward the unit. Use pipe compound or thread sealant and carefully thread regulator to pipe so that there is no cross threading, etc., which could cause leakage.
1. Apply wrench only to the flat areas around the pipe tapping at the end being threaded to the pipe to avoid possible damage to the
regulator body which could result in leakage.
2. Connect the gas supply line from the service gas shutoff valve to the inlet side of
the gas pressure regulator using 3/4” pipe.
Avoid kinks or sharp bends that could restrict gas flow.
NOTE: If flexible or semi-flexible connectors are used, an AGA listed flexible connector with an I.D. equal to 3/4” pipe must be used.
WARNING
DO NOT USE A DOMESTIC TYPE FLEXIBLE GAS CONNECTOR.
3. Turn gas shutoff valve on and carefully check for gas leaks immediately. Do this before attempting to operate the broiler.
WARNING
TEST ALL PIPE JOINTS FOR LEAKS BEFORE OPERATING BROILER. THIS INCLUDES ALL GAS CONNECTIONS THAT MAY HAVE LOOSE NE D DURIN G SHIPMENT. USE A RICH SOAP SOLUTION (OR OTHER ACCEPTED LEAK TESTER) AROUND ALL PIPE JOINTS. DO NOT USE AN OPEN FLAME. ABSOLUTELY NO LEAKAGE SHOULD OCCUR, OTHERWISE THERE IS A DANGER OF FIRE OR E XPL O S IO N D EP E N D IN G U PO N CONDITIONS. DO NOT USE UNIT IF LEAKAGE IS DETECTED.
After piping has been checked for leaks, all piping receiving gas should be fully purged to remove air.
GAS PRESSURE REGULATOR
WARNING
DO NOT INSTALL UNIT WITHOUT AN APPLIANCE REGULATOR.
7
INSTALLATION
THE BROILER IS DESIGNED FOR USE WITH A PRESSURE REGULATOR. THE REGULATOR(S) SUPPLIED WITH THIS UNIT MUST BE USED.
For Natural Gas
This gas pressure regulator is factory adjusted
for 6.0” W.C. manifold pressure. The rated
inlet pressure to the regulators should not exceed 1/2 psig (3.45 kPa).
For Propane Gas
This gas pressure regulator is factory adjusted
for 10.0” W.C. manifold pressure. The rated
inlet pressure to the regulator should not exceed 1/2 psig (3.45 kPa).
The broiler is equipped with fixed orifices for
use with a manifold pressure of 6.0” W.C. for natural gas and 10.0” W.C. for propane gas.
Position the gas pressure regulator outside the broiler as near to the unit as possible.
CAUTION
3. Make sure that the regulator is mounted in the horizontal position with the arrow going in the direction of the gas flow.
4. Remove the main burner control valve knobs, Figure 5.
Burner Valve Knobs Screws
Control Valve Knobs
(Figure 5)
5. Remove the control valve panel by removing two screws.
THE GAS PRESSURE REGULATOR MUST BE LOCATED OUT OF THE HEAT ZONE TO PREVENT DAMAGE TO THE REGULATOR.
ADJUSTMENT PROCEDURE
WARNING
DO NOT ALLOW UNTRAINED PERSONNEL TO MAINTAIN OR SERVICE THE GAS PRESSURE REGULATOR.
1. Before adjusting the regulator, check the incoming gas line pressure into the
regulator. Incoming pressure must be 8.0” W.C. for natural gas, or 14” W.C. for
propane gas.
2. If incoming pressure is not correct, have the gas source checked and adjusted.
6. Connect a manometer to the pressure tap provided on the broiler unit gas piping manifold, Figure 6.
7. Check the manometer reading. The
reading must be 6.0” W.C. for natural gas, or 10.0” W.C. for propane gas. (DYNAMIC)
8. If incoming line pressure is not correct, adjust the regulator. Remove the seal cap on the top of the regulator.
9. Insert a slot screwdriver into the top of the regulator.
10. Turn the adjust screw clockwise to increase the pressure, or counter clockwise to decrease the pressure.
While watching the manometer, turn the adjustment screw to set proper regulator outlet pressure to the manifold.
8
INSTALLATION
Manifold
Manometer
Connection Pressure
Tap
Gas Pressure Tap
(Figure 6)
PILOT INITIAL ADJUSTMENT
Each burner has a separate pilot burner. The pilot flame is adjusted through access holes in the valve control panel, Figure 7. Pilot access is through the broiler panel opening.
3. Adjust pilot valve adjustment screw so that each pilot burner has a steady blue flame, Figure 8.
1/2” 1/2”
Pilot Burner
(Figure 8)
Adjustment Screw
Pilot Value
(Figure 9)
Pilot Valves Valve Panel
Pilot Valves
(Figure 7)
1. Turn the main gas shutoff valve to the on position.
NOTE: Pilots are on at all times if main shutoff valve is in the on position and pilot adjustment valves are open.
2. Light each pilot.
BURNER ADJUSTMENT
The efficiency of the broiler depends on a delicate balance between the supply of air and the volume of gas at each main burner resulting in complete combustion. Whenever this balance is disturbed, poor operating characteristics occur. An air shutter, Figure 9, on the front of each main burner controls the air supply.
9
Loading...
+ 25 hidden pages