Exploded View and Parts List ..................................................................... Page 29 - 32
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected and packed
by skilled personnel before leaving the factory. The transportation company assumed full
responsibility for safe delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE - Be certain this is noted on freight bill or express receipt, and
signed by person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY - Regardless of the extent of damage.
3. CONCEALED LOSS OR DAMAGE - If damage is unnoticed until merchandise is unpacked,
notify transportation company or carrier immediately, and file “concealed damage” claim with
them. This should be done within fifteen (15) days of date that delivery was made to you. Be sure
to retain container for inspection.
We cannot assume responsibility for damage incurred in transit. We will, however, be glad to furnish you with
the necessary documents to support your claim.
IMPORTANT
FOR YOUR SAFETY
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property
damage, injury or death. Read the operating and maintenance instructions thoroughly before
installing or servicing this equipment.
WARNING
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or
any other appliance.
NOTE: This manual has been prepared for personnel qualified to install commercial
equipment who should perform the initial field start-up and the adjustments of the equipment
covered by this manual.
NOTE: Instructions to be followed in the event the user smells gas must be posted in a
prominent location. This information may be obtained by consulting the local gas supplier.
1
INTRODUCTION
GENERAL
The Gas Broilers covered in this manual are
manufactured for use with the type of gas
indicated on the nameplate. Some models
include a cabinet, conventional oven, or
convection oven.
Montague Gas Broilers are produced with the
best possible material and workmanship.
Proper installation is essential for safe,
efficient, trouble-free operation.
MODELS
Model Features
Typical I.D. Plate
(Figure 1)
36W36
Cabinet Based Broiler with
Warming Oven
Cabinet Based Broiler with
43W36
Warming Oven
Broiler with Conventional
136W36
Oven and Warming Oven
Broiler with Convection
V136W36
Oven
236W36 Double Broiler
243W36 Double Broiler
C36 Broiler Only
C45 Broiler Only
SERIAL NUMBER LOCATION
RECEIVING & INSPECTING THE
EQUIPMENT
Care should be taken during unloading so the
equipment is not damaged while being moved
into the building.
1. Visually inspect the exterior of the package
and skid or container. Any damage should
be noted and reported to the delivering
carrier immediately.
2. If damaged, open and inspect the contents
with the carrier.
3. In the event that the exterior is not
damaged, yet upon opening, there is
concealed damage to the equipment, notify
the carrier. Notification should be made
verbally as well as in written form.
4. Request an inspection by the shipping
company of the damaged equipment. This
should be done within 10 days from receipt
of the equipment.
Always have the serial number of your unit
available when calling for parts and service.
The serial number is on the nameplate that
also includes the model number. A typical
identification plate is shown in Figure 1.
5. Freight carriers can supply the necessary
damage forms upon request.
6. Retain all shipping materials until an
inspection has been made or waived.
2
INTRODUCTION
ORIFICES
Fixed for specified Gas type:
Gas Inlet Size: 3/4” NPT at lower left rear (all
models).
# Burners
Model
(Broilers Only)
Natural Gas: #33 DMS
Propan Gas: #48 DMS
Manifold Pressure
Natural Gas Propane Gas
6” W.C.10” W.C.
Natural BTU/h Propone BTU/h Total BTU/h
36W36 2 42,000 ea. 42,000 ea. 84,000
43W36 3 42,000 ea. 42,000 ea. 126,000
136W36 2 42,000 ea. 42,000 ea. 124,000
V136W36 2 42,000 ea. 42,000 ea. 129,000
236W36 4 42,000 ea. 42,000 ea. 168,000
243W36 6 42,000 ea. 42,000 ea. 252,000
C36 2 42,000 ea. 42,000 ea. 84,000
C45 3 42,000 ea. 42,000 ea. 126,000
3
INSTALLATION
This manual has been prepared for personnel
qualified to install gas equipment, who should
perform the initial field start-up and
adjustments of the equipment covered by this
manual.
