Montague 115Z User Manual

INSTRUCTION MANUAL
MONTAGUE
Convection Ovens
MODELS:
70, 115, R85, 2-70,
2-115 & R2-85 Series
These instructions should be read thoroughly before attempting installation.
Set up and installation should be performed by qualified installation personnel.
Keep area around appliances free and clear from combustibles.
PLEASE RETAIN THIS MANUAL
FOR FUTURE REFERENCE.
THE MONTAGUE COMPANY
1830 Stearman Avenue P.O. BOX 4954
HAYWARD,CA 94540-4954
TEL: 510/785-8822 FAX: 510/785-3342
CONTENTS
INSTALLATION ………. 3 MAINTENANCE ……… 21 OPERATION ………….. 11 SERVICE ……………… 26 COOKING HINTS ……. 16
IMPORTANT
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the operating and maintenance instructions thorough­ly before installing or servicing this
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appli­ance.
equipment.
INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE USER SMELLS GAS MUST BE POSTED IN A PROMINENT LOCATION. THIS INFORMATION MAY BE OBTAINED BY CONSULTING THE LOCAL GAS SUPPLIER.
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected and packed by skilled personnel before leaving the factory. The transportation company assumes full responsibil­ity for safe delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE—Be certain this is noted on freight bill or express receipt, and signed by person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY—Regardless of the extent of damage.
3. CONCEALED LOSS OR DAMAGE—If damage is unnoticed until merchandise is unpacked, notify transportation company or carrier immediately, and file “concealed damage” claim with them. This should be done within fifteen (15) days of date that delivery was made to you. Be sure to retain container for inspection.
We cannot assume responsibility for damage incurred in transit. We will, however, be glad to furnish you with necessary documents to support your claim.
2
INSTALLATION
Vectaire gas convection ovens are manufactured for use with the type of gas and electric supply indicated on the nameplate behind the fire box panel.
The Vectaire oven is produced with the best possible material and workmanship. PROPER INSTALLATION IS ESSENTIAL FOR SAFE AND EFFICIENT TROUBLE-FREE OPERATION.
THE INSTALLATION INSTRUCTIONS CONTAINED HEREIN ARE FOR THE USE OF QUALIFIED INSTALLATION AND SERVICE PERSONNEL ONLY. INSTALLATION OR SERVICE BY OTHER THAN QUALIFIED PERSONNEL MAY RESULT IN DAMAGE TO THE OVEN AND/OR INJURY TO THE OPERATOR.
Qualified installation personnel are individuals, a firm, corporation or company which either in person, or through a representative are engaged in, and are responsible for:
A. The installation or replacement of gas piping or the connection, installation, repair or ser-
vicing of equipment, who is experienced in such work, familiar with all precautions re­quired, and has complied with all requirements of state or local authorities having jurisdic­tion. Reference: National Fuel Gas Code Z223.1-latest addenda, Section 1.4.
B. The installation of electrical wiring from the electric meter, main control box or service out-
let to the electric appliance. Qualified personnel must be experienced in such work, be fa­miliar with all precautions required and have complied with all requirements of state and local authorities having jurisdiction. Reference: National Electric Code, N.F.P.A. No. 70– latest addenda.
READ CAREFULY AND FOLLOW THESE INSTRUCTIONS
THE OVEN MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL FUEL CODE, ANSI Z223.1-LATEST ADDENDA, INCLUDING:
1. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. (3.45kPa).
2. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig. (3.45kPa).
THIS UNIT WHEN INSTALLED MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES, OR IN ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE, ANSI/NFPA No.70– LATEST ADDENDA.
PROVISIONS MUST BE MADE FOR ADEQUATE AIR SUPPLY TO THE UNIT.
3
INSTALLATION
Ventilating Hood
The ideal method of ventilating a convection oven is the use of a properly designed ventilat­ing hood. The hood should extend at least 6‖ beyond all sides of the oven. The hood should be connected to an adequate mechanical exhaust system.
Information on the construction and installation of ventilating hoods may be obtained from the ―Standard for the Installation of Equipment for the Removal of Smoke and Grease Laden Va­pors from Commercial Cooking Equipment‖, NFPA No. 96– latest addenda, available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
It is also necessary that sufficient room air ingress be allowed to compensate for the amount of air removed by the ventilating system. Otherwise, a subnormal atmospheric pressure will occur which may interfere with burner performance or may extinguish the pilot flame. In case of unsatisfactory oven performance, check with the exhaust fan in the ―OFF‖ position.