Qualified installation personnel are individuals,
a firm, corporation, or company which either in
person or through a representative are
engaged in and are responsible for:
1. The installation or replacement of gas
piping or the connection, installation, repair
or servicing of equipment, who is
experienced in such work familiar with all
precautions required, and have complied
with all requirements of state or local
authorities having jurisdiction. reference:
National Fuel Gas Code, ANSI Z223.1,
section 1.4, latest addenda.
2. The installation of electrical wiring from the
electric meter, main control box or service
outlet to the electric appliance. Qualified
installation personnel must be experienced
in such work, be familiar with all
precautions required and have complied
with all requirements of state and local
authorities having jurisdiction. Reference:
National Electric Code, ANSI / NFPA No.
70, latest addenda.
individual manual shutoff valve during any
pressure testing of the gas supply piping
system at test pressures equal to or less
than 1/2 psig (3.45 kpa).
Post in a prominent location the instructions to
be followed in the event the smell of gas is
detected. This information can be obtained
from the local gas supplier.
In the event of a power failure, do not attempt
to operate this device.
IMPORTANT
IN THE EVENT A GAS ODOR IS
DETECTED, SHUT DOWN UNITS AT MAIN
SHUTOFF VALVE AND CONTACT THE
LOCAL GAS COMPANY OR GAS
SUPPLIER FOR SERVICE.
CAUTION
PROVISIONS MUST BE MADE TO ASSURE
ADEQUATE AIR SUPPLY TO UNIT FOR
PROPER BURNER OPERATION.
CLEARANCES
The following are minimum clearances from
combustible and noncombustible materials.
READ CAREFULLY AND FOLLOW THESE
INSTRUCTIONS
The broiler(s) must be installed in accordance
with local codes, or in the absence of local
codes, with the national fuel gas code, ANSI
Z223.1 latest addenda, including:
1. The appliance and its individual shutoff
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psig (3.45 kpa).
2. The appliance must be isolated from the
gas supply piping system by closing its
Combustible
Noncombustible
Location
Construction
Construction
Back Wall 6”0”
Left Side 6”0”
Right Side 6”0”
With 6” Legs: Suitable for installation on
combustible floors.
Without Legs: For use with special insulated
base on noncombustible floors only.
4
INSTALLATION
VENTILATING HOOD
The broiler(s) must be installed under a
properly designed ventilating hood. The hood
should extend at least 6” beyond all sides of
the unit. The hood should be connected to an
adequate mechanical exhaust system.
Information on construction and installation of
ventilating hoods may be obtained from the
“Standard for the Installation of Equipment for
the Removal of Smoke and Grease Laden
Vap ors f ro m Com merc ial Co okin g
Equipment”, NFPA No. 96-1987, available
from the National Fire Protection Association,
Batterymarch Park, Quincy, MA. 02269.
It is also necessary that sufficient room air
ingress be allowed to compensate for the
amount of air removed by the ventilating
system. Otherwise, a subnormal atmospheric
pressure will occur which may interfere with
burner performance or may extinguish the
pilot flame. In case of unsatisfactory broiler
performance, check with the exhaust in the
“OFF” position.
ASSEMBLY
Ceramic radiants, Figure 1 & 2, are located on
each side of the burners. Ceramic end pieces
are installed at both ends of each burner
assembly. Five (5) ceramic radiants are
installed on each side of each burner with the
pointed side facing down and the holes facing
up (See Figure 3).
4 2 3 1
1 Frame
2 Ceramic Radiants
3 Burner
4 Ceramic Ends
Uncrate broiler as near to final location as
possible. For easier and lighter handling of
broiler, remove grids, grid frame, drip tray and
grease container. Remove all packing
materials and accessories from broiler interior.
Legs
Some broilers are mounted on legs.
Screw the legs into the modular stand.
Tightly screw the complete leg assembly into
the mounting holes in the bottom of the broiler
at each corner. If the unit is intended for curb
installation, no legs are provided. The curb
must be noncombustible material.
Ceramic Radiants
Burner Assembly and Ceramic Radiants,
Top View
(Figure 1)
Burner Assembly and Ceramic Radiants,
Front View
(Figure 2)
5
INSTALLATION
Ceramic Radiant
(Figure 3)
1. Insert ceramic end pieces at front and rear
of the burner frame. Four (4) are required
for each burner.