Direct Flue Connection
If the oven is connected directly to an outside flue, a draft hood P/N 04391-5 or 04392-3 for Model 70, 115, SE70 and SE115 series and P/N 03109-7 or 03099-6 for Model 2-70, 2-115, SE2-70 and SE2-115 series must be used. (See Fig. 2 & 5) The flue should rise at least 10 feet above the roof or any surrounding structure. The flue must be terminated with an U.L. listed vent cap or spinner.
Clearances
Adequate clearance must be provided in the aisle and at the side and back to allow the doors to open sufficiently to permit the removal of the racks and for serviceability. Adequate clear­ance for air openings into the combustion chamber must be provided.
CLEARANCES
MODEL 70, 115, SE70 & SE115 SERIES WITH ENCLOSED BASE & MODULAR STAND:
COMBUSTIBLE CONSTRUCTION NONCOMBUSTIBLE CONSTRUCTION Back: 6” 5” Left & Right Side: 6” 0 WITH 4” OR 6” LEGS: SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOORS.
MODEL 2-70, 2-115, SE2-70 & SE2-115 SERIES:
COMBUSTIBLE CONSTRUCTION NONCOMBUSTIBLE CONSTRUCTION Back: 6” 5” Left & Right Side: 6” 0 WITH 4” OR 6” LEGS: SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOORS. CURB MOUNT WITH 1” TOE BASE (P/N: 555): FOR USE ONLY WITH NONCOMBUSTIBLE FLOORS.
4
INSTALLATION
CAUTION
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION
AIR TO THE OVEN. KEEP THE APPLIANCE AREA FREE AND CLEAR
FROM COMBUSTIBLES
Solid state components have a very short life span when exposed to temperatures above 185°F (85° C), therefore, certain installation precautions are necessary. The ―SE‖ ovens have been designed to operate below this temperature when properly installed. The following precautions must be observed:
1. Do not obstruct the flow of air through the vent openings at the top of the oven, or the flow of room air to the oven bottom or lower front portion of the burner access panel.
2. Do not mount the oven on a curb unless it has been equipped with the No.555 Toe Base (P/N:06024-0) for this type of installation.
3. When stacking ovens, never reverse the top and bottom oven sections.
4. Never stack an ―SE‖ series convection oven with a standard Vectaire or another
bra brand of oven without first consulting the factory. Certain ovens are not
compatible, or a stacking kit may be required.
SPECIAL CAUTION
DO NOT PLACE HIGH HEAT PRODUCING EQUIPMENT ADJACENT TO THE RIGHT SIDE OF AN ―SE‖ VECTAIRE CONVECTION OVEN, OR ANY OVEN EQUIPPED WITH THE IFO FAN CONTROL. SURFACE TEMPERATURES EX­CEEDING 185°F (85°C) CAN CAUSE PREMATURE COMPONENT FAILURE NOT COVERED UNDER MANUFACTURER’S WARRANTY.
ASSEMBLY
Model 70, 115, SE70 & SE115 Series (Fig. 1 & 2) Uncrate oven and base as near to final location as possible. Remove all packing material and accessories from oven interior. Install rack guides (if provided) in base. Place oven on stand as shown in Figure 1. Install flue deflector (P/N 16522-0 or 16532
-8) or draft hood (P/N 04391-5 or 04392-3). Either a flue deflector or a draft hood is
shipped with every unit. The flue deflector is intended for use when the oven is in­stalled under a properly designed hood.
When oven is directly connected to vent system, the draft hood must be used. (See Figure 2 & 6). When oven is in permanent position, level entire unit by placing carpen­ter’s level on oven rack and adjusting the foot of the bottom of each leg so that oven is level from front to back and side to side.
5
INSTALLATION
Enclosed Base
P/N 16522-0 (Painted) or P/N 16532-8 (S/S)
Flue Deflector
Figure 1
Modular Stand
P/N 4391-5 (Painted) or 4392-3 (S/S)
Draft Hood
Figure 2
6
INSTALLATION
Installation of Rack Guides in Base -Kit No. 04651-5
(If provided See Fig. 3)
1. Set base upright and place on rack guide in position with rod extensions toward rear and through holes in back.
2. Install stop (B) behind vertical flange forming base opening.
3. Place screw through clamp (A), upper hole of base flange (B) and stop. Install nut.
4. Repeat step 3 with lower hole of flange and stop. Tighten both nuts.
5. Repeat step 2, 3, and 4 for installation of other rack guide on opposite side.
Figure 3
Vectaire Models 2-70, 2-115, SE2-70 & SE2-115 Series (Fig. 4 & 5)
1. Screw the adjustable feet of the legs in all the way. Then tightly screw the complete leg assembly into the mounting holes at each corner of the lower dock (note logs on top of lower deck). If unit is intended for curb mounting, Toe Base (P/N:6024-0) must be used. The Toe Base is factory installed when curb mount is specified.