2. Tilt ceramic radiants sideways to clear
burner and frame assembly, then lower
radiant into position with one flange resting
on burner ledge and one flange resting on
frame edge.
Floor Mounted Ranges
1. Place the first unit in the exact position it
will occupy in the battery.
2. Using a carpenter’s level, level the unit
front to rear and side to side. An
unleveled unit will adversely affect
performance. Adjust as follows:
FLOOR INSTALLATION ON LEGS
Level by turning foot on leg.
CURB INSTALLATION
Place shim under the low side. This operation
is important since variations in floors and
curbs are common. Unless units are level,
aligning the gas supply manifold will be
difficult and the units will not fit together tightly.
3. Remove the valve panel from the broiler.
4. Move the unit into position.
3. Install the remaining ceramic radiants so
that five (5) ceramic radiants are located
on each side of the burner.
LOCATION
Adequate clearance for service and proper
operation must be provided at the front, top,
sides, and back. The combustion air openings
are provided in the front of the unit and must
not be obstructed.
LEVELING
After broiler is positioned, check that
appliance is level both side-to side and front-to
back.
BATTERY ARRANGEMENT
Setting In Place
Model No”s 36W36, 43W36, 136W36, and
V136W36.
5. Engage union nut on manifold with male
fitting on next unit and draw up union nut
hand tight. Be sure appliances meet
together both front and rear. If manifolds
do not align, then units are not level. In
extreme cases it may be necessary to
loosen manifold bolts and adjust.
6. Continue leveling and connecting gas
supply manifolds together until all
appliances in battery are connected.
7. Tighten manifold gas union. Use backup
wrench to prevent manifold from rotating.
Failure to do this may result in damage
to the pilots and gas valves.
GAS CONNECTION
Before connecting the broiler(s) to the gas
supply line, be sure that all new piping has
been cleaned and purged to prevent any
foreign matter from being carried into the
controls by the gas. In some cases, filters
6
INSTALLATION
or drops are recommended. A separate gas
shutoff valve must be installed upstream from
the gas pressure regulator adjacent to the
broiler and located in an accessible are.
It is important that adequately sized piping be
run directly to the point of connection at the
broiler with as few elbows and tees as
possible. Consult your local gas company for
proper piping size and gas pressure. Each
broiler has a 3/4” NPT manifold input located
at the lower left rear of the broiler, Figure 4.
On dual broilers, each broiler must have a
separate regulator.
NOTE: Pipe joint compound or thread sealant
that is used should be resistant to action of
liquefied petroleum gases.
3/4” NPT Gas Inlet
Gas Inlet
(Figure 4)
Install the gas pressure regulator with gas
flowing as indicated by the arrow on the
regulator. The arrow must be pointing in
toward the unit. Use pipe compound or thread
sealant and carefully thread regulator to pipe
so that there is no cross threading, etc., which
could cause leakage.
1. Apply wrench only to the flat areas around
the pipe tapping at the end being threaded
to the pipe to avoid possible damage to the
regulator body which could result in
leakage.
2. Connect the gas supply line from the
service gas shutoff valve to the inlet side of
the gas pressure regulator using 3/4” pipe.
Avoid kinks or sharp bends that could
restrict gas flow.
NOTE: If flexible or semi-flexible connectors
are used, an AGA listed flexible connector
with an I.D. equal to 3/4” pipe must be used.
WARNING
DO NOT USE A DOMESTIC TYPE
FLEXIBLE GAS CONNECTOR.
3. Turn gas shutoff valve on and carefully
check for gas leaks immediately. Do this
before attempting to operate the broiler.
WARNING
TEST ALL PIPE JOINTS FOR LEAKS
BEFORE OPERATING BROILER. THIS
INCLUDES ALL GAS CONNECTIONS THAT
MAY HAVE LOOSE NE D DURIN G
SHIPMENT. USE A RICH SOAP SOLUTION
(OR OTHER ACCEPTED LEAK TESTER)
AROUND ALL PIPE JOINTS. DO NOT USE
AN OPEN FLAME. ABSOLUTELY NO
LEAKAGE SHOULD OCCUR, OTHERWISE
THERE IS A DANGER OF FIRE OR
E XPL O S IO N D EP E N D IN G U PO N
CONDITIONS. DO NOT USE UNIT IF
LEAKAGE IS DETECTED.