2. Set upper deck unit in place on top of lower deck.
3. Install flue riser (P/N:25128-3) over outlet of the horizontal flue collector (P/N:25135-
6) of the lower deck. Secure in place with the screws that are provided. Install flue deflector (P/N:25328-6) over flue outlet of top oven section.
4. Install low profile deflector trim (P/N:26604-3) or draft hood (P/N:24678-6). Either a flue deflector or a draft hood is shipped with every unit. The flue deflector is intend­ed for use when the oven is installed under a properly designed hood. When the oven is directly connected to the vent system, the draft hood must be used.
5. When oven is in permanent location, level entire unit by placing a carpenter’s level on the oven rack and adjusting the foot on the bottom of each leg, so that the oven is level from front to back and side to side. Level a curb mounted unit by placing a shim under the slow side.
7
INSTALLATION
Figure 4
Figure 5
Figure 6
8
INSTALLATION
GAS CONNECTION
Before connecting oven to the gas supply line, be sure that all new piping has been cleaned and purged to prevent any foreign matter from being carried into the controls by the gas. In some cases, filters or drops are recommended. A separate gas shutoff valve must be installed upstream from the gas pressure regulator adjacent to the oven and be located in an accessi­ble area.
It is important that adequately sized piping be run directly to the point of connection at the oven, with as few elbows and tees as possible. Consult local gas company for proper piping size and gas pressure.
Each oven is equipped with an appliance gas pressure regulator. This gas pressure regulator is factory adjusted for the manifold pressure specified on the name plate.
THIS OVEN IS DESIGNED FOR USE WITH A GAS PRESSURE REGULATOR. THE REGULATOR SUPPLIES WITH THIS UNIT MAY BE USED.
For Natural Gas: This pressure regulator is factory adjusted for 3.5‖- W.C. manifold pressure. The maximum inlet pressure to the regulator should not exceed 10.5‖ water column.
For Propane Gas: This gas pressure regulator is factory adjusted for 10‖ W.C. manifold pressure. The maximum inlet pressure to the regulator should not exceed 21‖ water column.
Connect the gas supply line from the service gas shutoff valve to the inlet side of the gas pressure regulator using 3/4‖ pipe. If flexible or semi-flexible connectors are used, an AGA Listed flexible connector with an I.D. equal to 3/4‖ pipe must be used. DO NOT USE A DOMESTIC APPLIANCE TYPE GAS FLEXIBLE CONNECTOR. Avoid kinks or sharp bends that could restrict gas flow.
PIPE JOINT COMPOUND OR THREAD SEALANT THAT IS USED SHOULD BE
RESISTANT TO ACTION OF LIQUEFIED PETROLEUM GASES.
Turn gas shutoff valve ―ON‖ and immediately check carefully for gas leaks. Do this before attempting to operate the oven.
TEST ALL PIPE JOINTS FOR LEAKS BEFORE OPERATING OVEN. THIS INCLUDES ALL
GAS CONNECTIONS THAT MAY HAVE LOOSENED DURING SHIPMENT. USE A RICH
SOAP SOLUTION (OR OTHER ACCEPTED LEAK TESTER) AROUND ALL PIPE CONNEC-
TIONS AND ALL OTHER JOINTS. DO NOT USE AN OPEN FLAME. ABSOLUTELY NO
LEAKAGE SHOULD OCCUR, OTHERWISE THERE IS A DANGER OF FIRE OR
EXPLOSION DEPENDING UPON CONDITIONS. NEVER USE IF LEAKAGE IS DETECTED.
9
INSTALLATION
Model R85 (Refer to Fig. 2, p. 4)
Uncrate oven and base as near to final location as possible. Remove all packing material and accessories from oven interior. With help from at least two other people, tip the oven slowly on its side. With the oven lying on its side, hold the front leg securely and align the threaded stud on the leg with the nut located at the front corner of the accessible side. Insert the leg into the nut and turn the leg clockwise. Tighten the leg to the oven securely. Rotate the leg counter­clockwise slightly to align the two leg plate holes with the holes on the bottom of the oven. Secure the leg using the provided 3/8‖ bolts and washers. Repeat the procedure for the rear corner of the side off the ground. Tip the oven up on the secured legs and lean the oven against a wall so that the legs on the remaining side can be attached. Install the remaining two legs using the aforesaid procedure. Tip the oven back down on the newly installed legs and re-tighten all the bolts securely.
A flue detector is supplied in Kit RS1 with the gusset legs. A Draft Hood is also available as Kit RS2, and replaces the flue deflector. Either a flue deflector or a draft hood must be installed on the unit. The flue detector is intended for use when the oven in installed under a properly designed hood. When the oven is directly connected to a vent system, the draft hood must be used.
When the oven is in permanent position, level entire unit by placing a carpenter’s level on the oven rack and adjusting the foot on the bottom of each leg so that the oven is level from front to back and side to side.
Model R2-85 Series (Refer to Figs. 4, 5 & 6, p. 6)
Screw the adjustable feet of the legs in all the way. Then tightly screw the complete leg
assembly into the mounting holes at each corner of the lower R85 unit. Mount lugs on top of the lower R85 unit, as to center the top unit on the lower one.
Set upper deck unit in place on top of lower deck.
From Kit RD1, locate the flue riser, the flue collector, and the flue deflector. Install the
flue collector over the flue outlet on the lower R85 unit. Install the flue riser over the outlet of the horizontal flue collector. Secure in place with self-drilling sheet-metal screws. Install the flue deflector over the flue outlet of the upper R85 unit. This setup is intended for use when the oven is installed under a properly designed hood. Note: When the oven is to be directly con­nected to a vent system, Kit RD2 must be used in conjunction with Kit RD1. Replace the flue deflector with the Draft Hood ensuring that it covers the flue outlet of the upper R85 unit. It must cover the top of the flue riser as well.
When the oven is in permanent position, level entire unit by placing a carpenter’s level on the oven rack and adjusting the foot on the bottom of each leg, so that the oven is level from front to back and side to side.
10
OPERATION
GAS CONTROL SYSTEM—All Models Except with Suffix ―EI‖
Lighting
Turn on main gas shutoff valve and electrical service.
IN THE EVENT A GAS ODOR IS DETECTED, SHUT DOWN UNITS AT MAIN SHUTOFF VALVE AND CONTACT THE LOCAL GAS COMPLANY OR GAS SUPPLIER FOR SERVICE.
1. Turn oven burner valve clockwise to ―OFF‖ position.
2. Remove burner compartment access panel below oven doors by pulling bottom panel outward to disengage panel catches.
3. Press and hold red safety pilot in and apply lighted match to pilot burner. After pilot burner
ignites, continue to hold red button depressed for 30-45 seconds or until pilot remains burning when button is released.
4. Replace burner compartment access panel.
5. Set thermostat to desired temperature.
6. Turn oven burner valve counterclockwise to ―ON‖ position.
7. Turn on fan. Fan should be on at all times during cooking operation.
Shut Down
1. Stand By
a. Turn oven burner valve to ―OFF‖ position. b. Turn off fan.
2. Complete
a. Turn all gas valves to ―OFF‖ position b. Turn fan off. c. Turn electrical service off of disconnect electrical supply cord from wall receptacle.
Relighting
1. Turn oven burner valve to ―OFF‖ position.
2. Wait five (5) minutes then follow ―Lighting‖ instructions.
11
OPERATION
GAS CONTROL SYSTEM—Models With Suffix ―EI‖
(Equipped with electronic ignition system)
Operation
1. Turn manual valve to ―ON‖ position.
2. Set thermostat to desired temperature.
3. Push toggle of Start/Reset switch to ―UP‖ position and release. The electronic pilot ignition control will automatically light the pilot and burner each time the thermostat calls for heat.
4. If pilot fails to ignite within 30 seconds, a complete shut down of the ignition system will occur. To initiate a re-ignition, wait at least 30 seconds, push toggle of Start/Reset switch up, then release.
Shut Down
1. Turn manual valve to ―OFF‖ position.
2. Turn thermostat to lowest setting.
CAUTION
DO NOT ATTEMPT TO LIGHT THE PILOT MANUALLY WITH A MATCH. THIS COULD RESULT IN THE
MAIN VALVE BEING ENERGIZED IMMEDIATELY.
CONTROLS
Standard Models—Models With Suffix ―AE, AG, ZE, ZG‖
1. ―LIGHT-OFF‖ switch controls the oven interior lights.
2. ―FAN-OFF-COOL‖ switch controls the fan operation. It must be on to obtain satisfactory
performance.
a. The center position is ―OFF‖
b. Depressing ―FAN‖ side of switch causes the motor to run continuously when doors are closed. When doors are opened, fan will stop. This position is for cooking.
c. Depressing ―COOL‖ side of switch will result in continuous blower operation even with
doors open. This position is intended for cooling the oven at the end of work period or lowering oven temperature.