After piping has been checked for leaks, all
piping receiving gas should be fully purged to
remove air.
GAS PRESSURE REGULATOR
WARNING
DO NOT INSTALL UNIT WITHOUT AN
APPLIANCE REGULATOR.
7
INSTALLATION
THE BROILER IS DESIGNED FOR USE
WITH A PRESSURE REGULATOR. THE
REGULATOR(S) SUPPLIED WITH THIS
UNIT MUST BE USED.
For Natural Gas
This gas pressure regulator is factory adjusted
for 6.0” W.C. manifold pressure. The rated
inlet pressure to the regulators should not
exceed 1/2 psig (3.45 kPa).
For Propane Gas
This gas pressure regulator is factory adjusted
for 10.0” W.C. manifold pressure. The rated
inlet pressure to the regulator should not
exceed 1/2 psig (3.45 kPa).
The broiler is equipped with fixed orifices for
use with a manifold pressure of 6.0” W.C. for
natural gas and 10.0” W.C. for propane gas.
Position the gas pressure regulator outside
the broiler as near to the unit as possible.
CAUTION
3. Make sure that the regulator is mounted in
the horizontal position with the arrow going
in the direction of the gas flow.
4. Remove the main burner control valve
knobs, Figure 5.
Burner Valve Knobs Screws
Control Valve Knobs
(Figure 5)
5. Remove the control valve panel by
removing two screws.
THE GAS PRESSURE REGULATOR MUST
BE LOCATED OUT OF THE HEAT ZONE TO
PREVENT DAMAGE TO THE REGULATOR.
ADJUSTMENT PROCEDURE
WARNING
DO NOT ALLOW UNTRAINED PERSONNEL
TO MAINTAIN OR SERVICE THE GAS
PRESSURE REGULATOR.
1. Before adjusting the regulator, check the
incoming gas line pressure into the
regulator. Incoming pressure must be 8.0”
W.C. for natural gas, or 14” W.C. for
propane gas.
2. If incoming pressure is not correct, have
the gas source checked and adjusted.
6. Connect a manometer to the pressure tap
provided on the broiler unit gas piping
manifold, Figure 6.
7. Check the manometer reading. The
reading must be 6.0” W.C. for natural gas,
or 10.0” W.C. for propane gas. (DYNAMIC)
8. If incoming line pressure is not correct,
adjust the regulator. Remove the seal cap
on the top of the regulator.
9. Insert a slot screwdriver into the top of the
regulator.
10. Turn the adjust screw clockwise to
increase the pressure, or counter
clockwise to decrease the pressure.
While watching the manometer, turn the
adjustment screw to set proper regulator outlet
pressure to the manifold.
8
INSTALLATION
Manifold
Manometer
Connection Pressure
Tap
Gas Pressure Tap
(Figure 6)
PILOT INITIAL ADJUSTMENT
Each burner has a separate pilot burner. The
pilot flame is adjusted through access holes in
the valve control panel, Figure 7. Pilot access
is through the broiler panel opening.
3. Adjust pilot valve adjustment screw so that
each pilot burner has a steady blue flame,
Figure 8.
1/2”1/2”
Pilot Burner
(Figure 8)
Adjustment Screw
Pilot Value
(Figure 9)
Pilot Valves Valve Panel
Pilot Valves
(Figure 7)
1. Turn the main gas shutoff valve to the on
position.
NOTE: Pilots are on at all times if main shutoff
valve is in the on position and pilot adjustment
valves are open.
2. Light each pilot.
BURNER ADJUSTMENT
The efficiency of the broiler depends on a
delicate balance between the supply of air and
the volume of gas at each main burner
resulting in complete combustion. Whenever
this balance is disturbed, poor operating
characteristics occur. An air shutter, Figure 9,
on the front of each main burner controls the
air supply.
9
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.