NOTE: When cooling oven down, the burner valve should be turned off to prevent burner operation.
3. The thermostat controls the oven temperature. The ―BURNER‖ indicator light remains lit until
desired oven temperature is reached.
4. The timer is only a time reminder. It has no control over the oven.
12
OPERATION
Models With Suffix ―EI‖
Same as ―Standard Models‖ above except for ―START/RESET‖ switch for the electronic ignition system. Depress switch momentarily at the start of the work period.
INTERMITTENT FAN OPERATION (IFO) CONTROLS (Optional)
The IFO fan control cycles the fan ON for 30 seconds and OFF for 30 seconds during a variable time of 0.1 to 10 minutes of the cook period.
IFO Control
1. START SWITCH (MOMENTARY) Activated the IFO cycle.
2. CYCLE TIMER (0.1 TO 10 MIN.) Controls the duration of the IFO cycle.
3. INDICATOR LIGHT (AMBER) When lighted, indicates the oven is in the IFO cycle.
IFO Operation
To set the IFO controls, first set the ―Cycle Timer‖ knob for the desired IFO time period. Once the oven has reached temperature, load the product to be baked and close the door. Immediately set and start the standard timer for the overall cook cycle. Next, push the ―Start‖ switch on the IFO control. The amber indicator light will come on, the fan will stop, and then cycle on and off every 30 seconds until the set time has expired. The amber light will remain on continuously until the set time has expired.
Once the amber light is on, additional pushing of the ―Start‖ switch will have no effect. Also the ―Cycle Timer‖ knob does not count down during the IFO cycle, but remains at its setting for repeat cycle if desired.
To cancel the IFO cycle once started, simply rotate the ―Cycle Timer‖ knob counterclockwise until it stops.
Once started, the IFO time period can be readjusted by simply repositioning the ―Cycle Timer‖ knob. If the knob is turned counterclockwise to a setting that is less than the current time expired during the cycle, the cycle will be terminated. To restart a cycle, simply push the ―Start‖ switch.
If it is necessary to open the door during the IFO cycle, the fan will shut off if it is running. The IFO timed cycle will continue uninterrupted, however, until the set time has expired. If there is a loss of power during the cycle, it will be terminated.
13
OPERATION
OPERATION
MOIST AIR CONTROLS & OPERATION (optional)
Moist Air (Steam) Option The Moist Air option permits the operator to add steam to the oven chamber during the cooking cycle. This is desirable during baking operations for crusting purposes or to maximize growth during the initial bake period. It can also be useful for products requiring more moisture during the cook cycle.
Moist Air Components The Moist Air option includes a water shut-off valve, water regulator/filter assembly, solenoid valve, steel piping, spray nozzle, steam pan and Moist Air control cluster. During operation, activating controls causes the solenoid valve to open and heated water to be sprayed into the hot oven chamber where it is turned into steam. The steam pan converts any excess spray to steam and controls residue accumu­lation.
INSTALLATION
ATTENTION!
The Moist Air option requires a connection to good quality water that is low in total dissolved
solids and free of particulate matter. A water purification/treatment system must be installed if
harsh water conditions exist. If in doubt, have your water supply checked by a water treatment
company.
The water regulator filter assembly with shut-off valve (supplied with the Moist Air option) should be wall mounted near the oven so that the four foot removable hose will reach the water connection on the back of the oven. A permanent 1/2‖ cold water connection should be made at the shut-off valve. This filter is meant to remove final traces of taint, odor, rust, and scale when used with good quality water or a water purification/treatment system. It is not a substitute for a water treatment if harsh wa­ter conditions exist.
All other normal installation requirements for a Vectaire convection oven, as described in the ―Installation‖ section of the main Vectaire manual, should be followed.
OPERATION The Moist Air control regulates the spray of water that created steam in the oven chamber. The duration of the water spray can be varied from .3 to 30 MOIST AIR seconds. The spray is initiated by depressing the start switch.
To set the Moist Air controls, first set the ―Cycle Timer‖ knob for the desired time period. Once the oven has reached temperature, load the product to be baked and close the door. Immediately set and start the standard timer for the overall cook cycle. Next, push the ―Start‖ switch on the Moist Air control. The blue indicator light will come on, and remain on continuously until the set time has expired. Steam is being generated in the oven when the light is on.
Once the blue light is on, additional pushing of the ―Start‖ switch will have no effect. The ―Cycle Timer‖ knob does not count down, but remains at its setting for repeat cycle if desired.
14
Loading...
+ 31 hidden pages